IBC Boilers DC 15-96, DC 33-160, DC 20-125, DC 15-95 Installation And Operating Instructions Manual

DC Series Boilers / Water Heaters
DC 15-95, DC 15-96, DC 20-125, DC 33-160
(Natural Gas or Propane)
WARNING: If the information in this manual is not followed exactly, a re or
explosion may result causing property damage, personal injury, or loss of life.
Do not store or use gasoline or other ammable vapours and liquids or other combustible materials in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a nearby phone. Follow the gas
supplier’s instructions.
If you cannot reach your gas supplier, call the re department.
Installation and service must be performed by a qualied installer, service
agency or the gas supplier.
This Manual is also available in French - contact IBC or visit our web site www.ibcboiler.com
INSTALLATION AND OPERATING INSTRUCTIONS
www.ibcboiler.com
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
If the information in this manual is not followed
exactly, a re or explosion
may result causing property damage, personal injury, or loss of life.
SAFETY CONSIDERATIONS
Installation, start-up and servicing of IBC boilers / water heaters must
be done with due care and attention, and should only be performed by
competent, qualied, licensed and trained heating technicians. Failure to
read and comply with all instructions and applicable National and local codes may result in hazardous conditions that could result in property damage and injury to occupants which in extreme cases might result in death.
HAZARDS & PRECAUTIONS
DANGER
Points out an immediately hazardous situation which
must be avoided in order to prevent serious injury or
death.
WARNING
Points out a potentially hazardous situation which
must be avoided to prevent
serious injury or death.
CAUTION
Points out a potentially hazardous situation which
must be avoided to prevent possible moderate injury and/
or property damage
NOTE
Points out installation, maintenance and operation details that will result in
enhanced efciency, longevity
and proper operation of your
boiler / water heater.
BEST PRACTICES
Points out recommendations for better installation.
Supplied with the boiler / water heater - The IBC boiler / water heater is shipped with an accessory parts kit consisting of the following items:
1 x Wall Mounting Bracket, IBC Part # 250-647
1 x Condensate Assembly
1 x Pressure Relief valve, 3/4NPT, 30psi
1 x Outdoor Temperature Sensor
Air Vent and Relief Valve ttings
1 x Automatic Air Vent
4 x Lag Screws, Hex Head, Zn-Pl, 1/4 x 2-1/2 and Washers
1 x DC Installation & Operating Instructions
1 x DC/HC User Manual
1 x DC/HC Controller Manual
2
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
SPECIFICATIONS
SPECIFICATION DC 15-95 DC 15-96 DC 20-125 DC 33-160
CSA Input (Natural Gas or Propane) – MBH 15 - 95 15 - 96 20 - 125 33 - 160
CSA Input (Natural Gas or Propane) – KW 4.4 - 27.8 4.4 - 28.1 5.6 - 36.6 9.7 - 46.9
CSA Output – MBH 14.4 - 85.5 14.5 - 85.9 18.6 - 110.8 30.4 - 140.0
CSA Output - KW 4.2 - 25.0 4.3 - 25.2 5.4 - 32.5 8.9 - 41.0
DHW - CSA Input (Natural Gas or Propane) ­MBH
DHW - CSA Input (Natural Gas or Propane) - KW 4.4 - 27.8 4.4 - 28.1 5.6 - 36.6 9.7 - 36.3
A.F.U.E 95% 96% 95% 94%
Min Gas Pressure (Nat. Gas or Propane) – inch
w.c.
Max Gas Pressure (Nat. Gas or Propane) – inch
w.c.
Power (120Vac/60Hz) - Watts @ full re with
internal pump
Weight (empty) – lbs/Kg 97 / 44 105 / 48 105 / 48 105 / 48
Pressure Vessel water content – USG/Liters 0.37 / 1.4 0.5 / 1.9 0.5 / 1.9 0.5 / 1.9
Max boiler ow rate - USgpm 10 10 11 11
Min boiler ow rate - USgpm 2 2 3 3
Max Operating Pressure – Space Heating Coil -
psig
Max Operating Pressure – Domestic Hot Water Coil - psig
Approved installation altitude - ASL 10,000 ft 10,000 ft 10,000 ft 10,000 ft
Ambient Temperature – Low (°F/°C) 32 / 0 32 / 0 32 / 0 32 / 0
Ambient Temperature – High (°F/°C) 122 / 50 122 / 50 122 / 50 122 / 50
Max relative humidity (non-condensing) 90% 90% 90% 90%
Min water Temperature - Space Heating (°F/°C) 50 / 10 50 / 10 50 / 10 50 / 10
Max water Temperature – Space Heating (°F/°C) 194 / 90 194 / 90 194 / 90 194 / 90
Min water Temperature – Domestic Hot Water (°F/°C)
Max water Temperature – Domestic Hot Water (°F/°C)
Min ow rate to activate DHW heating - USgpm 0.5 0.5 0.5 0.5
Max ow rate DHW heating - USgpm 3.0 3.0 4.0 4.0
Max equivalent vent length 3" (each side) 120' 120' 120' 120'
Max equivalent vent length 2" (each side) 35' 35' 35' 35'
* Natural Gas boilers / water heaters require a Propane conversion kit (see page #3-2, Table 10) to be ordered separately if converting a Natural Gas boiler / water
heater to Propane. Propane (LP) boilers / water heaters require a Natural Gas conversion kit (see page #3-2, Table 10) to be ordered separately if converting a Propane boiler / water heater to Natural Gas.
† boilers / water heaters are shipped with 30 psig pressure relief valve
15 - 95 15 - 96 20 - 125 33 - 124
5 5 5 5
14 14 14 14
128 128 130 164
43.5 43.5 43.5 43.5
150 150 150 150
104 / 40 104 / 40 104 / 40 104 / 40
149 / 65 149 / 65 149 / 65 149 / 65
INSTALLATION AND OPERATING INSTRUCTIONS
3
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
DANGER
HOT
BURN
Water temperture over 125°F (52°C) can cause severe burns instantly
°
or death from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
°
See instruction manual before setting temperature at boiler.
°
Feel water before bathing or showering.
°
Temperature limiting valves are available, see manual.
°
WATER HEATER INSTALLATION GUIDELINES
WARNING
This boiler must be installed in accordance with local codes, if any; if not follow the National
°
Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CAN/CSA B149.1, as applicable.
Failure to correctly install and operate this appliance can result in severe personal injury
°
or death.
The water heater, if utilized, shall have a pressure relief valve installed within 6” [152mm] of the
°
DHW HOT outlet connection. Refer to the Boiler User’s Manual before operating relief valve.
The water heater, if utilized, requires a pressure relief valve identified with the ASME V or HV
°
symbol and set to relieve at or below 150psi of domestic water pressure and a minimum relieving capacity of 125,000 Btu/hr with 3/4” NPT threads. For safe operation of the water heater, the relief valve must not be removed from its designated point of installation or plugged.
For complete information refer to installation manual.
°
Read and follow warnings and instructions.
°
CAUTION
Hotter water increases the risk of scald injury. Before changing the temperature setting, see
°
instruction manual.
ADJUSTABLE TEMPERATURE SETTING
Press the and hold for 2 seconds, then press again. When the LED is lit, the
°
Domestic Hot Water temperature can be set.
4
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
CONTENTS
1.0 INSTALLATION....................................................1-1
1.1 GENERAL ...................................................1-1
1.2 CODE REQUIREMENTS........................................1-2
1.3 LOCATION ...................................................1-2
1.4 EXHAUST VENTING AND AIR INTAKE.............................1-3
1.5 CONDENSATE REMOVAL......................................1-16
1.6 WATER PIPING - SPACE HEATING ..............................1-20
1.7 DOMESTIC HOT WATER SYSTEM...............................1-28
1.8 GAS PIPING.................................................1-32
1.9 ELECTRICAL CONNECTIONS ..................................1-33
2.0 BOILER / WATER HEATER SYSTEMS AND OPERATION..................2-1
2.1 GENERAL ...................................................2-1
2.2 CONTROL ...................................................2-2
2.3 INSTALLER INTERFACE ........................................2-2
2.4 TANKLESS DOMESTIC HOT WATER MODES.......................2-4
2.5 ADDING DOMESTIC HOT WATER STORAGE.......................2-4
2.6 SPACE HEATING..............................................2-5
2.7 SEQUENCE OF OPERATION ....................................2-6
3.0 STARTUP AND COMMISSIONING ....................................3-1
3.1 LIGHTING AND SHUTTING DOWN THE BOILER ....................3-1
3.2 PRIOR TO START-UP ..........................................3-2
3.3 COMMISSIONING .............................................3-2
3.4 FUEL CONVERSION ...........................................3-4
4.0 MAINTENANCE ...................................................4-1
4.1 BOILER / WATER HEATER MAINTENANCE ........................4-1
5.0 TROUBLESHOOTING ..............................................5-1
5.1 PRELIMINARY CHECKS ........................................5-1
5.2 ELECTRONIC COMPONENTS ...................................5-2
6.0 DIAGRAMS.......................................................6-1
6.1 PARTS DIAGRAMS ............................................6-2
6.2 WIRING DIAGRAMS ...........................................6-6
INSTALLATION AND OPERATING INSTRUCTIONS
5
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
The Installer must carefully read this manual to ensure that all installation details can be adhered to. Special attention is to be paid to clearances and access, vent travel and termination, gas supply, condensate removal and combustion air supply.
DANGER
Should overheating occur
or the gas supply fails to shut off, do not turn off or disconnect the electrical supply to the pump. Instead shut off the gas supply at a location external to the appliance.
WARNING
Do not use this boiler / water
heater if any part has been under water. Immediately call
a qualied service technician to inspect the boiler / water
heater and to replace any part of the control system and any gas control that has been under water.
CAUTION
Care must be taken to properly size the boiler /
water heater for its intended
use. Prolonged full re run time, over-sizing or under­sizing, and incorrect ow rates through the boiler /
water heater can lead to increased maintenance
costs, equipment stress and
premature failure.
The Installer should do a pre-installation check the to ensure that the following precautions can be observed:
The boiler / water heater should be installed in areas where the combustion
air source is not subject to chemical fouling or agricultural vapours.
Exposure to corrosive chemical fumes such as chlorinated and/or uorinated
hydrocarbons can reduce the life of a boiler. Cleaners, bleaches, air
fresheners, refrigerants, aerosol propellants, dry-cleaning uids, de-greasers
and paint-removers all contain vapours which can form corrosive acid
compounds when burned in a gas ame. Airborne chlorides such as those
released with the use of laundry detergents are also to be avoided.
The boiler / water heater should be located where water leakage will not result
in damage to the area. If a location such as this cannot be found, a suitable drain pan should be installed under the appliance. The boiler / water heater is not to be installed above carpeting.
At a new construction site, or during renovations, action must be taken to
protect the boiler / water heater from drywall dust or other construction related contaminants; combustion air should be drawn from a CLEAN source (e.g. outdoors) and the boiler / water heater should be isolated from interior dust sources.
When the boiler / water heater is in operation, the impact of the steam plume
normally experienced at the exhaust terminal of a condensing boiler / water heater should be assessed. Generally, intake and exhaust pipes should terminate at a rooftop or sterile wall location. Boiler / water heater condensate is corrosive. Protective measures must be taken to prevent corrosion damage to metal roofs or other metal building components in contact with the condensate. Keep exhaust plumes well away from all building air intakes including those of neighbouring properties.
The exhaust outlet should be placed so as to reach 12" minimum above the
down-turned intake - to avoid exhaust re-ingestion.
For sidewall venting options: Both the inlet and exhaust terminations should
normally be located on the same plane (side) of the building. The elevation of both pipes can be raised in “periscope style” after passing through the wall to gain required clearance above grade and snow level.
Examine the condensate outlet to ensure proper disposal of condensate will
occur during operation. If condensates are to be discharged into building drain piping materials that are subject to corrosion, a neutralization package must be used.
Ensure that the pressure relief valve will be installed with no valves or other
means of isolation between its inlet and the boiler / water heater. Make sure the relief valve outlet will be piped with unobstructed piping (minimum 3/4" diameter) to a safe discharge location.
In locations where power supply quality varies or is unstable, installation of
surge protection and power conditioners up to and including battery back-up uninterrupted power supply devices should be considered.
Ensure the domestic hot water demands are considered before purchasing
the DC Series boiler / water heater. The addition of a storage tank or an IBC Indirect Water Heater may be required in some cases.
6
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
INSTALLATION1.0
MODEL NUMBER
DC 15-95 29.0" [736]
DC 15-96 31.3" [796]
DC 20-125 31.3" [796]
DC 33-160 31.3" [796]
HEIGHT
1.1
GENERAL
DC Series gas-red modulating boilers / water heaters are low pressure, fully
condensing units having variable input ranges (see specication chart - page 3). The boilers / water heaters are approved as “Category IV” vented appliances using Direct Vent (sealed combustion).
Figure 1 shows outer case dimensions and piping and electrical holes. Use this
diagram to nd a suitable location for the boiler / water heater. See also Section
1.3 Location.
DESCRIPTION
A Exhaust Outlet 3" Schedule 40
B Combustion Air 3" Schedule 40
C
Cold Domestic Water Connection
D Hot Domestic Water Connection 3/4" Male NPT
E Heating Water Inlet (Return) 1" Male NPT
F Heating Water Outlet (Supply) 1" Male NPT
G Gas Inlet 1/2" Male NPT
H Condensate Outlet 3/4" Hose
I Knock-out (3) 1/2"
DC SERIES BOILERS / WATER HEATERS
3/4" Male NPT
Table 1: Connections
Figure 1a: Dimensions / Connections for DC Series Figure 1b: Dimensions / Connections for DC Series
INSTALLATION
1-1
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1.2
1.3
WARNING
Keep boiler / water heater area
free and clear of combustible materials, gasoline, and
other ammable vapours and liquids.
WARNING
Combustion air must not be
drawn from areas containing
corrosive air from swimming
pools or spas, including air directly next to outdoor pools and spas.
WARNING
The boiler / water heater
shall not be exposed to
water leaks from piping or components located overhead.
This includes condensation dropping from un-insulated
cold water lines overhead.
WARNING
Ensure the gas ignition system components are
protected from water (dripping, spraying, rain, etc.) during
appliance operation and when
servicing (pump replacement, condensate trap servicing, control replacement, etc.)
CODE REQUIREMENTS
The DC 15-95, DC 15-96, DC 20-125, DC 33-160 models were tested to and
certied under CSA 4.9 / ANSI Z21.13 and Water Heater CSA 4.3 / ANSI
Z21.10.3.
The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, and/or Natural Gas and Propane Installation Code, CAN/CSA B149.1. The installation must also conform to the Canadian Electrical
Code Part 1 CSA C22.2 No.1 and/or the National Electrical Code ANSI/NFPA
70. Where required by jurisdiction, installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1.
If there is any conict, then the more stringent will apply.
LOCATION
The DC series boilers / water heaters are designed and approved for indoor
installation (wall), with signicant exibility of location provided with the available
venting options. The boiler / water heater can be placed in an alcove, basement, closet or utility room. Surrounding ambient conditions shall be 0°C to 50°C and less
than 90% relative humidity.
Install the boiler / water heater in areas where the combustion air source is not subject to chemical fouling or agricultural vapours. Exposure to corrosive chemical fumes such as chlorinated and/or uorinated hydrocarbons can reduce the life of a boiler / water heater. Cleaners, bleaches, air fresheners,
refrigerants, aerosol propellants, dry-cleaning uids, de-greasers and paint-
removers all contain vapours which can form corrosive acid compounds when
burned in a gas ame. Airborne chlorides such as those released with the use of
laundry detergents are also to be avoided. Similarly, ensure any direct vent air source is not adjacent to a clothes dryer exhaust terminal. Avoid agricultural
applications where the boiler / water heater and/or the intake air source are affected by ammonia and/or dust.
Locate the boiler / water heater where water leakage will not result in damage to the area. If a location such as this cannot be found, a suitable drain pan should be installed under the appliance. The boiler / water heater is not to be installed above carpeting.
Boiler / Water Heater Weight – approximately 105 lb / 44 kg. For support fasteners, use the supplied 4 x 1/4" x 2-1/2" long lag screws. Installer to supply 1/4" bolts if metal mounting systems are used. Fasteners are to be attached to solid material capable of supporting the combined weight of the boiler / water heater and piping assembly components.
Other factors affecting potential mounting sites:
Ensure minimum clearance requirements for combustible materials (see
Table 2) are satised.
Minimum 24" clearance at the front and 10" above is recommended for
adequate servicing. Check local codes for additional access and service clearance requirements.
At a new construction site, or during renovations, action must be taken to protect the boiler / water heater from drywall dust or other construction related contaminants; combustion air should be drawn from a CLEAN source (e.g. outdoors) and the boiler / water heater should be isolated
from interior dust sources.
1-2
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
Exposed water piping and associated components
(relief valves, circulators, etc.)
should not be in contact with
combustible materials. Check local codes for required clearances and/or provide adequate insulation.
WARNING
DO NOT MOUNT THIS BOILER / WATER HEATER TO HOLLOW WALL STRUCTURES - The
combined weight of the boiler, its water contents and associated piping
components can exceed 150
pounds. Fasteners must be rated for this strain, and must
be rmly anchored into solid
material that will support this weight.
SURFACE
Front 2" 24"
Rear 0" 0"
Left Side 1.5"
Right Side 4"
Top 2" 24"
Bottom 8" 24"
Table 2: Clearance from boiler / water heater cabinet
A minimum distance below the boiler / water heater of 11" is required to provide clearance for the supplied condensation trap assembly. More clearance will typically be required to accommodate associated water and
gas piping.
