IAI SCON-CGB, SCON-CGAL, SCON-CA, SCON-CB, SCON-CAL First Step Manual

...
Dummy Plug
SCON
First Step Guide
Ninth Edition
Thank you for purchasing our product. Make sure to read the Safety Guide and detailed Instruction Manual (DVD) included with the product in addition to this First Step Guide to ensure correct use. This Instruction Manual is original.
Using or copying all or part of this Instruction Manu al without permission is prohibited.
The company names, names of products and trademarks of each company shown in the sentences are registered trademarks.
Product Check
This product is comprised of the following parts if it is of standard configuration. If you find any fault in the contained model or any missing parts, contact us or our distributor.
1. Parts (The option is excluded.)
No. Part Name Model Reference
1 Controller Main Body
Refer to “How to read the model plate”, “How to read controller model”
Accessories
SMSTB2.5/5-ST-5.08AU
(Maker: Phoenix Contact) Enclosed in CA/CB/C Type
DeviceNet Specifications
MSTB2.5/5-STF-5.08AUM (Maker: Phoenix Contact)
Enclosed in CAL Type
SMSTB2.5/5-ST-5.08AU
CA (Maker: Phoenix Contact)
Enclosed in CA/CB Type
MSTB2.5/5-STF-5.08AU
CAL (Maker: Phoenix Contact)
Enclosed in CAL Type
CC-Link Specifications (Enclosed in terminal resistance)
MC1.5/5-ST-3.81
C (Maker: Phoenix Contact)
Enclosed in C Type
PROFIBUS-DP Specifications
Prepare D-sub 9-pin (female) connector.
CompoNet Specifications
Prepare flat cable connector dedicated for CompoNet.
MECHATROLINK-Ⅰ/Ⅱ
Specifications
Connector recommended for MECHATROLINK-Ⅱ.
2
Fieldbus Connector
MECHATROLINK-Ⅲ Specifications
Flat cable recommended for MECHATROLINK-Ⅲ.
~750W Motor
FMC1.5/4-ST-3.5
(Maker: Phoenix Contact)
3 System I/O Plug
3000W~Motor
FMC1.5/6-ST-3.5
(Maker: Phoenix Contact)
4 Power Supply Plug for Brake MC1.5/2-ST-3.5
(Maker: Phoenix Contact)
Applicable Cable Size
1.25mm2 to 0.5mm2 (AWG16 to 20)
~750W Motor
MSTB2.5/6-STF-5.08
(Maker: Phoenix Contact)
Applicable Cable Size Controller: 0.75mm2 (AWG18) Motor: 2.0mm2 (AWG14)
5
AC Power Supply Plug
3000W~Motor
PC5/6-STF-7.62
(Maker: Phoenix Contact)
Applicable Cable Size Controller: 0.75mm2 (AWG18) Motor: 3.3mm2 (AWG12)
6 Absolute Battery AB-5
Enclosed in Absolute Type (Excluded for battery-less absolute)
7 Dummy Plug DP-5
Enclosed in SCON-CGAL/CGB
8
External Regenerative Resistor Unit Connecting Plug (3000W~ Motor)
GIC2, 5/2-STF-7.62
(Maker : Phoenix Contact)
Applicable Cable Size
0.75mm
2
(AWG18)
9 Connector for Multi Function
Plug:10114-3000PE, Shell:10314-52F0 (Maker : 3M)
Enclosed in Servo Press Type
10 First Step Guide 11 Instruction Manual (DVD) 12 Safety Guide
2. Teaching Tool (Option)
A teaching tool such as PC software is necessary when performing the setup for position setting, parameter setting, etc. that can only be done on the teaching tool. Please prepare either of the following teaching tools such as PC software. (Note) TB-01/01D/01DR are not applicable for CC-Link IE.
No. Part Name Model
1
PC Software (RS232C converter adapter and external equipment communication cable are included)
RCM-101-MW
2
PC Software (USB converter adapter, USB cable and external equipment comm unication cable are included)
RCM-101-USB
3
Touch Panel Teaching TB-01(Standard/with dead-man switch attached on the left/with dead-man switch attached on the right)
TB-01/01D/01DR 4 Touch Panel Teaching TB-02 (Standard/with dead-man switch attached) TB-02/02D 5 Data Setter TB-03 TB-03
3. Instruction manuals related to this product, which are contained in the Instruction manual (DVD).
No. Name Manual No.
1 SCON-C Controller Instruction Manua l ME0161 2 SCON-CA/CAL/CGAL Controller Instru ction Manual ME0243 3 SCON-CB/CGB Controller Instruction Manual/Servo Pressing Function Instruction Manual ME0340/ME0345 4 CC-Link (Remote I/O Type) Instruction Manual (for SCON-C)/(For excluding SCON-C) ME0123/ME0254 5 DeviceNet (Remote I/O Type) Instruction Manual (for SCON-C)/(For excluding SCON-C) ME0124/ME0256 6
PROFIBUS-DP (Remote I/O Type) Instruction Manual (for SCON-C)/(For excluding SCON-C)
ME0153/ME0258 7 CompoNet Instruction Manual (For excluding SCON-C) ME0220 8 MECHATROLINK Instruction Manual (For excluding SCON-C) ME0221 9 MECHATROLINK- Instruction Manual (for SCON-CA) ME0317
10 CC-Link IE Instruction Manual ME0389 11 PC Software RCM-101-MW/ RCM-101-USB Instruction Manual ME0155 12 Touch Panel Teaching TB-01/TB02/TB03 Position Controller Instruction Manual
ME0324/ME0355/ME0376
4. How to read the model plate
5. How to read controller model
Basic Specifications
List of Specifications
SCON-C/CA/CB/CGB
Item
Less than 400W 400 to 750W 3000 to 3300W
SCON-CAL/CGAL
Corresponding Motor Capacity 12W to 399W 400W to 750W 3000 to 3300W 12W to 200W Power-supply Voltage Single-Phase
100 to 115V AC Single-Phase 200 to 230V AC (Power-supply Fluctuation ±10% or less)
Single-Phase 200 to 230V AC (Power-supply Fluctuation ±10% or less)
Three-Phase 200 to 230V AC (Power-supply Fluctuation ±10% or less)
Single-Phase 100 to 115V AC Single-Phase 200 to 230V AC (Power-supply Fluctuation
±10% or less) Power-supply Voltage 100V AC
Rush Current *1
Power-supply Voltage 200V AC
30A (Controller side), 80A (Drive side)
30A (Controller side), 80A (Drive side)
40A (Controller side), 40A (Drive side)
30A (Controller side),
80A (Drive side)
3.0mA 3.5mA 3.0mA
Leak Current *2
Primary side when noise filter is connected to power supply line
Load Capacity, Heat Generation
Refer to Power Capacity and Heat Generation Power Supply Frequency 50/60Hz PIO Power Supply *3 24V DC±10% Power Supply for Electromagnetic Brake (for actuator equipped with brake)
24V DC±10% 1A (MAX.)
