HydroTherm R-180C, R-210C, R-250C, R-300B Installation, Operation & Maintenance Manual & Replacement Parts List

MMOODDEELL RR SSEERRIIEESS
IINNSSTTAALLLLAATTIIOONN,,
OOPPEERRAATTIIOONN &&
MMAAIINNTTEENNAANNCCEE
MMAANNUUAALL &&
RREEPPLLAACCEEMMEENNTT
PPAARRTTSS LLIISSTT
RRCC22--1100004
4
4422--99115599
GGaass--FFiirreedd WWaatteerr CCaasstt IIrroonn BBooiilleerrss
118800,,000000 ttoo 330000,,000000 BBttuuhh IInnppuut
SSttaannddiinngg PPiilloott,, IInntteerrmmiitttteenntt PPiilloott &
VVeenntt DDaammppeer
SSEECCTTIIOONN 11:: BBOOIILLEERR IINNSSTTAALLLLAATTIIOON
Introduction............................................................ 2
Step 1: Locating & Setting Boiler........................... 3
Step 2: Installing/Purging Water Piping................. 5
Step 3: Venting Boiler............................................ 8
Step 4: Installing/Testing Gas Piping..................... 10
Step 5: W
SSEECCTTIIOONN 22:: SSTTAARRTT--UUPP&& OOPPEERRAATTIIOON
Safety Controls......................................................
Start-Up & Adjustments.........................................
iring Boiler.............................................. 11
r
N
N
t
&
17 17
SSEECCTTIIOONN 33:: MMAAIINNTTEENNAANNCCE
Water Treatment.................................................... 20
Freeze Protection................................................... 20
Before Each Heating Season................................
o Change Orifices........................................
How T
Troubleshooting..................................................... 21
(French V
Appendix
Replacement Parts List.......................................... 23
A
E
20 21
ent Damper Translation)..... 22
TES: 260 NOR
A
UNITED
IN
IN CANADA: 5211 CREEKBANK ROAD, MISSISSAUGA, ONT. L4W IR3 (905) 625-2991/FAX (905) 625-6610
TH ELM ST., WESTFIELD, MA 01085 (413) 564-5515/FAX (413) 568-9613
AANNSSII//AASSMMEE CCOODDEE CCOOMMPPLLIIAANNCCEE:
D
*LOCATED IN FRONT ON MODELS R-180C AND R-210C
PRESS. RELIEF VALVE
TEMP./PRESS. INDICATOR
HI-LIMIT AQUASTAT
7"
GAS VALVE
*
2" SUPPLY
BOILER MODEL
R-300B
R-250C
R-210C
R-180C 28-1/4" 58-5/8" 7"21-7/8"
DIMENSIONS
ABCD
28-1/4"
32-1/4"
28-7/8"
61-7/8" 65-5/8"7"7"
8"
32-1/4"
29-3/8" 66-1/8"
25-1/8"
B
2" RETURN
9-1/2"
9-1/2"
12"
SPILL SWITCH
ROLLOUT SWITCH
NOTE: SPILL & ROLLOUT SWITCHES USED ON R-180 THRU R-250.
VENT DAMPER
3 5/8"
C
36 3/4"
21 1/4"
A
25 1/2"
:
Installation must conform to requirements of authority having jurisdiction or, in absence of such requirements, to National Fuel
as Code ANSI Z223.1-latest edition and to National
G Electric Code NFPA-70-latest edition. Where required by authority having jurisdiction, installation must also con­form to Standard for Controls and Safety Devices for
utomatically Fired Boilers, ANSI/ASME CSD-1.
A
BBOOIILLEERR SSHHIIPPMMEENNTT::
Each boiler is shipped in a single carton. There is a vent damper packed separately with the boiler (for model R-300 vent damper is optional)
WWAARRNNIINNGG:: IInnssttaalllleerrss mmuusstt ffoollllooww llooccaall rreegguullaattiioonns wwiitthh rreessppeecctt ttoo tthhee iinnssttaallllaattiioonn ooff CCOO ddeetteeccttoorrss aannd ffoollllooww tthhee mmaannuuffaaccttuurreerr''ss ssttaatteedd mmaaiinntteennaanncce sscchheedduullee ffoorr tthhiiss bbooiilleerr!