DISTANCE FROM COMBUSTIBLE SURFACES
RECOMMENDED DISTANCE FOR INSTALLATION AND SERVICE
6" (labels may be difcult to read with
reduced clearance)
6" (labels may be difcult to read with
reduced clearance)
Installers are to take all
necessary precautions
to avoid injury during the installation of this boiler /
water heater.
1.4
DANGER
Do not common vent the DC modulating series boilers /
water heaters with any other existing or new appliance.
INSTALLATION
Figure 2: Wall mounting of boiler
EXHAUST VENTING AND AIR IN­TAKE
It is important to carefully plan the installation to ensure the appropriate
vent materials, travel and termination decisions are incorporated. Specic
attention is warranted to manage the impact of the steam plume normally experienced at the exhaust terminal of a condensing boiler. Generally,
intake and exhaust pipes should terminate at a rooftop or sterile wall location, to maximize customer satisfaction. Keep exhaust plumes well away from all building air intakes including those of neighbouring
properties.
1-3
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
Venting, condensate drainage,
and combustion air systems
for all IBC boilers / water
heaters must be installed in compliance with all applicable codes and the instructions of
their respective Installation Manuals.
Inspect nished vent and air
piping thoroughly to ensure all are airtight and comply
with the instructions provided and with all requirements of
applicable codes.
Failure to comply will result
in severe personal injury or
death.
All venting must be installed in accordance with the requirements of the jurisdiction having authority: in Canada, Part 8, Venting Systems of the B149.1­10 Code and any other local building codes are to be followed. In the USA the National Fuel Gas Code, ANSI 223.1, latest edition, prevails. Where there is a discrepancy between the installation instructions below, and the code requirements, the more stringent shall apply.
Provisions for combustion and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, or Clause 8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the local building codes.
NOTE
The minimum wall thickness for venting is 1” and the maximum wall thickness for venting is 14”.
NOTE
A water heater shall not be
connected to a chimney ue serving a separate appliance,
designed to burn solid fuel.
Figure 3: Basic exhaust vent assembly
IMPORTANT
When an existing boiler / water heater is removed from a common venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it.
When re-sizing any portion of the common venting system, the common venting system should be re-sized to approach the minimum size as determined using the appropriate tables in the National Fuel Gas Code, ANSI Z223.1 - latest edition. In Canada, use the B149.1 Installation Code - latest edition.
At the time of removal of an existing boiler the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation.
Seal any unused opening in the common venting system.
Visually inspect the venting system for proper size and horizontal pitch and
determine there is no blockage or restriction, leakage, corrosion and other
deciencies which could cause an unsafe condition.
Insofar as is practical, close all building doors and windows and all doors
between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer
exhaust fan. Close replace dampers.
1-4
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Place in operation the appliance being inspected. Follow the lighting
instructions. Adjust thermostat so appliance will operate continuously.
After it has been determined that each appliance remaining connected to the
common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, replace dampers and any other gas-burning
appliance to their previous conditions of use.
Any improper operation of the common venting system should be corrected
so the installation conforms with the National Fuel Gas Code, ANSI Z223.1 ­latest edition. In Canada, all installations must conform with the current CAN/ CGA - B149.1 Installation Code and/or local codes.
1.4.1 Applications
All DC Series boilers / water heaters must be installed as a Direct Vent venting system. The combustion air must be piped in from the outdoors and connected directly to the boilers / water heaters combustion air connection. See section
1.4.7 for air intake piping requirements.
1.4.2 Exhaust Vent Material
WARNING
Covering non-metallic vent pipe and ttings with thermal
insulation shall be prohibited.
EXHAUST VENT MATERIAL – CANADA
Only PVC, CPVC, Polypropylene (PPs) or stainless steel* vent component systems approved under ULC-S636 Standard for Type BH Gas Venting Systems are to be used. Ensure compliance with exhaust temperature limitations for
the respective materials. The vent temperature is limited with the use of a ue
temperature sensor and software to ensure the maximum temperature of the PVC venting material is not exceeded.
ULC-S636 PVC
ULC-S636 CPVC
ULC-S636 PPs
EXHAUST VENT MATERIAL – USA
PVC, CPVC, PPs venting materials are approved for use with this boiler /
water heater in the USA. The vent temperature is limited with the use of a ue
temperature sensor and software to ensure the maximum temperature of the
PVC venting material is not exceeded. PVC venting material shall be certied to Sch. 40 ASTM D1785 or D2665. CPVC venting material shall be certied to Sch.
40 ASTM F441.
INSTALLATION
1-5
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
Do not mix venting materials from different Manufacturers.
These venting materials are
designed to be installed as part of a complete system.
Failure to comply may result
in severe personal injury or
death.
Do not use ABS or any cellular core pipe for exhaust venting.
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in venting systems shall be prohibited.
The boiler / water heater offers 3" venting connections. Fittings are to be used to adapt to the appropriate diameter (see Vent Travel below). CPVC or PVC
Exhaust Venting is to be inserted directly into the 3" female stainless steel tting
on left side of the boiler’s top panel. The clamp must be tightened to secure the
pipe into the tting. If PPs materials are being used, ensure the proper adapter is
used to transition from the Schedule 40 diameter to the PPs size diameter.
For PPs material, use the 3" transition/ adaptor tting (Sch 40 to PPs) offered
by the respective PPs manufacturers Centrotherm / InnoueTM (their part # ISAA0303) or M&G Dura Vent /PolyPro (#3PPS-AD). For PPs material exposed to outdoor weather, follow the venting suppliers’ recommendations on UV protection.
Combustion air piping is inserted directly into the 3" female stainless steel tting
on the right (see Section 1.4.7).
Venting shall be supported in accordance with applicable code.
1.4.3 Vent Travel
CPVC or PPs (Rigid Single Wall) piping is the standard venting option; with this, the DC Series boilers / water heaters, for example, can be vented up to 120 equivalent feet from the vent termination using 3". The actual vent travel allowance is reduced for ttings in accordance with Table 3. – e.g. for the models listed above using 6 x 90º CPVC long sweep elbows, the maximum lineal measure of pipe allowed using 3" pipe is 90 feet (120' – (6 x 5' = 30) = 90').
WARNING
Fully insert the approved venting material into the boilers / water heaters
exhaust outlet and tighten
clamp to ensure the venting connection is locked in place.
For 3" Flexible PPs, up to 35 actual lineal feet are allowed in a nominally vertical orientation (>45°). The equivalent length of 3" Flexible PPs shall be computed using a multiple of 1.4:1, e.g. 35' x 1.4 = 49' equivalent. The balance of the venting allowance is still available for use with rigid PPs piping material. 2" Flexible PPs is not allowed.
EXHAUST PIPE SIZE/FITTINGS MAXIMUM EQUIVALENT LENGTH
Schedule 40 PVC, CPVC or PPs – Allowances are for each side separately.
2" 35'
3" 120'
2" or 3" 90' Long Sweep Vent Elbow Allow 5 equivalent feet
2" or 3" 90' Short Sweep Vent Elbow Allow 8 equivalent feet
2" or 3" 45' Vent Elbow Allow 3 equivalent feet
PPS
PPs 87-90' Elbow Allow 8 equivalent feet
Flex PPS
3" PPs Flex (Max. 35) actual feet times 1.4
Table 3: Maximum Exhaust Venting Length
Exhaust venting must slope down towards the boiler / water heater with a pitch of at least 1/4" per foot (PPs vent: follow PPs manufacturer requirements) so condensate runs back towards the trap. Support should be provided for intake and vent piping, particularly so for horizontal runs (follow local code).
1-6
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 4
Exhaust piping is inserted directly into the 3" female stainless steel tting on the
top, left side of the boiler / water heater and run horizontally or vertically to the outdoors. Bird screen of 1/4" stainless steel or plastic mesh (eg. IPEX System 636 drain grate for CPVC systems) is useful to guard against foreign objects.
BEST PRACTICES
To reduce the possibility of
expansion noise, allow a 1/4"
gap around the exhaust and
air intake piping.
Follow all installation instructions supplied by the pipe and tting
manufacturer.
Ensure all venting components are clean of burrs/debris prior to assembly. Care is to be taken to avoid ingestion into the fan of PVC/ABS debris left in the combustion air piping.
All joints must be secured using appropriate solvent cement to bond the respective pipe material (Canada: CPVC cement approved under ULC-S636, in accordance with its manufacturer instructions; USA: PVC (ASTM D2564), or PVC/ABS (D2235) - Use transition glue anywhere that PVC and CPVC are joined. Follow the cement manufacturer’s instructions closely when joining various components. For PPs, connections shall be secured using approved retainer clips supplied by the respective PPs manufacturer.
All vent connections must be liquid and pressure tight. Prior to ring the boiler,
and before any of the venting run is concealed by the building construction, the installer must test the exhaust joints under fan pressure with the vent blocked,
using a soap/water solution. Installer must ll condensate trap prior to test.
1.4.4 Venting Passage Through Ceiling and Floor
Conrm material meets local codes including re stopping requirements.
Some local jurisdictions require a minimum initial length of pipe be exposed or
accessible for inspection.
Pipe clearances - no IBC requirements, but best practice allows a minimum
1/4" gap around the pipe to prevent binding and expansion noise; follow local codes.
All piping must be liquid and pressure tight.
INSTALLATION
1-7
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
CAUTION
Vent termination clearances
in this section are
code minimum, or IBC
recommended minimum
requirements, and may be inadequate for your installation. Building envelope
details must be examined carefully, and ingress of moisture into building
structures is to be avoided.
Serious structural damage
may occur if adequate
precautions and clearances are not allowed for.
These precautions are to be
observed for neighbouring
structures as well as for the
structure the boiler(s) are
installed in.
1.4.5 Rooftop Vent Termination
DIRECT VENT - TWO PIPE
Rooftop vents must terminate as follows:
The exhaust pipe can terminate in an open vertical orientation without concern
about rain inltration; rain will drain away through the condensate trap.
The intake air pipe is not typically drained, so it must be terminated with a down­turned elbow (see Figure 5). The intake pipe does not need to penetrate the roof at the same elevation as the exhaust; lower down the roof is OK.
The air intake pipe may terminate on the side wall of the building as long as
the air intake terminal is turned down and the side wall of the building is not exposed to large wind loads i.e.: prevailing winds.
Optional bird screen may be placed in a termination tting. Leave unglued,
and hold in place with a short nipple. This permits easy access for cleaning.
For roof top venting of multiple boiler / water heater sets, group all intake
terminals together for a common penetration through a custom cap. Alternatively, place in the closest proximity achievable using commonly
available pipe ashing. Similarly group the exhaust pipes and place the 2
separate groups of pipes at least 3' apart (the closest intake and exhaust pipes shall be 36" - or more - apart). Use the same 12" (minimum) vertical separation for 2 pipe option. For alternate group terminations, contact the IBC Factory for written guidance.
DO NOT exhaust vent into a common venting system.
Figure 5a: Rooftop exhaust venting with sidewall combustion air.
WARNING
Condensate can cause corrosion of metal roong
components and other
roong materials. Check with the builder or roong
contractor to ensure that materials will be resistant to
acidic condensate. pH levels can be as low as 3.0
1-8
Figure 5b: Rooftop vent terminal congurations
DIRECT VENT CONCENTRIC ROOF TOP TERMINATION
Roof Top Concentric Termination Kits are approved for use with this boiler / water heater model. The installation of the vertical roof top concentric termination must follow the installation instructions supplied with the venting material manufacturer. Care must be taken to install the termination kit a minimum horizontal distance of 10' (305cm) away from any portion of the building and a minimum of 18" (46cm) above the roof line plus the anticipated snow line. See Figure 6 and 7 on page 1-9.
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 6: Vertical Concentric Termination - Two Kits
INSTALLATION
Figure 7: Vertical Concentric Termination - Single Kit
1.4.6 Sidewall Vent Termination
DIRECT VENT - TWO PIPE
Sidewall direct vent applications shall be vented as follows:
Both the inlet and exhaust terminations should normally be located on the
same plane (side) of the building.
The exhaust outlet is to be placed so as to reach 12" minimum above the
down-turned intake - to avoid intake re-ingestion of exhaust gases.
The elevation of both pipes can be raised in “periscope style” after passing
through the wall, then congured as in Figure 8, to gain required clearance.
1-9
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
It is extremely important to maintain at least the minimum
separation of exhaust vent termination from boiler / water heater intake air as illustrated in gures 5, 8 and
13. Failure to do so can result
in a dangerous situation where exhaust gasses are re-ingested with combustion air. Damage to the boiler
/ water heater can result
from a failure to maintain these separations. Improper
installation will void the
warranty.
Use a 45° elbow on the exhaust termination to launch the plume up and off
the sidewall, for protection of wall.
Bird screen of 1/4" stainless steel or plastic mesh eg. (IPEX System 636 drain
grate for CPVC systems) is useful to guard against foreign objects.
Figure 8: Sidewall vent termination - piping conguration
WARNING
In areas of high snowfall,
Users must be advised to check side wall vent and air intake terminations on
a regular basis to ensure
blockage does not occur.
DIRECT VENT SIDE WALL TERMINATION KITS
The following Side Wall Termination Kits are approved for use with the DC series boilers / water heaters and are subject to the following restrictions. NOTE: Some jurisdictions may not allow this type of side wall termination due to close proximity to the neighboring properties. See Figures 9a, 9b and 10 on page 1-11.
The installation instructions, clearances and wall thickness requirements of the approved vent termination manufactures must be followed.
Approved Side Wall Termination Kits are listed as follows: (Alternate vent termination kits must be submitted to IBC for approval prior to installation.)
Ipex - #196984 – 2" PVC low prole termination kit (see Figure 10).
Ipex - #196985 – 3" PVC low prole termination kit (see Figure 10).
1-10
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 9a: Horizontal Concentric Termination - Two Kits
INSTALLATION
Figure 9b: Horizontal Concentric Termination - Single Kit
Figure 10: Ipex #196984 2" PVC and #196985 3" PVC
For side venting of multiple boiler / water heater sets, group all intake terminals together with 6" (minimum) lateral spacing, and similarly group the exhaust pipes. Place the 2 groups on the same plane of the building (e.g. north facing wall). Place the 2 groups of pipes at least 3' apart (the closest intake and exhaust pipes shall be 36" - or more – apart. Use same 12" (minimum) vertical separation (See (A) in Figure 13). Alternately, as long as the boilers / water heaters are identical models - intake and exhaust terminals can maintain a minimum of 12" of separation horizontally from any exhaust or inlet termination of an adjacent boiler (See (B) in Figure 13). For alternate group terminations, contact the IBC Factory for written guidance.
1-11
Figure 11: IBC recommended minimum vent terminal clearance under ventilated soft
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 13: Sidewall vent termination - multiple vent piping conguration
CONCENTRIC SIDE WALL TERMINATION KITS:
Must be installed on the same horizontal line (not stacked)
Must be installed with a min separation of 12” center to center
Use caution when installing Concentric Side Wall Termination Kits when the outdoor design temperature is below 5°F / -15°C. Possible blockage of the combustion air intake increases when the outdoor temperature drops below this temperature.
The clearances recommended by the vent termination manufacture must be followed.
Approved Concentric Side Wall Termination Kits are listed as follows: (Alternate vent termination kits must be submitted to IBC for approval prior to installation.)
Centrotherm – Innoue #ICWT242 (2” termination) + ICTC0224 (2” concentric
transition to 2 pipe)
Centrotherm – Innoue #ICWT352 (3” termination) + ICTC0335 (3” concentric
transition to 2 pipe)
Duravent – Polypro #3PPS-HK – Horizontal Termination Kit – Concentric
Ipex - # 197009 – 3” CPVC concentric termination kit
Ipex - # 196006 – 3” PVC concentric termination kit
VENT TERMINAL CLEARANCE MINIMUMS ARE AS FOLLOWS:
Figure 12: Prohibited installation
The vent for this appliance shall not terminate:
1. Over public walkways; or
2. Near soft vents or crawl space vents or other areas where condensate or
3. Where condensate vapor could cause damage or could be detrimental to the
1-12
vapor could create a nuisance or hazard or cause property damage; or
operation of regulators, relief valves, or other equipment.
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
In addition to preventing
ingestion of chemical contaminants, care must
be taken to ensure air intake terminals are not
installed in locations where contamination might occur due to ingestion of particulate
foreign material (dust, dirt and debris).
WARNING
Intake air openings must be congured such that rain
or other forms of moisture
cannot enter the air intake piping system. Otherwise serious damage to the boiler /
water heater may result.
NOTE
Care must be taken when installing air intake piping to ensure that a “trap” is not
formed in the piping so as to allow a build-up of water, and
blockage of intake air.
Such blockage will result in a boiler / water heater safety
shut-down.
CANADIAN INSTALLATIONS
A= Clearance above grade, veranda, porch, deck, or balcony
B= Clearance to window or door that may be opened
C= Clearance to window or door that may be opened
D= Clearance to permanently closed window
E= Clearance to
unventilated soft
F= Clearance to outside corner
G= Clearance to inside corner
H= Clearance to each side of center line extended above meter/regulator assembly
I= Clearance to service regulator vent outlet
J= Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance
K= Clearance to a mechanical air supply inlet
L= Clearance above paved sidewalk or paved driveway located on public property
M= Clearance under veranda, porch deck, or balcony
1 In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code
2 In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family
dwellings and serves both dwellings.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier.