(supplied from external equipment)
24V DC±10%
0.1A (MAX.) (Note) Necessary to supply 1.5A (max.) to actuator separately
24V DC±10% 1A (MAX.)
Transient Power Cutoff Durability SCON-C : 10ms (50Hz), 8ms (60Hz)
SCON-CA/CB/CGB : 20ms (50Hz), 16ms (60Hz)
20ms (50Hz),
16ms (60Hz) Motor Control System Sine Wave PWM Vector Current Control Corresponding Encoder
Incremental Serial Absolute Serial
ABZ (UVW) Parallel •
Battery-less Absolute
Incremental Serial
Absolute Serial
Encoder Resolution
Battery-less Absolute (ISB): 131072 pulse/rev
Battery-less Absolute (RCS2/3): 16384 pulse/rev
* In any models other than above, refer to instruction manual of each actuator. Actuator Cable Length MAX. 20m Serial Communication Interface RS485 : 1CH … based on Modbus Protocol RTU/ASCII Speed : 9.6 to 230.4Kbps
Control available with serial communication in the modes other than the pulse train
PIO Specifications
Signal I/O dedicated for 24V DC (selected from NPN/PNP) … Input 16 ports max.,
output 16 ports max.
External Interface (Each the dedicated controller)
Fieldbus Specifications
DeviceNet, CC-Link, PROFIBUS-DP, CompoNet *, MECHATROLINK-Ⅰ/Ⅱ*,
EtherCAT *, EtherNET/IP *, PROFINET IO *, MECHATROLINK-*, CC-Link IE *
(* Some types cannot connect it.)
PIO MAX. 10m RS485 Total cable length 100m or less.
Cable Length
Fieldbus Refer to each Fieldbus specification Data Setting and Input PC Software, Touch Panel Teaching, Teaching Pendant, Data Setter Data Retention Memory
C
: Saves position data and parameters to non-volatile
memory (There is 100,000 times in number of writing)
CA/CB/CGB: Saves position data and parameters to non-volatile
memory (There is no limitation in n umber of writing)
Saves position data and parameters to non-volatile memory (There is no limitation
in number of writing) Number of Positions 768 points (Changing on the selection in operation mode) Feedback Pulse (Dedicated for Servo Press Specifications)
CB/CGB Type : Differential System (Line Driver System)
MAX. 2.5Mpps
Common : Open Collector Type 500Kpps max. (under
condition JM-08 is used)
SCON-C/CA/CB/CGB
Item
Less than 400W 400 to 750W 3000 to 3300W
SCON-CAL/CGAL
LED Display (mounted on Front Panel)
PWR (green) : Controller in normal condition, SV (green) : Servo ON, ALM (orange) : Alarm generated, EMG (red) : Emergency Stop,
WRG (orange): Warning generated (only CAL/CGAL Type) Electromagnetic Brake Compulsory Release Switch (mounted on Front Panel)
Switching NOM (standard)/BK RLS (compulsory release)
Insulation Resistance 500V DC 10MΩ or more Insulation Strength 1,500V AC for 1 min. (Note) Withstand voltage of force control loadcell is 50V DC
Surrounding Air Temperature
0 to 40°C
Surrounding Humidity
85%RH or less (non-condensing)
Surrounding Environment
[Refer to Installation Environment]
Surrounding Storage Temperature
-20 to 70°C (non-condensing)
Surrounding Storage Humidity
85% or less (non-condensing)
Environment
Vibration Durability
XYZ Each direction 10 to 57Hz Pulsating amplitude 0.035mm (continuous)
0.075mm (intermittent)
57 to 150Hz 4.9m/s2 (continuous) 9.8m/s2 (intermittent) Mass
SCON-C:
Approx. 800g
SCON-CA/CB/CGB:
Approx. 900g
SCON-C: Approx. 1000g SCON-CA/CB/CGB: Approx. 1200g
Approx. 2800g Approx. 560g
Cooling Method Natural air-cooling Forced Air Cooling Forced Air Cooling Force d Air Cooling External Dimensions [mm] 58W × 194H × 121D 72W × 194H × 121D
92.7W × 300H × 187.7D
49W × 158H × 116D
Power Capacity and Heat Generation
Rated Power Capacity = Motor Power Capacity + Control Power Capacity Peek Max. Power Capacity = Peek Max. Motor Power Capacity + Control Power Capacity
Actuator Motor Type
Motor Power
Capacity
[VA]
Peek Max.
Motor Power
Capacity [VA]
Control Power
Capacity
[VA]
Rated Power
Capacity
[VA]
Peek Max.
Power Capacity
[VA]
Heat
Generation
[W] 12 41 123 89 171 30 20 26 78 74 126 30
30D (Excluding RS) 46 138 94 186 31
30R (for RS) 138 414 186 462 33
60 138 414 186 462 33
60 (RCS3-CTZ5) 197 591 245 639 32
100 234 702 282 750 35
100S (LSA) 283 851 331 899 36
150 328 984 376 1032 37 200 421 1263 469 1311 38
200(DD) 503 1509 551 1557 7.5
200S
(LSA excluding LSA-N15H)
486 1458 534 1506 38
200S (LSA-N15H) 773 2319 821 2367 56
300S (LSA) 662 1986 710 2034 40
400 920 2760 968 2808 45
400 (RCS3-CT8) 1230 3690 1278 3738 47
600 1164 2328 1212 2376 56
600 (DD) 1462 4386 1510 4434 20.8
750 3042 3090
750S
1521
4563
1569
4611
58
3000 5657 16970 5705 17018 180 3300 6014 18041
48
6062 18099 182
RS : Rotary Shaft LSA : Linear Actuator DD : Direct Drive Motor
Selection of Circuit Interrupter
3 times of the rated current may flow to the controller during the acceleration/ deceleration. Select an interrupter that does not trip with this value of current. If a trip occurs, select an interrupter that possesses the rated current of one grade higher. (Refer to the operation characteristics curves in the product catalog.)
Select an interrupter that does not trip with the in-rush current. (Refer to the operation characteristics curves in the product catalog.)
Consider the current that enables to cutoff the current even when a short circuit current is flown for the rated cutoff current. Rated Interrupting Current > Short Circuit Current = Primary Power Capacity / Power Voltage Consider margin for the rated current on the circuit breaker.
