Hytronik HMW38/RF Installation And Instruction Manual

1. Technical Specifications
Product type RF wireless microwave motion sensor (tri-level control)
Operating voltage 120~277VAC 50/60Hz
Rated load Capacitive: 400W@120V; 800W@220-277V
Resistive: 800W@120V; 1600W@220-277V
Power consumption < 1.5W
Detection angle 360
Detection area (DxH) 10 x 12m (Maximum)
Mounting height 12m (Maximum)
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 2 ~ 500Lux, Disable
RF transmission distance 30 meters in the open area
RF frequency 868MHz (FSK mode)
Warming up time 20s
Operating temperature -20oC ~ +50oC
IP rating IP65
3. Rotary Switch for RF grouping
8
4. Functions
The built-in daylight sensor can read ambient natural light and switch off the fixture automatically whenever artificial light is not required (natural light lux level exceeds daylight threshold). Note: if the stand-by time is preset at "+∞", the fixture never switches off even when natural light is sufficient.
4.2 Lux Off Function
2. Installation
Warnings:
1. Installation must be carried out by a qualified engineer in accordance with local regulations.
2. Disconnect power supply before installing.
3. Install to a solid surface - vibrations may cause mis-triggering.
4. Ensure environmental conditions are suitable for electronic equipment
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas it requires a light change notice before switch-off. It offers 3 levels of light: 100%-->dimmed light-->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
4.1 Tri-level Control (Corridor Function)
Installation and Instruction Manual
HIGH BAY RF WIRELESS MICROWAVE MOTION SENSOR HMW38/RF
HF
HMW38/RF-20180227-A2
15 channels are available for fast grouping via rotary switch. By simply selecting the same channel on each unit, the grouping is automatically completed.
Noted: channel "0" is not for fast grouping, and sensors can only be grouped by remote control.
Rotary switch for RF grouping (Please see the location in 2. Installation)
The light will flash ONCE rapidly after receiving the command from the remote controller. Note: There is no load indication (the light will not flash) when button ON/OFF, POWER 100% or POWER 80% is pressed.
4.3 Load Indication
59.6
66.6
4.1
81.5
80.7
59.3
57.3
47.5
29.5
91.5
75
53
4.1
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Cable entry
Installation rack
A. Ceiling mount
61.4
59.6
89.9
0.825”
29
64
75
59.3
50.5
57.3
57.3
47.5
53
B. Screw to the Luminaire by conduit
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Cable entry
33.7
84.5
9.2
o29
59.3
57.3
47.5
66.6
53
146.6
59.6
18
50
C. Attach to the shade by clamp
Sensor module
Daylight sensor
LED indicator
Infrared receiver
Rotary switch
Angle adjustment
Luminaire clamp
8.
Descriptions of the Button Functions
(remote control HRC-11)
HMW38/RF-20180227-A2
10%
30%
75%
50%
Ceiling mounted detection pattern (m)
Ceiling mounted height(m)

6. Wiring Diagram
7. Detection Pattern
HMW38/RF
Brown
LED driver
L
N
1-10V+
1-10V-
L N
Blue
Grey
Red
Black
5. RF grouping
Step1
The receiver unit
LED indicator flashes slowly
Short press ”Learn /Erase” button
Short press “Learn/Erase” button on RC to the receiver to activate pairing mode, and the LED indicator on receiver unit will flash slowly. Note: up to 30 units can be paired.
Step2
The commander unit
LED indicator flash 3 times
Short press ”Transmit” button
LED indicator flashes quickly then slowly when RF signal is received successfully
Step3
The receiver unit
LED indicator flashes rapidly
Short press ”Learn /Erase” button
Short press “Transmit” button on RC to the commander, the LED indicator on commander unit will flash for 3 times to send the transmission signal.
Upon receiving the transmission signal, the indicator on receiver unit will flash quickly then slowly to indicate the success of pairing. One more short press on “Learn/Erase” button to the receiver unit to complete the pairing process, the receiver unit will quit the pairing mode.
The sensor can serve as both commander and receiver, simply repeat above steps the other way around.
Erase: Long press “Learn/Erase” button for 3s to the sensor unit, the indicator rapidly flashes 12 times, all commands that it has received before will be erased.
The receiver unit
HRC-11
&
A
II
I
1
3
7
9
6
8
10
11
12
13
14
2
4
5
9. Troubleshooting
MALFUNCTION CAUSE REMEDY CAUSE REMEDY
The fixture does not light up
The fixture is always on
Check detection area setting
The fixture is on when it should not
Incorrect daylight threshold setting
Continous movement in the detection zone
Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows
Detection zone not targeted
Faulty fixture
No power supply
Adjust daylight threshold setting
Replace fixture
Check power to sensor
Check detection area setting
Adjust zone, change installation site
Detection range [ zone ]
Press buttons in zone to set detection range at 100% / 75% / 50% / 10%.
8
8
Scene prog. [ zone ] (One-key-commissioning)
1. Press button “start” to program.
2. Select the buttons in “Detection range”, / “Daylight hreshold”, “Hold time”, “Stand-by time”, “Stand-by dimming level” to set all parameters.
3. Press button “Memory” to save all the settings programmed in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be as follows: Press button Start, button 100%, Disable, Shift, 5min, Shift, +∞, 30%, Memory. By pointing to the sensor unit(s) and pressing Apply, all settings are passed on the sensor(s).
7
7
7
7
3
3
8
8 9
10
10
11 1312
11 12
13
Permanent ON/OFF [ ]
Press button ,to select permanent ON or permanent OFF mode. * Press button / to resume automatic operation.
Power output [ button ]
Press button , the light output shifts between 80% and 100%. Note: the function of “Sensor off” and “Twilight” are disabled.
button
Auto Mode [ button ]
Brightness +/- [ button ]
Press button to adjust the light brightness between 10%~100% .
Shift [ button ]
RESET[ button ]
Press button , all settings go back to the default setting.
Press button to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF. Note: the function of semi-auto is disabled.
Press button , the LED on the top left corner will flash to indicate mode selection. All values / settings in RED are valid for 20 seconds.
1
2
2
3
3
4
4
5
6
6
5
1
2
4
Ambient daylight threshold [ button ]
1. Press button Shift, the red LED is on for indication.
2. Press button , the ambient lux level is sampled and set as the new daylight threshold.
3
10
Stand-by dimming level [ zone ]
Press buttons in zone to set the stand-by dimming level at 10% / 20% / 30% / 50%. Note.the function of 24h / 12h / 4h / 30s are disabled.
13
Dual tech & RF mode [ zone ]
1. HF, PIR, HF+PIR, HF/PIR are disabled.
2. Short press button "Learn/Erase" to activate pairing mode on all receiver (slave) units to be paired. Note:up to 30 units can be paired.
3. Short press button "Transmit" at the commander unit(master), the LED will flash for 3 times to indicate that the transmission signal has been sent. The receiver units flashes slowly to indicate the success of pairing. Repeat this process for two way communications, a single sensor may act as both commander and receiver.
4. Long press “Learn/Erase” button for 3s, and the receiver unit clears all commands it has received before.
5. Press button RX100%, the light on receiver unit is 100% on upon receiving RF on signal; Press “RX STBY%” button, the light(s) goes to presset stand-by dimming level directly.
14
13
10
Daylight threshold [ zone ]
Press buttons in zone to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable. Note: To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button Shift at first.
9
9
3
Stand-by time [ zone ]
Press buttons in zone to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞. Note: “0s” means on/off control; “+∞” means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence after hold-time.
Hold time [ zone ]
Press buttons in zone to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button Shift at first.
2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode. *To exit from Test mode, press button or any button in zone .