Hypertherm DuraChill 5 HP User Manual

0p
Operators Manual
DuraChill™ 5 HP Air-Cooled Chiller
For Hypertherm
110-482
05-21-10
806600r0
Table of Contents
Section 1 – Safety and Warranty Information
1.1 Safety
1.2 Warranty
1.3 Unpacking
Section 2 – Introduction
Section 3 – Specifications
Section 4 – Installation and Startup
Section 5 – Normal Operation
2.1 General Description
2.2 Component Identification
2.2.1 Control System
2.2.2 Fluid Circulation System
2.2.3 Cooling System
3.1 Air-Cooled Chillers — DA 500
4.1 Site Requirements
4.1.1 Ambient Temperature and Relative Humidity
4.1.2 Location
4.1.3 Clearance
4.2 Plumbing
4.2.1 Process Piping
4.2.2 Reservoir Vent
4.2.3 Reservoir Drain
4.3 Reservoir Low Level Float Switch Alarm
4.4 Fan
4.5 Electrical Power
4.5.1 Power Phase Requirements
4.5.2 Remote On / Off
4.6 Startup
4.6.1 Process Coolant
4.6.2 Starting Process Fluid Flow
4.6.3 Adjusting the Set Point
4.6.4 Selecting Celsius or Fahrenheit
5.1 Power On
5.2 Controller Display / Menu Structure
5.3 Controller Display / Menu Navigation
5.4 Checking / Adjusting Set Point
5.5 Selecting Celsius or Fahrenheit (ºC or ºF)
5.6 Pressure Display – 0 to 247 psi; 0 to 1700 kPa
5.7 High Temperature Limit (HL)
5.8 Low Temperature Limit Value (LL)
5.9 High Ambient Temperature Limit (HA)
5.10 Low Temperature Band (Compressor Turn Off)
5.11 Upper Temperature Band (Compressor Turn On)
5.12 Temperature Calibration Offset (c1)
5.13 Low Ambient Temperature Alarm Setting (LA)
5.14 Controller Operating, Alarm, and Error Messages
5.15 Dual Float Switch
5.16 Loss of Power
5.17 High Pressure Bypass Setting
5.18 Enabling/Disabling the Local Lockout
5.19 Automatic Restart from Alarm Mode
5.20 Fuse Bits
- 2 -
Section 6 – Routine Maintenance
6.1 Recommended Routine Maintenance Schedule
6.2 Routine Maintenance Procedures
6.2.1 Inline Strainers
6.2.2 Reservoir Coolant Level
6.2.3 Coolant Freeze Protection
6.2.4 Air Filters
Section 7 – Troubleshooting
7.1 Unit will not operate (no cooling or pumping)
7.2 No Pumping
7.3 Insufficient Pumping
7.4 No Cooling or Insufficient Cooling
7.5 Triac Failure
7.6 Internal Probe Failure
7.7 Pump Overload Fault Ft 19
7.8 Fan Overload Fault “Ft 21”
7.9 Compressor Overload Ft 20
Section 8 - Service and Technical Support Appendix
A.1 Flow Diagram A.2 Wiring Diagram A.3 Parts Replacement
This symbol marks chapters and sections of this instruction manual which are particularly relevant to safety. When attached to the unit, this symbol draws attention to the relevant section of the instruction manual.
This symbol indicates that hazardous voltages may be present.
Read all instructions pertaining to safety, set-up, and operation.
Proper operation is the users’ responsibility.
Section 1 – Safety and Warranty Information
1.1 Safety
It is the user’s responsibility to read and understand all instructions and safet y precautions included in this manual prior to installing or operating this equipment. Contact our Customer Service Department with any questions regarding the operation of this chiller or the information contained in this manual.
Installation, operation, or maintenance of this equipment should be performed in strict accordance with the instructions outlined in this manual. Failure to follow those instructions may increase the risk of personal injury, damage the equipment, and/or void the warranty.
Exercise care when unloading, loading, rigging, or moving this equipment.
All warning labels should be carefully observed. Never remove or obstruct a warning labe l.
- 3 -
Make sure that ventilation is adequate when welding or brazing around this equipment. Protect adjacent materials from flames or sparks. Keep an approved fire extinguisher close at hand.
Always operate this equipment within the stated design specifications.
Be sure to remove power from the equipment, reclaim the refrigeration charge, and relieve any residual pressure before cutting into the refrigeration system.
Do not attempt to operate leaking or damaged equipment.
Service should only be performed by fully qualified personnel.
Follow all applicable electrical and safety codes when connecting power to this equipment.
Do not attempt to override the power interlock switch or any other safety features on this equipment.
Always remove power from the equipment prior to performing any service or maintenance.
Do not move the equipment without first disconnecting power.
Make sure the equipment’s main power switch is in the OFF position before connecting or disconnecting power.
Additional Precautions
Do not attempt to operate this equipment without an appropriate cooling fluid in the reservoir. Always empty the fluid reservoir before moving the unit.
1.2 Warranty
Thank you for purchasing this chiller. We are confident it will serve you for a long time. Our warranty to you is as follows:
The manufacturer agrees to correct for the original user of this product, either by repair, or at the manufacturer's election, by replacement, any defect that develops after delivery of this product within the period as stated on the warranty card. In the event of replacement, the replacement unit will be warranted for 90 days or warranted for the remainder of the original unit’s parts or labor warranty period, whichever is longer.
If this product requires service, contact the manufacturer/supplier's office for instructions. When return of the product is necessary, a return authorization number will be assigned and the product should be shipped, (transportation
- 4 -
charges pre-paid), to the indicated service center. To insure prompt handling, the return authorization number should be placed on the outside of the package and a detailed explanation of the defect enclosed with the item.
This warranty shall not apply if the defect or malfunction was caused by accident, negl ect, unreasonable use, improper service, or other causes not arising out of defects in material or workmanship. There are no warranties, expressed or implied, including, but not limited to, those of merchantability or fitness for a particular purpose which extends beyond the description and period set forth herein.
The manufacturer's sole obligation under this warranty is limited to the repair or replacement of a defe c tive product and shall not, in any event, be liable for any incidental or consequential damages of any kind resulting from use or possession of this product. Some states do not allow: (A) limitations on how long an implied warranty lasts; or (B) the exclusion or limitation of incidental or consequential damages, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights. You may have other rights that vary from state to state.
1.3 Unpacking
Your chiller is shipped in a special container. Retain the container and all packing materials until the unit i s completely assembled and working properly. Set up and run the unit imm ediately to confirm proper operation. Beyond one week, your unit may be warranty repaired, but not replaced. If the unit is damaged or does not operate properly, contact the transportation company, file a damage claim and contact the company where your unit was purchased immediately.
Section 2 – Introduction
2.1 General Description
®
The PolyScience self-contained chiller is engineered to provide accurate temperature control.
Standard Features
Process temperatures from 32° to 86°F (0° to 30°C)
Ambient temperatures from 14° to 104°F (-10° to 40°C)
±2°F (±1.11°C) temperature stability
High efficiency vertical air exhaust
Accurate microprocessor control with LED temperature readout
Over/under temperature process fluid alarms
Copeland Scroll
Stainless steel centrifugal pump
Integral pump and compressor protection
Locking casters
NEMA 12 style electrical enclosure with door-mounted power disconnect
Power phase monitor
Full Flow Bypass Valve
Low tank level indicator/alarm – Dual Float Switch
DuraChill chiller offers exceptional performance, reliability, and operational simp licity. This robust
®
compressor
2.2 Component Identification
Your Chiller consists of three basic sub-systems:
Control system
Fluid circulation system
Cooling system
This section describes these sub-systems in detail and includes information on the av ailable options. See Sections A.1 and A.2.