For ~750W Motor
Rated Current for Circuit Interrupter > (Rated Motor Power Capacity [VA] + Control Power Capacity [VA]) / AC Input Voltage × Safety Margin (reference 1.2 to 1.4 times)
For 3000~3300W Motor
Rated Current for Circuit Interrupter > (Rated Motor Power Capacity [VA] + Control Power Capacity [VA]) / AC Input Voltage × Safety Margin (reference 1.2 to 1.4 times) / √3
External Dimensions
SCON-C/CA/CB/CGB (For ~750W Motor)
Less than 400W 400 to 750W
A
pplicable to Fieldbus
Model
Serial number
In Absolute Battery Attachment (Absolute Encoder Type)
In Absolute Battery Attachment (Absolute Encoder Type)
Side View (Common)
Warning : Operation of this equipment requires detailed installation and operation instructions which are
provided on the DVD Manual included in the box this device was packaged in. It should be retained with this device at all times.
A hardcopy of the Manual can be requested by contacting your nearest IAI Sales Office listed at
the back cover of the Instruction Manual or on the First Step Guide.
SCON-CA-20 I HA-NP-3-1-DN-**
<Series>
<Type>
C : Standard Type CA : High Performance Type CB : High Perform ance Type CGB : Safety Category Compliant Type CAL : Sm all Type CGAL:
Safety Category Compliant Type
<Actuator Characteristics> [Motor Type] * For SCON- CAL/CGAL, 200W or Less
12 : 12W 200S : 200W (LSA) 20 : 20W 300S : 300W ( LSA) 30D : 30W (Excluding RS) 400 : 400W 30R : 30W (for RS) 600 : 600W 60 : 60W 750 : 750W 100 : 100W 750S : Equipped with loadcel 100S : 100W (LSA) RCS2-RA13R l 150 : 150W 3000
: 3000W
200 : 200W 3300 : 3300W
<Encoder Type>
I : Incremental A : Absolute G : Spurious Absolute
(Note 1)
WAI : Battery-less Absolute (Incremental)
(Note 3)
<Option>
No Indication : Standard Type
I :
Index Absolute Type (DD)
(Note 1)
HA : High Acceleration/Deceleration Type M :
Multi-Rotation Absolute Type (DD)
(Note 1)
F : Servo Pressing Type (dedicated for servo press actua tors)
<Identification for IAI use only> * There is no identification in some cases.
<Type of Installation
(dedicated for SCON-CAL/CGAL)
> Not Specified : Screw Attachment Type DN : DIN Rail Mounting Type
<Power-supply Voltage>
1 : Single-Phase 100V AC 2 : Single-Phase 200V AC 3 : Three-Phase 200V AC
<I/O Cable Length>
0 :
Equipped with no cable
2 : 2m
3 : 3m (Standard) 5 : 5m
<I/O Type>
NP : NPN Specification (Sink Type) (Standard) ML : MECHATROLINK-Ⅰ/Ⅱ Connection Type
(Note 2)
PN : PNP Specification (Source Type) ML3 : MECHATROLINK Connection-
(Motion) Type
(Note 1)
DV : DeviceNet Connection Type EC : EtherCAT Connection Type
(Note 2)
CC : CC-Link Connection Type EP : EtherNet/IP Connection Type
(Note 2)
PR : PROFIBUS-DP Connection Type PRT : PROFINET-IO Connection Type
(Note 2)
CN : CompoNet Connection Type
(Note 2)
CIE : CC-Link IE Connection Type
(Note 3)
(Note 1) Specified only for SCON-CA/CB/CGB (Note 2) Except for SCON-C (Note 3) Specified only for SCON-CB/CGB
DeviceNet Connector
CA/CB/C Type CAL Type
CC-Link Connector
CA/CB Type CAL Type C Type
DA
DB
DG
SLD
FG
CC-Link Terminal Resistance
Connector for Multi Function
System I/O Plug
~750W Motor 3000W~Motor
AC Power Supply Plug
~750W Motor 3000W~Motor
Brake Power Supply Plug
Absolute Battery
Regenerative Resistor Unit Connecting Plug 3000W~Motor
16.85
17.15
1.5
φ5
4.5
145
154
136
R2.5
4.5
106.5
5
30.7
34
1.5
1.5
Ø5
4.5
145
154
136
4.5
115
5
30.7
34
1.5
4
4
8.5
(77 from DIN rail center)
(9)
PC Software <RCM-101-USB> Optional
PC
Regenerative Resistor Unit (RESU-2 : option) Required depending on usage condition
LED Display
Axis Number Setting Switch
Pulse Train Mode Changeover Switch
System I/O Connector
CB-SC-REU010
CB-ST-REU010
Regenerative Resistor Unit (RESU-1 [for secondary unit]: option)
Power Supply Connector
FG Connection Terminal
Absolute Battery
(for Absolute Type)
Mode Changeover Switch
Brake Release Switch Brake Power Supply Connector
Communication Cable
PLC (please prepare separately)
Touch Panel Teaching (option) or Teaching Pendant (option)
Enlarged View of Pulse Train Mode Changeover Switch
1 of pulse train mode changeover switch ON: Selection of pulse train control mode OFF: Selection of positioner mode
Actuator Except for the next model
· RCS2-RA13R-with brake, or with loadcell
· NS actuator with brake
SW
ADRS
1 2
ON
SCON-CAL/CGAL
* There is no DIN rail part on the type with screw attachment.
22.5
146.5
4.5
4
116
122.6
For DIN Rail
Mounting Type
For Screw-fixed Type
(6)
φ
4.5
(6)
DIN Rail
(8.5)
35.4
(Width of 35mm DIN Rail)
82.5 from DIN rail center
158
49
(17)
SCON-CGB (For 3000 to 3300W Motor)
Regenerative Resistor Unit (Option)
This is a unit that converts the regenerative current to heat when the motor decelerates.
RESU (D)-1, RESU (D)-2 [Specification] [Appearance]
Item Specification
RESU W34mm × H154mm × D106.5mm
Body Size
RESUD W34mm × H158mm × D115mm
Body Weight 0.4kg
Internal Regenerative Resistor 235Ω 80W
First Unit
RESU-2
RESUD-2
Controller Connection Cable
(Model Code CB-SC-REU010) 1m
Accessories
2nd unit
or later
RESU-1
RESUD-1
Controller Connection Cable
(Model Code CB-ST-REU010) 1m
[Guideline for number of units to be connected]
Motor Wattage
Horizontal Mount/Vertical Mount
Connectable Number of
Regenerative Resistor Units
To 10 0W
(Note 3)
Not Required
101 to 400W 1
401 to 750W 2
(Note 1) This is a reference for the case when the actuator is ran forward
and backward on 1,000mm stroke with the operation duty 50% under the rated acceleration/deceleration speed and rated load.
(Note 2) It is necessary to have the regenerative resistor listed above when the
operation duty is above 50%. The maximum quantity of the external regenerative resistor units that can be connected is as stated below:
2 units for less than 400W 4 units for 400W or more
(Note 3) It is necessary to have one unit for LSA/LSAS-N10S Type.
