Hytronik HMW31 User Manual

IP65 High Bay HF Motion Sensor
HMW31
1-10V Dimming with Remote Control
Technical Data
Input Characteristics
Model No.
Mains voltage Stand-by power
Load ratings:
Capacitive
Resistive
400VA@120V; 800VA@220 -277V
800W@120V; 1600W@220 -277V
HMW31
120~277VAC 50/60Hz
<1W
20sWarming-up
HF
Sensor Data
Model No.
Operation frequency
Transmission power
Detection range
Detection angle
HMW31
High Frequency (microwave) Sensor principle
5.8GHz +/- 75MHz
<0.2mW
Max. ( O x H) 10m x 15m
360
O
Safety and EMC
Safety standard (LVD)
Radio Equipment (RED)
Certication
EN55015, EN61000
EN60669-1, EN60669-2-1
EN300440, EN301489-1,
EN62479
Semko, CB, CE , EMC, RED, RCM
Mechanical Structures and Installations
For more details, please refer to user manual.
A. Ceiling mount
Daylight sensor
LED indicator
Environment
Operation temperature
IP rating
Rotary switch
Infrared receiver
Ta: -20OC ~ +70OC
IP65
4.1
75
80.7
91.5
IP65RED
313
Hytronik Microwave motion sensor
Sensor module
Installation rack
Cable entry
4.1
66.6
81.5
59.3
57.3
47.5
www.hytronik.com
24.5
B. Screw to the Luminaire by conduit
g
s
T
gh
C. Attach to the shade by clamp
LED indicator
Daylight sensor
Sensor module
Rotary switch
Infrared receiver
Cable entry
59.3
75
57.3
47.5
59.6
66.6
89.9
0.825”
64
35.2
4.5
15
4.5
28.5
29
LED indicator
Daylight sensor
Sensor module
*OUFMMJHFOU 1IPUPDFMM
0OF,FZ $PNNJTTJPOJOH
Rotary switch
Infrared receiver
"NCJFOUEBZMJHIU
UISFTIPME
Angle adjustment
Luminaire clamp
3PUBSZ4XJUDI
1SPHSBNJOH
%FUFDUJPO1BUUFSO

33.7
75
59.6
66.6
59.3
84.5
163.2
Functions and Features
Intelligent Photocell (daylight detection prior to motion detection)
1
The built-in photocell will also automatically turn off the light when the ambient natural light exceeds the programmed lux level for more than 5min, regardless of whether motion is detected or not. This feature can be disabled if it is required that the xture stays at dimmed level during absence.
With sufcient natural light, the light
th sufcient natural light, the li does not switch on when presence is detected.
With insufcient natural light, the sensor
th insufcient natural light, the switches on the light automatically when presence is detected.
The sensor switches off the light when
he sensor switches off the li natural light is sufcient, even with presence.
Note: if the stand-by time is preset at "+∞", the xture never switches off but stays at preset dimming level even when natural light is sufcient.
www.hytronik.com
Hytronik Microwave motion sensor
314
Tri-level Control (Corridor Function)
2
Hytronik builds this function inside the motion sensor to achieve tri-level control, for some areas which require a light change notice before switch-off. The sensor offers 3 levels of light: 100%-->dimmed light (natural light is insufcient) -->off; and 2 periods of selectable waiting time: motion hold-time and stand-by period; Selectable daylight threshold and freedom of detection area.
Zero-cross Relay Operation
3
Designed in the software, sensor switches on/off the load right at the zero-cross point, to ensure that the in-rush current is minimised, enabling the maximum lifetime of the relay.
Rotary Switch Preset
A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels are available:
Rotary switch preset
Note: settings can also be changed by remote control HRC-11. The last action controls.
zero-cross point
Channel Hold-time
Detection
range
0 5s100% Disable 1 1min100% 2Lux 2 5min100% 10Lux 3 5min100% 30Lux 4 5min100% 10Lux 5 5min100% 30Lux 6 5min100% Disable 7 10min100% 2Lux 8 10min100% 10Lux 9 10min100% 30Lux
A 10min100% Disable B 10min75% 30Lux C 10min50% 10Lux D 30min100% 50Lux E F
30min100% Disable 5s100%
Daylight sensor
Alternating current
Stand-by time
10s 5min 10min 30min 0s +∞ +∞ 10min 30min +∞
+∞ +∞ +∞ +∞ +∞ 10s
Stand-by dim level
10% 10% 10% 10% Disable 10% 30% 10% 10% 10%
30% 10% 10% 10% 30% 10%2Lux
Detection Pattern
Ceiling mounted height(m)

