Hytronik HMW39/RF + HC034RF Installation And Instruction Manual

1. Technical Specifications
Product type RF wireless microwave DALI sensor (tri-level control)
Operating voltage 120~277VAC 50/60Hz
Rated load Maximum 20pcs DALI devices, Maximum 40mA
Power consumption < 1.5W
Detection angle 360
o
Mounting height 12m (Maximum)
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 2 ~ 500Lux, Disable
RF transmission distance 30 meters in the open area
RF frequency 868MHz (FSK mode)
Warming up time 20s
Operating temperature -20oC ~ +50oC
IP rating IP65
8
2. Installation
Warnings:
1. Installation qualified engineer must be carried out by a in accordance with local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may cause mis-triggering.
4. Ensure environmental conditions are suitable for electronic equipment
Sensor module
Photocell
59.6
66.6
4.1
81.5
61.4
59.6
89.9
0.825”
29
64
75
59.3
33.7
84.5
9.2
o29
59.3
57.3
47.5
66.6
53
146.6
59.6
18
50
50.5
57.3
57.3
47.5
53
80.7
59.3
57.3
47.5
29.5
91.5
75
53
4.1
LED indicator
Infrared receiver
Rotary switch for RF grouping
Cable entry
Installation rack
Sensor module
Photocell
LED indicator
Infrared receiver
Rotary switch for RF grouping
Sensor module
Photocell
LED indicator
Infrared receiver
Rotary switch for RF grouping
Rotary switch for RF grouping
Cable entry
Angle adjustment
Luminaire clamp
A. Surface Mounting
B. Conduit Fixing
C. Clamp Fixing
HC
034RF (RF receiver
)
RF antenna
Infrared remote receiver
1-10V+
1-10V-
L’
N
N
L
71.5
4.2
37.5
38.3 25
11.8
78.2 87
Installation hole
Installation and Instruction Manual
HIGH BAY RF WIRELESS MICROWAVE DALI SENSOR HMW39/RF + HC034RF
HF
HMW39/RF-20170510-A1
Product type RF wireless receiver
Operating voltage 220-240V 50Hz
Rated load Capacitive:400W; Resistive:1200W
IP rating IP20
4. Functions
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas require a light change notice before switch-off. It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
4.1 Tri-level Control (Corridor Function)
15 channels are available for fast grouping via rotary switch on both HMW39/RF and HC034RF. Simply selecting the same channel on each unit, the grouping is automatically completed.
Noted:channel "0" is not for fast grouping, and sensors can only be grouped by remote control.
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is not required (natural light lux level exceeds daylight threshold). Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural light is sufficient.
4.2 Lux Off Function
HMW39/RF
HC034RF
3. Rotary Switch for RF grouping
commander
receiver
8.
Description of the Button Functions
(remote control HRC-11)
HRC-11
6
8
10
11
12
13
14
2
4
1
3
7
9
5
HMW39/RF-20170510-A1
10%
30%
75%
50%
Ceiling mounted detection pattern (m)
Ceiling mounted height(m)
5
0
12
6. Wiring Diagram
7. Detection Pattern
HC034RF
L N DALI
+
DALI
-
L N
Brown
LED Driver
Blue
Yellow
Black
HMW39/RF
5. RF grouping
Step1
The receiver unit
Beeper is on for 3min
Short press ”Learn /Erase” button
Short press “Learn/Erase” button on RC to the receiver to activate pairing mode, and the receiver unit will beep once every second for 3min. Note: up to 30 units can be paired.
Step2
The commander unit
LED indicator flash 3 times
Short press ”Transmit” button
Beeper beeps rapidly beep 3 times in 1s when RF signal is received successfully
Step3
The receiver unit
Beeper is on
Short press ”Learn /Erase” button
Short press “Transmit” button on RC to the commander, the red indicator on commander unit will flash 3 times to send the transmission signal.
Upon receiving the transmission signal, the receiver unit will rapidly beep 3 times in 1s to indicate the success of pairing. One more short press on “Learn/Erase” button to the receiver unit to complete the pairing process, the receiver unit will quit the pairing mode.