RESU-35T (For SCON-CGB 3000 to 3300W Motor) [Specification]
Item
Specification
Body Size
W45mm × H300mm × D197mm
Body Weight
1.8kg
Internal Regenerative Resistor
30Ω 450W
Operation Temp. 130°C±5°C
Contact Format
b Contact
Built-in Temp . Sensor
Contact Open-Close
Capacity
DC30V, 200mA(MAX)
[Guideline for number of units to be connected] Servo Press Type : It is necessary to have one unit for RCS3-RA15R
when the cycle time is at 2.5s or less.
: RCS3-RA20R requires two units at maximum
depending on the cycle time. Transfer Type : It depends on the operational condition (payload, transfer velocity, duty ratio). [Refer to each instruction manual for details.]
Brake Box (Option) : RCB-110-RA13-0
This is applied on NS Actuator and RCS-RA13R with brake. 1 unit of Brake Box possesses brakes for 2 shafts.
[Specification]
Item Specification
Body Size W 162 × H94 × D65.5mm
Power Voltage and Current 24V DC±10% 1A
Connection Cable
Encoder Cable
(Model Code CB-RCS2-PLA010) 1m
[24V Power Supply Connector]
Item Specification
Connector on
Cable Side
(Enclosed in
standard package)
MC1.5/2-STF-3.5 (Phoenix Contact)
Applicable Cable AWG28 to 16
Pin No. Signal Explanation
1 0V
Power Supply Grounding for
Brake Excitation
Term i na l
Assignment
2 24VIN
For Brake Excitation and
24V Power Supply
[Connectors 1 and 2 for external brake release switch connection]
Connected Equipment
Brake Release Switch
Connector on
Cable Side
(Please prepare
separately)
XAP-02V-1
(Contact BXA-001T-P0.6) (JST)
Switch Rating 30V DC Minimum Current 1.5mA
Pin No. Signal Explanation
1 BKMRL Brake Release Switch Input
Term i na l
Assignment
2 COM
Power Supply Output for Brake
Release Switch Input
(Note) Short circuit of pin No. 1 and 2 of this connector releases the brake compulsorily. Same as the brake release switch on SCON main unit, it is possible to release the brake.
Do not keep the compulsory release condition while in automatic operation.
Loadcell (Dedicated Option for SCON-CA/CB/CGB)
This is the pressing force measurement unit that is used for the force control. This is used by connecting to the actuator corresponding to the force control or servo press.
[Specification]
Item Specification
Loadcell System Strain Gauge
Rated Capacity [N] 200 600
2000 6000 20000 30000 50000
Allowable Overload [%R.C*1] 200
200 200 200 200 200
Loadcell Accuracy [%R.C*1]
±1 ±1 ±1
Applicable Temperature Range
[°C] 0 to 40
*1 R.C : Rated Capacity
[Refer to each actuator instruction manual for details of how to attach and the dimensions.]
Installation Environment
This product is capable for use in the environment of pollution degree 2*1 or equivalent. *1 Pollution Degree 2 : Environment that may cause non-conductive pollution or transient conductive pollution by frost
(IEC60664-1)
1. Installation Environment Do not use this product in the following environment
Location where the surrounding air temperature exceeds the range of 0 to 40°C
Location where condensation occurs due to abrupt temperature changes
Location where relative humidity exceeds 85%RH
Location exposed to corrosive gases or combustible gases
Location exposed to significant amount of dust, salt or iron powder
Location subject to direct vibration or impact
Location exposed to direct sunlight
Location where the product may come in contact with water, oil or chemical droplets
Environment that blocks the air vent [Refer to Installation and Noise Elimination]
When using the product in any of the locations specified below, provide a sufficient shield.
Location subject to electrostatic noise Location where high electrical or magnetic field is present
Location with the mains or power lines passing nearby
2. Storage Environment
Storage environment follows the installation environment. Especially in a long-term storage, consider to avoid condensation of surrounding air. Unless specially specified, moisture absorbency protection is not included in the package when the machi ne is delivered. In the case that the machine is to be stored in an environment where dew condensation is anticipated, take the condensation preventive measures from outside of the entire package, or directly after opening the package.
Installation and Noise Elimination
1. Noise Elimination Grounding (Frame Ground)
2. Precautions regarding wiring method
1) Wire is to be twisted for the 24V DC power supply.
2) Separate the signal and encoder lines from the power supply and power lines.
3. Noise Sources and Elimination Carry out noise elimination measures for power devices on the same power path and in the same equipment. The following are examples of measures to eliminate noise sources.
1) AC solenoid valves, magnet switches and relays
[Measure] Install a Noise killer parallel with the coil.
2) DC solenoid valves, magnet switches and relays
[Measure] Mount the windings and diodes in parallel. Select a
diode built-in type for the DC relay
4. Heat Radiation and Installation Design and Build the system considering the size of the controller box, location of the controller and cooling factors to keep the ambient temperature around the controller below 40°C Apply screws sized M4 × 10mm when attaching the product with screws.
SCON-C/CA/CB/CGB
(For ~750W Motor)
SCON-CAL/CGAL
SCON-CGB (For 3000 to 3300W Motor)
Connection Diagram
SCON-C/CA/CB/CGB (For ~750W Motor)
Standard
Noise killer
Relay coil
Relay coil
R
C
+24V 0V
+24V 0V
+-
10mm or more
50mm or more
50mm or more
50mm or more
50mm or more
50mm or more
50mm or more
100mm or more
30mm or more
10mm or more
100mm or more
150mm or more
Air Flow
Air Flow
Fan
Brake Box
Regenerative Resistor Unit
Place a fan to make the ambient temperature even
94
70
12
5 5 152
162
142
4-φ5
LS Input Connector
Encoder Input Connector
Encoder Output Connector
Primary
Shaft
min100
12
Connector 1 for External Brake Release Switch Connection (for the primary shaft)
Power Supply Input Connector
POWER ON LED (turns in green while on)
Connector 2 for External Brake Release Switch Connection (for the secondary shaft)
Secondary
Shaft
[App
earance
]
10mm or more 10mm or more 10mm or more
1mm or more 1mm or more
50 mm
or more
50 mm
or more
Air Flow
150mm or more
Screw Attachment Type
RESU-1 RESU-2
DIN rail Attachment Type
RESUD-1
-
[Appearance]
Air flow
150mm or more
100mm
or more
50mm
or more
30mm or more 50mm or more 30mm or more
Earth Terminal
FG Connection Terminal of main body and PE terminal on the power supply connector on 3000W or more.
Use a copper wire cable with its width 2.0mm
2
(AWG14) or more for wiring. Have the size 3.3mm2 (AWG12) or bigger for 3000W and above.
Controller
Controller
Controller
Other equipment
Other equipment
Other equipment
Do not share the ground wire with or connect to other equipment. Ground each controller.
