Hytronik HMW12 Installation And Instruction Manual

1. Technical Specifications
Product type High bay microwave motion sensor (Daylight harvest)
Operating voltage 120~277VAC 50/60Hz
Rated load Resistive:700W@120V; 1600W@220-277V;
Capacitive:400VA@120V; 800VA@220-277V;
Power consumption < 1W
Detection angle 360
Detection area (DxH) 12 x 12m (Maximum)
Mounting height 15M(Maximum)
Detection range 10% / 50% / 75% / 100%
Hold time 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min
Stand-by time 0s / 10s / 1min / 5min / 10min / 30min / 1h / +
Stand-by dimming level 10% / 20% / 30% / 50%
Daylight threshold 50 ~ 500Lux, Disable
Warmming up time 20s
Operating temperature -20oC ~ +50oC
IP rating IP42
3. Rotary Switch Settings
A rotary switch is built inside the sensor for scene selection / fast programming. Total 16 channels available:
Note: settings can also be changed by remote control HRC-11. The last action controls.
8
SURFACE MOUNT HIGH BAY MOTION SENSOR HMW12
Installation and Instruction Manual
Rotary switch preset (Please see the location in 2. Installation)
4. Functions
The motion sensor is employed, but only activated on the manual press of the push switch, The light remains on during presence and dims down in absence, eventually switching off automatically after the stand-by time has expired. Note: in this mode, the push terminal used for the ‘manual on’ switch input. End-user can choose either function 4.3 or 4.4 for application. Default function is 4.3.
4.2 Lux Off Function
4.4 Semi-auto Function (Absence Detection)
4.3 Manual Override
With the help of push-switch, this sensor maybe over-ridden by the end-users to switch on/off the lights manually, or adjust the light brightness during motion hold-time. This makes the product more user-friendly and offers more options to fit for extra-ordinary demands. * Short push (<1s): on/off function; ON OFF: the light turns off immediately and cannot be lighten for a certain time (equals to hold time preset) even there is movement is detected. After this period, the sensor goes back to auto sensor mode. OFF ON: the light turns on 100% and goes to auto sensor mode, even when ambient Lux level exceeds the daylight threshold. * Long push (>1s): adjust the target lux level by turning the light up or down. Both the adjustment on remote control and push switch can overwrite each other, the last adjustment remains in memory.
HMW12-20170309-A1
2. Installation
Warnings:
1. Installation must be carried out by a qualified engineer in accordance with local regulations.
2. Disconnect supply before installing.
3. Install to a solid surface - vibrations may cause mis-triggering.
4. Ensure environmental conditions are suitable for electronic equipment
29
50.2
Direct junction “J” box mounting
a. Separate control board (A) from facia (B) & Surface box (C). C is not required. b. Make electrical connections to control board (A). See detailed wiring diagram on next page. c. Secure control board (A) to junction box. d. Set-up sensor modes as per sections 3 & 4 of this manual. e. Clip facial plate (B) to control board (A).
Surface mount assembly
a. Separate control board (A) from facia (B) & Surface box (C). b. Securely mount surface box (C) to a flat and solid surface. c. Make electrical connections to control board (A). See detailed wiring diagram on next page. d. Set-up sensor modes as per sections 3 & 4 of this manual. e. Secure control board (A) to surface box (C). f. Clip facial plate (B) to control board (A).
32.5
53.7
C - Surface box
B - Facia Cover
A - Control Board
Rotary switch preset
Photocell
Infrared receiver
HF Sensor module
LED indicator
4.1 Daylight Harvest (Daylight Regulating)
Daylight sensor measures the available surrounding natural light, calculates how much electrical light is needed to reach the total lux expected. The demand is given to the LED driver by 1-10V signal, so as to deliver the needed amount of electric light.
0 24
Light level
Time (hrs)
Normal Electric Light
Daylight controlled light
Energy Saving Zone
Natural light
Hold time
Stand-by time
Detection range
Channel
0 1 2 3 4 5 6 7 8 9 A B C D E F
100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
5s 1min 5min 5min 5min 5min 10min 10min 10min 10min 20min 20min 30min 30min 30min 5s
10s 5min 10min +∞ +∞ +∞ 30min +∞ +∞ +∞ 1h +∞ +∞ +∞ +∞ 10s
10% 10% 10% 10% 10% 30% 10% 10% 10% 30% 10% 30% 10% 30% 50% 10%
Disable 50Lux 50Lux 75Lux 100Lux 200Lux 50Lux 75Lux 100Lux 200Lux 100Lux 200Lux 100Lux 200Lux 400Lux 100Lux
Hold time
Stand-by time
Stand-by dimming level
Daylight threshold
The light dims to minimum level even switches off completelly if ambient daylight is sufficient (natural light level exceeds target lux level), no matter it is during hold-time or stand-by time, with or without motion. Note: if the stand-by time is preset at "+∞", the light never turns off even when natural light is sufficient.