!
s d e
For Canada, the installation must be in accordance with Standards CAN/CGA-B149 (.1 or .2) Installation Codes for Gas Burning Appliances and Equipment and with Standard C.S.A. C22.1 Canadian Electrical Code, Part 1 and Part 2, and/or local codes.
AATTTTEENNTTIIOONN:: OObbsseerrvveerr lleess rrèègglleemmeennttss rrèèggiioonnaall àà ll''ee­ggaarrdd ddeess ddéétteecctteeuurrss ddee mmoonnooxxyyddee ddee ccaarrbboonnee eet oobbsseerrvveerr eennttrreettiieenn ddee mmaannuuffaaccttuurriieerr ppoouurr cceetttte cchhaauuddiièèrree!
!
­t
e
The following terms are used throughout this manual to bring attention to the presence of potential hazards or to important information concerning the product:
DDAANNGGEERR:: IInnddiiccaatteess aann iimmmmiinneennttllyy hhaazzaarrddoouuss ssiittuuaa­ttiioonn wwhhiicchh,, iiff nnoott aavvooiiddeedd,, wwiillll rreessuulltt iinn ddeeaatthh,, sseerrii­oouuss iinnjjuurryy oorr ssuubbssttaannttiiaall pprrooppeerrttyy ddaammaaggee.
WWAARRNNIINNGG:: IInnddiiccaatteess aa iimmmmiinneennttllyy hhaazzaarrddoouuss ssiittuuaa­ttiioonn wwhhiicchh,, iiff nnoott aavvooiiddeedd,, ccoouulldd rreessuulltt iinn ddeeaatthh,, sseerrii­oouuss iinnjjuurryy oorr ssuubbssttaannttiiaall pprrooppeerrttyy ddaammaaggee.
MMOODDEELL RR BBOOIILLEERR DDIIMMEENNSSIIOONNSS
.
.
CCAAUUTTIIOONN:: IInnddiiccaatteess aa iimmmmiinneennttllyy hhaazzaarrddoouuss ssiittuuaa-
-
ttiioonn wwhhiicchh,, iiff nnoott aavvooiiddeedd,, mmaayy rreessuulltt iinn mmiinnoorr iinnjjuurry
-
oorr pprrooppeerrttyy ddaammaaggee.
NNOOTTEE:: UUsseedd ttoo nnoottiiffyy ooff ssppeecciiaall iinnssttrruuccttiioonnss oon
-
iinnssttaallllaattiioonn,, ooppeerraattiioonn oorr mmaaiinntteennaannccee wwhhiicchh aarre
-
iimmppoorrttaanntt ttoo eeqquuiippmmeenntt bbuutt nnoott rreellaatteedd ttoo ppeerrssoonnaal iinnjjuurryy hhaazzaarrddss.
.
.
-
y
n e
l
2
SSEECCTTIIOONN 11:: BBOOIILLEERR IINNSSTTAALLLLAATTIIOON
FRONT
ALCOVE
REAR
(6")
W/O CIRC.
24" WITH
CIRCULATOR
(RECOMMENDED
FOR SERVICING)
RECOMMEND MORE FOR ACCESS TO VENT DAMPER POSITION INDICATOR
VENT DAMPER
6" 6"
LEFT
6"
SIDE
VIEW
FRONT
VIEW
TOP
38"
RIGHT
6"
N
SSTTEEPP11:: LLOOCCAATTIINNGG && SSEETTTTIINNGG TTHHEE BBOOIILLEER
R
PPRROOCCEEDDUURREE AA:: CChheecckk tthhaatt pprroovviissiioonnss ffoorr ccoommbbuussttiioonn aaiirr aarree iinn aaccccoorrddaannccee wwiitthh NNaattiioonnaall FFuueell GGaass CCoodde
AANNSSII ZZ222233..11--llaatteesstt eeddiittiioonn aanndd aallll aapppplliiccaabbllee llooccaall ccooddeess.. IInn CCaannaaddaa,, ffoollllooww CCAANN//CCGGA BB114499((..11 oorr ..22)) iinnssttaallllaattiioonn ccooddeess.
.
WWAARRNNIINNGG:: AAddeeqquuaattee ffrreesshh aaiirr mmuusstt bbee pprroovviiddeedd ffoor ccoommbbuussttiioonn.. OOtthheerrwwiissee,, iimmpprrooppeerr bbooiilleerr ooppeerraattiioon aanndd iinnaaddeeqquuaattee vveennttiinngg ooff ddeeaaddllyy fflluuee ggaasseess mmaay
.
rreessuulltt.