12 in (30 cm) 12 in (30 cm)
6 in (15 cm) for appliances ≤
10,000 Btuh (3 kW), 12 in (30 cm) for appliances > 10,000 Btuh
(3 kW) and ≤ 100,000 Btuh (30
kW), 36 in (91 cm) for appliances
≤100,000 Btuh (30 kW)
* *
* *
* *
* 4 ft (1.22m) or local code, whichever is stricter
* 4 ft (1.22m) or local code, whichever is stricter
3 ft (91 cm) within a height 15 ft above the meter/regulator assembly
3 ft (91 cm) *
6 in (15 cm) for appliances ≤
10,000 Btuh (3 kW), 12 in (30 cm) for appliances > 10,000 Btuh
(3 kW) and ≤ 100,000 Btuh (30
kW), 36 in (91 cm) for appliances
≤100,000 Btuh (30 kW)
6 feet (1.83 m) 3 ft (91 cm) above
7 ft (2.13 m) † *
12 in (30 cm) ‡ *
1
US INSTALLATIONS
6 in (15 cm) for
appliances ≤ 10,000
Btuh (3 kW), 9 in (23 cm) for appliances > 10,000 Btuh (3 kW)
and ≤ 50,000 Btuh (15
kW), 12 in (30 cm) for appliances > 50,000 Btuh (15 kW)
* 4 ft (1.22m) or local code, whichever is stricter
* 4 ft (1.22m) or local code, whichever is stricter
*
6 in (15 cm) for
appliances ≤ 10,000
Btuh (3 kW), 9 in (23 cm) for appliances > 10,000 Btuh (3 kW)
and ≤ 50,000 Btuh (15
kW), 12 in (30 cm) for appliances > 50,000 Btuh (15 kW)
if within 10 ft (3 m) horizontally
2
INSTALLATION
1-13
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
INSIDE
CORNER DETAIL
G
V
A
D
V
E
B
V
L
V VENT TERMINAL X AIR SUPPLY INLET AREA WHERE TERMINAL IS NOT PERMITTED
Figure 14A: Vent Terminal Clearance
H
B
C
FIXED
V
CLOSED
OPERABLE
V
F
B
V
OPERABLE
B
B
A
B
V
FIXED
CLOSED
I
X
V
J
M
V
X
K
Figure 14B: Distance Inside / outside minimums
1.4.7 “Direct Vent” Combustion Air Intake Piping
The boiler / water heater must always be installed as a Direct Vent venting system with the combustion air piped directly from the outdoors to the boilers / water heaters combustion air connection. Provisions for combustion and ventilation air in accordance with the section “Air for Combustion and Ventilation,” of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Clause 8.2, 8.3 or 8.4 of Natural Gas and Propane Installation Code, CAN/CSA B149.1, or applicable provisions of the local building codes.
1-14
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 15: Direct vent combustion air intake
For 3" Flexible PPs, up to 35 actual lineal feet are allowed in a nominally vertical orientation (>45°). The equivalent length of 3" Flexible PPs shall be computed using a multiple of 1.4:1, e.g. 35' x 1.4 = 49' equivalent. The balance of the venting allowance is still available for use with rigid PPs piping material. 2" Flexible PPs is not allowed.
INTAKE PIPE SIZE/FITTINGS MAXIMUM EQUIVALENT LENGTH
Schedule 40 ABS PVC, CPVC or PPs – Allowances are for each side separately.
2" 35'
3" 120'
2" or 3" 90' Long Sweep Vent Elbow Allow 5 equivalent feet
2" or 3" 90' Short Sweep Vent Elbow Allow 8 equivalent feet
2" or 3" 45' Vent Elbow Allow 3 equivalent feet
PPS
PPs 87-90' Elbow Allow 8 equivalent feet
Flex PPS
3" PPs Flex (Max. 35) actual feet times 1.4
Table 4: Maximum intake piping length.
For the inlet air – Schedule 40 PVC, CPVC, ABS or PPs piping of any type is permitted. Use same diameter as Vent pipe.
INSTALLATION
Combustion air piping is inserted directly into the 3" female stainless steel tting
on the top, right side of the boiler / water heater and run horizontally or vertically to the outdoors. Bird screen of 1/4" stainless steel or plastic mesh (eg. IPEX System 636 drain grate for CPVC systems) is useful to guard against foreign objects.
Care must be taken to ensure adequate separation is maintained between the
air intake inlet and the vent terminal. Refer to the vent terminal conguration
drawings in the Vent Termination section above.
1-15
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Support should be provided for intake piping, particularly so for horizontal runs (follow local code).
WARNING
Fill trap with water before
boiler / water heater is rst red to prevent exhaust
fumes from entering room.
Never operate the boiler /
water heater unless the trap is
lled with water.
Failure to comply will result
in severe personal injury or
death.
1.5
1.4.8 “Indoor Air” Combustion Air Intake
Using Indoor Combustion Air is not approved for use with the DC series boilers / water heaters.
1.4.9 Closet Installations
For installations in a conned space (such as a closet), ventilation openings may
be needed through a door or wall to prevent excessive heat from building up inside the space.
The boiler / water heater shall not be exposed to ambient conditions above 122°F (50°C) or below 32°F (0°C).
CONDENSATE REMOVAL
IBC’s specied vent conguration promotes the safe drainage of moisture from the boiler / water heater and exhaust venting without owing liquids back through
the heat exchanger.
Reliable system operation requires (1) proper design and installation of exhaust venting to allow condensate to run back to the drain/trap; (2) acid neutralization as appropriate. To achieve these:
WARNING
The Trap Hook must be
installed as instructed and all
trap ttings must be tightened as instructed to prevent leakage of ue gasses.
Failure to comply may result
in severe personal injury or
death.
1-16
Figure 17: Condensate Trap, disassembled
1. Allow for a 1/4" per foot slope back to the vent connection, with appropriate
2. Ensure the supplied trap is correctly installed and lled with water.
3. When required, add (and maintain in good condition) a neutralization tank.
hangers to maintain that gradient.
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 18: Condensate trap installation
NOTE
It is the responsibility of
the installing and/or service Contractor to advise and
instruct the end User in how to perform the Trap cleaning
procedure, and to advise that the Trap be checked at least every two months and cleaned as required.
1.5.1 Condensate Trap
A condensate trap must be installed on the drain connection at the base of the boiler / water heater as shown in Figure 18.
1.5.2 Condensate Trap Assembly - Installation
1. Undo Drain Spout Compression Nut, remove Drain Hose from Trap Drain
Outlet. Remove Upper Compression Nut and Washer and slide over Boiler / Water Heater Drain Outlet (A). Insert one Trap Hook barb into the back mounting hole.
2. Fill Trap with water, and slide Trap Body over Boiler / Water Heater Drain
Outlet (A). Swing Trap Hook (B) around the Drain Outlet connection threads. Insert remaining Trap Hook barb into the front hole. Pull the trap slightly downward to seat it against the hook and tighten Upper Compression nut.
3. Attach Drain Hose and tighten Drain Spout Compression Nut.
INSTALLATION
1-17
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1.5.3 Condensate Trap Assembly - cleaning procedure
1. Turn off the power to the boiler / water heater and allow it to cool down.
2. Remove the trap from the boiler / water heater (reverse the installation
procedure above).
3. Remove the Trap Cleanout Assembly, from the Trap Body and clean and
ush the debris out.
4. Re-assemble trap components, re-ll trap, and replace on boiler / water
heater as described in the installation instructions above.
1.5.4 Further installation details
Condensate drain must be piped to within 1" of a drain or be connected to a
condensate pump.
Drainage line must slope down to the drain at a pitch of 1/4" per foot so
condensate runs towards the drain.
Condensate traps should be checked every 2 months, and cleaned and
relled as necessary.
1-18
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 19: Condensate trap disassembly for cleaning
WARNING
If condensates are to be discharged into building drain piping materials that are subject to corrosion, a neutralization
package must be used.
DANGER
The water in the condensate
neutralizer can cause severe burns to the skin. Use extreme caution when servicing the
condensate neutralizer. Wear
protective gloves and eyewear.
Figure 20: Condensate trap drainage
CAUTION
When a condensate
neutralization package is installed, the pH of the
condensate discharge must be measured on a regular schedule to ensure the
neutralizing agent is active and effective.
INSTALLATION
Figure 21: Condensate neutralization tank
1-19
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1.6
WATER PIPING - SPACE HEATING
1.6.1 General Piping Considerations
The DC series boilers / water heaters include a factory installed, integral Grundfos UP 15/58 heating pump. The pump is designed to provide adequate
ow through the boiler / water heater and near boiler / water heater piping. The
pump is pre wired.
Figure 22: Overview of piping options
Primary/secondary piping or the use of a buffer tank / hydraulic separator is
recommended for maximum exibility in multi zone/load applications. Piping loads in parallel is only acceptable in systems where the minimum ow rate is
guaranteed to be higher than the minimum for the boiler / water heater and the
boilers / water heaters pump is adequate to provide the required ow rate and
pump head for the system.
There are some important details to consider however, and this section of the Installation and Operating Manual will walk you through them so you can enjoy a trouble-free installation.
Table 5: Boiler side pump curve
1-20
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
During operation, the relief valve
may discharge large amounts
of steam and/or hot water.
Therefore, to reduce the potential for bodily injury and property
damage, a discharge line MUST
be installed that it:
1. is connected from the valve outlet with no intervening valve and directed downward
to a safe point of discharge.
2. allows complete drainage
of both the valve and the
discharge line. is independently supported
3.
and securely anchored so as
to avoid applied stress on the valve.
4. is as short and straight as possible
5. terminates freely to atmosphere where any discharge will be clearly
visible and is at no risk of
freezing.
6. terminates with a plain end which is not threaded.
7. is constructed of a material suitable for exposure to
temperatures of 375°F or
greater.
8. is, over its entire length, of a pipe size equal to or greater than that of the valve outlet.
DO NOT CAP, PLUG OR OTHERWISE OBSTRUCT THE DISCHARGE PIPE OUTLET!
The DC series modulating boilers / water heaters are designed for use within a closed loop, forced circulation, low pressure system. A 30 PSI pressure relief valve (3/4" NPT) is supplied for eld installation at the boilers / water heaters top connection point. A Relief Valve and Air Vent Piping Kit is also included with each DC series boiler / water heater to aid in the proper installation of the relief valve and air vent.
Figure 23: Relief Piping
System piping is connected to the boiler / water heater using the 1" NPT Male
threaded ttings located on the bottom of the boilers. Unions and gate or ball
valves at the boilers / water heaters supply and return water connections are recommended to simplify servicing. Un-insulated hot water pipes must be installed with a minimum 1/4" clearance from combustible materials.
CAUTION
Installers should inquire of local water purveyors as to the
suitability of their supply for use in hydronic heating systems. If water
quality is questionable, a local
water treatment expert must be consulted for testing, assessment
and, if required, treatment.
Alternatively, water or hydronic uid of known quality can be
brought to the site.
NOTE
See Domestic Hot Water Warnings on page 1-27.
INSTALLATION
Fluid ll is most often accomplished by using a boiler regulator & ll valve set at 12 psig or more, with appropriate backow prevention device as required
by local code. This is acceptable in areas where municipal water or well water
has been treated and ltered to remove excessive minerals and sediment, and
water chemistry is known to be suitable for closed loop hydronic systems. In areas where water quality is in question, or when chemical treatment or glycol is required, other options should be considered. Follow applicable Codes and good piping practice.
There are a number of boiler feed and pressurization devices on the market
today that may be a better choice than a raw water ll from the mains. When
regular maintenance requires relief valve blow-off, the discharge may be directed
back into the pressurization unit for recycling of boiler uid and chemicals
back into the system. In buildings that may be unoccupied for long periods of
time, pressurization units are useful to prevent ood damage should leakage occur from any component in the system. An additional benet is that backow
prevention devices are not required when using these devices.
1-21
WARNING
Close ll valve after any
addition of water to the
system, to reduce risk of
water escapement.
NOTE
Application drawings can be downloaded from our web site.
www.ibcboiler.com
NOTE
The boiler / water heater,
when used in connection with a refrigeration system, must be installed so the chilled medium is piped in parallel
with the boiler / water heater with appropriate valves to prevent the chilled medium from entering the boiler /
water heater.
NOTE
The boiler piping system of a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation
must be equipped with ow control valves or other automatic means to prevent gravity circulation of the
boiler water during the cooling cycle.
WARNING
Ensure the gas ignition system components are
protected from water (dripping, spraying, rain, etc.) during
appliance operation and when
servicing (pump replacement, condensate trap servicing, control replacement, etc.)
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 24: Boiler / water heater trim basic options – concept drawing. This drawing is only a simple schematic guide.
Do not place any water connections overhead the boiler / water heater; leaks can damage the fan and controls. If needed, create a shield over the top of
the cover, but allow clearance for airow and service access.
For best results, use a Primary: Secondary piping system, with a boiler loop using 1" (1-1/4" for the DC 33-160) piping for the DC Series Boilers / Water Heaters. The boiler / water heater comes with the boiler (primary) pump installed
in the boiler and will provide adequate ow for the boiler and primary loop piping
only.
The minimum ow rate required through the heat exchanger is 2 USgpm with a
maximum of 11 USgpm allowed. Primary/Secondary piping ensures adequate
ow and de-couples Δ°T issues (boiler / water heater vs. distribution). Aim for a 20° to 30° F Δ°T across the heat exchanger at high re.
The DC Series modulating boilers / water heaters are designed to supply the heating load with temperatures within the range of 86°F to 194°F. Use closely spaced tee’s to connect each pumped space heating load to the primary loop. As an option, a hydraulic separator or buffer tank can be used to separate the heating loads from the boiler / water heater.
Ensure the pump is rated for the design circulating water temperatures; some pumps have a minimum water temperature rating above the low temperature
potential of the boiler / water heater. Following installation, conrm actual performance by measuring Δ°T (under high and low ow conditions) after establishing the correct ring rate.
A variety of application drawings showing basic design options are available from the IBC web site at www.ibcboiler.com
1-22
INSTALLATION AND OPERATION INSTRUCTIONS
WARNING
Water quality has a signicant
impact on the lifetime and
performance of an IBC Boiler / Water Heater heat exchanger.
Improperly prepared water in a heating circuit may cause damage to the heat exchanger through corrosion or fouling. Repeated or uncontrolled
water lls will increase the
potential for damage.
High levels of dissolved
solids or minerals may
precipitate out of the uid
onto the hottest part of the heat exchanger, impairing heat transfer and resulting in
overheating and premature
failure. The amount of solids that may form on the heat exchanger will depend on the degree of hardness and
the total water volume in the system. A high water volume
system with a low hardness count may cause as much damage as a system with less
volume and higher hardness,
so it is recommended to treat
water so as to remove all dissolved solids. Other water
chemistry allowable limits are as follows:
Acidity pH is to be between
6.5 and 8.5
Chloride is to be less than
125 mg/l
Iron is to be less than 0.3
mg/l
Cu less than 0.1 mg/l
Conductivity is to be less
than 400μS/cm (at 25°C)
Hardness is to be 7 Grains
or less
IMPORTANT: Ensure that
these limits are acceptable for the other water-side components in the system.
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 25: Basic Primary/Secondary piping with closely-spaced tees concept – concept drawing. This drawing is only a simple schematic guide.
We recommend water ow after burner shutdown to utilize legacy heat – this is signicant due to the mass of the heat exchanger. The boiler / water heater pump
is under the control of the boiler / water heater to allow pump purge after burner shut-down. Default software values will run the boiler’s pump for 1 minute after the burner shuts down.
Schematics for several piping layouts are provided herein, and additional drawings are available at www.ibcboiler.com. Installers shall conform the piping
design to one of the provided congurations to simplify the control application, promote good loads and ow management.
Propylene glycol solution is commonly used in a closed loop where freeze protection is required. Its density is lower than that of water, resulting in
lower thermal performance at a given ow and pressure. As a rule of thumb,
a 50%:50% solution of propylene glycol and water will require an increased system circulation rate (gpm up 10%), and system head (up 20%) to provide performance equivalent to straight water.
The DC series modulating boilers / water heaters offer exceptional matching
of heat generation to radiation. The low minimum ring is better suited to low
thermal loads presented in a typical multi-zoned radiation system. However, where individual zones in a heating system have loads under 10,000 Btu/hr, the
system will still benet through use of a buffer tank to ensure a controlled supply
temperature, and to prevent short cycling. Buffering should be added on the secondary piping of the relevant load, to avoid bulking up the thermal mass of the primary piping circuit (and potentially lengthen the duration of the transition from hot to cool loads).
DC modulating series boilers / water heaters can be connected directly to a oor
of non-oxygen barrier polybutylene material (PB tubing). The internal boiler / water heater piping, and connections are all non-ferrous with the exception of the corrosion resistant epoxy coated cast iron pump. For maintenance of warranty
on such systems, we require evidence of a thorough ushing of all loops, plus installation of a dirt separator or side stream lter. A separator/lter maintenance routine shall be carried out after the retrot, with lter clearing after the 1st day,
1st week, month and annually thereafter. The installer must insure that all external piping components and pumps are non-ferrous when connecting
the boiler / water heater to a system with non-oxygen barrier tubing.
INSTALLATION
1-23
WARNING
Do not use automotive-
type ethylene or other
types of automotive glycol
antifreeze, or undiluted
antifreeze of any kind. This may result in severe boiler / water heater damage. It
is the responsibility of the Installer to ensure that glycol solutions are formulated to inhibit corrosion in hydronic heating systems of mixed materials. Improper mixtures
and chemical additives may
cause damage to ferrous and non-ferrous components as well as non-metallic, wetted components, normally found in hydronic systems. Ethylene glycol is toxic, and may be prohibited for use by codes applicable to your installation
location. For environmental and toxicity reasons, IBC
recommends only using non­toxic propylene glycol.