315
Hytronik Microwave motion sensor
Wiring Diagram
10%
30%
50%
75%
L N
Brown
Blue
Grey
Red
Black
L
LED driver
N
1-10V+
-
1-10V
HMW31
www.hytronik.com
Settings (Remote Control HRC-11)
ON/
Permanent ON/OFF function
OFF
Press button “ON/OFF” to select permanent ON or permanent OFF mode. * Press button “AUTO”, “RESET” to quit this mode.
mode will change to AUTO Mode after power failure.
The
Reset Settings
Press button “RESET”, all settings go back to rotary switch settings.
Shift Button
Press button “Shift”, the LED on the top left corner is on to indicate mode selection. All values / settings in RED are valid for 20 seconds.
AUTO mode
Press button “AUTO” to initiate automatic mode. The sensor starts working and all settings remain as before the light is switched ON/OFF.
Note: “Semi-auto” function is disabled.
A
&
III
Power output
Press the buttons to select light output at 80% (at initial 10,000 hours) or 100%.
Note: “Sensor off” and “Twilight” functions are disabled.
Brightness +/-
Press the buttons to adjust the light brightness during hold-time.
Load Indication: The light will ash ONCE rapidly after receiving the commamd from the remote control successfully.
HRC-11
Scene program - 1-key commissioning
1. Press button “Start” to program.
2. Select the buttons in “Detection range”, “Daylight threshold”, “Hold-time”, “Stand-by time”, “Stand-by dimming level” to set all parameters.
3. Press button “Memory” to save all the settings programmed in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s).
For example, to set detection range 100%, daylight threshold Disable, hold-time 5min, stand-by time +∞, stand-by dimming level 30%, the steps should be: Press button “Start”, button ”100%”, “Disable”, “Shift”, “5min”, “Shift”, “+∞”, “30%”, “Memory”. By pointing to the sensor unit(s) and pressing “Apply”, all settings are passed on the sensor(s).
Detection range
Press buttons in zone “Detection range” to set detection range at 100% / 75% / 50% / 10%.
Daylight threshold
Press buttons in zone “ Daylight threshold” to set daylight sensor at 2Lux/ 10Lux / 50Lux / 100Lux / 300Lux / 500Lux / Disable.
Note: To set daylight sensor at 100Lux / 300Lux / 500Lux, press “Shift” button rst.
www.hytronik.com
Hytronik Microwave motion sensor
316
Ambient daylight threshold
1. Press button “Shift”, the red LED starts to ash.
2. Press button “Ambient”, the surrounding lux level is sampled and set as the new daylight threshold.
Hold-time
Press buttons in zone “hold-time” to set the hold-time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min.
Note: 1. To set hold-time at 30s / 5min / 15min / 30min, press “Shift” button rst.
2. 2s is for testing purpose only, stand-by period and daylight sensor settings are disabled in this mode.
*To exit from Test mode, press button “RESET” or any button in “Hold-time”.
Stand-by time (corridor function)
Press buttons in zone “stand-by time” to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞.
Note: “0s” means on/off control; “+∞” means bi-level control, the xture is 100% on when there is motion detected, and remains at the stand-by dimming level when no presence after motion hold-time.
Stand-by dimming level
Press the button in zone “stand-by dimming level” to set the stand-by dimming level at 10% / 20% / 30% / 50%.
Auto-conguration function
All buttons in this zone are disabled.
Dual tech & RF mode
All buttons are disabled.
317
Hytronik Microwave motion sensor
www.hytronik.com
Loading...