iBall NIRANTAR 1006B, NIRANTAR 3001E, NIRANTAR 1012E User Manual

1KVA - 3KVA Online UPS
User Manual
Table of Contents
1. Important Safety Warning ....................................................................................................... 1
2. Installation and Setup ............................................................................................................. 3
3. Operations .............................................................................................................................. 5
4. Troubleshooting .................................................................................................................... 14
5. Storage and Maintenance .................................................................................................... 15
6. Specifications ................................................................................................ ....................... 16
1
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully
1-1. Transportation
Please transport the UPS system only in the original package to protect against shock
and impact.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.  Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1-3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.  Do not connect domestic appliances such as hair dryers to UPS output sockets.  The UPS can be operated by any individuals with no previous experience.  Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
When installing the equipment, it should ensure that the sum of the leakage current of
the UPS and the connected devices does not exceed 3.5mA.
1-4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS output
sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.
2
1-5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input voltage.
Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary when working with batteries:
remove wristwatches, rings and other metal objects use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries.  Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and
eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.
3
2. Installation and Setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use. NOTE: There are two different types of Online UPS: standard and long-run models. Please refer to the following model table.
Model
Type
Capacity
1006B
With Battery
1KVA
1012E
Without Battery
1KVA
3001E
Without Battery
3KVA
2-1. Rear panel view
iBall Nirantar Online
UPS – 1006B / 1012E
iBall Nirantar Online
UPS – 3001E
1. AC Input
2. Input Circuit Breaker
3. USB Communication Port
4. RS-232 Communication Port
5. SNMP Intelligent Slot
6. External Battery Connection (only available for E model)
7. Output Receptacles
2-2. Setup the UPS Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. The power cord is supplied in the UPS package.
Step 2: UPS output connection
For socket-type outputs, simply connect devices to the outlets.  For terminal-type input or outputs, please follow below steps for the wiring configuration:
a) Remove the small cover of the terminal block b) Suggest using AWG14 or 2.1mm2 power cords. c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
4
Step 3: Communication connection Communication port:
USB port RS-232 port Intelligent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for SNMP card. When installing SNMP card in the UPS, it will provide advanced communication and monitoring options.
Please note: USB port and RS-232 port can’t work at the same time.
Step 4: Turn ON the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full battery run capability during this initial charge period.
Step 5: Install software
For optimal computer system protection, install UPS monitoring software to fully configure UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If not, please click on below link to download and install monitoring software from the internet:
http://www.iBall.co.in/File/Product/Drivers/iBall%20ViewPower%20For%20Windows.rar
1. Follow the on-screen instructions to install the software.
2. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock. Note: For Linux or Mac software, please visit www.iBall.co.in website or write us at
support@iball.co.in
Step 6: External battery connection (for E models only) Follow the right chart to make external battery connection.