- 5 -
2.2.1 Control System
This system controls and monitors Chiller operation. It consists of a microprocessor-based controller linked to the various sensors, gauges, valves, switches, and signal input/output connections on the unit.
Control Panel
— Temperature set point, temperature units, and other operating parameters are set via the Control
Panel. Operating information is displayed on a local LED readout. TEMPERATURE CONTROLLER PCB = Part No.: 500-367 POWER SUPPLY PCB
= Part No.: 215-513
Pressure/Flow Display
Power Switch / Disconnect functions as a power disconnect when access to the unit’s electrical components and terminal blocks is required; the access door cannot be opened until the Power Switch / Disconnect is placed in the Off position.
DISCONNECT SWITCH Temperature Probe — An internal RTD is used to measure fluid temperature downstream of the pump. Its reading is
displayed on the Control Panel LED. PLATINUM TEMPERATURE PROBE = Part No.: 200-450 Pressure Sensor
— Measures fluid pressure at the outlet of the Chiller.
PRESSURE TRANSDUCER
2.2.2 Fluid Circulation System
This system governs the circulation of fluid through the unit. Reservoir Tank — This polyethylene tank is used to maintain stable temperature control and an adequate reserve of
fluid for the system. It is equipped with a float switch that monitors fluid level and activates an alarm if the level drops too low.
Tank Sight Glass or Level Indicator the Reservoir Tank.
Process Pump
— The high pressure turbine pump is used to pump fluid from the Reservoir Tank to the process. 1HP TURBINE PUMP 200-240/380-460V 50/60Hz = Part No.: 505-174 575-600V 60Hz = Part No.: 505-178 Recirculation Pump — The stainless steel centrifugal pump assures adequate flow through the evaporator to optimize
heat transfer. ½ HP CENTRIFUGAL PUMP 200-240/380-460V 50/60HZ = Part No.: 505-175 575-600V 60HZ = Part No.: 505-177
Units/Menu
Select Button
Temperature Display
Select/Set Knob
Power Button
— The main power switch is located on the front door of the unit. This switch also
= Part No.: 215-629
= Part No.: 750-757
— This indicator serves as a convenient means of checking the liquid level within
- 6 -
Dual Float Switch — If fluid level should fall below the upper float switch (7 gallons low) the right hand display will alternately show “EFL” and fluid temperature, Audible alarm will intermittently sound. This will continue indefinitely until attended to.
If fluid level should fall below the lower float switch (9 gallons low) the right hand display will alternately show “EF2” and fluid temperature, Audible alarm will intermittently sound and after a delay the unit will turn off.
DUAL FLOAT S WITCH Flow Switch
— Monitors internal recirculation flow. If flow rate is less than 4 gpm or fluid level in reservoir is below
= Part No.: 235-064
lower float switch an alarm message - “EF2” is displayed and chiller turns off. FLOW SWITCH
= Part No.: 235-052 Strainer — Traps debris which could potentially clog the Evaporator. RECIRCULATION PUMP ‘Y’ FILTER (3/4”) PROCESS OUTLET ‘Y’ FILTER (1/2”) Bypass Valve
— Used to prevent overloading of pump in the event that the process piping becomes restricted or
clogged. Diverts flow from process line back to Reservoir Tank. 200 PSI PRESSURE RELIEF VALVE
2.2.3 Cooling System
The condenser on your Chiller is air-cooled. The following components are common to all systems.
Common Cooling System Components
Evaporator
— Serves as the heat exchanger between the refrigeration and fluid flow system. Cools fluid before it
returns to process. BRAZED PLATE HEAT EXCHANGER = Part No.: 750-214 Compressor
— The unit incorporates a 5-HP Copeland Scroll® compressor. The Compressor is protected from
overloads through high and low refrigerant pressure cutouts. 5HP COMPRESSOR 200-230V 50/60Hz = Part No.: 750-833 380-460V 50/60HZ = Part No.: 750-813 575-600V 60HZ = Part No.: 750-832 Filter Dryer
— Removes residual particulate and moisture from the refrigeration system. Must be replaced whenever
the sealed refrigeration lines are opened for service.
FILTER DRYER = Part No.: 750-229
Sight Glass SIGHT GLASS Expansion Valve
— Used to observe refrigerant liquid flow to Evaporator.
= Part No.: 750-230
— Controls refrigerant superheat at the outlet of the Evaporator to prevent liquid from returning to
the compressor. TXV (Thermostatic Expansion Valve) = Part No.: 750-814 Hot Gas Bypass Solenoid Valve
— Injects refrigerant vapor into the Evaporator to stabilize temperature control when
operating at less than a full heat load. SOLENOID VALVE = Part No.: 750-222 COIL = Part No.: 750-216 Refrigerant Relief Valve
— Automatic safety used to vent refrigeration gas in the event that pressure exceeds a
factory set value. This valve is set to open at 650 PSI. SAFETY RELIEF VALVE ¾ MPT (650PSI) = Part No.: 750-815
- 7 -
= Part No.: 400-710
Part No.: 775-174
= Part No.: 776-090
Condensing Fan — A 1 HP fan that draws air over the condenser coils to cool refrigerant gas. The standard fan is fixed speed and cycles on/off based on refrigerant pressure. It turns on when refrigerant pressure is 400 PSI or greater, turns off when refrigerant pressure falls below 300 PSI.
1HP FAN MOTOR
200-240/380-460V 50/60 Hz = 575-600V 60 Hz = Part No.: 215-603
Refrigerant Pressure Switches — These switches automatically disconnect power from the condenser system in the event that refrigerant pressure is outside factory set high/low values. The Low Pressure Switch is set to open at 10 PSI and close at 30 PSI. The High Pressure Switch is set to cutout at 630 PSI.
HIGH PRESSURE CUTOUT SWITCH LOW PRESSURE CUTOUT SWITCH Fan Cycling Switch
pressure reaches 400 PSI; it is turned Off when the discharge pressure drops below 300 PSI. FAN CYCLING SWITCH = Part No.: 215-726
— This switch controls fan operation. The fan is turned On when the compressor discharge
Section 3 – Specifications
3.1
Part No.: 215-435
= Part No.: 235-071
= Part No.: 215-436
Model DA500
Process Temperature 32° to 86°F (0° to 30°C)
Temperature Stability ±2.0°F (±1.11°C)
Ambient Operating Temperature 14° to 104°F (-10° to 40°C)
Compressor (nominal HP) 5 HP Copeland Scroll®
1, Capacity based on 95°F (35°C) entering air and 120°F (49°C) condensing temperature. Leaving water 50°F (10°C). Allowance made for heat gain from pump.
2. Flow rate based on 2.4 GPM (US) per ton (0.54m
Refrigerant Charge (R-410A) 10 lbs.
Cooling Capacity1
Nominal Evaporator Flow2
GPM (US)
Fan 1 HP
Condenser Discharge Air Flow 3,500 CFM
Reservoir Tank Capacity 16 gallons
Dimensions (D x W x H) 54 x 34.5 x 67 inches
Shipping Weight 990 Lb. (449 Kg)
Voltage ±10%
200-240V, 3 phase,50/60Hz
380-440V, 3 phase, 50Hz
460-480V, 3 phase, 60Hz
575-600V, 3 phase, 60Hz
55,920 BTU/hr
Nominal Rated Amps
3
/hr/ton)
4.66 tons
16,384 watts
11.7
30 A 20 A 15 A 12 A
- 8 -
Section 4 – Installation and Startup
4.1 Site Requirements
4.1.1 Ambient Temperature and Relative Humidity
The Chiller is designed for indoor installation in ambient temperatures between 14° and 104°F (-10° to 40°C); relative humidity should be between 20% and 80% (non-condensing).
