IAI America RCB-ISL-SIO User Manual

r
SIO Isolator RCB-ISL-SIO
Operation Manual First Edition
Thank you very much for purchasing our product. Make sure to read this Operation Manua l to ensure cor re ct use fo r saf ety.
1. Scope
The RC-SIO isolator is used to isolate the SIO (RS485) communication line between the controllers. There are the cases such that the distance to the control box is long, or the communication ground (0V) line is not shared because both the DC24 type controllers and AC100V/200V type controllers are used. In such cases, by means of isolating the communication line using this RC-SIO isolator, the power can be supplied to each of the controllers independently.
The controllers connectable to this product are as follows. PCON-C/CGCYSECF ERC2ERC2-SE ACON-C/CGCYSE SCON RCP2 Gateway Unit ROBONET
2. Specifications
Item Specifications Remarks Power supply DC5V Number of
connectable
2 per SIO module
controllers Surrounding air
temperature Surrounding
humidity Surrounding
environment Isolation
resistance
Isolation strength
0 to 40
95%RH or less (non-condensing) There should be no corrosive gas, flammable
gas, oil mist and/or dust. 10M
or more at DC500V
DC60V continuous
Protection class IP20 Weight Approx. 40g
External dimensions
Mounting method
25W×126.5H×37D mm
35mmDIN rail Terminal Resistance
Accessories
(220,1/4W, with a e-Con connector) 1unit e-Con connector 1unit
Supplied from the axis 1 controller
Between the e-Con
connector and modular connector
Between the modular
connector axis 1 and the axis 2
3. Names and Functions of Each Section
Name Functions
communication line (RS485) with the host or linking the connectors when two or more connectors are used.
through CN1 (supplied from the axis 1 controller), it is turned ON in green. However, in the case that the communication speed is slow, it flashes. When the power is not supplied, it is turned OFF.
transmission from the controller side to the host side. When the data transmission is stopped, it is turned OFF.
receipt in the1st/2nd controller from the host side. It is turned ON in green during data receipt operation. When the data receipt is stopped, it is turned OFF.
Module Connector CN1
Module Connector CN2
Connector for connecting the communication line for the axis 1 controller
Connector for connecting the communication line for the axis 2 controller
axis 1 6-pole Module Connector
axis 2 6-pole Module Connector
e-Con Connecto (Left) CN3 (Right) CN4
e-Con Connector Connector for connecting the
POWER LED When the 5V power is supplied
SD LED It flashes during the data
RD1/RD2 LED It is displayed when the data
axis 1 6-pole
axis 2 6-pole
4. External Dimensions
Isolator Link Cable
5. Inner Block Diagram
The communication line (RS485) on the host side is isolated from the communication line (RS485) on the controller side using the signal isolation IC. The power to the circuit for the signal isolation IC on the host side is supplied from the axis 1 controller power unit. Therefore, make sure to connect CN1.
Connect the RCP2 controller to the axis 2 controller (CN2). It can not be connected to the axis 1 controller (CN1).
Host side
CAUTION
Link Connection (To the next isolator)
SIO Isolator
Signal
isolation
IC
Power
isolation
IC
Signal
isolation
IC
(axis 1)
(axis 2)
6. Connection Example
(1) Connection Example 1: In the case that the controller is connected to the host PC through
In the case that the 0V line for the power to each controller can not be shared, or the DC24V type controllers are used together with the AC100/200V controllers, the power source can be separated for each controller as shown in the figure.
Personal Computer
the SIO link :
SIO Isolator
SIO Isolator
SIO Isolator
Terminal Resistance
Cable Name Model Remarks
USB Cable
Isolator
Isolator Link Cable CB-ISL-SIO Preparation separately ④ External Machine
CAUTION
1.PC software can not be used with this connection example.
2.Because the power to the primary circuit inside the SIO isolator is supplied from CN1, make sure to connect CN1.
(2) Connection Example 2: In the case that the connector is connected to the host PC or PLC
In the case that the 0V line for the power to each controller can not be shared, or the DC24V type controllers are used together with the AC100/200V controllers, the power source can be separated for each controller as shown in the figure .