(
Formerly Class-
ΙΙΙ
grounding
)
Grounding resistance at 100Ω or less
NF
*3
SK
*2
+24V
0V
L1
L2
L1C
L2C
NC
PE
BK+
PWR-
100V AC or 200V AC (Refer to Controller Power Voltage Specifications)
Circuit Breaker
Ground Fault Circuit Interrupter
CLF
*1
Class D grounding
(Formerly Class- grounding)
24V DC Power Supply
SCON
AC Power Supply Input Connector
B. Motor Power Supply
A. Control Power Supply
Brake Power Supply Input Connector
Brake Release Box
Emergency stop reset switch
Emergency stop switch
Cable for PC software or dummy plug
Short-circuit in the cable for PC software
System I/O connector
SIO connector
(Note 1)
(Note 1)
(Note 2)
(Note 3)
(Note 4)
Motor power supply
Control power supply
Temperature sensor contact of external regenerative resistor
AC power supply input connector
Emergency stop circuit exclusive use 24V
Stop Circuit
Contact output for the external drive cutoff
SCON-CGB
Circuit Breaker
Leakage Breaker
EMG Switch
Regenerative Resistor Unit Required depending on usage condition
Noise Filter Necessary to noise prevention
Host Controller System
Circuit Breaker Select and connect a circuit breaker that can apply to the capacity of controller
Actuator
PC Software <RCM-101-USB> Optional
PC
24V DC
NFB
Absolute Battery
Brake for Power Supply
Teaching Pendant
LED Display
Mode Changeover Switch
Brake Release Switch
Communication Cable
Teaching Tool
Power Cutoff Breaker
As SCON-CGB for 3000 to 3300W does not have the drive cutoff circuit, make sure to establish cutoff externally.
Load Display
Device etc.
Communication Cable
For Models Equipped with brake Except for RCS2-RA13R and NS Actuators
RSC2-RA13R Equipped with Brake, with no Loadcell, or NS Actuators with Brake
For RCS2-RA13R equipped with no brake and with loadcell for SCON-CA/CB/CGB or for when connecting
the servo press actuator to CB/CGB Servo Press Type
RCS2-RA13R Equipped with Brake and Loadcell in SCON-CA/CB/CGB
SCON-CAL/CGAL
SCON-CGB (For 3000 to 3300W Motor)
Power Supply and Emergency Stop Circuit
Wiring for Power Supply (to be prepared by customer)
SCON-C/CA/CAL/CGAL/CB/CGB (For ~750W Motor)
SCON-CGB (For 3000 to 3300W Motor)
Power consumption varies depending on the connected actuator, etc. Select the circuit breaker that suits to the specification. [Refer to Basic Specifications] A ground fault circuit interrupter needs to be selected carefully considering the purposes of prevention of fire and protection of human. Use the “harmonic type” for the ground fault circuit interrupter. Also, check the leak current at the set points. Refer to the instruction manual for the recommended models for the noise filter, clump filter and surge absorber.
Wiring for Emergency Stop Input The following diagram shows an example of how the emergency stop switch for the teaching pendant may be included in the emergency stop circuit you may construct.
SCON-C/CA/CAL/CGAL/CB/CGB (For ~750W Motor)
Note 1 The power rating of the motor power-off relay turning ON/OFF with contact CR1 is 24V DC and 10mA or less. Note 2 Connect such as a connector to L1/L2 terminals when cutting off the motor power source externally. Note 3 CGAL/CGB Types are not equipped with a relay to enable to automatically identify a teaching tool was inserted and
switch the wiring layout. (The system I/O connector does not get short-circuited between S1 and S2 terminals even if a teaching tool is removed. Connect the enclosed dummy plug DP-5 to the SIO connector when it is necessary to have short-circuit.) The controller on except for CGAL/CGB Types automatically identifies that a teaching tool was inserted. (Short-circuit is made between S1 and S2 terminals inside the controller once connection is detected.)
Note 4 Since there is no motor power cutoff relay in CGAL/CGB Types, make sure to establish a cutoff relay externally.
SCON-CGB (For 3000 to 3300W Motor)
Note 1 The power rating of the motor power-off relay turning ON/OFF with contact CR1 is 24V DC and 10mA or less.
Note 2 Connect such as a connector to L1/L2/L3 terminals when cutting off the motor power source externally.
(This controler not equipped with the drive cutoff relay mounted inside the controller.)
Note 3 It is the contact output to control the drive source breaker connected externally. The rating is 30V DC and 20mA or less. Note 4 Connect a temperature sensor when an external regenerative resistor unit is connected.
Operation Modes and Functions (other than MECHATROLINK-Ⅲ)
(Note) Refer to the Section f or MECHATROLINK- for the operation modes and features of MECHATROLINK-Ⅲ.
SCON-C Type is available for the operation of Remote I/O Mode. SCON-CA/CB/CGB Type is available for all the operation modes in the next table. SCON-CAL/CGAL Type is available for the operations in the modes e xcept for those in the shaded area in the next table.
The following operation modes are available to select for the operation.
(1) Remote I/O Mode : This is the mode to perform operation by PIO (24V I/O) with Fieldbus. (2) Posi tion / : This is the mode to perform operation by indicating the target position by inputting the value directly. Simple Direct Mode The values of the position data already registered for the speed, acceleration/deceleration and
positioning band are to be used in this mode.
(3) Semi-Direct Mode : This is the operation mode to indicate the speed, acceleration/deceleration and pressing
current, as well as the target position, by inputting the values directly.
(4) Full-Direct Mode :
This is the operation mode to indicate all related to the position control by inputting the values directly.
(5) Remote I/O Mode 2 :
This is the mode that the function to read the current position and the current speed is added to Remote I/O. (6) Position / : This is the mode corresponding to the force control function instead of the teaching and zone Simple Direct Mode 2 functions in (2). (7) Semi-Direct Mode 2 :
This is the mode that enables to read the loadcell data instead of reading the command current value in (3). (8) Remote I/O Mode 3 :
This is the mode that the function to read the current position and loadcell data is added to (1) functions. (9) Semi-Direct Mode 3 : This is the mode that equips the vibration control function instead of the jog function in (3).
(10) Full Functional Mode : It is a mode dedicated for the servo press type.
DeviceNet
Specification Refer to the DeviceNet Instruction Manual [ME0256 : CA/CB Type, ME0124 : C Type]
LED Indicators for Monitoring
LED Color Illumination Status Explanation
Steady Light In normal operation
GN
Blinking A hardware error occurred. Condition sometimes recovers after the power reboot.
Steady Light A hardware error occurred. Board must be replaced.
OR
Blinking
An error occurred in the user settings. It is just a simple error such like configuration error. It can be recovered with a rebuild of the settings.