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1.6.2 Basic Heating Piping Arrangements
PRIMARY / SECONDARY PIPING - BENEFITS AND INSTALLATION RULES
1.
Good circulating water ow through the boiler irrespective of load or radiation
system head
2. Allows exible ΔT° control in secondary loops
3. Adds to the system’s thermal buffering, to assist in handling small loads and
temperature transition.
A Primary / Secondary piping conguration requires an extra pump, independant
from any secondary load pumps. The DC series modulating boiler / water heater includes the boiler Primary Pump installed inside the boiler / water heater cabinet and is pre-wired. The pump’s volute is epoxy coated to allow compatibility with the non-oxygen barrier tubing found in some older radiant heating systems.
For optimal performance, place pumps on the supply side of secondary loops to facilitate air evacuation. Use pumps with internal check valves to avoid ghost
ows and thermal siphoning.
The DC series boilers are designed to be piped in a Primary/Secondary piping arrangement. In some cases the boiler can be piped in series with the heating
load if the boiler’s pump is capable of providing the ow and head the system
requires. For example a DC series boiler and an IBC Air Handler series can be installed together without the use of an additional pump if the air handler is installed within close proximity of the boiler and with properly sized supply and return piping (see Figure 29a).
Propylene Glycol mixtures of 25% - 50% are acceptable for use within the boiler and piping system. In general, the use of propylene glycol will reduce the heating capacity of the heating system and increases the pump head required for
adequate boiler / water heater ow.
If the installation involves small loads, as in typical zoned baseboard heating applications, use of a buffer tank is recommended. To aid in temperature transition from hot to cool loads, a 3-way mixing valve can be placed at the
entrance to the cool load (this will also provide oor protection). This will permit immediate circulation of mixed ow into the cool loop.
1.6.3 Boiler Pump Air Bleeding
After lling the boiler for the rst time, bleed any air trapped in the boiler pump.
An absorbent cloth should be placed beneath the large slotted screw in the center of the pump. Turn this screw counter-clockwise until water drips from behind it and air is purged. Reseal the screw, but do not over-tighten.
1-24
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
NOTE
The piping drawings in this manual are simple schematic guides to a successful installation. There are many necessary components not shown, and details such as thermal traps are left out so
the drawings have greater clarity. We require that our boilers / water heaters be
installed by licensed and experienced trades people who are familiar with the applicable local and national codes. System design is to be completed by an experienced hydronic designer or Engineer. It is necessary to carefully read and follow these installation instructions along with the application
drawing that ts your system.
MULTIPLE BOILER PIPING - BENEFITS AND INSTALLATION RULES
Multiple IBC DC Series boilers / water heaters can be installed in a single heating system to provide redundancy, increased output, and greater heating plant turn­down capabilities. Primary/Secondary piping must be employed. This approach
provides constant head and ow at each boiler, regardless of ow variations in
the main building loop.
Each boiler / water heater will control its own pump, turning it off or on when heat is required. This approach saves electricity by reducing the pumping power required as load conditions are reduced. A multiple boiler system can be
Figure 26: Multiple boiler / water heater piping concept concept drawing. This drawing is only a simple schematic guide.
controlled by installing an external boiler staging controller with dry contacts for each boiler / water heater. These controllers are available from your local heating wholesaler.
Check valves are to be used in each boilers piping to prevent reverse ow when
the boiler is off.
INSTALLATION
1-25
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 26a: Closely-spaced tees on secondary piping concept drawing.
Figure 27: Typical two temperature space heating piping concept with direct domestic hot water – concept drawing. This drawing is only a simple schematic guide.
1-26
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 28: Typical two temperature space heating piping concept with indirect domestic hot water – concept drawing. This drawing is only a simple schematic guide.
Figure 29a: Air handler and direct domestic hot water – parallel piping for low head loss heat emitter concept drawing. This drawing is only a simple schematic guide.
INSTALLATION
Figure 29b: Air handler and direct domestic hot water – primary/ secondary concept drawing. This drawing is only a simple schematic guide.
1-27
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
DOMESTIC HOT WATER SYSTEM1.7
DANGER
HOT
BURN
Water temperture over 125°F (52°C) can cause severe burns instantly
°
or death from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
°
See instruction manual before setting temperature at boiler.
°
Feel water before bathing or showering.
°
Temperature limiting valves are available, see manual.
°
WATER HEATER INSTALLATION GUIDELINES
WARNING
This boiler must be installed in accordance with local codes, if any; if not follow the National
°
Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CAN/CSA B149.1, as applicable.
Failure to correctly install and operate this appliance can result in severe personal injury
°
or death.
The water heater, if utilized, shall have a pressure relief valve installed within 6” [152mm] of the
°
DHW HOT outlet connection. Refer to the Boiler User’s Manual before operating relief valve.
The water heater, if utilized, requires a pressure relief valve identified with the ASME V or HV
°
symbol and set to relieve at or below 150psi of domestic water pressure and a minimum relieving capacity of 125,000 Btu/hr with 3/4” NPT threads. For safe operation of the water heater, the relief valve must not be removed from its designated point of installation or plugged.
For complete information refer to installation manual.
°
Read and follow warnings and instructions.
°
CAUTION
Hotter water increases the risk of scald injury. Before changing the temperature setting, see
°
instruction manual.
ADJUSTABLE TEMPERATURE SETTING
Press the and hold for 2 seconds, then press again. When the LED is lit, the
°
Domestic Hot Water temperature can be set.
1-28
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
A potentially hazardous situation, which can cause serious injury or death, can exist if the un-used domestic water connections are capped off. The unused domestic water connections are meant to be left open if not used to allow for the air in the coil to expand
and contract as the boiler / water
heater is in operation.
WARNING
Bacteria growth can develop in domestic hot water tanks and
indirect water heaters if the minimum water temperature is
not set high enough to prevent
its growth.
WARNING
HOT WATER CAN SCALD!
Water Temperatures over 125°F / 52°C can cause severe burns
instantly or death from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
Never leave them unattended
in or near the shower, bathtub
or sink.
Never allow small children to
use a not water faucet or draw their own bath.
To avoid any potential scald hazard or if codes require specic
water temperatures at the hot water faucet, the installer may:
Install a thermostatic mixing
valve at this appliance and ensure it is working properly.
AND
Set the thermostatic mixing
valve to the lowest temperature which satises your hot water
needs.
TO AVOID INJURY:
Feel and adjust water
temperature before bathing or showering.
Water drained from the system
drain valve may be extremely
hot.
Make sure all connections are
tight.
Direct water ow away from
any person.
1.7.1 Domestic Hot Water System
The DC series boilers / water heaters have an independent piping circuit for
efciently generating Domestic Hot Water. When a faucet is opened to draw hot water, water ow is detected with a ow sensor and the DC Series boiler / water heater res up to begin generating domestic hot water. Due to the unique design of the boiler’s heat exchanger, the boiler / water heater can re with either no water in the alternate space heating circuit or without ow of water if pressurized
with the heating system water.
The cast aluminum heat exchanger has two separate copper water passage­way’s encased into the aluminum heat transfer block. Each copper passageway is completely isolated from the other to eliminate cross contamination in the event of a leak. This heat exchanger complies with the double wall heat exchanger requirements in many regional jurisdictions.
The unique design of the cast aluminum heat exchanger acts as a heat buffer, eliminating the cold sandwich effect when turning on and off the water repeatedly. The domestic hot water operation can be set to operate in 3 different ways.
Standard Mode: The boiler / water heater responds to a call for domestic hot
water when a faucet is opened. After the faucet is closed the boiler / water heater shuts down and waits for a call for the faucet to open.
Comfort Mode: After the faucet is closed the boiler / water heater will
maintain the programmed domestic hot water temperature so that the next time the faucet is opened, hot water is delivered to the faucet immediately without the “Cold Water Sandwich” effect.
Eco Comfort Mode: As above, the boiler / water heater will maintain the
programmed domestic hot water temperature but based on a learned pattern, the boiler / water heater will allow the water to cool. For example during the
night, the boiler / water heater will see no ow of domestic hot water therefore
will allow the boiler / water heater to cool down each night. If hot water is required at night, the boiler / water heater will respond to an open faucet just as if it was in the Standard Mode.
While the DC Series boiler / water heater is less susceptible to lime scale build­up than other units on the market, water quality must always be considered when installing the boiler / water heater. Treating hard water and adjusting the pH to 6.5 and 8.5 is strongly recommended. As a reference Table 6 represents some of the drinking water guidelines published by the US EPA. Consult a water treatment advisor in your area to assess your local needs. Proper water treatment will aid in
the longevity of the boiler / water heater and ensure maximum efciencies.
DESCRIPTION MAX MIN
Water Pressure 150 psi 40 psi
Programmable water temperature 149°F (65°C) 104°F (40°C)
Minimum Flow Rate to Activate DHW Sensor N/A 0.5 GPM
Acceptable pH range 8.5 pH 6.5 pH
Chloride 250 mg/L
Iron 0.3mg/L
Total Dissolved Solids 500mg/L
Total Hardness 7 grains
Table 6: Water Quality
INSTALLATION
1-29
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
NOTE
See Domestic Hot Water on page 1-27.
1.7.2 – Domestic Hot Water Piping
The domestic water piping connections are located at the bottom of the boiler / water heater, see Figure 30, Page 1-29. The connections are 3/4" male NPT threads. The cold water inlet is on the right side and the hot water outlet is on the left side.
A Pressure Relief valve with a maximum pressure setting of 150PSI and rated for a minimum capacity of not less than the rated input of the boiler / water heater (NOT Supplied with the boiler / water heater) must be installed within 6” of the domestic hot water outlet. The pressure relief valve must be installed between the boiler’s outlet and any isolation valve so as to ensure the pressure relief valve cannot be isolated by closing a valve. A valve kit designed for this purpose is recommended to reduce installation time and reduce the space required.
If required by local code, a eld-supplied Domestic Hot Water Thermostatic
Mixing Valve can be installed on the outlet of the DC Series boiler / water heater to prevent excessively hot water from reaching a faucet if the boiler / water heater is used in a high temperature heating system. If the boiler / water heater
is being used to heat a low temperature heating system like a radiant oor at
temperatures at or below 120°F/49°C then the thermostatic mixing valve may not be needed.
If the boiler / water heater installation is only using the space heating portion of the heat exchanger and not using the Domestic Hot Water portion of the heat exchanger, then the mixing valve and the Temperature and Pressure Relief valve need not be installed.
Do not cap off the hot and cold piping connections if they are not being used.
The DC Series boilers / water heaters can be connected to the pressurized 1/2" or larger domestic cold water supply piping and the domestic hot water piping in the home. The minimum domestic water pressure required is 40PSI and recommended to be 50PSI or higher. Generating domestic hot water with a water pressure lower than 40PSI will reduce the amount of hot water generated and will increase the risk of scaling in the heat exchanger.
The domestic water piping must be installed with isolation valves and ushing
taps installed on both the cold and hot domestic connections.
Thermal expansion of the water in the domestic hot water piping and boiler / water heater can cause excessive pressures to build in the piping system. This can cause the pressure relief valve to discharge on a regular basis. This condition must be prevented with the installation of a properly sized and installed domestic water expansion tank or other device designed for the purpose.
1-30
INSTALLATION AND OPERATION INSTRUCTIONS
CAUTION
The eld supplied
thermostatic mixing valve
may be installed on the direct domestic hot water piping
connections at the boiler /
water heater or at the outlet of a domestic hot water storage
tank if the domestic hot water
function is used. Failure to install the thermostatic
mixing valve may result in a
hazardous situation which can cause serious injury or death. See section 1.7.2
Paragraph 3.
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
DOMESTIC HOT WATER DELIVERY
@ 70°F / 39°C temperature rise
DC 15-95 2.4 GPM
DC 15-96 2.4 GPM
DC 20-125 3.2 GPM
DC 33-160 3.2 GPM
INSTALLATION
Figure 30: Tankless DHW Piping Options – concept drawing. This drawing is only a simple schematic guide.
1-31
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1.8
WARNING
This boiler / water heater model
can burn either Natural gas or
Propane. Refer to section 3.3
for further instruction.
If a boiler / water heater is to be converted from one fuel to another, a conversion kit
must be ordered prior to the
conversion. The conversion kit must be installed according
to the detailed instructions
supplied with the kit.
Failure to perform the required fuel conversion correctly can
result in serious injury or death.
NOTE
It is essential to check gas supply pressure to each boiler /
water heater with a manometer
or other high-quality precision measuring device. Pressure
should be monitored before
ring the boiler, when the regulator is in a “lock-up”
condition and during operation, throughout the boiler’s full modulation range.
Pay special attention to retrot
situations where existing
regulators may have an over­sized orice and/or worn seats, causing pressure “creep” and high lock up pressures.
GAS PIPING
The boiler / water heater should normally have an inlet gas pressure of at least
7.0" w.c. for natural gas and 11" w.c. for propane gas. For either fuel, the inlet
pressure shall be no greater than 14.0" w.c. Conrm this pressure range is
available with your local gas supplier.
The inlet gas connection of the boiler’s gas valve is 1/2" NPT (male).
Adequate gas supply piping shall be provided with no smaller than 1/2" Iron Pipe Size (e.g. Iron Pipe Size (IPS) and using a 1" w.c. pressure drop, in accordance with the following chart:
MODEL 1/2" IPS 3/4" IPS 1" IPS
DC Series (Natural Gas) 20' 70' 200'
DC Series (Propane) 50' 200' 600'
Table 7: Maximum Pipe Length (ft) – DC series 33-160 boiler
Gas piping must have a sediment trap ahead of the boiler / water heater’s gas valve (see Figure 32). A manual shutoff valve must be located outside the boiler, in accordance with local codes/standards. All threaded joints in gas piping should be made with an approved piping compound resistant to the action of natural gas/propane. Use proper hangers to support gas supply piping as per applicable codes.
The boiler / water heater must be disconnected or otherwise isolated from the gas supply during any pressure testing of the system at test pressures in excess of 1/2 psig. Dissipate test pressure prior to reconnecting. The boiler / water heater and its gas piping shall be leak tested before being placed into operation.
The boiler / water heater and its individual shutoff valve must be disconnected
from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The boiler / water heater must be isolated from the gas supply piping system
by closing, disconnecting and capping its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or greater than 1/2 psi (3.5 kPa).
The gas valve is provided with pressure taps to measure gas pressure upstream (supply pressure) and downstream (manifold pressure) of the gas valve (see
Figure 31). Note that manifold pressure varies slightly in accordance with ring
rates with the modulating series boilers / water heaters, but will always be close to 0" w.c.
Figure 32: Gas PipingFigure 31: Gas Valve
1-32
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1.9
NOTE
The IBC boiler / water heater (like any modern appliance that contains electronic equipment), must have a “clean” power
supply, and can be disabled
by power surges and spikes, lightning strikes and other forms of severe electrical “noise”. Power conditioning equipment (surge protectors, APC or UPS devices) may be required in areas where power quality is suspect.
WARNING
Do not apply power to any connection point on the controllers terminal strips. A potentially hazardous situation could occur which must be
avoided to prevent possible
serious injury or death.
NOTE
The IBC control only
recognizes a true dry contact closure as a call for heat.
Thermostats and other devices that use a “Triac” output
cannot be used as a call for heat without the installation of
an intervening relay with dry contacts to connect to the IBC
terminal strip.
NOTE
A hot water boiler / water heater installed above radiation level or as required by the Authority Having Jurisdiction, must be provided with a low water cut-off device at the time
of installation. If a low water cut-off is not factory installed,
instructions shall be provided
for the installation and wiring of a low water cut-off.
ELECTRICAL CONNECTIONS
All Electrical wiring to the boiler / water heater (including grounding) must conform to local electrical codes and/or National Electrical Code, ANS/NFPA No. 70 – latest edition, or The Canadian Electrical Code, C22.1 - Part 1.
If an external electrical source is utilized, the boiler, when installed, must be electrically bonded to ground in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National
Electrical Code, ANSI/NFPA 70, and/or the Canadian Electrical Code Part I, CSA C22.1, Electrical Code.
1.9.1 120VAC Line Voltage Hook-up
Line-voltage wiring is done within the eld-wiring box. (Refer to Section
6.2.Wiring Diagram on page 6-4). Connect the boiler / water heater to the grid
power using a separate, fused circuit and on/off switch within sight of the boiler / water heater. Use 14-gauge wire in BX cable or conduit properly anchored to the boiler / water heater case for mains supply and pump circuits.
The boiler / water heater is equipped with 3 x 1/2" electrical knock-outs located behind the power supply terminal strip.
Connect the 120 VAC /15 amp power supply to the AC in connections located to the right side of the controller. To access the terminal strip, remove the boiler / water heater cover and slide open the controller drawer. Ensure 120 VAC polarity is correct and that the boiler / water heater is properly grounded.
The DC Series boilers / water heaters include a factory installed and pre-wired
pump. The pump is intended to supply adequate ow for the boiler’s primary
heating circuit only. The system heating pump will need to be switched through a separate relay or control box.
A second set of contacts is available to connect a DHW pump. This pump will
allow the connection of an indirect red storage water heater to heating circuit to
take full advantage of the boiler /water heater’s heating capacity. The maximum amperage rating of the connected pump is 1.0 amps. If the connected pump has a rating higher than 1.0 amps, an external isolation relay is required to protect the boiler / water heater’s controller.