4.1.2 Location
The Chiller should be installed on a level surface capable of supporting 990 pounds (449 kg) or more and should be located as close to possible to the process requiring cooling. It should not be installed closer than 4 feet (1.4 meters) to a heat generating source, such as heating pipes, boilers, etc.). If possible, it should be located near a suitable drain to prevent flooding in the event of leaks.
For ease of final positioning and maneuverability, the Chiller is supplied with four heavy-duty locking casters. Use fork lift if moving more than 20 feet.
4.1.3 Clearance
At least 18 to 24 inches (45.7 to 61 cm) of clearance should be allowed on the front, sides, and rear of the Chiller for access to connections and components. Chillers require at least 4 feet (1.4 meters) of overhead clearance to dissipate the exhaust from the Chiller’s top-mounted fan.
4.2 Plumbing
See Figure 4-1
4.2.1 Process Piping
The Chiller incorporates two 1/2” MPT x ¾”- 16 male 37 process inlet and outlet connections.
To maintain a safe workplace and to avoid leaks, special care should be taken when choosing hoses and connections for the Chiller.
Pressure Ratings — Hoses should be able to withstand a minimum of 250 PSI.
Flexible Tubing — Avoid tubing that will expand and take up fluid volume when operating at the desired
pressure.
- 9 -
° flare, #8 JIC fittings on the rear of the enclosure for the
4.2.2 Reservoir Vent
A ¾ inch female NPT connection is provided at top of sight glass for the reservoir vent line. This vent is intended to prevent siphoning and/or overflows in the event of a problem with process liquid circulation. The vent pipe should extend to a height at least 6 to 12 inches (15.2 to 30.5 cm) above the process equipment. If desired you may fill the chiller through vent fitting providing the reservoir cap is off to let air escape.
4.2.3 Reservoir Drain
A ¾ inch female NPT connection is provided at bottom of sight glass for the reservoir’s gravity drain. It should be piped to a drain or receptacle positioned lower than the bottom of the reservoir. If a receptacle is used, be sure is of sufficient volume to hold all the water in the reservoir, process, and process lines.
4.3 Reservoir Low Level Float Switch Alarm This is designed to alert you when the fluid level in the Chiller’s reservoir drops too low
4.4 Fan
The Chiller’s fan may be allowed to exhaust freely into the area in which the unit is located or may be vented to an exhaust duct of the appropriate size. If it is connected to an exhaust duct, the duct work should incorporate an auxiliary blower to prevent back pressure from impacting fan operation.
4.5 Electrical Power
All electrical connections should be made by a qualified, licensed electrician. Proper building codes and safety regulations should be followed.
4.5.1 Electrical Phase Requirements The Chiller is designed with a junction box on the rear of the unit to connect the electrical power supply conduit. See
Figure 4-1.
Make sure that the power supply to the Chiller is the same voltage, frequency, and phase as indicated on the identification label.
Be sure to connect the wires in the proper phase sequence. i.e.: L1, L2 and L3. Provide suitable conduit strain relief and grounding.
Your chiller is equipped with a phase monitor. It is located inside the controls enclosure. It will prevent startup if phase connection is incorrect. It will also turn the chiller off in the event of a loss of one phase. It will also prevent chiller operation if the voltage mismatch between any two phases is greater than 8%.
IMPORTANT: Do not turn Controller power On until the Chiller reservoir has been filled. When Controller power is turned On, both pumps automatically begin pumping. If the reservoir has not been filled, the pumps will be damaged.
4.5.2 Remote On / Off This allows the user to turn the Chiller on and off using a 24 VDC input to turn unit on and removal or loss of 24 VDC
will turn the unit off and “Ec“ (External control) will be displayed in the “Temperature Display”. A mating plug for connector on rear panel has been shipped with manual. A 3 conductor, 22 AWG Cable (Consolidated PN: 5401-CL, Multi-Conductor Cable or equivalent) to be supplied by user. Connect terminals “1” and “2” to user suppl ied source of 24VDC. See Figure 4-1 and A.2 Wiring Diagram.
- 10 -
4.6 Startup IMPORTANT: Be sure to turn main power Off before filling the reservoir.
4.6.1 Process Coolant
Use only Hypertherm Premixed Coolant
= Part No.: 028872
69.9% Distilled Water, 30% Polypropylene Glycol, 0.1% Benzotriazole
Provides freeze protection to -12ºC (10ºF).
Do not use flammable fluids as a fire hazard may result.
WARNING: Coolant freeze protection must be 14ºC (25ºF) below the lowest possible display temperature. The lowest possible display temperature is equal to the process setpoint minus the Lower Band “Lb” setting.
If additional freeze protection is required, use 100% glycol to achieve required mixture.
Hypertherm 100% Glycol
= Part No.: 028873
Filling the Reservoir See Figure 4-2. Remove the panel from the rear left side of the enclosure. It is held in place with 1/4-20 Philips head captive scre ws. Remove the filler cap from the reservoir and fill it to a level approximately 2 inches (5.1 cm) from the top of the
reservoir. Do not replace the cap at this time.
- 11 -
4.6.2 Starting Process Fluid Flow
Turn main power On. NOTE: When the Power Switch/Disconnect is placed in the On position, five decimal points (…..) will appear on the
Controller’s LED displays. This signifies that the Controller is in “standby” and ready for p ower up.
WARNING: The first time the chiller is operated it should be run 12 hours in the standby mode. The compressor crankcase heater will boil off any refrigerant absorbed in the compressor oil.
IMPORTANT: Do not turn Controller power On until the Chiller reservoir has been filled. When Controller power is turned “On”, both pumps automatically begin pumping. If the reservoir has not been filled, the pumps will be damaged.
Press the Controller’s “POWER” button. The system startup sequence will begin and proceed as follo ws:
The pump will turn on.
NOTE: On initial startup and after long periods of inactivity, run the unit for 10 seconds,
shut off unit and restart 3 times to remove any air in the lines.
The current set point temperature will briefly appear on the “Temperature Display”. After a short time delay or
upon pressing the knob the actual temperature reading will appear. The right decimal point on the “Temperature Display” will flash while the set point value is displayed.
The system will then go through a short initialization sequence.
Once the initialization has been completed, the compressor will turn on. When the pressure in the discharge line
reaches 400 PSI, the fan will turn on.
The Controller will displa y the actual process fluid temperature. The appropriate “degrees” LED will be lit
continuously (Centigrade “C” or Fahrenheit “F”).
Check the fluid level in the reservoir. The liquid level should drop as fluid flows to the process. Slowly add fluid to the reservoir until the level in the reservoir stops going down. This means that the system is filled and any entrained air purged. Replace the reservoir cap and securely tighten.
Check for leaks in the process lines and at the process line connections.
4.6.3 Adjusting the Set Point
NOTE: The factory default set point temperature is 15°C (59°F). Press the Select/Set Knob on the front panel. The current set point temperature will be displa yed and the decimal
point at the bottom right of the display will flash, indicating the temperature can be changed. Rotate the Select/Set Knob until the desired set point temperature is displayed. The setting is accepted after either
pressing the Select/Set Knob a second time or will be accepted automatically after a few seconds of inactivity.
4.6.4 Selecting Celsius or Fahrenheit / Reset Factory Default Values
The chiller as supplied will read in °C. The LED's adjacent to the Temperature Display indicate the unit of measure (°C or °F). To change from °C to °F or
vice versa, proceed as follows:
To change to °F and hold the Units/Menu Select Button while returning the Disconnect Switch to the “On” position.
To change to °C and hold the Power Button on the front panel while returning the Disconnect Switch to the “On” position.
IMPORTANT: All user settings, calibration offset, return to the original factory default values when the unit in which temperature is displayed is changed. The Chiller’s temperature set poi nt and various alarm settings should be reset to the desired values.