MS
Off Power is not supplied during DeviceNet initializing. Steady Light Connection is established and the communication under normal condition
GN
Blinking
Online but network connection is not yet established. Communication is stopped. (Network is in normal condition)
Steady Light
Node address duplication or bus-off state was detected. Communication is not possible.
OR
Blinking Communication error (Communication time-out is detected.)
NS
Off Not online. DeviceNet Power is not supplied.
24V DC
Power Supply for Brake
Absolute Battery
(for Absolute Type)
Actuator The following models are excluded:
RCS2-RA13R with brake or loadcell equipped
NS Actuators with brake equipped
24V DC
Power Supply for Brake
For LS (option)
Brake Box
CB-RCS2-PLA010 (enclosed to Brake Box)
For LS (option)
NS Actuators (with Brake
RCS2-RA13R (with Brake
Connect to back side
Absolute Battery
(for Absolute Type)
CB-LDC-LTL
CB-RCS2-PLLA
RCS2-RA13R (with Loadcell and Brake)
CB-RCS2-PLA (enclosed to Brake Box)
24V DC
Brake Box RCB-110-RA13-0
Connect to back side
Absolute Battery
(for Absolute Type)
Power Supply for Brake
Motor Power Cutoff Relay
Motor power supply
Control power supply
(Note 3)
(Note 1)
(Note 1)
(Note 2)
(Note 4)
System I/O connector SIO connector
EMG A EMG B
Emergency stop reset switch
Emergency stop switch
Emergency stop switch for the teaching pendant
Emergency stop circuit exclusive use 24V
AC power supply input connector
CB-RCS2-PLLA
RCS2-RA13R (with Loadcel)
Absolute Battery
(for Absolute Type)
* For RCS3 servo press actuator:
It should be CB-RCS2-PLDA, and cable should be 3 branched → 2 branched.
Station Number Setting (Pay attention not to duplicate) Station number is set with parameter. Set Parameter No. 85 “NADR : Fieldbus Node Address” with using the PC software for RC. Available range for Setting : 0 to 63 (setting at delivery : 63)
Baud Rate Setting There is no need to set the baud rate since it automatically follows the master setting.
(Note) Make sure to reboot the controller after the parameter setting is
complete, and do not forget to turn the mode changeover switch to “AUTO” side.
Operation Mode Setting and Address Assignment Please refer to the Instruction Manual for DeviceNet (ME0256)
.
[Refer to DeviceNet (ME0124) Instruction Manual regarding the interface part of SCON-C]
Interface Area (SCON-C excluded)
Wiring * It is no enclosed in terminal resistor
CC-Link
Specification
Refer to the CC-Link Instruction Manual [ME0254 : CA/CB Type, ME0123 : C Type]
SCON-CA/CB/CGB
● SCON-CAL/CGAL
Interface Area Interface Area
Station Number Setting (Pay attention not to duplicate) Station number is set with parameter. Set Parameter No. 85 “NADR : Fieldbus Node Address” with using the PC software for RC. Available range for Setting : 1 to 64 (setting at delivery : 1)
Baud Rate Setting Set Parameter No. 86 “FBRS : Fieldbus Baud Rate Setting” with using the PC software for RC.
Setting Value Baud Rate
0 (at the delivery) 156kbps
1 625kbps 2 2.5Mbps 3 5Mbps 4 10Mbps
(Note) Make sure to reboot the controller after the parameter setting is
complete, and do not forget to turn the mode changeover switch to “AUTO” side.
Operation Mode Setting and Address Assignment
Please refer to the Instruction Manual for CC-Link (ME0254)
Status LED
LED Color
Illumination Status
Contents of display (Detailed Explanation)
Steady Light
• An error occurred (CRC Error, Station Number Switch Setting Error, Baud Rate
Switch Setting Error)
Since turning the power on or software reset till completion of CC-Link initialization
Off • Communication in normal condition
STATUS 1 ERR
OR
Blinking
• The station number setting or the baud rate setting is changed during the
communication
Steady Light • Communicating
STATUS 0 RUN
GN
Off • Not in communication
[Refer to CC-Link (ME0123) Instruction Manual regarding the interface part of SCON-C]
Wiring
PROFIBUS-DP
Specification
Refer to the PROFIBUS-DP Instruction Manual [ME0258 : CA/CB Type, ME0153 : C Type]
Communication Connector (Pins No. 1, 2, 4, 7 and 9 are not to be used.)
Pin No. Description Contents
3 B-Line R × D • T × D (positive side communication line) 5 GND Signal Grounding (insulated) 6 +5V +5V Output (insulated) 8 A-Line /R × D • /T × D (negative side signal line)
Housing Shield Cable Shield (connected to housing)
SCON-CA/CB/CGB
SCON-CAL/CGAL
Interface Area Interface Area
Status LED
LED Color
Illumination Status
Contents of display (Detailed Explanation)
Steady Light Online from fieldbus and communication in normal condition.
GN
Blinking Offline from fieldbus
STATUS 1 NS
OR Blinking Communication error is occurred.
Steady Light In normal operation
GN
Blinking Getting ready for operation
STATUS 0 MS
OR Steady Light
An error detected on communication-related hardware during preparing for operation.
[Refer to PROFIBUS-DP (ME0153) Instruction Manual regarding the interface part of SCON-C]
Bus Termination
When connecting to the network terminal, apply a terminal resistor to PROFIBUS-DP Communication Connector as shown below or apply a connector already equipped with a terminal resistor.
An example for a connector equipped with a terminal resistor : SUBCON-PLUS-PROFIB/AX/SC (Phoenix Contact)
Connection of Terminal Resistor
* It is no enclosed in terminal resistor
Wiring
CompoNet (SCON-C excluded)
Specification
Refer to the CompoNet Instruction Manual [ME0220 : CA/CB Type]
LED Indicators for Monitoring
LED Color
Illumination Status
Explanation
GN Steady Light In normal operation
Steady Light A hardware error occurred. Board must be replaced.
RD
Blinking
An error occurred in the user settings. It is just a simple error such like configuration error. It can be recovered with a rebuild of the settings.
MS
Off Power is not supplied during CompoNet initializing. Steady Light Connection is established and the communication under normal condition
GN
Blinking
Online but network connection is not yet established. Communication is stopped. (network is in normal condition)
Steady Light Duplication of the node address is considered.
RD
Blinking Communication error (communication time-out is detected.)
NS
Off Not online. Power is not supplied.
Interface Area
Station Number Setting Station number is set with parameter. Set Parameter No. 85 “NADR : Fieldbus Node Address” with using the PC software for RC. Available range for Setting : 0 to 63 (setting at delivery : 0) (Note) There is no need to set the baud rate since it automatically
follows the master setting.
(Note) Make sure to reboot the controller after the parameter setting is
complete, and do not forget to turn the mode changeover switch to “AUTO” side.
Operation Mode Setting and Address Assignment Please refer to the Instruction Manual for CompoNet (ME0220).