When communicating directly with the outside, each
r
opening must have a minimum free area of one square
n
inch per 4000 Btu/hr of gas input. When ventilation air is
y
provided by openings in doors, etc. to adjoining spaces
A
having adequate infiltration, each opening must have a
IIff bbooiilleerr iiss iinnssttaalllleedd iinn aann uunnccoonnffiinneedd ssppaaccee,
,
adequate
air will be available via normal infiltration.
IIff bbooiilleerr iiss iinnssttaalllleedd iinn aa ccoonnffiinneedd ssppaacce
e
(a space with a volume of less than 50 cubic feet per 1000 Btu/hr of gas input for all fuel burning equipment) or building con­struction is unusually tight, adequate air for combustion must be provided by two openings: one located about 6”
minimum free area of one square inch per 1000 Btu/hr of gas input.
NNOOTTEE:: BBooiilleerr eemmppllooyyss aattmmoosspphheerriicc ccoommbbuussttiioonn. CCoommbbuussttiioonn aaiirr mmuusstt nnoott bbee ccoonnttaammiinnaatteedd wwiitthh hhaalloo­ggeennaatteedd hhyyddrrooccaarrbboonn vvaappoorrss,, aaeerroossooll pprrooppeellllaannttss oor
ffrreeoonn;; ootthheerrwwiissee,, hheeaatt eexxcchhaannggeerr wwiillll bbeessuubbjjeecctt tto ccoorrrroossiioonn,, rreedduucciinngg bbooiilleerrlliiffee.
.
below the ceiling, the other about 6” above the floor.
e
.
-
r
o
PPRROOCCEEDDUURREE BB:: CChheecck mmiinniimmuumm cclleeaarraanncceess tto ccoommbbuussttiibblleess aarree pprrooppeer aass sshhoowwnn.. LLooccaall rreeqquuiirree­mmeennttss mmaayy ssppeecciiffy ggrreeaatteerr cclleeaarraanncceess && mmuusst bbee aadd--hheerreedd ttoo.
BBooiilleerr sshhaallll bbee iinnssttaallll--eed ssuucchh tthhaatt tthhee ggaass iiggnniittiioon ssyysstteemm ccoommppoonneennttss aarre pprrootteecctteedd ffrroomm wwaatteer ((ddrriippppiinngg,, sspprraayyiinngg,, rraaiinn, eettcc..)) dduurriinngg aapppplliiaanncce ooppeerraattiioonn aanndd sseerrvviiccee ((cciirr­ccuullaattoorr rreeppllaacceemmeenntt,, ccoonn­ddeennssaattee ttrraapp,, ccoonnttrrool rreeppllaacceemmeenntt,, eettcc..)).
WWAARRNNIINNGG:: NNeevveerr iinnssttaallll bbooiilleerr oonn ccoommbbuussttiibbllee fflloooorr­iinngg oorr ccaarrppeettiinngg aass hheeaatt ddaammaaggee aanndd//oorr ffiirree mmaay rreessuulltt.
.
.
.
k
o
r
-
y
t
d n
e
r
,
e
-
­l
NNOOTTEE:: DDoo nnoott lloooosseenn ttiiee rrooddss oonn aabbssoorrppttiioonn uunniitt.
-
TThheeyy aaccccoommmmooddaattee tthheerrmmaall eexxppaannssiioonn.. LLoossss ooff bbooiill-
y
eerr ssttrruuccttuurraall iinntteeggrriittyy aanndd wwaatteerr lleeaakkss//ddaammaaggee mmaay
.
rreessuulltt.
CCAAUUTTIIOONN:: LLooccaattee bbooiilleerr ssoo hhoorriizzoonnttaall ccoonnnneeccttiinng fflluuee ppiippee iiss aass sshhoorrtt aass ppoossssiibbllee.. MMaaxxiimmiizzee hheeiigghhtt oof vveerrttiiccaall fflluuee ccoonnnneeccttoorr.
.
FIGURE 1.1
.