— Place the main Disconnect Switch on the front of the chiller in the “Off” position. Press
— Place the main Disconnect Switch on the front of the chiller in the “Off” position. Press
- 12 -
Section 5 – Normal Operation
Pressure/Flow Display
5.1 Power On
When the “Power Disconnect Switch” is placed in the “On” position, the Controller goes into a “standby” mode. Five decimal points (…..) will appear on the Controller’s displays.
IMPORTANT: Do not turn Controller power on until the Chiller reservoir has been filled. When Controller power is turned on, both pumps automatically begin pumping. If the reservoir has not been filled, the pumps will be damaged.
Press the Controller’s On button. The system startup sequence will begin and proceed as follows:
1. Both pumps will turn on.
2. The current set point temperature will briefly appear on the display followed by the actual temperature reading.
The “°F” LED will flash while the set point value is displayed.
3. The system will then go through an initialization sequence.
4. Once the initialization has been completed, the compressor will turn on. When the pressure in the discharge line
reaches 400 PSI, the fan will turn on.
5. The Controller will display the actual process fluid temperature. T he appropriate “degrees” LED will be lit
continuously.
NOTE: Once installed, leave in standby mode to keep compressor oil active.
Units/Menu
Select Button
Temperature Display
Select/Set Knob
Power Button
- 13 -
5.2 Controller Display / Menu Structure To access the user menu press and hold the Units/Menu Select button until “HL” appears. Press and release the
Units/Menu Select button to scroll through the menu items.
Menu Item Description Choices / Ranges / Comments Default
HL
LL
HA
FP
w/PSI LED lit
FP
w/KPa LED lit
FL
w/GPM LED lit
FL
w/LPM LED lit
Lb
Ub
c1
c2
c3
Cd
High Temperature Limit
Alarm Set Point
Low Temperature Limit Alarm Set Point
Front Panel High Ambient Temperature Alarm Set Point
Maximum Fluid Pressure Alarm Set Point
Maximum Fluid Pressure Alarm Set Point
Minimum Flow Rate Alarm Set Point
Minimum Flow Rate Alarm Set Point
Lower Temperature Band
Upper Temperature Band
Calibration Offset Temp 1
Calibration Offset Temp 2
Calibration Offset Temp 3
Compressor Delay 10 – 300 seconds 20 sec.
-20°C to +27°C / -4° to 80°F 4ºC (39°F)
+30° to 75°C. Always displayed and set in °C. 45ºC
10 to 250 PSI 250 PSI
0.68 to 17 (x 100) kPa
NA 0.0 GPM
NA 0.0 LPM
1.0 to 5.0°C. Always displayed and set in °C
1.0 to 5.0°C. Always displayed and set in °C
±2.9°C. Always displayed and set in °C. Special access procedure required. See Section 5.13.
NA
NA
-15° to 45°C ( 5° to 113°F)
Setting
35ºC (95°F)
(x 100) kPa
5.0°C
5.0°C
0.0°C
0.0°C
0.0°C
17
Fc dS Sh
PC
LA
Pd td
NOTE: See Section 5.14 for Alarm and Error messages.
Flow Calibration NA Factory Set Coolant Density NA 8.35 Coolant Specific Heat NA 1.00
Communications Baud Rate
Low Ambient Alarm Setpoint
Password 0 to 999 (for service use only) 0 HGB Valve Delay 0 to 999 (for service use only) 2
- 14 -
NA 9600
1 to 7°C. Always displayed and set in °C 2°C
5.3 Controller Display / Menu Navigation
Actual Fluid Temperature — Fluid temperature leaving the chiller is displayed on the right hand LED display. Pressure and Flow Rate -- The pump pressure and flow rate are displayed on the left hand LED display. Press and
release the Units/Menu Select button to choose the measurement to be displayed. F low meter is not fitted on this model. Scrolling down this menu shows “At” ambient temperature in control compartment and “P2” Remote temperature (not fitted on the model.)
Set Point Temperature Operational Setup Menus and Values — Operational Setup Menus are accessed by press ing and holding the
Units/Menu Select button until “HL” is displayed. Continued pressing of the Units/Menu Select button will scroll through the menu.
Menu parameters are changed by turning the Select/Set knob. Displayed values can be accepted by pressing either the Select /Set knob or simply allowing a few seconds to pass without any keypad activity.
NOTE: After a few seconds of keypad inactivity, the Controller automatically returns to the normal operating display.
5.4 Checking / Adjusting the Set Point
NOTE: The factory default set point temperature is 15°C (59°F). Press the Select/Set Knob on the front panel. The current set point temperature will be displa yed and the decimal
point at the bottom right of the display will flash, indicating the temperature can be changed. Rotate the Select/Set Knob until the desired set point temperature is displayed. The setting is accepted after either
pressing the Select/Set Knob a second time or will be accepted automatically after a few seconds of inactivity.
— The set point temperature can be checked at any time by pressing the Select/Set knob.
5.5 Selecting Celsius or Fahrenheit (°C or °F)
The LED’s adjacent to the Temperature Display indicate the unit of measure (°C or °F). To change from °C to °F or vice versa, proceed as follows:
To change to °F and hold the Units/Menu Select Button while returning the Disconnect Switch to the “On” position.
To change to °C and hold the Power Button on the front panel while returning the Disconnect Switch to the “On” position.
IMPORTANT: All user settings, except calibration offset, return to the original factory defaults when the unit in which temperature is displayed is changed. The Chiller’s temperature set poi nt and various alarm settings should be reset to the desired values.
5.6 Pressure Display – 0 to 247 psi; 0 to 1700 kPa
Psi – Pressure will display from 0 to 99 psi. Above 99 a decimal point will appear bet ween the digits. This means drop the decimal and add 100 to the reading. For example; 1.2 = 112 psi, 7.4 = 174 psi. Above 199 psi display will read _._.
kPa x 100 – Pressure will display from 0 to 1700 kPa.
5.7 High Temperature Limit (HL)
This menu item serves two functions. First, it establishes the maximum allowable set point temperature and thus helps prevent an operator from inadvertently setting the temperature set point above a pre-establis hed temperature. Secondly, it serves as a high temperature alarm, automatically activating both audio and visual alarm indicators when the measured fluid temperature reaches the HL setting. The compressor, heater, fan, and pump will also turn off.
To change the high temperature limit value, rotate the Select/Set Knob until the desired value is displayed on the temperature display.
— Place the main Disconnect Switch on the front of the chiller in the “Off” position. Press
— Place the main Disconnect Switch on the front of the chiller in the “Off” position. Press
HL
- 15 -
35.0
5.8 Low Temperature Limit (LL)
This menu item also serves a dual function. First, it establishes the minimum allowable set point temperature and thus helps prevent an operator from inadvertently setting the temperature set point below a pre-established temperature. Secondly, it serves as a low temperature alarm, automatically activating both audio and visual alarm indicators when the measured fluid temperature drops to the LL setting. The compressor, heater, fan, and pump will also turn off.
To change the low temperature limit value, rotate the Select/Set Knob until the desired value is disp layed on the temperature display.
LL
NOTE: See Section 4.6.1 for freeze protection requirements.
5.9 High Ambient Temperature Limit (HA)
This menu item protects the Chiller from overheating due to a high ambient temperature. Should the ambient temperature rise above the limit value, the audio and visual alarms will activate and the compress or, heater, fan, and pump will turn off.
To change the high ambient temperature limit value, rotate the Select/Set Knob until the desired value is displayed on the temperature readout.
NOTE: This value is always displayed and set in °C.
HA
5.10 Lower Temperature Band (Compressor Turn Off)
This menu item provides access to the Lower control band value. This is the amount below set point that the process temperature can drop before the compressor turns off. It is useful at heat loads less than 30% of full capacity. The highest setting of 5.0°C will give longest compressor life.