* It is no enclosed in terminal resistor
* It is unnecessary to supply the communication power to SCON for CompoNet Type.
However, connect the communication power supply to BS+ and BS when multi power supply is required.
MECHATROLINK-/ (SCON-C excluded)
Specification
Refer to the MECHATROLINK Instruction Manual [ME0221 : CA/CB Type]
Status LED
LED Color
Illumination Status
Explanation GN Steady Light Online from fieldbus and communication in normal condition. RD Steady Light Communication error is occurred.
STATUS1 ST1
Off Offline from fieldbus
GN Steady Light In normal operation
RD Steady Light
An error detected on communication-related hardware during preparing for operation.
STATUS0 ST2
Off While in preparation or the po wer is yet to be supplied.
SCON-CA/CB/CGB Interface Area
Node Address Setting Node address can be set with the parameter. Set Parameter No. 85 “NADR : Fieldbus Node Address” with using the PC software for RC. Available range for Setting : 97 to 127 [hex] (setting at delivery : 97)
Baud Rate Setting Set Parameter No. 86 “FBRS : Fieldbus Baud Rate Setting” with using the PC software for RC.
Setting Value Baud Rate Data Length
0 4Mbps (MECHATROLINKⅠ) 17 bytes 1 10Mbps (MECHATROLINK Ⅱ
) 17 bytes
2 (at the delivery) 10Mbps (MECHATROLINK Ⅱ
) 32 bytes
(Note) Make sure to reboot the controller after the parameter setting is
complete, and do not forget to turn the mode changeover switch to “AUTO” side.
Operation Mode Setting and Address Assignment Please refer to the Instruction Manual for MECHATROLINK (ME0221)
.
Wiring Connect the dedicated cable for MECHATROLINK.
MECHATROLINK-(Dedicated for SCON-CA/CB)
Since MECHATROLINK-is applicable for the standard servo profile, and not for the standard I/O profile, it is not applicable for the operation modes (e.g. Full Direct Mode) and vibration control, pressing force, servo press that other fieldbus products are applicable for.
Specification
Refer to the
MECHATROLINK-Instruction Manual
Status LED
LED Colo r
Illumination Status
Explanation
GN
Steady Light
Receiving CONNECT (connected to master)
CON
Off
Connection is not established to master
OR
Steady Light
Illumination flashes when communication alarm or command alarm is generated (warning excepted). Illumination turned off when alarm is cancelled
ERR
Off
In normal condition (no alarm generated)
LK1
GN Steady Light
LK2
GN Steady Light
Illumination turns on when physically connected to another device applicable for MECHATROLINK- (for cable breakage check purpose)
NS
MS
LED Indicators for Monitoring
RD WT
LB
BK
DeviceNet Communication Connector
Female Connector
on SCON Side
Male Connector on Network Side (Opposite View
from Insertion Side)
9
6
5
1
9
8
6
5
3
1
GND
A-Line
B-Line
+5V
390Ω, 1/4W
220Ω, 1/4W
390Ω, 1/4W
Network Cable
CompoNet Communication Connector
BS­BDL BDH BS+
NS
MS
LED Indicators for Monitoring
Master
Unit
SCON
SCON
+5V
A-Line
B-Line
GND
+5V
A-Line
B-Line
GND
+5V
A-Line
B-Line
GND
390Ω
220Ω
390Ω
390Ω
220Ω
390Ω
Class D grounding
(Formerly Class- ground ing)
CC-Link Communication Connector
1
STATUS
0
FG
SLD
DG
DB
DA
FG
SLD
DG
DB
DA
CC-Link Communication Connector
Status LED
Status LED
STATUS
1
0
NC
/DATA
DATA
SH
MECHATROLINK Communication Connector (2 systems)
Status LED
SCON-CAL/CGAL Interface Area
ST1
ST2
NC
/DATA
DATA
SH
Status LED
MECHATROLINK Communication Connector (2 systems)
BL
WT
RD
BK
CAN_H
CAN_L
V+
V-
CAN_H
CAN_L
V+
V-
CAN_H
CAN_L
V+
V-
Drain
(Shielded)
Drain
(Shielded)
Drain
(Shielded)
Terminal Resistor 121Ω
Terminal Resistor
121Ω
Class D grounding
(
Formerly Class-
ΙΙΙ
grounding
)
24V
Power Supply
M
aster Unit
SCON
SCON
BL
WT
RD
BK
BL
WT
RD
BK
STATUS
1
0
Status LED
Status LED
PROFIBUS-DP Communication Connector
PROFIBUS-DP Communication Connector
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
SCONSCON
Terminal Resistor Terminal Resistor
SLD and FG are connected inside.
The terminal resistor differs depending on the type of the dedicated cable for CC-Link.
• Cable FANC-SBH···130Ω1/2W (High Performance Cable dedicated for CC-Link)
• Cable FANC-SB······110Ω1/2W (
Dedicated cable for CC-Link
)
Master
Unit
Class D grounding
(
Formerly Class-
ΙΙΙ
grounding
)
Station Number Setting Station number is set with parameter. Set Parameter No. 85 “NADR : Fieldbus Node Address” with using the PC software for RC. Available range for Setting : 0 to 125 (setting at delivery : 1)
Baud Rate Setting There is no need to set the baud rate since it automatically follows the master setting.
(Note) Make sure to reboot the controller after the parameter
setting is complete, and do not forget to turn the mode changeover switch to “AUTO” side.
Operation Mode Setting and Address Assignment Please refer to the Instruction Manual for PROFIBUS-DP (ME0258).
Interface Area
Node Address Setting
Node address can be set with the parameter. Set Parameter No. 85 “NADR : Fieldbus Node Address” with using the PC software for RC. Available range for Setting : 3 to 239 [hex] (setting at delivery : 3)
Data Length Setting Establish the setting in Parameter No. 86 “FBRS : Fieldbus Communication Speed” in RC PC software considering the data length to be used.
Setting Value
Data Length
Baud Rate
0 32 bytes
1 (at the delivery)
48 bytes
100Mbps
Electronic Gear Ratio Setting
Set the electronic gear numerator in Parameter No. 65 “CNUM : Electronic Gear Numerator” and the electronic gear
denominator in No. 66 “CDEN : Electronic Gear Denominator”. In the RC PC software Establish the settings to satisfy the following condition:
Strok e [mm] Electronic Gear Ratio Denominator Ball Screw Lead Length [mm]
Electronic Gear Ratio Numerator
Pulse Count Direction Setting
Set the value in Parameter No . 62 “FPIO : Pulse Count Direction” to be the same as what is set in No. 5 “ORG :
Home-Return Direction” in the RC PC software.
(Note) Reboot the po wer on the controller after the parameter settings are completed, and make sure to put the
switchover switch on the front face of the controller back to the AUTO side.