A eld supplied, external safety device can be connected to the boiler / water
heater by connecting the safety device in series with the boiler / water heater’s 120 VAC power supply. Ensure the external safety device is rated to accept 120 VAC and the total load connected to the boiler / water heater. For an interlock designed for the sole purpose of protecting the heating circuit of the boiler, the Auxiliary Safety interlocks can be wired in series with the Call for heat (X4.6 and X4.7). Do not apply power to the X4 terminal strip. The Auxiliary Safety interlocks must be a Dry Contact.
Figure 33: X4 Terminal Strip for connection of the DHW Aquastat (optional), Thermostat or end switches (mandatory), Outdoor Sensor (optional)
BOILER SYSTEMS AND OPERATION
1-33
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
EXTERNAL PROBE TYPE LOW WATER CUT OFF DEVICE
An external low water cut-off device is never required if the boiler / water heater is only being used as a direct domestic hot water unit.
If an external low water cut-off device is required, an electronic probe style device is recommended.
The probe type low water cut-off device must be installed in the boiler / water
heater supply water piping, with a tee connection, at a level above the top of the boiler / water heater.
The probe type low water cut-off device must be wired in series with the
120Vac power supply so that when the device trips on a low water condition the power supply to the boiler / water heater is interrupted.
Figure 34: External Probe Type Low Water Cut Off Device
Figure 34a: Alternate Probe Type Low Water Cut Off Device Location
1-34
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1.9.2 Power Quality and Electrical Protection
In areas of unreliable power, appropriate surge protectors and or power conditioning equipment should be installed to protect the boiler / water heater.
1.9.3 Zone Valve and Zone Pump Connections
Zoning can be accomplished with either zone pumps or zone valves. In either case the controls and relays that may be required to accomplish this will need to be installed externally.
Zone Valve end switches can be wired to together in parallel and connected to a fan center relay. See Figure 36 and 37. Do not apply power to the X4 terminal strip. Alternately the zone valves and thermostats can be connected to a zoning panel control system available from your local heating wholesaler.
Zone Pumps can be connected to the boiler / water heater with a zone pump control available from your local heating wholesaler.
1.9.4 Thermostat / Sensor Wiring
A Thermostat from a single zone heating system can be connected directly to the controller’s terminals X4.6 and X4.7. Do not apply power to the X4 terminal strip.
The Outdoor Sensor is not required for the boiler / water heater to operate. If the outdoor sensor is not connected, the boiler / water heater will operate at the designated maximum space heating water temperature. If outdoor reset functionality and the Summer Shut Down feature is required then the Outdoor Sensor must be connected to X4.8 and X4.9. The Outdoor Sensor is a 12K ohm thermistor type sensor. The sensor should be installed on the exterior of the building on the north side. The sensor should be installed so that it is not effected by any heat sources from the building such as a dryer or exhaust fan outlet, relief air or combustion air grill above a window or door, or mounted directly under a
deck or soft overhang.
DHW Aquastat or 10KΩ sensor can be connected to the controller’s terminals
X4.9 and X4.10. Do not apply power to the X4 terminal strip.
INSTALLATION
1-35
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
1-36
Figure 35: Electrical Wiring Connections (full page ladder diagram at back of this manual)
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 36: Suggested Field Wiring for Space Heating
BOILER SYSTEMS AND OPERATION
1-37
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 37: Suggested Field Wiring for Space Heating and priority DHW (for indirect DHW tank applications only)
1-38
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
2.0
2.1
BOILER / WATER HEATER SYSTEMS AND OPERATION
GENERAL
The DC series modulating condensing boilers / water heaters are designed to heat both your indoor space and your domestic hot water. The boiler / water heater’s unique heat exchanger design incorporates separate copper water ways for space heating and for domestic hot water generation.
The boiler / water heater’s control is equipped to provide outdoor reset control for the space heating load and also can provide a set-point water temperature for the space heating load. Installing the outdoor sensor is optional but recommended for
additional efciency.
The boiler / water heater is equipped with a factory installed pump. The pump is pre-wired and will operate with any call for space heating and when heating an IBC indirect water heater. The pump will not operate with a call for domestic hot water using the internal domestic hot water tankless coil.
The boiler / water heater pump will operate for 10 seconds every 24 hours to help prevent pump from seizing. The pump will be energized 24 hours after the last call for heat and every 24 hours after that until the next call for heat.
The DC series boiler / water heater can generate domestic hot water in several ways. The DC series boiler / water heater can be used as a tankless water heater with or without a storage tank and also with an IBC indirect water heater.
The boiler / water heater is equipped with an electronic controller, which ignites
the burner and continuously monitors the ame throughout each call for heat. The
control also displays the current operating conditions of the boiler / water heater and any error messages should a problem occur.
The boiler / water heater’s controller also provides frost protection. When the boiler / water heater’s heat exchanger becomes too cold the burner switches on to keep the heat exchanger warm. Please ensure that the condensate trap is protected from freezing. The boiler / water heater must be installed indoors in a heated space.
DANGER
HOT
BURN
Water temperture over 125°F (52°C) can cause severe burns instantly
°
or death from scalds.
Children, disabled, and elderly are at highest risk of being scalded.
°
See instruction manual before setting temperature at boiler.
°
Feel water before bathing or showering.
°
Temperature limiting valves are available, see manual.
°
BOILER SYSTEMS AND OPERATION
2-1
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
2.2
CONTROL
1
Power Indicator
2
Space Heating
3
Domestic Hot Water
4
Main Display
5
Fahrenheit and PSI
6
Celsius and Bar
7
Comfort / ECO / OFF - Indicator
8
Comfort / ECO / OFF - Indicator
9
Service Display
10
Flashes to indicate a fault
A
Power - ON / OFF
B
Space Heating / DHW Toggle
C
Minus
D
Plus
E
Fahrenheit/Celsius
F
Domestic Hot Water Comfort / Eco
G
Service
H
Reset Button
Table 8: Controller Indicators and Buttons
NOTE:
combination with a period after the letter. Example: C, c., c are all valid parameter codes. When adjusting settings, double check that you are in the correct parameter. See DC / HC Controller Manual for details.
2.3
INSTALLER INTERFACE
2.3.1 Appliance ON/OFF
The boiler / water heater can be switched on and off with the On/Off button. When the boiler / water heater is “ON”, the green LED above the On/Off button will be on. When the boiler / water heater is on and there is no call for heat or DHW the displays are blank. When the boiler / water heater is “OFF” the main display reads the system pressure, e.g. “14P” for 14 psi.
If the boiler / water heater is being powered up after a power outage, the boiler / water heater will return to heating as it was when the power was removed from the boiler / water heater.
2-2
The control displays codes that include upper and lower case letter and a
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
2.3.2 PSI and Fahrenheit / Bar and Celsius
PSI and Fahrenheit are the default setting as shipped from the factory. To change to Bar and Celsius simply press the to toggle Fahrenheit and Celsius.
NOTE
See separate publication
DC / HC Controller Manual (supplied with the boiler)
for discussion of displayed codes.
NOTE
The domestic hot water thermostat is adjusted to its lowest temperature position when shipped from the factory. It’s recommended to set the domestic hot water
thermostat to 120°F/49°C as
an initial setting and further
adjust as required. For energy efcient operation,
this setting should be set as low as practical for the consumer’s needs.
2.3.3 Programing Mode
There are 2 parameters available in the User Set-Up Menu.
USER MENU
Adjusting the Space Heating Water Temperature
To enter the User Menu simply hold down the Space Heating /DHW Toggle button for 2 seconds. The LED beside the will illuminate and the current maximum heating system water temperature will be displayed in the 4 digit display. To alter this value simply press the Plus + or the Minus - buttons.
Adjusting the Domestic Hot Water Temperature
Press the Space Heating /DHW Toggle beside the will illuminate and the current tankless domestic hot water temperature target is displayed in the Main Display. To alter this value simply press the Plus
Saving the Changes
To exit from the User Menu and save the changes press the Reset Pressing the On/Off button will also exit the User Menu but will NOT save the changes.
The Controller has four levels: User Menu, Installer Menu code (15), a Master Installer Menu code (20), RF Menu code (30),(future use.) See separate
publication DC / HC Controller Manual (supplied with the boiler) for more information.
CHECKING THE DHW FLOW
The DHW ow (read in US gallons per minute or in liters per minute) sensed by
the water heater can be read by pressing and holding the + button during DHW operation.
or Minus - buttons.
+
button a second time and the LED
button.
BOILER SYSTEMS AND OPERATION
2-3
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
2.4
TANKLESS DOMESTIC HOT WATER MODES
2.4.1 Tankless Domestic Hot Water - Standard, Comfort and ECO Comfort Modes
Standard Mode (both LEDs are off): The boiler’s heat exchanger will not maintain its domestic hot water temperature between demands for hot water. The boiler / water heater will respond to a call for domestic hot water as a priority over
the space heating demand. When the domestic hot water demand is satised the
boiler / water heater will return to the space heating load if the load is still calling.
Comfort Mode (the bottom LED is on): The boiler’s heat exchanger will maintain the pre-programmed temperature set in parameter n. or as set for the Tankless hot water temperature. This temperature will be the minimum temperature of the heat exchanger at all times unless the boiler / water heater is heating a lower temperature load.
ECO Comfort Mode (the top LED is on): This mode operates like the Comfort Mode but has the added advantage of learning when the domestic hot water is used. During the low use periods the boiler /water heater’s heat exchanger is allowed to cool.
To toggle between the 3 modes simply press the Domestic Hot Water Comfort / Eco button.
2.5
ADDING DOMESTIC HOT WATER STORAGE
2.5.1 Tankless Domestic Hot Water with a Storage Tank
The DC series boiler / water heater has the ability to connect a domestic hot water storage tank to the boiler / water heater to provide larger volumes of domestic hot water during peak demands.
The storage tank will be piped to the boiler’s domestic hot and cold water piping connections (see Figure #30 on Page 1-30). A bronze or stainless steel pump must be installed to circulate water from the storage tank through the boiler’s domestic hot water coil. The pump and the tank aquastat can be wired directly to the boiler’s control for ease of installation.
Alternately, the pump and aquastat can be wired together without connecting to
the boiler / water heater. When the pump is energized, the ow of water through the domestic hot water coil in the boiler / water heater will be sensed by the ow
sensor and activates the boiler / water heater. The boiler / water heater will switch off its internal pump and operate at its programmed water temperature.
2-4
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
The correct 10KΩ temperature sensor (or aquastat) must be
used to operate the indirect water heater properly. If the incorrect sensor is used the domestic hot water may
overheat causing serious
injury or death.
2.6
2.5.2 Domestic Hot Water with an IBC Indirect Water Heater
The DC series boiler / water heater can be connected to an IBC indirect water heater. Connect the IBC indirect water heater’s boiler / water heater supply and boiler / water heater return connections to the boiler’s primary loop (see Figure #28, Page 1-26). Properly sized piping must be installed. A properly sized pump must also be installed between the boiler / water heater and the IBC indirect water heater.
SPACE HEATING
2.6.1 Overview
The DC series boiler / water heater is designed to be installed in a primary/ secondary type piping system. The boiler / water heater comes complete with a factory installed boiler pump. The pump is designed to circulate heating system water through the boiler’s heat exchanger and primary loop piping only. The building’s distribution piping system requires a dedicated pump or pumps to provide circulation of the space heating water through the heating system. The building pump or pumps will require a separate control system or relays to operate the pumps.
Zoning of the space heating system can be accomplished many ways. Several control packages are available from your local wholesaler and offer an easy method of connecting the zoning system to the boiler / water heater. Example piping and electrical drawings are available at www.ibcboiler.com
The boiler / water heater supplies heat to the space using an Outdoor Reset Curve. With an outdoor sensor installed the boiler / water heater will automatically adjust its space heating water temperature based on the parameters programmed into the boiler / water heater. See separate publication DC / HC Controller Manual for parameter information. If the Outdoor Sensor is not installed, the boiler / water heater will use the temperature set in the User Set Up menu “Boiler Supply Temperature” to supply hot water to the space heating system.
STARTUP AND COMMISSIONING
2-5
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
2.7
NOTE
The boiler / water heater is equipped with a Frost
Protection feature. This feature will operate the boiler pump and the burner to help
protect the boiler / water
heater from freezing. If the
boiler / water heater is in a hard lock-out condition
the burner will not operate,
however the boiler / water
heater pump will operate.
IBC is not responsible for damages to the boiler, and/
or related components, nor property damages that may result from freezing conditions.
SEQUENCE OF OPERATION
The boiler / water heater will operate in a similar way for both a space heating and a domestic hot water call for heat. When the boiler / water heater is powered up the controller enters a self diagnostic mode and displays 2 in the Service Display.
The Sequence of Operation is as follows:
1. The boiler / water heater receives a call for heat from closing terminals X4.6
and X4.7 (24 volts). The boiler / water heater can also receive a call from
Domestic Hot Water heating from the internal ow sensor, or from a 10KΩ
sensor or aquastat (X4.9 and X4.10 in 24V terminal).
2. The boiler / water heater does a safety check and energizes the fan for a pre-
purge (Service Display = 3)
3. Once the 5 second pre-purge is compete, the boiler / water heater enters a 5
second trial for ignition (Service Display = 4). If the boiler / water heater fails to ignite, the boiler / water heater will compete a 5 second inter-purge then another 5 second trial for ignition. This is repeated 4 times before a hard lock out occurs. The Reset button and allow for another attempt.
4. Once the burner is lit and ame has been proven the boiler / water heater
operates as it is programmed (Service Display = 5 for Space Heating or 6 for Domestic Hot Water)
5. If the boiler / water heater reaches its target temperature and there is still a
call for heat or hot water. (Service Display = 1)
6. After the call for heat is satised, the boiler / water heater pump will operate
for an adjustable amount of time (Service Display = 0)
7. If the burner is on to maintain the heat exchanger temperature for DHW
Comfort mode or for Freeze Protection mode (Service Display = 7)
8. If the burner is on for Frost Protection (Service Display = 9)
must be pressed to reset the controller
Table 9: Operating Display and Service Display Codes.
2-6
MAIN
DISPLAY
[Pressure
e.g., 14 P]
(blank) (blank) No Call for Heat - Standby
XXX 0 Boiler / water heater pump running – pump post purge
XXX 1 Boiler / water heater water temperature reached target –
XXX 2 Self-test – When power is applied to the boiler / water
XXX 3 Fan Pre-purge , Inter-purge and Post-purge
XXX 4 Trial for Ignition and Flame Proving
XXX 5 Heating – Space Heating
XXX 6 Heating – DHW
XXX 7 Burner on for Comfort mode or Freeze Protection mode
SERVICE DISPLAY
- The boiler / water heater is OFF. Press the On/Off
DESCRIPTION
button to turn on the boiler
boiler / water heater pump is energized, call for heat still present
heater the controller enters a self diagnostic mode for 5 seconds
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
STARTUP AND COMMISSIONING3.0
3.1 LIGHTING AND SHUTTING DOWN THE BOILER
STARTUP AND COMMISSIONING
3-1
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
3.2 PRIOR TO START-UP
DANGER
Fill trap with water before
boiler / water heater is rst red to prevent exhaust
fumes from entering room.
Never operate the boiler /
water heater unless the trap is
lled with water.
Failure to comply will result
in severe personal injury or
death.
DANGER
Making adjustments to the IBC gas valve without
a properly calibrated gas combustion analyzer and by persons who are not trained and experienced in its use is forbidden. Failure to use an analyzer can result in an immediate hazard.
3.2.1 Pre-Ignition Checks
1. Fill condensation trap. Ensure venting system is complete and seal tested.
Conrm any common venting system at the installation site is isolated and
independent of the DC boiler / water heater, that any holes left from removal
of a previous boiler have been sealed, and that any resizing of the old ue
has been done.
2.
Check water piping system is fully ushed and charged, and that all air has
been discharged through loosened bleed caps. Use a minimum water pressure
of 12 psig and conrm pressure relief valve is installed and safely drained.
3. Check to see that adequate gas pressure is present at the inlet gas supply
test port. With the boiler / water heater gas valve shut off, open the test port
(using a small (1/8" or 3 mm) at screwdriver, open the test port by turning its
center-screw 1 full turn counterclockwise. Connect a manometer and open the gas control valve. Requirements are minimum 5" w.c and maximum 14" w.c. Check to ensure no gas leaks.
4. Perform a nal check of electrical wiring and provide power to the boiler /
water heater to initialize operation.
3.2.2 Test Ignition Safety Shutoff
With the boiler / water heater in operation, test the ignition system safety shutoff device by shutting the manual gas valve immediately outside the boiler / water heater case. Ensure boiler / water heater has shut off and the appropriate Error information is displayed on the Main Display screen. To restart boiler, reset power.
3.3
COMMISSIONING
The DC Series modulating boilers / water heaters are factory calibrated to operate with natural gas at sea level. The Low Fire (Zero Offset) screw is not to be
adjusted in the eld. The High re (Gas : Air Ratio Adjustment) screw may have
to be adjusted to attain optimum combustion results if required, however, no
mixture adjustment shall be performed unless done by a qualied technician using properly functioning and calibrated combustion analyzing equipment.
This boiler / water heater model can burn either Natural gas or Propane if
equipped with the correct specied orice. Examine the rating plate of the boiler / water heater to ensure it is congured for the fuel you are using. If
the boiler / water heater is to be converted from Natural Gas to Propane or from Propane to Natural Gas a Fuel Conversion Kit must be installed. The correct Fuel Conversion Kit part number can be found in Table 10.