Lb
NOTE: See Section 4.6.1 for freeze protection requirements.
5.11 Upper Temperature Band (Compressor Turn On)
This menu item provides access to the Upper control band value. This is the amount above set point that the process temperature can raise before the compressor turns on. It is useful at heat loads less than 30% of full capacity. The highest setting of 5.0°C will give longest compressor life.
4.0
45
5.0
Ub
5.12 Temperature Calibration Offset (c1)
This menu item allows you to adjust the Chiller’s displayed temperature reading to match that of a traceable standard. It allows you to offset the displayed temperature value by as much as ±1.9°C.
NOTE: Calibration offset values are always set and displayed in °C. To prevent the operator from accidentally changing the calibration offset, a special sequence of keystrokes is required to access this function.
1. Press and hold the Units/Menu Button until HL appears on the display.
2. Press and release the Units/Menu Button until
3. Press and hold
4. While holding the Units/Menu Button, press and release the Select/Set Knob.
5. When CAL appears on the temperature readout, release the Units/Menu Button. The current calibration
offset value will appear on the temperature readout. Notice that the display will alternate bet ween the offset value and the calibrated temperature.
6. Rotate the Select/Set Knob until the desired calibration offset is displayed. Press the Select/Set Knob or
simply allow the display to time out to accept the displayed value.
the Units/Menu Button.
c1
- 16 -
5.0
Ub appears on the display.
0.0
5.13 Low Ambient Temperature Alarm Setting (LA)
This menu item allows you to set the ambient temperature at which the chiller will alarm and turn off. This serves to protect the chiller from short cycling at low ambient temperatures. This value is always displayed and set in °C.
LA
5.14 Controller Operating, Alarm, and Error Messages
When certain conditions are detected, a message code flashes on the display and the local audio alarm sounds. Depending on the nature of the condition, power to various systems components, such as the compressor, heater, fan, and pump, is removed. When condition is rectified, push front panel Power button or turn circuit breaker off then on to clear the fault or error.
Message
Code
Description Action Required
Normal – Unit idle until remotely activated.
EC
External remote control
active, Chiller in standby.
on rear panel to “Local” position.)
Fluid level in reservoir below upper float switch (7
EFL
EF2
Low Water Level
Water Level / Flow Alarm
gallons low) An alarm will sound until attended to. Fill to within 2 inches of top.
Warning Alarm — Either of 2 conditions..
1. Fluid level below lower float switch (level 9 gallons low. Fill to within 2 inches of top.
2. Insufficient flow to heat exchanger. An alarm will sound and after a delay, unit will shut down. Troubleshoot recirculation pump.
2.0
(To operate locally press switch
EHA
EHL
ELA
ELL
LLO
CAn
Note: When the following faults occur, Ft will be displayed on the left display and the error code will appear on the right display
- 17 -
Front panel high ambient temperature warning.
High temperature set point warning
Front panel low ambient temperature warning.
Low temperature set point warning
Local Lockout
Cancel Local Lockout
Warning - The ambient temperature is higher than the set ambient limit.
Lower ambient temperature or raise temperature limit. Warning — The temperature set point is higher than
the high temperature limit value. If not corrected, the high temperature limit alarm will be activated when fluid temperature rises above established the HL value.
Lower temperature set point or increase high temperature limit value.
Warning – The ambient temperature is lower than the set ambient limit.
Raise ambient temperature or low temperature limit. Warning — The temperature set point is lower than
the low temperature limit value. If not corrected, the low temperature limit alarm will be activated when fluid temperature falls below the established LL value.
Increase temperature set point or decrease low temperature limit value.
Normal — Indicates that Local Lockout feature (see Section 5.18) is enabled. Appears momentarily when Select/Set Knob is pressed to view/change set point value.
Normal — Indicates the Local Lockout feature (see Section 5.18) has been disabled. Appears momentarily when Local Lockout status is changed from enabled (LLO) to disabled.
Ft appears on the left hand display
01
Factory Reserved None.
02
Low limit temperature alarm
03
High limit temperature alarm
Over-temperature protection alarm
04
(Select models only) Low liquid level alarm
05
(Select models only) High bath temperature alarm
06
(Select models only)
07
Low flow alarm
08
High pressure alarm
09
Internal software fault Fault — Power to compressor, heater, fan, and pump turned off. Reset default values; see Section 4.6.4.
10
Triac fault Fault — Power to compressor, heater, fan, and pump turned off. See Section 7.5 – Troubleshooting.
Alarm — Process fluid temperature has dropped to low temperature limit value. Compressor, heater, fan, and pump turned off. Increase heat load on Chiller or decrease low temperature limit value.
Alarm — Process fluid temperature has reached high temperature limit value. Compressor, heater, fan, and pump turned off. Decrease heat load on Chiller or increase high temperature limit value.
Alarm — Process fluid temperature is above Chiller’s factory set high temperature safety cutoff. Power to condenser, heater, and fan turned off; pump remains on. Lower process temperature.
Delayed Alarm — Activated when the liquid level in the reservoir falls below an acceptable level for 30 seconds of longer. Compressor, heater, fan, and pump turned off. Add fluid to reservoir.
Alarm — Fluid temperature has exceeded 82°C (180°F). Compressor, heater, fan, and pump turned off. Lower fluid temperature.
Alarm — Flow rate has dropped below minimum flow rate setting. Power to compressor, heater, fan, and pump turned off. Note: Disabled during first 2 minutes of operation.
Correct cause of low flow rate or decrease minimum flow rate setting. Delayed Alarm — Activated when fluid outlet pressure has exceeded high-pressure limit value for 30 seconds. Compressor,
heater, fan, and pump turned off. Decrease outlet pressure by removing blockage or increase high-pressure temperature limit value.
11
Internal probe (P1) fault
12
Water inlet probe (P2) fault Fault — Faulty water inlet temperature probe. Power to compressor, heater, fan, and pump turned off. Contact supplier.
13
Communications fault Fault — Internal electronics failure. Power to compressor, heater, fan, and pump turned off. Contact supplier.
14
ADC fault, internal probe Fault — ADC for internal probe faulty. Power to compressor, heater, fan, and pump turned off. Contact supplier.
15
ADC fault, external probe Fault — ADC for external probe faulty. Power to compressor, heater, fan, and pump turned off. Contact supplier.
Front panel high ambient
16
temperature alarm
Rear panel high ambient temperature alarm
17
(select models only)
Ambient temperature probe
18
(P3) fault
19
Pump overload (DAP1) fault Fault — Power to compressor, heater, fan, and pump turned off. See Section 7.7 – Troubleshooting. Compressor overload (DAF2)
20
fault
Fault — Faulty internal temperature probe. Power to compressor, heater, fan, and pump turned off. See Section 7.6 – Troubleshooting..
Alarm — Ambient temperature at front panel is higher than high ambient temperature limit. Compressor, heater, fan, and pump turned off. Occurs when ambient temperature exceeds the set ambient limit by 5ºC or more.
Lower temperature in area in which Chiller is located or increase high ambient temperature limit value. Temperature limit is adjustable.
Alarm — Ambient temperature at rear panel is higher than high ambient temperature limit. Compressor, heater, fan, and pump turned off. Occurs when the ambient temperature exceeds the ambient limit.
Lower temperature in area in which Chiller is located or increase high ambient temperature limit value. Temperature limit is not adjustable.
Fault — Faulty internal temperature probe. Power to compressor, heater, fan, and pump turned off. Replace ambient tracking probe or operate Chiller using internal temperature probe. Contact supplier if problem persists.
Fault — Power to compressor, heater, fan, and pump turned off. See Section 7.9 – Troubleshooting.