RS232C conversion unit (RCB-CV-MW)
Cable
+24V
24V Power-
supply
PS1
Conversion
USB Adaptor
Communication Cable
Communication Cable
(Note)They can not be connected at the same time. Either of the two lines should be connected.
+24V
24V Power-
supply
PS2
0V
+24V
0V
24V Power-
supply
PS3
0V
CB-SEL-USB RCB-CV-USB
CB-RCB-SIO Preparation separately
CB-RCA-SIO PC Software accessories
through the SIO converter :
RS232C Cross Cable (goods on the market.)
0V
+24V
24V Power-
supply
PS4
(In case of SCON)
Single-phase
PC Software RCM-101-USB Accessories
Horizontal
Vertical
SIO Converter
24V Power-
supply
PS1
(This terminal can not be used with this
e-Con connector
+24V0V
Isolator Link Cable
EQPPGEVKQPGZCORNG
SIO Isolator
Isolator Link Cable
External machine communication cable
SIO Isolator
Terminal Resistance
+24V
24V Power-
supply
PS2
Controller
0V
+24V
24V Power-
supply
PS3
0V
+24V
Controller
0V
24V Power-
supply
PS4
(In case of SCON)
Single-phase
CAUTION
Because the power to the primary circuit inside the SIO isolator is supplied from CN1, make sure to connect CN1.
(3)
Connection Example 3: In the case of the link connection through the gateway unit:
In the case that the 0V line for the power to each controller can not be shared, or the DC24V type controllers are used together with the AC100/200V controllers, the power source can be separated for each controller as shown in the figure.
Master Unit
Gateway unit
Made by the client
e-Con Connector
24V Power-
supply
PS1
+24V0V
Isolator Link Cable
External machine communication cable
SIO IsolatorSIO Isolator
Terminal Resistor
+24V
24V Power-
supply
PS2
0V
Controller
+24V
24V Power-
supply
PS3
0V
+24V
0V
24V Power-
supply
PS4
Controller
(In case of SCON)
Single-phase
CAUTION
Because the power to the primary circuit inside the SIO isolator is supplied from CN1, make sure to connect CN1.
(4) Connection Example 4: In the case that the PC is connected while the positive side of the
Inside the most PCs, the GND (0V) line for the communication is short-circuited to FG (frame ground), when the PC is connected, a short-circuit occurs in the 24V power line which might cause the PC breakdown. In such case, connect the controller (including the gateway and ROBONET) using the SIO isolator and USB conversion adaptor (RCB-CV-USB) as shown in the figure.
24V power is grounded:
Personal Computer
SIO Isolator
Terminal Resistance
SIO connector
Required Cables
USB Cable CB-SEL-USB
USB Conversion Adaptor RCB-CV-USB
(attachment to the PC application software RCB-CV-USB)
Isolator Communication Cable CB-RCB-SIO
External Machine Communication Cable CB-RCA-SIO
□□□
□□□
24V
Power-
supply
+24V
0V
CAUTION
1. The RS232C conversion unit RCB-CV-MW (attachment to the PC application software RCM-101-MW) can not be used for the connection between the PC and SIO isolator.
2. Connect the external machine communication cable (3) to CN1 for the SIO isolator.
7. Attachment and Wiring
(1) Procedure
Because the RC-SIO isolator is attached onto the DIN rail, prepare the
following 35mm DIN rail and end plate.
35mmDIN rail
End plate
Lower the slider to the lowermost position on the rear side of the RC-SIO
isolator.
Slider
Lower the slider to the lowermost position.
There is the DIN rail attachment section on the slider on the rear side of the
isolator. Hook the DIN rail on the upper claw in the attachment section as shown in the picture and set the isolator onto the rail with the pin (spring type) on the lower position on the attachment section pulled down. Then, finally, release the pin to lock the isolator.
Hook the DIN rail on the claw.
Pull down the pin.