-
y
g
f
3
BAFFLE GRID
DOME
6"
4
" HOLLOW CLAY TILE (TWO COURSES) OPENINGS THRU
B
LOCKS IN TOP COURSE TO BE AT 90 ANGLE TO OPENINGS
THRU BOTTOM COURSE
0
22 GAUGE SHEETMETAL
FLOOR
6" OVERHANG OF BLOCK AND SHEETMETAL A
LL AROUND
LEFT TOP PANEL
FRONT PANEL (BOILER MOUNTED)
RIGHT SIDE PANEL
RIGHT TOP PANEL
LEFT SIDE PANEL
REAR PANEL
REMOVE KNOCK-OUT
ASSEMBLY SCREW
PPRROOCCEEDDUURREE CC:: CChheecckk ccoommppoonneenntt ppoossiittiioonniinngg..
1. Remove all packing material from boiler.
. Install boiler on non-combustible flooring only, unless
2 local codes permit use and fabrication of a recommend­ed fireproof base (see Figure 1.2A).
FIGURE 1.2A FIGURE 1.2B
3. Check that burners and controls are in the proper position.
. Check proper seating of baffle grid inside of dome
4 opening (see Figure 1.2B).
PPRROOCCEEDDUURREEDD:: IInnssttaallll jjaacckkeett.
.
1. Unpack jacket parts from carton and check that quan­tity is correct: two side panels, one rear panel, one left top panel and one right top panel (see Figure 1.3).
2. Stand left and right side panels in place and fasten to front panel with screws provided. Fasten side panels to rear panel in same manner.
3. Lock left and right halves of top panel together and fas­ten to side panels with screws provided.
FIGURE 1.3
4
SHUT-OFF VALVE
VERTICAL EXPANSION TANK ARRANGEMENT (PREFERRED)
DRAIN VALVE
SHUT-OFF VALVE
PRESS. RELIEF VALVE
AIR VENT
SHUT-OFF VALVE
PRESSURE REDUCING (FILL) VALVE
SHUT-OFF VALVES
CIRCULATOR
DRAIN VALVE
HORIZONTAL EXPANSION TANK ARRANGEMENT
DRAIN VALVE
SSTTEEPP22:: IINNSSTTAALLLLIINNGG && PPUURRGGIINNGG WWAATTEERR PPIIPPIINNG
PRESS. RELIEF VALVE
AIR VENT
RELIEF VALVE DISCHARGE PIPING
G
NNOOTTEE:: BBooiilleerr mmuusstt nnoott bbee uusseedd wwiitthhoouutt ffoorrccee cciirrccuu­llaattiioonn,, aass oovveerrhheeaattiinngg oorr ffaaiilluurree ooff ccaasstt iirroonn sseeccttiioonnss mmaayy rreessuulltt.
PPRROOCCEEDDUURREE AA:: IInnssttaallll pprreessssuurree rreelliieeff vvaallvvee aannd rreelliieeff vvaallvvee ddiisscchhaarrggee ppiippiinngg.. FFoorr MMooddeell RR--330000B ssuuppppllyy oouuttlleett iiss aatt rreeaarr aanndd rreelliieeff vvaallvvee ppiippiinngg iiss aat ffrroonntt ooff bbooiilleerr.
.
d
B
t
.
RReelliieeffVVaallvveeDDiisscchhaarrggeePPiippiinngg:: MMuusstt tteerrmmiinnaattee 66” aabboovvee fflloooorr && bbee ssaammee ssiizzee oorr llaarrggeerr tthhaann vvaallvvee oouuttlleett.
WWAARRNNIINNGG:: NNoo vvaallvvee ooff aannyy ttyyppee mmaayy bbee iinnssttaalllleed bbeettwweeeenn bbooiilleerr && rreelliieeff vvaallvvee ttoo pprreevveenntt aacccciiddeennttaal eexxpplloossiioonn ffrroomm oovveerr--pprreessssuurree..
PPRROOCCEEDDUURREE BB:: IInnssttaallll ssuuppppllyy aanndd rreettuurrnn wwaatteer ppiippiinngg.. FFoorr MMooddeellss RR--118800CC && 221100CC ssuuppppllyy oouuttlleett iis aatt ffrroonntt ooff bbooiilleerr aanndd rreelliieeff vvaallvvee ppiippiinngg iiss aatt rreeaarr oof
.
bbooiilleerr.
-
.