21
Fan overload (DAF1) fault Fault — Power to compressor, heater, fan, and pump turned off. See Section 7.8 – Troubleshooting.
- 18 -
5.15 Dual Float Switch
If fluid level should fall below the upper float switch (7 gallons low) the right hand display will alternately show “EFL” and fluid temperature, Audible alarm will intermittently sound. This will continue indefinitely until attended to.
If fluid level should fall below the lower float switch (9 gallons low) the right hand display will alternately show “EF2” and fluid temperature, Audible alarm will intermittently sound and after a delay the unit will turn off.
5.16 Loss of Power
In the event that power is lost while the Chiller is operating, the unit will automatically begin operating when power is restored.
If the unit was in the Standby mode when power was lost, it will power up in the Standby mode.
5.17 High Pressure Bypass Setting
Your chiller incorporates an automatic safety to maintain outlet pressure below a valve-regulated pressure.
5.18 Enabling/Disabling the Local Lockout
This feature is used to prevent unauthorized or accidental changes to the set point and other operatio nal values. When enabled, the set point and other values can be displayed, but not chang ed.
To enable the Local Lockout, press and hold the Select/Set Knob until “LLO“ is displayed (approximately 5 seconds). Once enabled, “LLO“ will appear briefly whenever the Select/Set Knob is pressed to display the set point.
To disable the Local Lockout, press and hold the Select/Set Knob until “CAn“ is momentarily displa yed (about 5 seconds). This will change the status from enabled to disabled.
5.19 Automatic Restart from Alarm Mode
This chiller is equipped with an automatic restart feature to avoid false alarms. If any alarm condition is detected the chiller will turn off, wait 30 seconds and then turn on.
This is to avoid nuisance trips due to temporary flow obstructions, temperature swings or electrical line noise. Three restart attempts will be made. If the alarm condition continues to exist then an alarm will sound and the chiller
will remain off until the problem is corrected.
5.20 Fuse Bits
This menu item allows you to select logic levels for these optional features.
- Remote dry contact on / off
- Remote 24 V on / off
- Reservoir Float Switch
To set fuse bits turn power off. While pressing knob and power button at the same time turn power switch on. Left display will show “Fb” and right hand display will show “h” followed by two digits, you may set by turning the knob. Press and release knob or wait and menu will time out with new setting.
LOGIC STATE h00 h01 h02 h03 h04 h05 h06 DRY CONTACT
DRY CONTACT
24 VOLTS
O VOLTS FLOAT
SWITCH FLOAT
SWITCH
TURNS UNIT OFF
TURNS UNIT ON
TURNS UNIT OFF
TURNS UNIT ON
LEVEL OK LEVEL OK LEVEL OK LEVEL
LOW
TURNS UNIT ON
TURNS UNIT OFF
DISABLED
LEVEL LOW
- 19 -
DISABLED
TURNS UNIT ON
TURNS UNIT OFF
LEVEL LOW
NOT USED
TURNS UNIT OFF
TURNS UNIT ON
TURNS UNIT OFF
TURNS UNIT ON
LEVEL LOW
LEVEL OK LEVEL OK LEVEL OK
TURNS UNIT ON
TURNS UNIT OFF
DISABLED
LEVEL LOW
DISABLED
TURNS UNIT ON
TURNS UNIT OFF
LEVEL LOW
Section 6 – Routine Maintenance
6.1 Recommended Routine Maintenance Schedule
Routine Maintenance Procedure Frequency1
Inspect and clean inline strainer Weekly for the first month of operation; every three months1 thereafter. Check reservoir coolant level Weekly Check coolant freeze protection Monthly Inspect and clean air filters Weekly for the first month of operation; monthly1 thereafter.
1. Minimum maintenance frequency. Your plant condition may require more frequent inspection and cleaning.
6.2 Routine Maintenance Procedures
6.2.1 Inline Strainers
The Chiller’s Inline Strainers should be inspected and cleaned weekly for the first month of operation. Once you are certain that all debris that may have been generated or dislodged has been filtered from the coolant, strainer inspection and cleaning can be performed less frequently.
1. Turn main Chiller power Off .
2. Using the Drain connection on the rear of the Chiller, remove a sufficient volume of coolant to bring the coolant level below the level of the Inline Strainer..
3. Remove the Chiller’s left rear side panel. One Inline Strainer is located just above the recirculation pump.
4. Using an adjustable wrench or the proper size hex head soc k et, loosen and remove the Inline Strainer drain cap.
NOTE: There will be some residual coolant within the fitting housing the strainer which will drain out when the cap is removed. Remove the strainer from the cap (or fitting) and clean off all trapped debris. Either water or high pressure air can be used to remove the accumulated material.
5. Insert the strainer into the cap and reinstall in the fitting. Be sure to adequately tighten strainer cap.
6. Repeat for Inline Strainer located at outlet on rear of unit.
7. Replace drained coolant.
8. Restore power and turn Chiller On.
9. Check for leaks.
10. Replace Chiller side panel.
6.2.2 Reservoir Coolant Level
The reservoir coolant level should be checked on a weekly basis and replenished as required. A proper fill level is approximately 2 inches (5.1cm) below the top of the reservoir. If fluid replacement is required, slowly add coolant to the reservoir until the proper fill level is achieved.
6.2.3 Coolant Freeze Pro t ectio n
For operation of unit at lower temperatures, the level of coolant freeze protection must be 14º C (25º F) below the operating temperature. Operation at minimum of 0º C requires a freeze point not more than -14ºC (6.8º F).
6.2.4 Air Filters Chillers incorporate three high-efficiency, reusable air filters. These should be inspected weekly during the first month
of operation to determine how frequently cleaning is necessary. Chillers located in dusty environments will require more frequent filter cleaning.
IMPORTANT: Do not allow the air filters to become caked with dust. This significantly reduces air flow and can compromise cooling efficiency. It can also lead to filter breakthrough, allowing dust to get into the condenser coils.
The Chiller’s air filters are removed and cleaned as follows:
1. Grasp the strap at the bottom center of the filter and gently lift up and away from the Chiller housing.
2. Using a water or high pressure air stream directed through the back of the air filter (the downstream side), rinse/blow accumulated dust from the filter. Allow the filter to dry, as required.
3. Replace the filter by positioning the top edge of filter in the upper channel of the Chiller housing and then gently lifting on the bottom strap while pushing the bottom edge of the filter toward the housing.
- 20 -
Section 7 – Troubleshooting
WARNING: Refer servicing to qualified service personnel. When power is on, dangerous voltages exist within chassis components. Use extreme care when measuring voltages on live circuits.
7.1 Unit Will Not Operate (no cooling or pumping)
Check that the power cord is plugged in to an operating electrical outlet.
Check that the Circuit Breaker/Power Switch is ON.
Check that the front panel Power Switch is ON.
7.2 No Pumping
Check the fluid level in the whole system to make sure the pump is receiving fluid.
Check if the pump motor is operating.
Check for blockage within the circulating system.
7.3 Insufficient Pumping
Check for low line voltage.
Check for too small of a hose diameter.
Check for too high of a fluid viscosity.
Check for restrictions in the connecting tubing.
7.4 No Cooling or Insufficient Cooling
Check for low or high line voltage.
Check for blocked airflow through air filters.
Check ambient air temperature. High air temperature may cause the refrigeration compressor to temporarily shut
down.
Check for excessive heat being transferred to the cooling fluid liquid as this may exceed the cooling capacity of the
refrigeration system.
7.5 Triac Failure “Ft 10”
Triac fault message appears on the display, indicating that the triac has failed or the line supply voltage has a
source of extreme interference from other equipment. Plug the unit into another power source. If it still displays triac failure, a triac or triac driver needs replacement.