MODEL NUMBER NATURAL GAS
TO PROPANE
DC 15-95 P-747 P-748
DC 15-96 P-747 P-748
DC 20-125 P-737 P-738
DC 33-160 P-702 P-703
Table 10: Fuel Conversion Kits
PROPANE TO NATURAL GAS
3-2
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
Check the rating plate of the boiler / water heater to ensure it is congured for the fuel
you are using. If the fuel is incorrect for the appliance,
a conversion kit must be ordered from IBC and the gas valve adjusted accordingly.
Failure to perform the
required fuel conversion can
result in an immediate hazard.
Gas Valve Adjust
Flue gas test port plug
The gas valve will automatically de-rate the maximum input in accordance with the density altitude, by approximately 2% per 1,000' above sea level. The gas valve’s zero governor will ensure that the gas:air mixture is not be affected at altitude.
To verify the proper operation of the gas valve in the eld, the following procedure can be carried out by a qualied technician (diagrams on this page).
1. Turn off the boiler’s gas shut off valve. With a small (1/8" or 3 mm) at
screwdriver, open the inlet gas supply pressure test port by turning its center-screw 1 full turn counterclockwise. Attach a manometer to the pressure test port and turn on gas to appliance. Static manometer reading should be ideally 7" w.c., for Natural Gas and 11" w.c. for Propane. Minimum and maximum static pressure should be between 7" and 14" w.c. Monitor pressure throughout the commissioning procedure. Pressure may droop up
to 1" to 2" w.c. at high re.
2. Allow the boiler / water heater to ignite / run against a large load, to maintain
high re. Enter the High Fire Manual Mode by pressing both the Service
and Plus + buttons together twice. “H” will be showing in the service display. NOTE: Do not make any adjustments if an “h” is showing in the service display. Allow the boiler / water heater to operate at High Fire for 3 minutes to stabilize. (The boiler / water heater will operate in manual mode for 10 minutes then switch back to the normal operating mode. To extend manual mode operation, press the Service and Plus + together twice while the boiler / water heater is operating in manual mode to reset the timer for 10 more minutes.) Pressing and holding + for more than 2 seconds while in the Service Mode will display the Flame Current in DC microamps. Expect
approximately 9.8μA at High Fire (6.5μA or higher at Low Fire).
3. With a combustion analyzer probe in the ue gas test port, turn the High Fire
(Gas : Air Ratio Adjustment) screw (see diagrams on this page) to achieve
results. This screw offers very ne adjustment, and may require several
turns. Clockwise richens, i.e. raises the CO2 value.
NOTE: Clock the gas meter to conrm full maximum rating plate input. Check
the measured results with Table 11 - High Fire.
4. Switch the boiler / water heater to low re by pressing both the Service
button and Minus - buttons at the same time. The boiler / water heater
will drop to low re. “L” will be showing in the service display. Compare the
readings with Table 11 - Low Fire.
5. Switch off the boiler / water heater by pressing the On/Off button. Turn
off the gas at the boiler / water heater gas shut off valve. Remove the ue
gas analyzer from the test port and reinstall the test port cap. Remove the gas pressure manometer from the gas valve and close the test port. Turn on the gas at the boiler / water heater’s gas shut off valve. Ensure there are no gas leaks and reinstall the front cover. Turn on the boiler / water heater by pressing the On/Off button.
STARTUP AND COMMISSIONING
CO2 VALUE (%) AT HIGH FIRE WITH THE FRONT COVER OPEN
NATURAL GAS PROPANE
Max. CO
Min. CO
CO
Max. CO
Min. CO
Table 11: CO
value 10.1% 11.5%
2
value 9.1% 9.8%
2
VALUE (%) AT LOW FIRE WITH THE FRONT COVER OPEN
2
value = value at High = value at High – 0.3%
2
value 9.1% 9.5%
2
Values and High and Low Fire
2
3-3
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
3.4
DANGER
Operating any IBC boiler /
water heater using a fuel other than the fuel listed on its rating plate is prohibited. If the information in this section
related to conversion to
alternate fuels is not followed exactly, a dangerous situation
can result, leading to re or
explosion, which may cause property damage, personal injury, or loss of life.
PROPANE ORIFICE CHART
MODEL NUMBER
DC 15-95 392
DC 15-96 392
DC 20-125 460
DC 33-160 580
ORIFICE SIZE
FUEL CONVERSION
The DC Series modulating boiler / water heater is factory re-tested to operate
with natural gas. The rating plate will be marked to indicate which fuel the particular boiler / water heater has been set up with. Firing a boiler / water heater with a fuel other than what is listed on the rating plate is prohibited unless the
following conversion procedure is completed by a qualied technician.
Refer to the preceeding section 3.3 - COMMISSIONING. The Low Fire (Zero Offset) valve adjustment cap on the gas valve has been factory set. This cap
must not be tampered with. The Zero-offset screw is not to be adjusted in
the eld.
Fuel conversion requires hardware adjustments (Orice Replacement) as well as
measurement and possible tuning of the gas :air mixture. Detailed instructions including parts and labeling are found in Fuel Conversion kits: Refer to Table 10
for the correct kit number.
CO2 VALUE (%) AT HIGH FIRE WITH THE FRONT COVER OPEN
NATURAL GAS PROPANE
Max. CO
Min. CO
CO
Max. CO
Min. CO
Table 12: CO
The following procedure must be carried out by a qualied technician.
value 10.1% 11.5%
2
value 9.1% 9.8%
2
VALUE (%) AT LOW FIRE WITH THE FRONT COVER OPEN
2
value = value at High = value at High – 0.3%
2
value 9.1% 9.5%
2
Values and High and Low Fire
2
NATURAL GAS ORIFICE CHART
MODEL NUMBER
DC 15-95 505
DC 15-96 505
DC 20-125 550
DC 33-160 725
ORIFICE SIZE
1. Select the correct Fuel Conversion Kit for your boiler / water heater from
Table 10.
2. Ensure the fuel conversion instructions supplied with the fuel conversion kit
are read, understood and followed carefully.
3. Ensure that the gas supply is turned off at the gas control valve.
4. Disconnect the gas valve harness plug from the gas valve.
5. Disconnect the nut at the gas valve outlet (top of the gas valve) and remove
the orice and O-ring.
6. Insert the correct orice into the O-ring and re-install into the nut at the gas
valve outlet (top of the gas valve) and tighten the nut.
7. Restore gas supply by opening the gas control valve, and using an approved
leak detection solution, soap test all joints.
8. Place the conversion labels associated with the new fuel onto the boiler
/ water heater at the positions indicated on the applicable conversion kit instruction sheet.
9. Carefully follow the “Prior to Start-Up” – Section 3.2 and “Commissioning” –
Section 3.3 procedures on the preceeding pages 3-2 and 3-3.
3-4
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Figure 36A: Blower (Torin) and Gas Valve Assembly (all models except HC/DC 15-95)
WARNING
Each DC series boiler / water heater is equipped with a Back Flow Valve installed at
Back Flow Insert. Note NG-only appers shown. Dual-fuel apper is black.
the outlet of the fan. Inspect
the Back Flow Valve annually.
WARNING
3.5.1 Gaining access to combustion chamber, burner
When converting a Natural Gas boiler / water heater to Propane, the Back Flow
Flapper must be replaced
with the black Propane Back
Flow Flapper, if not already
installed (see instructions in fuel conversion kit). Failure to
use the Propane Flapper may result in damage to the boiler, serious injury or death.
removal instructions
DIS-ASSEMBLY
1.
Turn off the main power switch to the boiler / water heater.
2. Turn off the gas supply valve to the boiler / water heater.
3. There is no need to drain the boiler’s water unless the boiler / water heater
will be subject to freezing conditions while the boiler / water heater is off.
4. Remove the front cover and allow the boiler / water heater to cool.
Figure 36B: Blower (EBM) and Gas Valve Assembly (HC/DC 15-95 only)
Figure 37: Orice and O-ring
STARTUP AND COMMISSIONING
3-5
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
NOTE
The safety warning regarding burner refractory on page
4-2 of this manual must be observed.
5. Disconnect the ue pipe from the condensate tray by rotating the nut
counter-clockwise about 1/4 turn. Slide the ue pipe up and dis-engage the bottom of the ue pipe from the condensate tray and slide down to remove.
6. Unplug the electrical connector at the gas valve.
7. Loosen both the lower gas valve connection nut. NOTE: There is an
O-ring in the lower gas connection and an O-ring and orice in the upper
gas valve connection. Place these in a safe location to be used for re­assembly. Cover the gas piping connections to prevent debris from entering the gas piping.
8. CAUTION: When removing the heat exchanger cover in step 9, be careful
not to damage the burner and refractory material located on the opposite side of the heat exchanger cover. Use caution when handling refractory materials. See Caution on page 4-2.
9. Remove all 9 or 11 – 6mm hex bolts and lock washers from the heat
exchanger cover and carefully remove the front cover complete with the fan and the gas valve attached. Carefully inspect the gasket sealing the heat exchanger to the heat exchanger cover for damage, hardness, cracks, and or discoloration. If damaged in any way the gasket must be replaced.
10. Place the heat exchanger cover in a safe location.
RE-ASSEMBLY
1.
Carefully inspect the gasket sealing the heat exchanger to the heat exchanger cover for damage, hardness, cracks, and/or discoloration. If damaged in any way the gasket must be replaced. Inspect and clean if necessary the mating gasket surface.
2. Place the heat exchanger cover onto the heat exchanger and loosely install
the 9 or 11 – 6mm hex bolts and lock washers removed in step 9. Tighten the 6mm hex bolts in a cross pattern as shown in diagram on this page.
3. Connect the gas line to the gas valve ensuring the O-ring is in place.
Tighten the gas valve nut. Ensure the upper gas valve connection is tight. Re-connect the gas valve electrical connection.
4. Re-connect the electrical connections to the fan.
5. Re-install the ue pipe to the vent connector at the top of the boiler / water
heater and to the condensate tray. Tighten the nut clockwise about 1/4 turn. Ensure the nut is properly engaged. Hand tighten only, Do Not Use
any tools to tighten the ue pipe nut.
6. Inspect the condensate trap for debris. Remove and clean if necessary. Fill
the condensate trap with water.
7. Turn on the gas supply valve to the boiler / water heater and inspect for
gas leaks. Use an approved leak detection solution; soap test all joints.
8. Ensure the boiler / water heater is full of water and purged of air if the
boiler / water heater was drained during dis-assembly - step 3.
9. Turn on the power to the boiler / water heater and create a call for heat or
for domestic hot water.
10. Inspect the gasket around the heat exchanger cover and ue pipe
connections for leaks.
11. Check ue gases for proper combustion. See Section 3.3 Commissioning
for proper adjustments.
12. Re-install the boiler / water heater cover and set the boiler / water heater
into normal operation.
3-6
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
MAINTENANCE4.0
4.1
CAUTION
The owner is responsible for general care of the boiler
/ water heater. Improper maintenance of the boiler /
water heater may result in a hazardous condition.
CAUTION
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
CAUTION
Periodic inspection of
Low Water Cut-Off Device including ushing of oat types is required, if installed as an accessory to the boiler /
water heater.
BOILER / WATER HEATER MAINTENANCE
4.1.1 General Care
Keep combustible materials and ammable liquids and vapours away from the boiler
/ water heater.
Keep vent terminals clear of obstructions (snow, dirt, etc.).
4.1.2 Inspection
Inspection of the boiler / water heater is to be performed annually by a qualied service technician.
4.1.3 Venting
Check vent terminals for and remove any obstructions (e.g. leaves, dust, other
debris).
Check, and clean or replace intake air lters or screens as required.
Check for holes or leaks in venting. Replace venting as needed.
Examine for any signs of moisture caused by sweating intake air pipes;
insulate as required.
Ensure proper resealing or reinstallation of venting on each servicing.
4.1.4 Condensate Traps
WARNING
Fill trap with water before
boiler / water heater is rst red to prevent exhaust
fumes from entering room.
Never operate the boiler /
water heater unless the trap
is lled with water. comply will result in severe
personal injury or death.
Failure to
WARNING
Whenever the burner is removed for inspection or boiler / water heater servicing, the sealing gaskets must be
examined and replaced if damaged.Upon re-assembly,
an approved leak test solution
must be applied around the
burner ange sealing area to ensure there is no leakage of combustible gas/air premix.
MAINTENANCE
Condensate trap must be examined every two months to see if cleaning is
necessary (refer to trap cleaning instructions, section 1.5.3 of this manual).
Ensure that trap has been re-lled completely before ring boiler / water
heater.
If condensate neutralization is used, check pH level of condensate discharge.
4.1.5 Burner
Annually, remove burner to inspect for extent of fouling (refer to burner
removal and reassembly instructions, section 3.5.1 of this manual). Blow clear
using compressed air. Ensure ame is stable and without excessive uttering. Normal ame pattern is evenly distributed over the burner surface.
If burner is operating improperly, remove and clean or replace. Use a CO
analyzer to determine proper combustion. See Table 11, page 3-3 for correct values.
Figure 38: Ignitor Gap - 3/16” / 4.5mm
2
4-1
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
CAUTION
The heat exchanger has a small amount of combustion
chamber insulation (refractory), which contains ceramic bers.
When exposed to extremely high temperatures, the ceramic
bers, which contain crystalline silica, can be converted
into cristobalite - which is
classied as a possible human
carcinogen.
Care should be taken to avoid disturbing or damaging
the refractory. If damage occurs, contact the factory for directions.
Avoid breathing and contact with skin and eyes and follow
these precautions:
1. For conditions of frequent use or heavy exposure,
respirator protection is
required. Refer to the “NIOSH Guide to the
Selection and Use of Particulate Respirators
Certied under 42 CFR 84" for selection and use of respirators certied by NIOSH.
For the most current
information, NIOSH can be contacted at 1-800-356-4676
or on the web at
www.cdc.gov/niosh.
2. Wear long sleeved, loose tting clothing, gloves and
eyes protection.
3. Assure adequate ventilation.
4. Wash with soap and water after contact.
5. Wash potentially contaminated clothes separately from other laundry and rinse washing machine thoroughly.
6. Discard used insulation in an air tight plastic bag.
NIOSH stated rst aid:
Eye contact - Irrigate and
wash immediately.
Breathing - Provide fresh
air.
4-2
4.1.6 Heat Exchanger
During annual inspection (with the heat exchanger cover removed), examine the heat exchanger for signs of contamination and clean if necessary. In areas of poor gas quality or contaminated combustion air, there may be a buildup of black plaque (typically sulfur). Other fouling agents: airborne dust, debris and volatiles. Clean the heat exchanger surface with a stiff plastic bristle brush only.
Inspect the heat exchanger gasket for signs of discoloration or brittleness. Replace as needed. Refer to heat exchanger cover removal instructions in Section 3.5.1 for access to combustion chamber and heat exchanger. Note that the safety
warning regarding burner refractory on this page must be observed.
4.1.7 Pump
Check that the pump is on in normal space heating operation and that the water Delta T is reasonable for the heating application. See 1.6.3 about bleeding air from the pump.
4.1.8 Gas Piping
Check for damage or leaks and repair as needed.
4.1.9 Control Module
Check that boiler / water heater operation is consistent with the steps in
Section 2.7 Sequence of Operation.
Check that water temperature targets and setpoint are satisfactory and have
not been adversely amended.
Check that the domestic hot water generation is performing as expected.
Fouling of the interior of the domestic heating coil can cause poor performance.
4.1.10 Water Heating System
Check water pressure and temperature. There should be no noticeable change if boiler / water heater and system components are functioning normally. Check for any noise in the system.
Check heating system water piping for damage or leaks and repair as needed.
Check for 12-15 psig in normal operation, and look to ensure pressure does not
run up toward 30 psig at high temperature. If pressure rises sharply, consider
replacement of expansion tank. Check also for noise at high re, which may
signal water quality problems.
Water chemistry shall be of a quality generally accepted as suitable for
hydronic applications. See Section 1.6 for details.
Ensure any direct “city ll” water connections are left in the closed position to
minimize exposure to leaks and ooding.
4.1.11 Freeze Protection
The boilers / water heaters control will operate the boiler / water heater to protect the boiler / water heater from freezing. If the boiler / water heater and system components are subject to possible freezing condition then a freeze protection solution is recommended. Check freeze protection. Use only antifreeze made
specically for hydronic systems. Inhibited propylene glycol is recommended.
Antifreeze concentration must be between 25% and 50% of the total volume of water in the system.
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
WARNING
Do not use automotive-
type ethylene or other
types of automotive glycol
antifreeze, or undiluted
antifreeze of any kind. This may result in severe boiler / water heater damage. It
is the responsibility of the Installer to ensure that glycol solutions are formulated to inhibit corrosion in hydronic heating systems of mixed materials. Improper mixtures
and chemical additives may
cause damage to ferrous and non-ferrous components as well as non-metallic, wetted components, normally found in hydronic systems. Ethylene glycol is toxic, and may be prohibited for use by codes applicable to your installation
location. For environmental and toxicity reasons, IBC
recommends only using non­toxic propylene glycol.
NOTE
Installers should inquire of local water purveyors as to
the suitability of their supply for use in hydronic heating systems.
If water quality is questionable,
a local water treatment expert must be consulted for testing,
assessment and, if required,
treatment.
Alternatively, water or hydronic uid of known quality can be
brought to the site.
CAUTION
Before testing the relief valve, make certain the discharge
pipe is properly connected to
the valve outlet and arranged
to contain and safely dispose
of equipment discharge.