CCAAUUTTIIOONN:: PPiippiinngg mmuusstt bbee iinnssttaalllleedd ffrroomm rreelliieeff vvaallvve
d
ddiisscchhaarrggee ssoo tthheerree wwiillll bbee nnoo ddaannggeerr ooff ssccaallddiinngg ppeerr-
l
ssoonnnneell.
r
IIff bbooiilleerr iiss iinnssttaalllleedd aabboovvee lleevveell ooff rraaddiiaattiioonn,, aa lloow
s
wwaatteerr ccuutt--ooffff mmuusstt bbee uusseedd.
.
.
f
AALLLLEEXXTTEERRNNAALLPPIIPPIINNGG MMUUSSTT BBEE SSUUPPPPOORRTTEEDD BBY HHAANNGGEERRSS,, NNOOTT BBYYBBOOIILLEERR AACCCCEESSSSOORRIIEESS.
FIGURE 1.4
e
-
w
Y
.
FIGURE 1.5
5
S
UPPLY
R
ETURN
50%
120° F
100%
140° F
1
00%
160° F
50%
160° F
50%
160° F
SYSTEM BYPASS
SUPPLY
RETURN
50%
120° F
100%
140° F
100%
160° F
50%
160° F
50%
160° F
PUMP AWAY
BYPASS
SUPPLY
RETURN
100%
120° F
200%
140° F
200%
160° F
100%
160° F
100%
160° F
PUMPED
BYPASS
CCAAUUTTIIOONN:: TToo pprreevveenntt ddaammaaggee dduuee ttoo eexxcceessssiivvee ccoonn­ddeennssaattiioonn,, oonnee ooff tthhee ffoolllloowwiinngg ppiippiinngg ooppttiioonnss sshhoouulld bbee uusseedd.
.
-
d
SSYYSSTTEEMM BBYYPPAASSS
S
For systems using a circulator on the return as either a single zone, or multiple zones with zone valves, install a system bypass line between the supply and return on the suction side of the circulator (see Figure 1.6). Install a
etering valve in this bypass line to regulate the amount
m of flow that will be diverted to the return. A plug valve offers the best control for this application. Although other valves may be less expensive, a plug valve will be easier to set accurately.
In the absence of a flow indicator, set the metering valve using temperature as a guide. The accompanying dia­gram suggests one scenario. This addition requires only two tees, a plug valve, and a small amount of pipe and offers the simplest approach to reliably control condensa­tion. For this system and those that follow, be aware that you are using a percentage of the pump capacity to blend, but the friction loss for the entire pump flow has been reduced. In most cases, the standard pump pack­aged with the boiler has enough capacity to feed the baseboard distribution system and the bypass line.
PPUUMMPPAAWWAAYYBBYYPPAASSS
S
For systems that use a single circulator to pump away from the boiler, the bypass should be installed on the dis­charge side of the circulator (see Figure 1.7). Full tem­perature water supplies the baseboard distribution sys­tem as before. Half of the circulator’s volume moves through the bypass, blending and heating the cooler return water. Again, the cost of installing the bypass is small and setting it by temperature can be accomplished with a contact thermometer.
FIGURE 1.6
PPUUMMPPEEDD BBLLEENND
D
An additional circulator can also be used to provide a return water temperature blend. This method works well with systems with multiple zones with circulators (see Figure 1.8). The dedicated bypass circulator provides a strong blending flow without diminishing the flow avail­able to any heating zone. Any residentially sized circula­tor is adequate for this purpose.
Each of these bypass solutions also has the added ben­efit of increasing circulation in the boiler which will maxi mize tankless coil output and increase the accuracy of temperature sensing controls.
FIGURE 1.7
-
FIGURE 1.8
6
VALVE “C”
VALVE “B”
VALVE “A”
VALVE “D”
VALVE “E”
VALVE “F”
NOTE: VALVES "H" OPENED ON HEATING WITH "C" VALVES CLOSED REVERSE PROCEDURE ON COOLING.
EXP. TANK
VENT
ROOM UNIT
DRAIN
CHILLER
BOILER
HCP
UMP
RELIEF VALVE
FILL VALVE
DRAINCH
BOILER
reverse
aquastat
N.O.
T
T
t'stat
G
V
115 volts
24 volts
circulator
operating
aquastat
N.C.