7.6 Internal Probe Failure “Ft 11”
The Internal Probe failure message appears on the display, indic ating that the internal probe has failed or there is a
problem with the circuitry reading the probe signal. Contact supplier.
7.7 Pump Overload Fault “Ft 19”
Check fuses located inside front electrical box.
Check pump overload relay. There is a reset button located in the upper right corner of the overload relay and the
tripping value is adjustable.
If alarm persists, contact supplier.
7.8 Fan Overload Fault “Ft 21”
Check fuses located inside front electrical box.
Check fan overload relay. There is a reset button located in the upper right corner of the overload relay and the
tripping value is adjustable. If alarm persists, contact supplier.
- 21 -
7.9 Compressor Overload “Ft 20 Resetting the High Refrigerant Pressure Safety Cutout
An excessive ambient and/or process heat load can cause the Chiller’s high refrigerant pressure safety cutout to activate, removing power from the compressor and fan. The safety is factory-set to activate at a refrigerant pressure of 630 PSI.
To reset the high refrigerant pressure safety cutout switch, proceed as follows:
1. Correct the condition causing the excessive head load.
2. Turn power to the Chiller OFF.
3. Remove the Chiller’s right front side panel.
4. Locate the high refrigerant pressure safety cutout switch. It is located near the compressor discharge and has a blue housing with red reset button.
5. Press the reset button on the top of the switch. There should be a tactile and/or audible click as it resets. NOTE: Allow sufficient time (approximately 15 minutes) for the pressure in the refrigeration system to decrease
below 630 PSI before resetting the safety switch. If the reset action seems “soft” or the Chiller will not resume operation on power up, it’s likely that the refrigerant pressure is still above the 630 PSI cutout value.
6. Replace the side panel.
7. Turn power to the Chiller back ON and resume normal operation.
NOTE: There is also a Low Refrigerant Pressure Safety Cutout in series with the High Pressure Cutout. This cutout will reset by itself once the pressure rises above it’s trigger point. If this safety continues to cutout contact a HVAC technician to troubleshoot the refrigeration system.
Section 8 – Service and Technical Support
If you have followed the troubleshooting steps outlined in Section 7 and your Chiller still f ails to operate properly, contact the supplier from whom the unit was purchased. Have the following information available for the customer service person:
Model, Serial Number, and Voltage (from side pa nel label)
Date of purchase and purchase order numb er
Supplier’s order number or invoice number
A summary of the problem
- 22 -
A.1 Flow Diagram
FAN
CYCLING SWITCH
TB1-9,11
HOT GAS BYPASS
SOLENOID VALV E
HIGH PRESSUR E
SENSOR SWITCH
TB1-17,19
TB1-21,23
COMPRESSOR
FILTER DRIER
PRESSURE
SENSOR
SWITCH
TB1-13,15
SUCTION
SIGHT GLASS
LOW
LINE
PRESSURE
RELIEF VA LV E
(650 PSI
SETPOINT)
TXV
THERMOSTATIC
EXPANSION
VALVE
HEAT
EXCHANGER
EVAPORATOR
DUAL
WATER
LEVEL
FLOAT
SWITCH
DRAIN
TO PCB
"FLW"
|
FLOW
SWITCH
RECIRC.
200 PSI
RELIEF
VALVE
TO PCB
"T1"
TURBINE
PROCESS
PUMP
SSC
PUMP
RECIRCULATION
STRAINER
RTD
TEMP
SENSOR
PSI
SENSOR
TB1-1,3,5
PROCESS STRAINER
RETURN
FROM
PROCESS
TO
PROCESS
A.2 Wiring Diagram
TB 1
261
GRN
FLUID
BLK
3
PRESSURE
SENSOR
FAN CYCLING
PRESSURE SWITCH
REFRIGERANT LO W
PRESSURE SWITCH
REFRIGERANT HIGH
PRESSURE SWITCH
HOT G AS
BYPASS
VALVE
GRN/YEL
4
RED
5
7218
109
WHT
BLK
12
11
13 14
WHT
BLK
15
16
18
17
WHT
BLK
2019
WHT
22
BLK
23
24
TB 1
REMOTE
GRN
OUTPUT
BLK
GROUND
SUPPLY VOLTAGE
RED
BLU
BLU
BLU
WHT WHT
HOT GAS BYPASS VALVE
RTD 100
TEMP. SENSOR
T2 T1/ITS
ON / OF F 24VDC = ON OVDC = OFF
LOCAL / REMOTE
FLUID PRESSURE SE NSOR
SWITCH
FAN CYCLING P SI SWI T CH
FLOW
SWITCH
LOWER
WATER LEVEL
200-280
BEAD
BLU BLU
1234
21
12
T3
PCB XFMR 1 PIN 10
D232
12345
6879
D
A
F
1
PCB U4 PIN 4
FLOAT SWITCH
BLK BLK
121212
PCB U4 PIN 1
FAN(S) OVERLOAD RELAY (NC) YEL YEL
PUMP OVERLOA D RELAY (NC)
21
D
D
A
A
P
P
2
1
200-284
DCMPDHRN PRK DPMP DFAN
2
21
1
21
GRN
YEL
RED
UPPER
WATER LEVEL
FLOAT SWITCH
DHPSDLPS
CONTROL PCB
500-328A-A
5
POWER
2
SUPPLY
1
215-513
D
A
F
2
GB
1212
F
L
W
1 3
1 2
5 3
R
C
S
PWR
123
BLK
GB
5 4
3
16
NO
24VDC
RELAY
121321321323412341234123412
R
C
V
WHT
* M ULTI- TAP TRANSF ORME R WI RING TABL E
INP UT VOLTAGE OUTPUT VOLTAGE
H1-H2 H1-H3 H1-H4 H1-H5 X1-X2 X1-X3 X1-X4
208 500 85 100 110 220 380 440 550 91 110 120 230 400 460 575 95 115 125 240 416 480 600 99 120 130
FAN
BLK
EMI
FILTER
WHT
GRN/YEL
HEFHITFPS
FAN HTR OTP CMP PMP
1
1
2
2
RJ-45
1
1
2
2
BLU
YEL
BLK WHT
BRN
GB
525-814
PULLUP
RESISTORS
TB 2
MULTI -TAP*
TRANSFORMER
120VAC OUTPUT
GB
PHASE
BLK
WHT
MONITOR
76 8
213
PUMP 2
STA
123
RC
FILTER
A2
A1
SSC RECIRC. PUMP 1
CONTACTOR
1 2
PUMP 1
5 4
FUSE
BLOCK
NO
NC
NO
NC
OVERLOAD
RELAY
FUSE
BLOCK
3.5A
1.4A
1.4A
FUSE
BLOCK
1 AMP
WHT
BLK
RC
FILTER
A2
A1
TURBINE
PROCESS
PUMP 2
L1 L2 L3 GND
JUNCTION BOX (REAR OF UNIT)
FRONT PANEL
DISCONNECT SWITCH
L3L2L1
A
A
A
BD
DCB
BLK
FAN
WHT
FUSE
BLOCK
CONTACTOR CONTACTOR
NO
NC
NO
NC
OVERLOAD
RELAY
RC
FILTER
C
A2
A1
C
BD
FAN
GBGBGB
DISTRIBUTION
FUSE
BLOCK
NO
NC
NO
NC
OVERLOAD
RELAY
BLOCK
CRANKCASE
HEATER
GRN/YEL
GROUND
BAR
BLK
RC
FILTER
1
2 3 4 5
6 7 8 9
CONTACTOR
A2
A1
COMPRESSOR
GB
FUSE
BLOCK
NO
NC
COMPRESSOR
A.3 Parts Replacement
Item
Description
No.