4.1.12 Boiler / Water Heater Treatment
Check consistency of any boiler / water heater treatment used, for appropriate mixture. Chemical inhibitors are consumed over time, lowering their density.
Verify proper operation after servicing.
4.1.13 Relief Valve - Maintenance and Testing
The relief valve manufacturer requires that under normal operating conditions a “try lever test” must be performed every two months. Under severe service conditions, or if corrosion and/or deposits are noticed within the valve body, testing must be performed more often. A “try lever test” must also be performed at the end of any non-service period.
Test at or near maximum operating pressure by holding the test lever fully open
for at least 5 seconds to ush the valve seat free of sediment and debris. Then
release the lever and permit the valve to snap shut.
If the lever does not activate, discontinue use of equipment immediately and
contact a licensed contractor or qualied service personnel.
If the relief valve does not completely seal, and uid continues to leak from the discharge pipe - perform the test again to try and ush any debris that may be
lodged in the valve. If repeated tries fail to stop the leakage, contact a licensed
contractor or qualied service personnel to replace the valve.
While performing a “try lever test”, a quantity of heat transfer uid will be discharged from the piping system and the system pressure will drop. This uid
must be replaced. It is highly recommended that a system pressurization unit, such as an Axiom Industries model MF200 be employed to rell and pressurize
your system. Capture the discharged uid in a container and recycle it by
returning it to the system feeder unit. This is particularly important when your system contains treatment chemicals or glycol solutions. If the system employs
plain water, the boiler / water heater auto ll valve must be turned on in order to recharge the lost uid.
4.1.14 Domestic Hot Water System
Quality of the domestic cold water is very important to the longevity of the boiler / water heater. The recommended pH of the domestic water is between 6.5 and
8.5. The internal domestic water heat exchanger tubing and the ow sensor is
subject to fouling if exposed to hard water (over 7 grains of hardness) or has a TDS of 500mg/L or higher. See Table 13.
DESCRIPTION MAX MIN
Water Pressure 150 psi 40 psi
Programmable water temperature 149°F (65°C) 104°F (40°C)
Minimum Flow Rate to Activate DHW Sensor N/A 0.5 GPM
Acceptable pH range 8.5 pH 6.5 pH
Chloride 250 mg/L
Iron 0.3mg/L
Total Dissolved Solids 500mg/L
Total Hardness 7 grains
Table 13: Domestic Water Quality Guidelines
MAINTENANCE
4-3
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
DANGER
When servicing or replacing
the fan the following parts
must be moved from the old
fan to the new fan.
Venturi
Back Flow Valve
Failure to relocate these parts to the new fan may cause an immediately hazardous situation which must be
avoided in order to prevent
serious injury or death.
4.1.15 Fan and gas valve removal instructions
1. Turn off the power and the gas supply to the boiler / water heater.
2. Remove the front cover and allow the boiler / water heater to cool down.
3. Disconnect the 2 electrical plugs attached to the fan.
4. Loosen the union nut at the top of the gas valve. Carefully remove the Orice
and O-ring and keep in a safe place for re-installation later. Ensure you protect the gas valve outlet from dust and debris.
5.
Remove the 2 hex nuts connecting the fan to the burner housing and carefully
remove the fan. You will nd a gasket attached to the fan outlet as well as a back ow valve above it, inserted in the heat exchanger. Keep these items in
a safe place for re-installation.
6. If the removed fan is to be re-installed, ensure the fan and venturi are clean
and dust free.
4.1.16 Fan and gas valve re-assembly instructions
1. If the fan is being replaced, move the venturi to the new fan. Note that the t
is tight.
2. Place the fan gasket on the outlet of the fan housing. The gasket has 2
locator pins to ensure the gasket does not move during installation.
3. Attach the fan to the burner housing and install the 2 hex nuts. Tighten the 2
hex nuts with a wrench.
4. Insert the Orice and O-ring between the gas valve outlet and the gas line to
the fan. Tighten the gas valve union nut with a wrench. Ensure the gas valve inlet (lower) nut is tight.
5. Connect the 2 electrical plugs to the fan
6. Restore gas supply to the boiler / water heater and test the gas valve inlet for
gas leaks.
7. Restore power to the boiler / water heater and create a call for heat or hot
water.
8. Check for leaks at the gas valve outlet and the connection between the fan
and the burner housing.
9. Install the cover to the boiler / water heater.
10. Reset the boiler / water heater to normal operation.
4-4
Figure 39
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.0 TROUBLESHOOTING
NOTE
This boiler / water heater is equipped with a blocked vent shutoff system, which
closes the gas supply upon detection of an irregular
venting condition.
The troubleshooting section is divided into 4 sections:
5.1 Preliminary Checks
5.2 Electronic Components
5.3 Warnings and Faults
5.4 Other Faults
Often, a problem can be identied and solved through simple checks of the basics: conrming the electrical power supply, gas ow and resetting the thermostat
control. To extend the cover of such preliminary checks, the boiler’s control module offers a clear visual display of the status of the various control circuit components.
Should a problem remain unsolved after applying the preliminary checks, proceed to the detailed system review, using the Troubleshooting Guide. The Guide covers potential error conditions as grouped into the following categories:
5.3.1 Warning Codes
5.3.2 Fault Codes
5.4.1 Burner does not Ignite
5.4.2 Burner Ignites Noisily
5.4.3 Burner Resonating
5.4.4 The Power is Reduced
5.4.5 No Space Heating
5.4.6 Indoor Temperature Does Not Reach Desired Temperature
5.4.7 No Hot Water (DHW)
5.4.8 Hot Water Does Not Reach Temperature
5.1
Below each section is a list of Symptoms, Diagnoses, and Remedies.
Also provided with this manual are a number of diagrams (see Section 6.0) for use with troubleshooting including:
Electrical Wiring Diagrams
Boiler / Water Heater Component Layout Diagrams
PRELIMINARY CHECKS
The rst step in troubleshooting this system should be a review of the Controller’s
display screen. There are a number of diagnostic features incorporated in the software that evaluate system integrity, display error conditions and provide initial suggested remedial actions.
In addition to checking the display, the following list is a guideline for troubleshooting:
1. Conrm power to the boiler: check that control module display is on (e.g.
display is lit).
2. Check that boiler / water heater is not in a safety lockout.
3. Ensure wiring is clean and secure.
4. Check that gas is reaching the unit.
5.
Conrm water system is properly charged to 12 psig and pump is serviceable.
TROUBLESHOOTING
5-1
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
Water temperature sensors
5.2
ELECTRONIC COMPONENTS
This section details the method for troubleshooting the non-standard electronic components on the boiler / water heater including the electronic water pressure sensor – type LWCO and the temperature sensors.
5.2.1 Temperature Sensors
The resistance of the temperature sensors varies inversely with temperature. To test, measure the temperature of the sensed environment and compare with the value derived from the measurement of the resistance (obtained by connecting a
good quality test meter capable of measuring up to 5,000 kΩ (5,000,000Ω) at the
controller end of the sensor lead).
To obtain a resistance reading, remove power to the boiler / water heater. For the supply water and return water temperature sensors, remove the wire leads by disconnecting their respective Molex connectors. Place multi-meter probes into sensor’s male Molex connector socket. Do not apply voltage to the sensor (damage may result).
12KΩ Temperature Sensors supplied with boiler / water heater. See Table 14 for resistance values.
SENSOR TYPE PURPOSE LOCATION
S1 NTC 12KΩ Supply Water Temperature Upper Left of Heat
Exchanger
S2 NTC 12KΩ Return Water Temperature Lower Left of Heat
Exchanger
S3 NTC 12KΩ Domestic Hot Water DHW Supply Pipe
S4 NTC 10KΩ Hot Water Tank External Water Heater
S5 NTC 12KΩ Outdoor Sensor Outdoors (North side)
NTC 12KΩ Flue Gas Temperature Bottom of Heat Exchanger
at Flue outlet
Water Pressure Heating Supply Pipe
Temperature and Pressure Sensors
TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE
F / C Ω - ohm F / C Ω - ohm F / C Ω - ohm
5F / -15C 76,020 77F / 25C 12,000 149F / 65C 2,752
14F / -10C 58,880 86F / 30C 9,805 158F / 70C 2,337
23F / -5C 45,950 95F / 35C 8,055 167F / 75C 1,994
32F / 0C 36,130 104F / 40C 6,653 176F / 80C 1,707
41F / 5C 28,600 113F / 45C 5,522 185F / 85C 1,467
50F / 10C 22,800 122F / 50C 4,609 194F / 90C 1,266
59F / 15C 18,300 131F / 55C 3,863 203F / 95C 1,096
68F / 20C 14,770 140F / 60C 3,253 212F / 100C 952
Table 14: Temperature Sensor Resistance Values – 12KΩ sensors.
5-2
INSTALLATION AND OPERATION INSTRUCTIONS
Fan Power and Control Plugs ­Torin fan for DC/HC models except 15-95
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.2.2 Fan/Blower
Operating power is provided by means of a separate 120 VAC connector at the upper right side of the fan (white/black/green). Control of the fan is provided via a four lead connector at the bottom of the fan.
5.2.3 Thermostat Connections
The boiler / water heater controller is designed to heat a single space heating load. The load can consist of a single zone or several zones. In either case the ‘Call for Heat’ must be from a device providing a DRY CONTACT and connected to X4.6 and X4.7. The use of power robbing thermostats directly will cause the boiler / water heater to operate erratically. If a power robbing thermostat is to be used it will have to be isolated through a relay.
5.2.4 Water Pressure Sensor-Type Low Water Cut Off (LWCO)
The DC boiler / water heater is equipped with a pressure sensor which serves as a low-water cut-off. The water pressure is displayed in the main display when the pressure is low. For example a system water pressure of 4.6psi would be
displayed as 4.6P. If the pressure is too low the controller will ash an error
message in the main display by toggling between the actual pressure and LO. Simply increase the system pressure to correct this error. The water pressure in the heating system must be higher than 8psi for the boiler / water heater to reach
maximum ring rate. When the water pressure less than 8psi, the boiler / water heater will restrict its ring rate. If the pressure is less than 4psi then the boiler / water heater will not re at all.
Domestic Water Flow Sensor
Water Pressure Sensor Type LWCO
TO TEST THE OPERATION OF THE PRESSURE SENSOR – TYPE LWCO
1.
Turn off the boiler / water heater at the controller by pressing the button.
The current system pressure will be displayed.
2.
Isolate the space heating circuit and reduce the water pressure. The displayed water pressure should drop as the system water is being removed. If the pressure is remaining steady then the pressure sensor may be blocked or faulty. If so, drain boiler / water heater and replace sensor, or dislodge any blocking debris from sensor inlet channel and reinsert.
3. If the pressure sensor is OK then simply rell the boiler / water heater and
open the closed valves. Ensure the system pressure is adequate for the heating system.
PRESSURE SENSOR LWCO REPLACEMENT
1.
Turn off the power to the boiler / water heater.
2. Isolate and drain the boiler / water heater.
3. Remove the Vent Stack.
4. Disconnect the electrical connection to the sensor.
5. Carefully remove the clip at the base of the sensor.
6. Twist the sensor as you are pulling to remove from the socket. There may
be some water leakage at this point. Ensure the water does not spill into the controller.
7. Push the new sensor into the socket while twisting slightly. Careful not to
damage the O-ring.
8. Reinstall the clip at the base of the sensor to ensure the sensor does not
come out when the boiler / water heater is pressurized.
TROUBLESHOOTING
5-3
DHW Temperature Sensor
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
9. Connect the electrical connector to the sensor.
10. Reinstall the vent stack.
11. Restore water pressure to the boiler / water heater.
12. Restore power to the boiler / water heater.
5.2.5 Vent High-Limit
This sensor has been installed to ensure the boiler / water heater is shut down safely if the heat exchanger or the venting system becomes blocked.
The Vent Hi-Limit is located at the bottom of the heat exchanger just to the left of the vent outlet and above the condensate tray. For access, remove the vent stack and the condensate tray.
5.2.6 Domestic Hot Water Flow Sensor
The DC series boilers / water heaters are equipped with a ow sensor to measure water ow through the domestic hot water circuit in the boiler / water heater. The minimum ow required to activate the boiler / water heater is 0.5
GPM or 2 L/min.
To service or replace the Water Flow Sensor:
Disconnect power to the boiler
Turn off the Cold and Hot water valves below the boiler, release the water pressure and drain the domestic hot water circuit. Leave the drain valves open.
Disconnect the Molex connector at the sensor
Remove the sensor by turning the nut counter-clockwise. Take care not to
drain the water onto any of the electrical components.
Clean or replace the ow sensor as required and reassemble in reverse order.
5.2.7 Domestic Hot Water Sensor
The DC Series boilers / water heaters are equipped with a domestic hot water temperature sensor. The sensor is located on the hot water outlet pipe and is just behind the boiler’s condensate tray. For access, remove the vent stack and the condensate tray.
5.2.8 Outdoor Sensor
An Outdoor Sensor is supplied with each boiler / water heater. The sensor should be mounted on the north side of the building away from any direct sunlight. The sensor must also be kept away from any heat sources such as exhaust fan outlets, dryer outlets, mechanical room ventilation grills etc.
The Outdoor Sensor is a 12KΩ sensor with resistance values as listed in Table
14. If the sensor is not connected to the boiler, the boiler / water heater will operate at the Boiler / Water Heater Supply Temperature set in the User Set Up menu and operate as a Set Point load.
5-4
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.2.9 DHW Tank Sensor
The DC and HC Series boilers / water heaters allow the use of a tank sensor for controlling the domestic hot water tank temperature. IBC Indirect water tanks
come with a 10KΩ sensor. An Aquastat may also be used.
If a eld supplied domestic hot water sensor is used, it must be a 10KΩ sensor
matching the following table.
TEMPERATURE RESISTANCE TEMPERATURE RESISTANCE
°F °C Ω °F °C Ω
0 -18 85,362 100 38 5,828
5 -15 72,918 105 41 5,210 10 -12 62,465 110 43 4,665 15 -9 53,658 11 5 46 4,184 20 -7 42,218 120 49 3,760 25 -4 39,913 125 52 3,383 30 -1 34,558 130 54 3,050 35 2 29,996 135 57 2,754 40 4 26,099 140 60 2,490 45 7 22,763 145 63 2,255 50 10 19,900 150 66 2,045 55 13 17,436 155 68 1,857 60 16 15,311 160 71 1,689 65 18 13,474 165 74 1,538 70 21 11,883 170 77 1,403 75 24 10,501 175 79 1,281 80 27 9,299 180 82 1,172 85 29 8,250 185 85 1,073 90 32 7,334 190 88 983 95 35 6,532 195 91 903
Temperature Sensor resistance values – 10KΩ sensor
TROUBLESHOOTING
5-5
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.3 WARNINGS AND FAULTS
5.3.1 Warning Codes
During operation the controller can detect unusual situations and can take action to avoid damage to the heat exchanger or other unsafe operations. During these situations the controller will limit the temperature and power output of the burner, or temporarily disable operation entirely.
These warnings are shown ashing and visible on the main display, and only displayed when an unusual reading is
currently detected.
MAIN DISPLAY DISPLAY FAULT POSSIBLE SOLUTION
E1 Flue gas temperature approaching limit
E2 Direct DHW Tank Error - No ow
detected when enabling the external DHW pump
E3 S3 – DHW Sensor Open
E4 S3 – DHW Sensor Short
E5 S5 – Outdoor Sensor Short
E6 No pressure sensor detected (voltage
< 0.25V on orange sense wire, space heating is disabled)
E7 Pressure sensor out of range (above
4.25Bar/47psi, space heating is disabled)
LO P Boiler loop pressure too low
POLE Polarity detection fault
RF Physical stress on control board Loosen control board mounting screws
Supply water temperature too high
Ambient temperature too high
Check positioning of ue gas sensor
Heat exchanger front panel loose, check bolt torque
Check heat exchanger for contamination or debris
Replace ue gas temperature sensor
Pump failed – Replace pump
DHW piping loop air locked – Bleed Air
Flow Sensor / Flow Restrictor blocked – Remove and
Clean
Flow Sensor Faulty – Replace
Check wiring
HC boiler dened as DC
Replace Sensor
Check wiring
Replace Sensor
Check wiring
Replace Sensor
Bring the system back up to pressure
Check pressure sensor
Replace pressure sensor
Switch the Line and Neutral wire on the power supply
Check grounding
Check for high potential on Neutral wire
Replace controller
5-6
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.3.2 Fault codes
If the fault LED is ashing, the controller has detected a fault. A fault code will be displayed on the main display. Once
the fault has been corrected the burner controller can be restarted. Press the Reset button on the operating panel to restart the burner controller.