REVERSE
AQUASTAT
SET AT 120° F
RREEVVEERRSSEE AACCTTIINNGG AAQQUUAASSTTAATTS
S
An alternative for existing systems experiencing conden­sation that does not require re-piping the boiler utilizes a reverse acting aquastat, one that makes on temperature
ise. This approach works best in single zone systems.
r Wired in series with the circulator, this control holds the cir­culator off until the boiler reaches an acceptable tempera­ture and then starts system circulation (see Figure 1.9).
he most commonly available reverse acting aquastat is
T a Honeywell L4006B. The aquastat should be mounted in an immersion well directly installed in the boiler. The use of heat conductive grease (Honeywell part # 972545) in the immersion well is strongly recommended for fast and accurate temperature response. Set this adjustable aquastat to make at no less than 130° F. While this method can cause the circulator to cycle more frequently, setting the aquastat’s differential to the maximum (25­30°F) will minimize short cycling.
FIGURE 1.9
PPRROOCCEEDDUURREE CC:: FFoorr ccoommbbiinnaattiioonn hheeaattiinngg aanndd ccooooll­iinngg iinnssttaallllaattiioonnss oonnllyy.
.
If a hot water boiler is installed in connection with a water chiller, the chilled water must be piped in parallel with the boiler, using appropriate valves to prevent the chilled medium from entering the boiler (see Figure 1.10). When boilers are connected to heating coils located in air han­dling units where they may be exposed to refrigerated air circulation, such boiler piping system shall be equipped with flow-control valves or other means to prevent gravi­ty circulation of the boiler water during the cooling cycle.
PPRROOCCEEDDUURREE DD:: CCoommpplleetteellyy ffiillll && ppuurrgge hheeaattiinngg ssyysstteemm.. MMaakkee ssuurree tthhaatt aallll hheeaatt­iinngg ssyysstteemm mmaannuuaall aaiirr vveennttss aarree cclloosseedd.
e
­.
1. Check flow direction arrows on hydronic components are facing in proper direction.
Attach hose to drain valve “B” and close
2. valve “A”. Open valves “C”, “D”, “E” and “F” and drain valve “B”. Fill system with water until water runs out of the hose in a steady stream (no visible air bubbles).
3. Close valves “C” and “D”. Open valve “A”. When water runs out of the hose in a steady stream (no visible air bubbles), close drain valve “B”.
-
FIGURE 1.10
4. Open valves “C” and “D”.
FFOORR WWAATTEERR TTRREEAATTMMEENNTT && FFRREEEEZZEE PPRROOTTEECCTTIIOONN RREEQQUUIIRREEMMEENNTTSS,,
SSEEEESSEECCTTIIOONN 33:: MMAAIINNTTEENNAANNCCEE IINN TTHHIISS MMAANNUUAALL
FIGURE 1.11
7
SSTTEEPP33:: VVEENNTTIINNGG TTHHEE BBOOIILLEER
FLOW DIRECTION ARROW POINTS UP
MOUNT VENT DAMPER OVER DRAFTHOOD
MAKE SURE MOTOR IS LOCATED ON LEFT SIDE
ATTACH LOWER PORTION OF VENT DAMPER TO DRAFTHOOD WITH 1/2" OR SHORTER SCREWS OR POP RIVETS
OPEN
OPEN
1
REMOVE SHIPPING CLIP
2
OBSERVE DAMPER ROTATES TO OPEN POSITION WITHOUT OBSTRUCTION
PLUG INTO MOLEX RECEPTACLE ON FRONT OF BOILER
PLUG INTO MOLEX RECEPTACLE INSIDE DAMPER MOTOR
VENT DAMPER WIRE HARNESS
I
NSTALL
SWITCH
IN OPENING
ON DRAFTHOOD
C
ONNECT
WIRE
LEADS
I
NSTALL
MOUNTING
BRACKET
ON DRAFTHOOD
R
DDAANNGGEERR:: DDrraafftt hhoooodd aanndd vveenntt oouuttlleett mmuusstt nnoott bbe aalltteerreedd,, aass pprrooppeerr ooppeerraattiioonn wwoouulldd bbee jjeeooppaarrddiizzeedd; ffllaammee rroolllloouutt,, ffiirree oorr ccaarrbboonn mmoonnooxxiiddee ppooiissoonniinng wwiillll rreessuulltt.
.
e
;
g
PPRROOCCEEDDUURREE AA:: MMoouunntt ddrraafftt hhoooodd aanndd ssppiillll sswwiittcchh oon
.
bbooiilleerr.
1. Install draft hood on boiler. If draft hood shroud has a hole near the relief opening, mount draft hood so hole faces to the front of the boiler.