1 PCB, CONTROL 040289 500-367 2 PCB, POWER SUPPLY 040290 215-513
PHASE MONITOR, 240VAC 040291 215-511 PHASE MONITOR, 380VAC 040292 215-351
3
PHASE MONITOR, 480VAC 040293 215-512
PHASE MONITOR, 600VAC 040294 215-602 4 DISCONNECT SWITCH 040268 215-629 5 TRANSFORMER,250VA,MULTI-TAP,1.1AMPS 040320 215-645 6 FUSE, PHASE MON., KLK, 1.0 AMP 040280 200-447
FUSE, JTD1ID, 1.0 AMP 040272 200-368
FUSE, JTD15ID, 15.0 AMP 040273 200-358
FUSE, JTD2.5ID, 2.5 AMP 040274 200-374
FUSE, JTD3.5ID, 3.5 AMP 040275 200-376 7
FUSE, JTD30ID, 30.0 AMP 040276 200-388
FUSE, JTD4ID, 4.0 AMP 040277 200-378
FUSE, JTD5ID, 5.0 AMP 040278 200-380
FUSE, JTD6ID, 6.0 AMP 040279 200-382
CONTACTOR, ABB, A12-30-10-84 (COMPRESSOR) 040265 200-422 8
CONTACTOR, ABB, A26-30-10-84 (COMPRESSOR) 040266 215-424 9 CONTACTOR, ABB, A9-30-10-84 (FAN-PUMP) 040267 200-421
OVERLOAD RELAY, 1.7-2.4 AMP 040286 200-414
10
OVERLOAD RELAY, 2.2-3.1 AMP 040287 200-458
OVERLOAD RELAY, 2.8-4.0 AMP 040288 200-429
11 FUSE, XFMR, KLDR, 1.4 AMP 040281 200-407 12 FUSE, XFMR, MIDGET, 3.5 AMP 040282 200-405 13 FAN, AXIAL, 115V, 32CFM, CTL. COMPARTMENT 040270 215-509
HEATER, COMPRESSOR BAND, 240V,70W 040317 215-721
14
HEATER, COMPRESSOR BAND, 480V,70W 040318 215-722
HEATER, COMPRESSOR BAND, 575V,70W
COMPRESSOR, 200-230V,50/60HZ 040312 750-833
15
COMPRESSOR, 380-460V,50/60HZ 040313 750-813
COMPRESSOR, 575V, 60HZ
16 SWITCH, HIGH PRESSURE CUTOUT, 630 PSI 040308 235-071 17 SWITCH, FAN CYCLING 300/400 PSI 040310 215-726 18 COIL, HOT GAS BYPASS 040306 750-216 19 SOLENOID VALVE, HOT GAS BYPASS 040305 750-222 20 SWITCH, LOW PRESSURE CUTOUT, 15/30 PSI 040309 215-436 21 VALVE, SAFETY RELIEF, 650PSI 040307 750-815 22 FILTER DRYER 040303 750-229 23 SIGHT GLASS 040323 750-230 24 EXPANSION VALVE, REFRIGERANT (TXV) 040304 750-814 25 DUAL FLOAT SWITCH, RSVR. LEVEL 040269 235-064 26 FLOW SWITCH, RECIRC. PUMP 040271 235-052
PUMP, RECIRCULATION, 1/2HP, SS CENTRIFUGAL 200-240/380-
460V,3PH,50/60HZ
27
PUMP, RECIRCULATION, 1/2HP, SS CENTRIFUGAL 575-600V,3PH,60HZ 040299 505-177
PUMP, PROCESS, 1HP TURBINE 200-240/380-460V,3PH,50-60HZ 040296 505-174
28
PUMP, PROCESS, 1HP TURBINE 575-600V,3PH,60HZ 040297 505-178
29 SENSOR, TEMP. PROBE, PLATINUM RTD 040300 200-450 30 PRESSURE RELIEF VALVE, 200 PSI 040295 776-090 31 SENSOR, WATER PRESSURE TRANSDUCER 040301 750-757 32 HEAT EXCHANGER, BRAZED PLATE, EVAPORATOR 040315 750-214 33 HEAT EXCHANGER, CONDENSER COIL 040316 750-262
MOTOR, FAN, 200-240/380-460V, 1140RPM 040284 215-435
34
MOTOR, FAN, 575-600V, 1140RPM 040285 215-603
35 AIR FILTER 040311 750-264 36 "Y" STRAINER, RECIRCULATION, 3/4" 040321 400-710 37 "Y" STRAINER, RECIRCULATION, 1/2" 040322 775-174
Part
PolyScience
No.
040319 215-723
040314 750-832
040298 505-175
Part No
DA504HY DA506HY DA508HY DA509HY
   
    
 
 
 
1211
7
Electrical
Box
13
ELECTRICAL
PANEL
FAN
RECIRCULATION
PUMP
PROCESS
PUMP
9 9
10
REAR OF
DOOR
COMPRESSOR
1
2
3
4
5
6
7
8
REFRIGERTION
COMPONENTS
17
16
15 14
ASSEMBLIES
25
18 19 20
21
22
23
24
PUMP
36
31
30
29
28
2726
DQD 507 Rev. 2009-09-01
Certificate o f Compliance
Certificate: 2302161
Project: Issued
PRODUCTS CLASS 8721 85 - ELECTRICAL EQUIPMENT FOR LABORATORY USE - Certified to US
CLASS 8721 05 - LABORATORY EQUIPMENT - Electrical
DuraChill™,
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 61010-1-04 - Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use, Part 1: General Requirements
CAN/CSA-C22.2 No.61010-010-04 - Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use—Part 2-010: Particular Requirements for Laboratory Equipment for the Heating of Materials.
UL Std. No. 61010-1 (2nd Edition) - Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 1: General Requirements
2302161
Polyscience
to:
Division of Preston Industries, 6600 W Touhy P.O. Box Niles, IL USA At te nt i on: S t e ve
The
products listed below are eligible to bear the CSA
Mark shown with adjacent
Canada and US or with adjacent indicator 'US'
US
only or without either indicator for Canada
P/N: DA504; DA506; DA508; DA509.
48312
60714
Standards
Ave
Rundle
Inc
indicators
Master
Date
Contract: 155859
Issued:
'C' and 'US' for
Peter Wong
Issued by: Peter Wong
2010/05/14
for
only.
The Produ cts her ewi th compli es with the req u irements , as stated bel o w, in accordance to the EC Low Volt age Directive 2006/95/EC and EC Electromagnetic Compatibility Directive 2004/108/EC, and carries the
We herewith declare:
That th e fol l owing equ ipment com plies with the essen tial requirements in resp ect to safet y and health, in accord ance to the EC Direct ives ba sed on its desi gn and type, as brought into circulation b y us . In case of a lteration of t he eq uipm ent, n ot agr e ed upon by us, this will lose its validity.
PolyScience Divi s ion of P reston Indu s tries , Inc. 6600 West Touhy Avenue P.O. Box 48312 Niles, Illinois 60714, USA
EC Declaration of Conformity
markin g accordin g ly.
Product Description: DURACHILL
Models : DA504, DA506, DA508, DA509
Applicable Directives and Harm onized Standards:
Testing Bodies:
Signat ure on Behalf of Manufa cturer or Authorized Representative:
Date of Validity:
Title of Si gnatory:
110-491 03/22/2010
Low Voltage Directive 2006/95/EC & Electromagnetic Compatibility 2004/108/EC and relev ant t ranspos itions into national law of the member states, including, but not limited to the following Harmon ized Standards:
EN 61010-1: 2001 IEC 61010-2-10 : 2005 IEC 61326-1:2005
CSA Internation al (Certification & Testing Division)
Wayne W. Walter
March 22, 2010
General Manager
Loading...