SIO Isolator RCB-ISL-SIO
Operation Manual First Edition
Thank you very much for purchasing our product.
Make sure to read this Operation Manua l to ensure cor re ct use fo r saf ety.
1. Scope
The RC-SIO isolator is used to isolate the SIO (RS485) communication line
between the controllers.
There are the cases such that the distance to the control box is long, or the
communication ground (0V) line is not shared because both the DC24 type
controllers and AC100V/200V type controllers are used. In such cases, by means
of isolating the communication line using this RC-SIO isolator, the power can be
supplied to each of the controllers independently.
The controllers connectable to this product are as follows.
・PCON-C/CG,CY,SE,CF ・ERC2,ERC2-SE
・ACON-C/CG,CY,SE, ・SCON
・RCP2 ・Gateway Unit
・ROBONET
2. Specifications
Item Specifications Remarks
Power supply DC5V
Number of
connectable
2 per SIO module
controllers
Surrounding air
temperature
Surrounding
humidity
Surrounding
environment
Isolation
resistance
Isolation
strength
0 to 40℃
95%RH or less (non-condensing)
There should be no corrosive gas, flammable
gas, oil mist and/or dust.
10MΩ
or more at DC500V
DC60V continuous
Protection class IP20
Weight Approx. 40g
External
dimensions
Mounting
method
25W×126.5H×37D mm
35mmDIN rail
・Terminal Resistance
Accessories
(220Ω,1/4W, with a e-Con connector) 1unit
・e-Con connector 1unit
Supplied from the axis 1
controller
・Between the e-Con
connector and modular
connector
・Between the modular
connector axis 1 and
the axis 2
3. Names and Functions of Each Section
Name Functions
communication line (RS485)
with the host or linking the
connectors when two or more
connectors are used.
through CN1 (supplied from
the axis 1 controller), it is
turned ON in green. However,
in the case that the
communication speed is slow,
it flashes. When the power is
not supplied, it is turned OFF.
transmission from the
controller side to the host side.
When the data transmission is
stopped, it is turned OFF.
receipt in the1st/2nd controller
from the host side. It is turned
ON in green during data
receipt operation. When the
data receipt is stopped, it is
turned OFF.
Module Connector
CN1
Module Connector
CN2
Connector for connecting the
communication line for the axis
1 controller
Connector for connecting the
communication line for the axis
2 controller
axis 1
6-pole
Module Connector
axis 2
6-pole
Module Connector
e-Con Connecto
(Left) CN3
(Right) CN4
① e-Con Connector Connector for connecting the
② POWER LED When the 5V power is supplied
③ SD LED It flashes during the data
④ RD1/RD2 LED It is displayed when the data
⑤ axis 1 6-pole
⑥ axis 2 6-pole
4. External Dimensions
Isolator Link Cable
5. Inner Block Diagram
The communication line (RS485) on the host side is isolated from the
communication line (RS485) on the controller side using the signal isolation IC.
The power to the circuit for the signal isolation IC on the host side is supplied
from the axis 1 controller power unit. Therefore, make sure to connect CN1.
Connect the RCP2 controller to the axis 2 controller (CN2). It can not be connected to the axis
1 controller (CN1).
Host side
CAUTION
Link Connection
(To the next isolator)
SIO Isolator
Signal
isolation
IC
Power
isolation
IC
Signal
isolation
IC
(axis 1)
(axis 2)
6. Connection Example
(1) Connection Example 1: In the case that the controller is connected to the host PC through
In the case that the 0V line for the power to each controller can not be shared, or the
DC24V type controllers are used together with the AC100/200V controllers, the power
source can be separated for each controller as shown in the figure.
Personal Computer
the SIO link :
SIO Isolator
SIO Isolator
SIO Isolator
Terminal Resistance
Controller
Cable Name Model Remarks
① USB Cable
② Isolator
③ Isolator Link Cable CB-ISL-SIO Preparation separately
④ External Machine
CAUTION
1.PC software can not be used with this connection example.
2.Because the power to the primary circuit inside the SIO isolator is supplied from CN1, make sure
to connect CN1.