Erase: Long press “Learn/Erase” button for 3s, the beeper on receiver unit rapidly beeps for 5s, all commands it has received before will be erased.
The receiver unit
9. Trouble Shooting
YDEMERESUACYDEMER ESUAC NOITCNUFLAM
The fixture does not light up
The fixture is always on
Check detection area setting
The fixture is on when it should not
Incorrect daylight threshold setting
Continued movement in the detection zone
Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows
Detection zone not targeted
Faulty fixture
No power supply
Adjust daylight threshold setting
Replace fixture
Check power to sensor
Check detection area setting
Adjust zone, change installation site
Detection range [ zone ]
Press buttons in zone to set detection range at 100% / 75% / 50% / 10%. Note: Disabled for HC034RF.
8
8
Scene prog. [ zone ] (One-key-commissioning)
1. Press button “start” to program.
2. Select the buttons in “Detection range”, / “Daylight hreshold”, “Hold time”, “Stand-by time”, “Stand-by dimming level” to set all parameters.
3. Press button “Memory” to save all the settings programmed in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, steps should be: Press button Start, button 100%, Disable, Shift, 5min, Shift, +∞, 30%, Memory. By pointing to the sensor unit(s) and pressing Apply, all settings are passed on the sensor(s).
7
7
7
7
3
3
8
8 9
10
10
11 1312
11 12
13
Permanent ON/OFF [ ]
Press button ,to select permanent ON or permanent OFF mode. * Press button / to resume automatic operation.
Power output [ button ]
Press button , the light output shifts between 80% and 100%. Note: the function of “Sensor off” and “Twilight” are disabled.
button
Auto Mode [ button ]
Brightness +/- [ button ]
Press button to adjust the light brightness between 10%~100% .
Shift [ button ]
RESET[ button ]
Press button , all settings go back to the rotary switch settings.
Press button to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF. Note: the function of semi-auto is disabled.
Press button , the LED on the top left corner will flash to indicate mode selection. All values / settings in RED are in valid for 20 seconds.
1
2
2
3
3
4
4
5
6
6
5
1
2
4
Ambient daylight threshold [ button ]
1. Press button Shift, the red LED is on for indication.
2. Press button , the ambient lux level is sampled and set as the new daylight threshold.
3
10
Dual tech & RF mode [ zone ]
1. HF, PIR, HF+PIR, HF/PIR are disabled.
2. Short press button "Learn/Erase" to activate pairing mode on all receiver (slave) units to be paired. Note:up to 30 units can be paired.
3. Short press button "Transmit" at the commander unit(master), the LED will flash 3 times to indicate the transmission signal has been sent. The receiver units will rapidly beep 3 times in 1s to indicate the success of pairing.
4. Long press “Learn/Erase” button for 3s, and the receiver unit clears all commands it has received before.
5. Press button RX100%, the light on receiver unit is 100% on upon receiving RF on signal; Press “RX STBY%” button, the light(s) goes to presset stand-by dimming level directly.
14
10
Daylight threshold [ zone ]
Press buttons in zone to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable. Note: 1. To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button Shift at first.
2. Disabled for HC034RF.
9
9
3
Stand-by time [ zone ]
Press buttons in zone to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞. Note: “0s” means on/off control; “+∞” means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence after hold-time.
Hold time [ zone ]
Press buttons in zone to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button Shift at first.
2. 2s is for test purpose only, stand-by period and daylight sensor settings are disabled in this mode. *To exit from Test mode, press button or any button in zone .
3
11
12
12
11
11
2
Stand-by dimming level [ zone ]
Press buttons in zone to set the stand-by dimming level at 10% / 20% / 30% / 50%.
13
13
Hytronik Industrial Ltd. | www.hytronik.com 3rd Floor, block C, complex building, 155#, Bai'gang road south, Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023 Tel: 86-752-2772020 Fax: 86-752-2777877