Using the same procedure, attach the required number of isolators onto the
DIN rail.
Rear side of the RC-SIO isolator
Fix the both ends of the attached RC-SIO isolators using the end plates.
Front side of the RC-SIO isolator.
End plate
Connect the cables.
Connect the adjacent isolators using the isolator link cable (CB-ISL-SIO
Connect the isolator with the each axis controller using the external machine communication
cable(CB-RCA-SIO
□□□
).
□□□
).
Insert the terminal resistance.
Insertion Port for Communication Cable on the Host Side.
Attach the attached terminal resistance at the end of the isolator link.
(2) List of the Cables to be used
Isolator Communication Cable CB-RCB-SIO□□□
CN1 NTC-66R
Signal
No.
1 2 3 4 5 6
5V SGA GND SGB GND 5V
Isolator Link Cable CB-ISL-SIO□□□
e-Con connector (Green)
CN1 4-1473562-4
Color
BL WT YW WT
External Machine Communication Cable CB-RCA-SIO□□□
-
Color
BR YW RD OR BL GR
Short-Circuit CableޓUL1007AWG2B(Black)
Shield Unconnected
Color
-
YW
-
OR
BL
-
Signal
Signal
SGA SGB GND
FG
5V SGA GND SGB GND
5V
No.
1 2 3 4
indicates the cable length L
□□□
No.
1
2 3 4 5 6
Shrink Tube(Black)
CN2 3-1473562-4
No.
1 2 3 4
Signal
SGA SGB GND FG
Color
Shrink Tube(Black)
CN2 4-1473562-4
No.
1 2 3 4
(Cable Length 2m) (Cable Length 5m)
YW
OR BL
-
No.
1 2 3 4
5 6 7
Signal
SGA SGB GND FG
8
FG
e-Con connector (Orange)
indicates the cable length L
□□□
Color
BL WT YW
WT
Signal
Color
YW
SGA
OR
SGB
5V
BR / GR
-
EMCS
BK
EMCA
-
24V GND
RD / BL
BK
EMGB
Shield
e-Con connector (Green)
(3) Pressure Welding Method for the e-Con Connector for the Client-made Cable
(RS485 Communication Line)
Host PLC Gateway Unit etc.
Use the following procedure for the connection to the attached e-Con connector.
Peel off the jacket 15 to 20 mm from the
double shield cable.
Twist the shield wires and weld them onto the
vinyl cable equivalent to AWG22.
Cover it with the cable protection tube
(perform the terminal treatment using the shrink tube).
Without peeling off the core jacket, insert four
core wires into the connector cable insertion holes (SDA, SDB, GND, FG).
Keeping the core wires in the holes,
pressure-weld the cable press-fitting housing from above.
Wire Connection Port
CAUTION
For the connection to the e-Con connector, use the cable with the same core-wire size (equivalent to AWG22) without peeling off the jacket of that core wires. If the jacket is peeled off, short-circuit might be caused due to a connection error.
Double Shield Cable Recommend : TAIYO ELECTRIC WIRE & CABLE HK-SB/20276×L 2P×AWG22
Shield cable
Pin No. of e-Con Connector
Locking claw
e-Con connector (Made of AMP 4-1473562-4 : Green)
Vinyl cable (AWG22)
Weld
SIO Isolator
Pressure-weld
Cable tube
Double shield cable
e-Con connector
Locking claw
IAI America Inc.
Head Office: 2690W 237th Street Torrance, CA 90505
TEL (310) 891-6015 FAX (310) 891-0815
Chicago Office: 1261 Hamilton Parkway Itasca, IL 60143
Atlanta Office: 1220-E Kennestone Circle,Marrietta,GA 30066
TEL (630) 467-9900 FAX (630) 467-9912 TEL (678) 354-9470 FAX (678) 354-9471
website: www.intelligentactuator.com
IAI Industrieroboter GmbH
Ober der Röth 4, D-65824 Schwalbach am Taunus, Germany
TEL 06196-88950 FAX 06196-889524
Manual No.: ME0207-1A
Loading...