(2) Connection Example 2: In the case that the connector is connected to the host PC or PLC
In the case that the 0V line for the power to each controller can not be shared, or the
DC24V type controllers are used together with the AC100/200V controllers, the power
source can be separated for each controller as shown in the figure .
RS232C conversion unit
(RCB-CV-MW)
Cable
+24V
24V Power-
supply
PS1
Conversion
USB
Adaptor
Communication
Cable
Communication
Cable
(Note)They can not be connected
at the same time.
Either of the two lines
should be connected.
+24V
24V Power-
supply
PS2
0V
+24V
0V
24V Power-
supply
PS3
0V
CB-SEL-USB
RCB-CV-USB
CB-RCB-SIO Preparation separately
CB-RCA-SIO PC Software accessories
through the SIO converter :
RS232C Cross Cable
(goods on the market.)
0V
+24V
24V Power-
supply
PS4
(In case of SCON)
Single-phase
PC Software RCM-101-USB
Accessories
Horizontal
Vertical
SIO Converter
24V Power-
supply
PS1
(This terminal can not be used with this
e-Con
connector
+24V0V
Isolator Link Cable
EQPPGEVKQPGZCORNG
SIO Isolator
Isolator Link Cable
External machine
communication
cable
SIO Isolator
Terminal Resistance
+24V
24V Power-
supply
PS2
Controller
0V
+24V
24V Power-
supply
PS3
0V
+24V
Controller
0V
24V Power-
supply
PS4
(In case of SCON)
Single-phase
CAUTION
Because the power to the primary circuit inside the SIO isolator is supplied from CN1, make
sure to connect CN1.

(3)
Connection Example 3: In the case of the link connection through the gateway unit:
In the case that the 0V line for the power to each controller can not be shared, or the
DC24V type controllers are used together with the AC100/200V controllers, the power
source can be separated for each controller as shown in the figure.
Master Unit
Gateway unit
Made by the client
e-Con
Connector
24V Power-
supply
PS1
+24V0V
Isolator Link Cable
External machine
communication
cable
SIO IsolatorSIO Isolator
Terminal Resistor
+24V
24V Power-
supply
PS2
0V
Controller
+24V
24V Power-
supply
PS3
0V
+24V
0V
24V Power-
supply
PS4
Controller
(In case of SCON)
Single-phase
CAUTION
Because the power to the primary circuit inside the SIO isolator is supplied from CN1, make
sure to connect CN1.
(4) Connection Example 4: In the case that the PC is connected while the positive side of the
Inside the most PCs, the GND (0V) line for the communication is short-circuited to FG
(frame ground), when the PC is connected, a short-circuit occurs in the 24V power line
which might cause the PC breakdown. In such case, connect the controller (including the
gateway and ROBONET) using the SIO isolator and USB conversion adaptor
(RCB-CV-USB) as shown in the figure.
24V power is grounded:
Personal Computer
SIO Isolator
Terminal Resistance
SIO connector
Required Cables
USB Cable CB-SEL-USB
USB Conversion Adaptor RCB-CV-USB
(attachment to the PC application software RCB-CV-USB)
Isolator Communication Cable CB-RCB-SIO
External Machine Communication Cable CB-RCA-SIO
□□□
□□□
24V
Power-
supply
+24V
0V
CAUTION
1. The RS232C conversion unit RCB-CV-MW (attachment to the PC application software
RCM-101-MW) can not be used for the connection between the PC and SIO isolator.
2. Connect the external machine communication cable (3) to CN1 for the SIO isolator.

7. Attachment and Wiring
(1) Procedure
① Because the RC-SIO isolator is attached onto the DIN rail, prepare the
following 35mm DIN rail and end plate.
35mmDIN rail
End plate
② Lower the slider to the lowermost position on the rear side of the RC-SIO
isolator.
Slider
Lower the slider to the lowermost position.
③ There is the DIN rail attachment section on the slider on the rear side of the
isolator. Hook the DIN rail on the upper claw in the attachment section as
shown in the picture and set the isolator onto the rail with the pin (spring type)
on the lower position on the attachment section pulled down. Then, finally,
release the pin to lock the isolator.
Hook the DIN rail on the claw.
Pull down the pin.
④ Using the same procedure, attach the required number of isolators onto the
DIN rail.