Ceiling mounted detection pattern (m)
Ceiling mounted height(m)
6
0
12
10%
10%
30%
30%
75%
75%
50%
50%
5. Wiring Diagram
8. Trouble Shooting
Description of the Button Functions (remote control HRC-11)
MALFUNCTION CAUSE REMEDY CAUSE REMEDY
The fixture does not light up
The fixture is always on
Check detection area setting
The fixture is on when it should not
Incorrect daylight threshold setting
Continued movement in the detection zone
Sudden change in temperature due to weather (wind, rain, snow) or air expelled from fans, open windows
Detection zone not targeted
Faulty fixture
No power supply
Adjust daylight threshold setting
Replace fixture
Check power to sensor
Check detection area setting
Adjust zone, change installation site
7.
HRC-11
6
8
10
11
12
13
14
2
4
1
3
7
9
5
Permanent ON/OFF [ ]
Press button to select permanent ON or permanent OFF mode. * Press button / to resume automatic operation.
Semi-auto Mode [ button & ]
Power output [ button ]
Press button , the light output shifts between 80% and 100%. Note: the function of “Sensor off” and “Twilight” are disabled.
Ambient daylight threshold [ button ]
Detection range [ zone ]
Press buttons in zone to set detection range at 100% / 75% / 50% / 10%.
Stand-by time [ zone ]
Press buttons in zone to set the stand-by period at 0s / 10s / 1min / 5min / 10min / 30min / 1h / +∞. Note: “0s” means on/off control; “+∞” means bi-level control, 100% on when motion detected, and remains at the stand-by dimming level when no presence after hold-time.
Daylight threshold [ zone ]
Press buttons in zone to set the daylight sensor at 2Lux / 10Lux / 50Lux / 100Lux / 300Lux / 500Lux or Disable. Note: 2lux / 10lux are disabled. To set daylight sensor at 100Lux / 300 Lux / 500Lux, press button Shift at first.
button
Auto Mode [ button ]
Brightness +/- [ button ]
Press button to adjust the light brightness to reset the target lux level.
Scene prog. [ zone ]
(One-key-commissioning)
1. Press button Shift, the red LED is on for indication.
2. Press button , the ambient lux level is sampled and set as the new daylight threshold / target Lux level.
Hold time [ zone ]
Press buttons in zone to set the hold time at 2s / 30s / 1min / 5min / 10min / 15min / 20min / 30min. Note: 1.To set hold-time at 30s / 5min / 15min / 30min, press button Shift at first.
2. 2s is for test purpose only, stand-by period and daylight sensor settings are disabled in this mode. *To exit from Test mode, press button or any button in zone .
Stand-by dimming level [ zone ]
Press buttons in zone to set the stand-by dimming level at 10% / 20% / 30% / 50%.
Dual tech & RF mode [ zone ]
All buttons in zone are disabled.
Detection Pattern6.
Shift [ button ]
LED Driver
1-10V
+
-
L
N
P
L N
1-10V
+
-
L’ N N L
RESET [ button ]
Press button , all settings go back to the rotary switch settings.
Press button to initiate automatic mode. The sensor starts working and all settings remain as before the light was switched ON/OFF.
1. Press button “Start” to program.
2. Select the buttons in “Detection range”, / “Daylight threshold”, “Hold time”, “Stand-by time”, “Stand-by dimming level” to set all parameters.
3. Press button “Memory” to save all the settings programmed in the remote control.
4. Press button “Apply” to set the settings to each sensor unit(s). For example, to pre-set detection range 100%, daylight threshold Disable, hold time 5min, stand-by time +∞, stand-by dimming level 30%, steps should be: Press button Start, button 100%, Disable, Shift, 5min, Shift, +∞ , 30%, Memory. By pointing to the sensor unit(s) and pressing Apply, all settings are passed on the sensor(s).
Press button , the LED on the top left corner is on for indication. All values / settings in RED are in valid for 20 seconds.
1. Press button Shift (the red LED is on for indication),
2. press button to initiate semi-auto mode. The fixture is manually on by push-switch and automatically off in semi-auto mode.
1
8
3
3
2
9
10
11
12
13
14
14
13
12
11
11
10
9
8
2
2
3
3
3
3
4
4
4
5
6
7
7
7
7
3
3
8
8 9
10
10
11
1312
11 12
13
6
5
4
1
2 4
3
HMW12-20170309-A1
HMW12
Hytronik Industrial Ltd. | www.hytronik.com 3rd Floor, block C, complex building, 155#, Bai'gang road south, Bai'gang village, Xiao Jin Kou town, Huicheng district, Huizhou 516023 Tel: 86-752-2772020 Fax: 86-752-2777877
Note: if neither function 4.3 nor 4.4 is desired, simply leave the “push” terminal disconnected.