iBall Nirantar UPS-621V User Manual

6 hours
CAUTION: NEVER connect a laser printer or scanner to the UPS
unit. This may cause the damage of the unit.
User Manual
INTRODUCTION
Thank you for purchasing iBall Nirantar UPS-621V. This UPS is specially aimed for use with multi function personal computer. It is equipped with boost & buck AVR to stabilize the wide input voltage range. It also comes with high-efficient switch-mode battery charger. This charger design minimizes power loss to save charging time. The built-in DC start function enables the UPS to be started up without a supply of AC power. The main features of this UPS are listed below:
600VA Line-interactive design 33% faster recharging Micro processor control guarantees high reliability Built-in enhanced boost & buck AVR Green power function for energy saving DC start function Auto restart during AC recovery
SYSTEM DESCRIPTION
INSTALLATION & OPERATION
1. Inspection
You should receive the following items inside of package:
- Nirantar UPS-621V
- User Manual
Remove the UPS from its packaging and inspect it for damage that may have occurred during shipping. If any damage is discovered, repack the unit and return it to the place of purchase.
2. Placement
Install the UPS in a protected area that is free of excessive dust and has adequate air flow. Please place the UPS away from other units at least 20 cm to avoid interference. Do NOT operate the UPS where the temperature and humidity is outside the specific limits. (Please check the specs for the limitations.)
3. Charging
Plug in the AC input cord to the wall outlet. For the best results, suggest to charge the battery at least 6 hours before initial use. The unit charges its battery while connecting to the utility.
4. Computer Connection
Plug in the loads to output receptacles on the rear panel of the UPS. Simply turn on the power switch of UPS unit, then devices connected to the UPS will be protected by UPS unit.
5. Turn On/Off
To turn on the UPS, press power switch lightly. To turn off the UPS, please press power switch again.
6. DC Start Function
DC Start Function enables UPS to be started up when AC utility power is not available and battery is fully charged. Just simply press the power switch to turn on the UPS.
Power Switch
AC Input
Output Receptacles
Status LED
IMPORTANT SAFETY INSTRUCTION
To safely operate this uninterruptible power supply system, please read and follow all instructions carefully. Please read this manual thoroughly before attempting to unpack, install, or operate UPS, and keep this manual for further reference.
This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the
unit. The unit contains no user replaceable parts. Only authorized service personnel may perform repairs.
Internal battery voltage is 12V DC. Sealed, lead-acid, 6 cells battery. Connection to any other type of receptacle other than a two-pole, three-wire grounded
receptacle may result in shock hazard as well as violate local electrical codes.
In the event of an emergency, press the OFF button and disconnect the power cord
from the AC power supply to properly disable the UPS.
DO NOT allow liquids or any foreign object to enter the UPS. Do not place beverages
or any other liquid-containing vessels on or near the unit.
This unit intended for installation in a controlled environment (temperature controlled,
indoor area free of conductive contaminants). Avoid installing the UPS in location where there is standing or running water, or excessive humidity.
DO NOT plug the UPS input into its own output. DO NOT attach a power strip or surge suppressor to the UPS. DO NOT attach non-computer-related items, such as medical equipment, life-support
equipment, microwave ovens, or vacuum cleaners to UPS
To reduce the risk of overheating the UPS, do not cover the UPS cooling vents and
avoid exposing the unit to direct sunlight or installing the unit near heat emitting appliances such as space heaters or furnaces.
Unplug the UPS prior to cleaning and do not use liquid or spray detergent. DO NOT dispose of batteries in a fire as they may explode. DO NOT open or destroy the battery or batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions should be taken. Keep unauthorized personnel away from batteries.
When replacing batteries, replace with the same number of the sealed lead-acid
batteries.
The batteries already installed by the supplier are operator installable and may be
operated by laymen.
The main socket outlet that supplier the UPS shall be installed near the UPS and shall
be easily accessible.
For any technical help on iBall products, please contact support@iball.co.in
*Product specifications are subject to change without notice. ** Battery backup may vary depending on the configuration of computer system & other devices used. * All trademarks, logos, brands & product names are properties of their respective owners. * Warranty: All iBall products are governed by iBall warranty terms. Refer www.iBall.co.in
TROUBLE SHOOTING
Use the table below to solve minor problems.
Problem
Possible Cause
Remedy
No LED display on the front panel.
1. Battery weak
1. Re-charge battery up to 6 hours.
2. Battery defect.
2. Replace with the same type of battery.
3. Power switch is not pressed.
3. Press the power switch again.
Alarm buzzer beeps continuously when AC supply is normal.
Overload of the UPS.
Verify that the load matches the UPS capability specified in the specs.
When power failure, backup time is shorten.
1. Overload of the UPS.
1. Remove some non-critical load.
2. Battery voltage is too low.
2. Charge battery 4-6 hours or more.
3. Battery defect due to high temperature operation environment, or improper operation to battery.
3. Replace with the same type of battery.
Mains normal but Green LED is flashing.
1. Fuse is blown.
1. Replace the same type of fuse.
2. Power cord is loose
2. Reconnect the power cord properly.
3. Battery defect.
3. Replace the same type of battery.
If any abnormal situations occur that are not listed above, please call service people immediately.
SPECIFICATION
CAPACITY
VA/W
600VA / 360W
INPUT
Voltage
230V AC
Voltage Range
140-300V AC
Frequency
45–65Hz
OUTPUT
Voltage
230V AC
Voltage Regulation (Battery Mode)
195-253V
Frequency
50Hz or 60Hz
Frequency Regulation (Battery Mode)
+ / - 1 Hz
Output Waveform
Modified Sine wave
BATTERY
Battery Type
12V, 7AH
Recharge Time
6 hours to charge 90% after complete discharge
TRANSFER TIME
Typical
4-8ms
INDICATOR
AC Mode
Green light
Backup Mode
Green light flashing
AUDIBLE ALARM
Backup Mode
Beeping every 10 seconds
Low Battery
Beeping every second
Overload
Beeping every 0.5 seconds
Fault
Continuously Beeping
PROTECTION
Full Protection
Discharge, overcharge, and overload protection
PHYSICAL
Outlet
3-Pin x 3
Dimension(mm),DxWxH
279 x 101 x 142 mm
Net Weight
4.2 kgs
ENVIRONMENT
Operating Environment
0ºC - 40ºC, 0-90 % RH (non-condensing)
Noise Level
Less than 40dB