MAIN DISPLAY DISPLAY FAULT POSSIBLE SOLUTION
10, 11, 12, 13, 14 Sensor fault S1
Supply Sensor (upper left side of the heat exchanger)
20, 21, 22, 23, 24 Sensor fault S2
Return Sensor (lower left side of the heat exchanger)
0 Sensor fault after self check Replace S1 and/or S2
1 Temperature too high
2 S1 and S2 interchanged
4 No ame signal
5 Poor ame signal
6 Flame detection fault
8 Incorrect fan speed
18 Flue Gas Temperature Sensor
Open – Lockout Condition
19 Flue Gas Temperature Sensor
Short – Lockout Condition
29,30 Gas valve relay faulty Replace controller
See below, 1 – Temperature too high
Check the positioning of S1
Check wiring for break
Replace S1
Check the positioning of S2
Check wiring for break
Replace S2
Air in system. Bleed the system of any remaining air
Pump not running, bleed air from and/or replace the pump
Insufcient ow in installation, radiators closed
Check wiring harness
Replace S1 or S2
Gas valve closed
Gas supply pressure too low or drooping under load
Gas valve or ignition unit not powered
No or incorrect ignition gap
Condensate drain blocked
Check grounding of all parts
Condensate drain blocked
Gas supply pressure too low or drooping under load
Check ignitor and ignition cable
Check gas valve adjustment
Check grounding of all parts of the installation
Check combustion air supply and ue gas exhaust piping and
terminations, possible ue gas recirculation in the system
Replace ignition cable + ignitor cap
Replace ignition module
Replace controller
Fan rubbing on casing
Wiring between fan and casing
Check wiring for poor wire contact
Replace fan
Replace controller
Inspect heat exchanger for fouling and clean as required
Check wiring
Replace Sensor
Inspect heat exchanger for fouling and clean as required
Check wiring
Replace Sensor
TROUBLESHOOTING
5-7
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.4 OTHER FAULTS
5.4.1 Burner Does Not Ignite
POSSIBLE CAUSES SOLUTION
Gas valve is closed. Open gas valve.
Air in gas line. Remove air form gas line.
Gas supply pressure too low. Contact the gas supply company.
No ignition. Replace ignition electrode.
No spark. Ignition module on gas valve faulty. Check the cabling. Check the ignitor cap. Replace the ignition module.
Gas/air adjustment not correctly set. Check adjustment. See gas/air adjustment.
Fan faulty. Check the wiring. Check the fuse (3.15A), if necessary, replace the fan.
Fan dirty. Clean the fan.
Gas valve faulty. Replace the gas valve. Re-adjust the gas valve, see gas/air adjustment
5.4.2 Burner Ignites Noisily
POSSIBLE CAUSES SOLUTION
Gas supply pressure too high. Gas pressure regulator may be faulty. Replace the regulator or contact the
Incorrect ignition gap.
gas company.
Replace the ignitor.
Check the ignitor gap (3/16” / 4.5mm).
Gas/air adjustment not correctly set. Check the setting. See gas/air adjustment.
Weak spark.
Check the ignition spark gap.
Replace the ignitor.
Replace the ignition module on the gas valve.
5.4.3 Burner Resonating
POSSIBLE CAUSES SOLUTION
Gas supply pressure too low. Gas pressure regulator may be faulty. Replace the regulator or contact the
Recirculation of combustion gasses. Check combustion air supply and ue gas exhaust piping and terminations,
Gas/air adjustment not correctly set. Check the setting, see gas/air adjustment.
gas company.
possible ue gas recirculation in the system.
5.4.4 The Power is Reduced
POSSIBLE CAUSES SOLUTION
At high rpm the power has fallen by more than 5%.
5-8
Check appliance and ue system for fouling.
Clean the appliance and ue system
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.4.5 No Space Heating
POSSIBLE CAUSES SOLUTION
Room thermostat (end switches or zone controller) / Outdoor sensor faulty.
No voltage (24V DC).
Internal Pump not running.
Burner not ring on space heating: sensor S1 or
S2 faulty.
Burner does not ignite. See 5.4.1 Burner Does Not Ignite
Room thermostat must be a DRY CONTACT style thermostat
Check the wiring.
Check and/or Replace the thermostat (end switches or zone controller).
Replace the outdoor sensor.
Check the wiring against the diagram.
Check the connector terminals X4.6 and X4.7 for 24V DC with thermostat
wires disconnected.
Check the Fuse.
Replace the controller.
Check the power supply.
Check connector X2.7 and X2.8 for 120VAC while the pump should be
running.
Replace faulty pump if 120VAC is present when the pump should be
running.
Replace the controller if 120V is not present when the pump should be
running.
Replace sensor S1 or S2. See fault code.
5.4.6 Indoor Temperature Does Not Reach Desired Temperature
POSSIBLE CAUSES SOLUTION
Room thermostat setting incorrect. Check the setting and if necessary adjust: Set heat anticipator to 0.1A.
Water temperature is too low. Increase the space heating water temperature. See Table of Programmable
Water temperatures are set incorrectly Target water temperature is set higher than the maximum water
Pump not running correctly. Pump setting is too low (variable speed pumps only).
No circulation in the heating system. Ensure the zone valves are open and there are no air blockages.
No heat transfer as a result of lime scale or fouling in the heat exchanger.
Thermostat must be a DRY CONTACT style thermostat
Parameters in DC / HC Controller Manual. Check outdoor sensor and wiring for short-circuit.
temperature.
Increase pump setting, or replace the pump.
De-scale or ush the heat exchanger on the space heating side.
5.4.7 No Hot Water (DHW)
POSSIBLE CAUSES SOLUTION
Flow sensor not functioning.
No voltage at the ow sensor (5V DC). Check the wiring according to the diagram.
Burner not ring on DHW: S3 faulty. Replace S3.
Burner does not ignite. See 5.4.1 Burner Does Not Ignite
DHW ow < 2.0 l/min – .5 GPM.
Clean or replace the ow sensor.
TROUBLESHOOTING
5-9
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
5.4.8 Hot Water Does Not Reach Temperature
POSSIBLE CAUSES SOLUTION
DHW ow too high. Adjust the inlet assembly, insert a ow restrictor.
Temperature setting for water circuit too low. Adjust the hot water circuit, depending on the desired temperature and
Water temperatures are set incorrectly Target water temperature is set higher than the maximum water
No heat transfer as a result of lime scale or fouling in the heat exchanger DHW side.
Cold water temperature <5°C.
system conguration. See Table of Programmable Parameters in DC/HC
Controller Manual.
temperature.
Descale or ush the exchanger DHW side.
5-10
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
6.0 DIAGRAMS
6.1 - PARTS DIAGRAMS
6.2 - WIRING DIAGRAMS
DIAGRAMS
6-1
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
6.1 PARTS DIAGRAMS
DC 15-95 Modulating Boiler / Water Heater – Parts Assembly
Diagram 6.1-1: Boiler / water heater assembly parts
6-2
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
ITEM NO. PART NO. DESCRIPTION QTY
10 240-067 IGNITOR 1 20 250-622 GASKET, IGNITOR 1 30 250-623 VIEWPORT HOLDER 1 40 250-624 GASKET, VIEWPORT HOLDER 1 50 250-625 GASKET, VIEWPORT GLASS 1 60 250-626 VIEWPORT GLASS 1 70 170-017 HEAT EXCHANGER DC 95 1 80 250-688 GASKET, H.Ex. FRONT PANEL, DC/HC 95 1 90 180-114 BURNER 1
100 250-646 GASKET, BURNER 1 110 250-627 GASKET, FAN 1 115 XXX GASKET, FAN - DISCONTINUED MODEL 120 240-145 FAN, EBM 1 130 250-633 GASKET, DHW WATER PIEP 3 140 250-634 GASKET, PUMP 2 150 240-144 VENTURI, 500, DC/HC 95 1 155 250-732 GAS LINE, UPPER, DC/HC 95 1
160
170 150-175 O-RING FOR ORIFICE 1 175 150-206 GASKET, GAS VALVE, INLET 1 180 180-097 GAS VALVE 1 190 240-069 GAS VALVE CABLE/INGITION MODULE 1 200 250-628 GAS LINE, LOWER 1 210 240-070 DHW TEMPERTURE SENSOR 1 220 250-629 SUPPLY PIPE, DHW 1 230 250-630 RETURN PIPE, DHW 1
235
240 240-071 WATER FLOW SENSOR 1 250 250-631 RETURN PIPE 1 260 180-098 PUMP 1 270 500-073 DOOR ASSEMBLY, DC/HC 95 280 500-116 CONTROLLER ASSEMBLY, DC/HC 95, 96 1 290 190-123 CONDENSATE PIPE ASSEMBLY 1 300 190-124 SEAL, COND. PIPE TO BOTTOM PAN 1 310 180-100 BOTTOM PAN, HEAT EXCHANGER 1 320 240-076 VENT HIGH LIMIT SWITCH 1 330 190-119 FITTING, 1/2" NPT-M 1 340 190-120 FITTING, 3/4" NPT-M 2 350 190-121 FITTING, 1" NPT-M 2 360 180-113 CONDENSATE TRAP, LONG DC SERIES 1 370 250-638 CONDENSATE TRAP HOOK 1 380 240-072 WATER PRESSURE SENSOR TYPE LWCO 1 385 150-204 C-CLIP, WATER PRESSURE SENSOR 1 390 240-073 WATER TEMPERATURE SENSOR 2 395 150-221 CLIP, WATER TEMPERATURE SENSOR 2 400 250-632 SUPPLY PIPE 1 410 250-635 GASKET, SUPPLY PIPE 1 420 250-674 EXHAUST DUCT, INTERNAL, DC/HC 95 1 430 250-636 EXHAUST DUCT 1 440 250-637 INTAKE DUCT 1
not shown 210-035 FAN POWER CABLE 1
180-095 ORIFICE, 505, NATURAL GAS, DC/HC 95 180-198 ORIFICE, 392, PROPANE, DC/HC 95
180-134 FLOW RESTRICTOR, DC 124, 125, 160
180-140 FLOW RESTRICTOR, DC 84
1
1180-135 FLOW RESTRICTOR, DC 106
Some parts are available in Kits. Please visit www.ibcboiler.com for more information.
DIAGRAMS
Diagram 6.1-2: Boiler assembly parts list (refer to Diagram 6.1-1 on opposite page)
6-3
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
DC 15-96, 20-125, and 33-160 Modulating Boilers / Water Heaters – Parts Assembly
Diagram 6.2-1: Boiler / water heater assembly parts
6-4
INSTALLATION AND OPERATION INSTRUCTIONS
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
ITEM NO. PART NO. DESCRIPTION QTY
10 240-067 IGNITOR 1 20 250-622 GASKET, IGNITOR 1 30 250-623 VIEWPORT HOLDER 1 40 250-624 GASKET, VIEWPORT HOLDER 1 50 250-625 GASKET, VIEWPORT GLASS 1 60 250-626 VIEWPORT GLASS 1
70
80 250-689 GASKET, H.Ex. FRONT PANEL, DC/HC 96, 125, 160 1
90 180-114 BURNER 1 100 250-646 GASKET, BURNER 1 115 XXX GASKET, FAN - DISCONTINUED MODEL 110 250-627 GASKET, FAN 1 120 240-068 TORIN FAN 1 130 250-633 GASKET, DHW WATER PIPE 3 140 250-634 GASKET, PUMP 2
150
155 250-733 GAS LINE, UPPER, DC/HC 96, 125, 160 1
160
170 150-175 O-RING FOR ORIFICE 1 175 150-206 GASKET, GAS VALVE, INLET 1 180 180-097 GAS VALVE 1 190 240-069 GAS VALVE CABLE/INGITION MODULE 1 200 250-628 GAS LINE, LOWER 1 210 240-070 DHW TEMPERATURE SENSOR 1 220 250-629 SUPPLY PIPE, DHW 1 230 250-630 RETURN PIPE, DHW 1
235
240 240-071 WATER FLOW SENSOR 1 250 250-631 RETURN PIPE 1 260 180-098 PUMP 1 270 500-074 DOOR ASSEMBLY, DC/HC 96, 125, 160
280
290 190-123 CONDENSATE PIPE ASSEMBLY 1 300 190-124 SEAL, COND. PIPE TO BOTTOM PAN 1 310 180-100 BOTTOM PAN, HEAT EXCHANGER 1 320 240-076 VENT HIGH LIMIT SWITCH 1 330 190-119 FITTING, 1/2" NPT-M 1 340 190-120 FITTING, 3/4" NPT-M 2 350 190-121 FITTING, 1" NPT-M 2 360 180-113 CONDENSATE TRAP, LONG, DC SERIES 1 370 250-638 CONDENSATE TRAP HOOK 1 380 240-072 WATER PRESSURE SENSOR TYPE LWCO 1 385 150-204 C-CLIP, WATER PRESSURE SENSOR 1 390 240-073 WATER TEMPERATURE SENSOR 2 395 150-221 CLIP, WATER TEMPERATURE SENSOR 2 400 250-632 SUPPLY PIPE 1 410 250-635 GASKET, SUPPLY PIPE 1 420 250-675 EXHAUST DUCT, INTERNAL, DC/HC 96, 125, 160 1 430 250-636 EXHAUST DUCT 1 440 250-637 INTAKE DUCT 1
170-018 HEAT EXCHANGER DC 96, 125 170-019 HEAT EXCHANGER DC 160
180-196 VENTURI, 510, DC/HC 96
180-141 VENTURI, 471, DC/HC 125
180-095 ORIFICE, 505, NATURAL GAS, DC/HC 95, 96 180-142 ORIFICE, 550, NATURAL GAS, DC/HC 125 180-108 ORIFICE, 725, NATURAL GAS, DC/HC 160 180-198 ORIFICE, 392, PROPANE, DC/HC 95, 96 180-143 ORIFICE, 460, PROPANE, DC/HC 125 180-096 ORIFICE, 580, PROPANE, DC/HC 160
180-134 FLOW RESTRICTOR, DC 124, 125, 160
180-140 FLOW RESTRICTOR, DC 84
500-116 CONTROLLER ASSEMBLY, DC/HC 95, 96
500-086 CONTROLLER ASSEMBLY, DC/HC 125
1
1180-112 VENTURI, 362, DC/HC 160
1
1180-135 FLOW RESTRICTOR, DC 106
1500-053 CONTROLLER ASSEMBLY, DC/HC 160
Some parts are available in Kits. Please visit www.ibcboiler.com for more information.
DIAGRAMS
Diagram 6.2-2: Boiler assembly parts list (refer to Diagram 6.1-1 on opposite page)
6-5
DC SERIES BOILERS / WATER HEATERS DC 15-95, DC 15-96, DC 20-125, DC 33-160
6.2 WIRING DIAGRAMS
Diagram 6.2-1: Pictorial wiring diagram
6-6
INSTALLATION AND OPERATION INSTRUCTIONS
INSTALLATION & COMMISSIONING REPORT
Boiler / Water Heater Details:
Model Number _____________________ Serial Number ______________________________________________
Date of Installation ______________ Address of installation __________________________________________
_____________________________________________________________________________________________
User contact information _______________________________________________________________________
Installer Information Company ___________________________________________________________________
Address ______________________________________________________________________________________
Phone/Fax/E-mail ____________________________________________________________________________ __
Fuel
Gas Supply Pressure (high re) _______ Inches w.c. Measured Rate of Input (high re) ____________ Btu/hr
Natural Gas Propane
Installation instructions have been followed and completed (Section 1 of Installation and Operating Instructions).
Check-out procedures have been followed and completed (Section 3 of Installation and Operating Instructions).
Leak testing completed gas piping venting system Fan and combustion components
System Cleaned and Flushed (type of cleaner used) ________________________________________________
System Filled (type/concentration of any glycol/chemicals used) _______________________________________
Air purge completed
Relief Valve correctly installed and piped Relief valve “try lever” test performed
Condensate trap lled
Ignition Safety Shutoff test completed. Flame current reading - High re _______ µA - Low re _______ µA
Owner advised and instructed in the safe operation and maintenance of the boiler / water heater and system.
Information regarding the unit and installation received and left with owner
Condensate drain clear and free owing Condensate Neutralization? Yes/No
Combustion Readings - recommended, but optional (required for fuel conversion):
CO
_____________ % O2 ______________ % CO ____________ ppm
2
Flue temperature _________ Return water temperature (measure simultaneously with ue temp.) _______________
Refer to website for registration.
Commissioning has been completed as listed on this report - Installer Signature _____________________________
NOTES
SERVICE RECORD
DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE
IMPORTANT
This Boiler / Water Heater is equipped with a feature that saves energy by reducing the
boiler / water heater water
temperature as the heating load decreases. This feature is equipped with an override
which is provided primarily to permit the use of an external energy management system
that serves the same function. THIS OVERRIDE MUST NOT BE USED UNLESS AT
LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE:
An external energy management system is installed that reduces the boiler / water heater water temperature as the heating load decreases.
This boiler / water heater is not used for any space heating.
This boiler / water heater is part of a modular or multiple boiler / water heater
system having a total input
300,000 BTU/hr or greater.
of
This boiler / water heater is equipped with a tankless coil.
US installers should contact IBC for any further information required.
REVISION HISTORY
R1 (JULY 2014) Initial release
R2 (SEPTEMBER 2014) Minor updates
R3 (MARCH 2015) Minor Updates, Change DHW Tank Sensor to 10KΩ
R4 (AUGUST 2015) Address Update
R5 (OCTOBER 2015) Addition of new model – DC 20-125
R6 (FEBRUARY 2016) Updated Parameters
R7 (JULY 2016) New Propane Back Flow Flapper, Revision to Exhaust Vent Material - USA
R8 (FEBRUARY 2017) Deletion of old model DC 33-124, Approval of PVC exhaust venting, Pressure-Sensor
Type LWCO language,
R9 (JUNE 2017) Separation of Controller Manual, Minor Updates
R10 (MAY 2018) Added information related to new models DC 15-95 and DC 15-96.
Removed references to discontinued models DC 23-84 and DC 29-106.
IBC Technologies Inc.
8015 North Fraser Way Burnaby, BC Canada V5J 5M8
Toll Free: 1.844.432.8422 Tel: 604.877.0277 Fax: 604.877.0295
www.ibcboiler.com
120-183-A-R10 88396710
May 2018
© IBC Technologies Inc. 2018
Loading...