Wiring Connect the dedicated cable for MECHATROLINK.
CC-Link IE (Dedicated for SCON-CB/CGB)
Specification
Refer to the CC-Link IE Instruction Manual
Status LED
LED Color
Illumination Status
Explanation
Steady Light Cyclic transmission in process
Blinking Cyclic transmission paused
GN: D LINK
Off Cyclic transmission not conducted, parallel off, Power not supplied
Steady Light Received data in error
NS
OR: L ERR
Off Received data in normal conditions, Power not supplied
Steady Light Operation in normal conditions
GN: RUN
Off Hardware error occurred, Power not supplied
Steady Light Error being occurred (Node Error / Station Number Setting Error)
MS
OR: ERR
Off Operation in normal conditions, Power not supplied
Steady Light Linkup in process
LINK GN
Off Link-down in process, Power not supplied
Steady Light Received data in error
L.ER OR
Off Received data in normal conditions, Power not supplied
Interface Area
Connector Name CC-Link IE Connector Remarks
Cable Side
Ethernet ANSI/TIA/EIA-568-B Category 5e and above 8P8C modular plug equipped with shield (RJ45)
Please prepare separately
Controller Side
Ethernet ANSI/TIA/EIA-568-B Category 5e and above 8P8C modular Jack equipped with shield (RJ45)
Pin No.
Signal Name Description
Applicable cable
diameter 1 TP0+ Data 0+ 2 TP0- Data 0­3 TP1+ Data 1+ 4 TP2+ Data 2+ 5 TP2- Data 2­6 TP1- Data 1­7 TP3+ Data 3+ 8 TP3- Data 3-
It is recommended to prepare a straight STP cable in Category 5e or above for the Ethernet cable.
Wiring
Starting Procedures
When using this product for the first time, make sure to avoid mistakes and incorrect wiring by referring to the procedure below. “PC” stated in this section means “PC software”.
Trouble Shooting
In the case an error is occurred, check the operation status on the LED display on the front panel [Refer to Each Fieldbus Section], and also, check the status monitor by connecting a teaching tool such as PC software for RC. Either of the following alarms will be shown for Fieldbus. Please refer to the Instruction Manual of the controller for other alarms to perform an appropriate treatment.
Code Error Name
ID
(*1)
RES (*2)
Cause / Treatment
0F2
Fieldbus
Module Error
05 ×
Cause : An error is detected on Fieldbus module Treatment : Check on the parameter
0F3
Fieldbus Module
Not Detected
04 ×
Cause : Module cannot be detected Treatment : Turn the power off and reboot. Please contact us
if the problem is not solved with this action. (*1) ID Simple alarm code (*2) RES Alarm reset available/unavailable : Alarm reset available / ×: Alarm reset unavailable
Manual No.: ME0260-9A
CON
ERR
Status LED
Upstream Side LK1 (link 1)LED
Downstream Side LK2 (link 2)LED
× No. of Encoder Pulses ×
2
31
* Refer to instruction manual of operation
for servo press type.
Top View of Connector on Controller side
L.ER
LINK
L.ER
LINK
Master Unit Slave Devices SCON CC-Link IE Type
Ethernet Straight Cable Category 5e or more Double shielded cable braided with aluminum foil recommended (Note) Terminal resistance is not required
There is no distinction of IN/OUT on the connector.
No →
No →
↓Yes
No →
Check the emergency stop circuit.
No
Yes
↓Yes
↓Yes
Yes
Check of Packed Items Are there all the delivered items?
Please contact the distributor.
Point Check Item
• Is frame ground (FG) connected?
• Has the noise countermeasure been taken?
Power Supply and Alarm Check Connect a teaching tool such as PC, turn the mode changeover switch to “MANU” side and turn the power on for each unit. Select [Teaching Mode 1 Safety Speed Activated / PIO Operation Invalid] in the teaching tool such as PC.
Check Item Is the orange light [ALM] on the LED status display off?
Connect the PC or teaching pendant and check the content of the alarm to have the right treatment.
Safety Speed Setting Set it in Parameter No. 35 if necessary. The safety speed is set to 100mm/s at the delivery.
Servo
ON Turn the servo on with the operation on the teaching tool such as PC.
Check Item Is the green light [SV] on the LED status display on?
If an alarm is generated, connect the PC or teaching pendant and check the content of the alarm to have the right treatment.
CAUTION Please perform this process with the actuator away from the mechanical end or interfering subjects as much as possible. Put the actuator away if it interferes with surroundings. It may generate an alarm if the actuator hit the mechanical end or interfering subjects when the servo is turned on. The slider may get slightly dropped by self-weight if servo on and off is repeatedly performed at the same position. Be careful not to pinch the hand or damage the work.
Safety Circuit Check Does the emergency stop circuit (drive cutoff circuit) work properly and turn the servo off?
Target Position Setting
(This section is not necessary for □□ Direct Mode and MECHATROLINK-
III
.) Set the target position in “Position” Box in each position table. Perform a home-return operation first when Direct Teaching is to be performed. When moving the actuator manually, set the Brake Release Switch to “BK RLS” side for the brake equipped type. Put the switch back after the setting is complete.
CAUTION To ensure safety, it is recommended that safety speed be enabled during initial movements.
If there is a vibration or abnormal noise generated, check the actuator if it is installed properly, the condition for its use is below the rated values, etc.
Test Run Adjustment
1) Check the operation with setting the safety speed invalid on the teaching tool such as PC software.
2)
Select “Monitor Mode 2 Safety Speed Invalid / PIO Available to Boot” in MANU Operation Mode and remove the PC or teaching pendant from the controller.
3) Set the Mode Changeover Switch to “AUTO” side.
4) Conduct the Fieldbus setting on the host side.
Check Item Turn on the power to the host side. Is the LED display on the front panel as shown below for each Fieldbus? CC-Link : STATUS 1 is off and STATUS 0 is turned on in green DeviceNet and CompoNet : Both MS and NS are turned on in green PROFIBUS, MECHATROLINKI and II : Both STATUS1 and STATUS0 are turned on in green. Either of MECHATROLINKIII- LK1 or LK2 is turned on in green
Now it is ready for operation. Proceed to the system operation adjustment.
Yes
No
Installation and Wiring Install and wire the actuator and the controller following the instructions described in the Instruction Manual and this guide.
Initial Operation Check Connect our controller to the actuator. Connect a teaching tool such as PC, set the operation mode setting switch to “MANU” side and turn the power on. Confirm the operation by performing a home-return operation and jog operation in full stroke range on the teaching tool.
CAUTION Be careful not to pinch the hand or damage the mechanical hand by the slider dropped with the self-weight when turning the brake release switch to “BK RLS” side if it is mounted vertically.
Yes
• Check the station number setting.
• Check the terminal resistor.
• Check the baud rate setting.
No