Rear side of
the RC-SIO isolator
⑤ Fix the both ends of the attached RC-SIO isolators using the end plates.
Front side of the RC-SIO isolator.
End plate
⑥ Connect the cables.
Connect the adjacent isolators
using the isolator link cable
(CB-ISL-SIO
Connect the isolator with
the each axis controller using
the external machine communication
cable(CB-RCA-SIO
□□□
).
□□□
).
⑦ Insert the terminal resistance.
Insertion Port for
Communication Cable
on the Host Side.
Attach the attached terminal
resistance at the end of
the isolator link.
(2) List of the Cables to be used
① Isolator Communication Cable CB-RCB-SIO□□□
CN1
NTC-66R
Signal
No.
1
2
3
4
5
6
5V
SGA
GND
SGB
GND
5V
② Isolator Link Cable CB-ISL-SIO□□□
e-Con connector
(Green)
CN1
4-1473562-4
Color
BL
WT
YW
WT
③ External Machine Communication Cable CB-RCA-SIO□□□
-
Color
BR
YW
RD
OR
BL
GR
Short-Circuit CableޓUL1007AWG2B(Black)
Shield Unconnected
Color
-
YW
-
OR
BL
-
Signal
Signal
SGA
SGB
GND
FG
5V
SGA
GND
SGB
GND
5V
No.
1
2
3
4
indicates the cable length L
□□□
No.
1
2
3
4
5
6
Shrink Tube(Black)
CN2
3-1473562-4
No.
1
2
3
4
Signal
SGA
SGB
GND
FG
Color
Shrink Tube(Black)
CN2
4-1473562-4
No.
1
2
3
4
(Cable Length 2m)
(Cable Length 5m)
YW
OR
BL
-
No.
1
2
3
4
5
6
7
Signal
SGA
SGB
GND
FG
8
FG
e-Con connector
(Orange)
indicates the cable length L
□□□
Color
BL
WT
YW
WT
Signal
Color
YW
SGA
OR
SGB
5V
BR / GR
-
EMCS
BK
EMCA
-
24V
GND
RD / BL
BK
EMGB
Shield
e-Con connector
(Green)

(3) Pressure Welding Method for the e-Con Connector for the Client-made Cable
(RS485 Communication Line)
Host PLC
Gateway Unit etc.
Use the following procedure for the connection to the
attached e-Con connector.
①Peel off the jacket 15 to 20 mm from the
double shield cable.
②Twist the shield wires and weld them onto the
vinyl cable equivalent to AWG22.
③Cover it with the cable protection tube
(perform the terminal treatment using the
shrink tube).
④Without peeling off the core jacket, insert four
core wires into the connector cable insertion
holes (SDA, SDB, GND, FG).
⑤Keeping the core wires in the holes,
pressure-weld the cable press-fitting housing
from above.
Wire Connection Port
CAUTION
For the connection to the e-Con connector, use the cable with the same core-wire size (equivalent to
AWG22) without peeling off the jacket of that core wires. If the jacket is peeled off, short-circuit might
be caused due to a connection error.
Double Shield Cable
Recommend : TAIYO ELECTRIC WIRE & CABLE
HK-SB/20276×L
2P×AWG22
Shield cable
Pin No. of e-Con Connector
Locking claw
e-Con connector
(Made of AMP 4-1473562-4 : Green)
Vinyl cable
(AWG22)
Weld
SIO Isolator
Pressure-weld
Cable tube
Double shield cable
e-Con connector
Locking claw
IAI America Inc.
Head Office: 2690W 237th Street Torrance, CA 90505
TEL (310) 891-6015 FAX (310) 891-0815
Chicago Office: 1261 Hamilton Parkway Itasca, IL 60143
Atlanta Office: 1220-E Kennestone Circle,Marrietta,GA 30066
TEL (630) 467-9900 FAX (630) 467-9912
TEL (678) 354-9470 FAX (678) 354-9471
website: www.intelligentactuator.com
IAI Industrieroboter GmbH
Ober der Röth 4, D-65824 Schwalbach am Taunus, Germany
TEL 06196-88950 FAX 06196-889524
Manual No.: ME0207-1A