2. R-C boilers are equipped with factory-mounted spill switch harness/mounting bracket as-sembly; spill switch is provided in bag on boiler front.
3. Install mounting bracket on outside surface of draft hood shroud with the screws provided (HARNESS MUST BE ON OUTSIDE OF SHROUD). Install spill switch in hole in shroud (on outside surface) with the screws pro­vided.
NNOOTTEE:: FFoorr bbooiilleerrss eeqquuiippppeedd wwiitthh iinntteerrmmiitttteenntt ppiilloot iinnssttaallll pplluugg ssuupppplliieedd iinn ddaammppeerr ppaacckkaaggee iinnttoo ddaammppeer vvaannee hhoollee.. FFoorr ssttaannddiinngg ppiilloott bbooiilleerrss ddiissccaarrdd pplluugg. AAddddiittiioonnaall vveennttiinngg aanndd cchhiimmnneeyy rreeqquuiirreemmeennttss aarre pprroovviiddeedd oonn ppaaggee 99.
.
n
4. Plug wiring leads from harness/bracket assembly onto flat terminals on spill switch.
NNOOTTEE::BBooiilleerr wwiillll nnoott ooppeerraattee uunnlleessss wwiirriinngg lleeaaddss tto ssppiillll sswwiittcchh aarree ccoonnnneecctteedd.
.
t r
.
e
FIGURE 1.8
o
PPRROOCCEEDDUURREE BB:: IInnssttaallll vveenntt ddaammppeerr.. ((FFoorr FFrreenncchh vveerrssiioonn,, sseeee AAppppeennddiixx AAaatt rreeaarr ooff mmaannuuaall..)
)
DDAANNGGEERR:: OOnnllyy tthhee bbooiilleerr mmaayy bbee sseerrvveedd bbyy tthhee vveenntt ddaammppeerr.. DDoo nnoott uussee iitt ttoo vveenntt aann aaddddiittiioonnaall aapppplliiaannccee; tthhiiss wwiillll ccaauussee ffiirree oorr ccaarrbboonn mmoonnooxxiiddee ppooiissoonniinngg.
11.. MMoouunntt ddaammppeerr oonn ttoopp ooff ddrraafftt hhoooodd.
FIGURE 1.13
33.. CChheecckk ddaammppeerr ooppeerraattiioonn.
.
.
.
22.. SSeeccuurree ddaammppeerr ttoo ddrraafftt hhoooodd.
44.. CCoonnnneecctt wwiirree hhaarrnneessss.
.
FIGURE 1.14
.
;
FIGURE 1.15
FIGURE 1.16
8
MAXIMUM
6-FT
APART
PITCH 1/4"
P
ER FOOT
S
ECURE FLUE PIPE TO VENT DAMPER
USE VENT SUPPORT(S) AS REQUIRED TO PREVENT SAGGING
INSTALL
F
LUSH
WITH
I
NSIDE
CHIMNEY
LINER
SEAL WITH
FURNACE
CEMENT
SINGLE WALL OR TYPE B FLUE PIPE R
-180 = 7" R-210 = 7" R
-250 = 7" R-300 = 8"
PPRROOCCEEDDUURREE CC:: IInnssttaallll fflluuee ppiippee bbeettwweeeenn vveenntt ddaammppeerr aannd
cchhiimmnneeyy ((66”” mmiinniimmuumm cclleeaarraannccee rreeqquuiirreed bbeettwweeeenn fflluuee ppiippee aanndd ccoommbbuussttiibblleess)).
d
.
d
ing system.
2. Visually inspect the venting system for prop­er size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining con-
1. Seal all unused openings in common vent-
ected to the common venting system are
n located and other spaces of the building. Turn on clothes dryers and any appliance not con­nected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being in-spect­ed. Follow the lighting instructions. Ad-just ther­mostat so appliance will operate continuously
.
5. Test for spillage at draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from cigarette, cigar or pipe.
FIGURE 1.17
AADDDDIITTIIOONNAALLVVEENNTTIINNGG RREEQQUUIIRREEMMEENNTTSS:
:
When connecting to gas vents or chimneys, vent installations shall be in accor­dance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1-latest edition, or applicable provisions of the local building codes.
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechanical draft sys­tems operating under positive pressure.
When two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the largest flue plus 50% of the areas of the additional flue or vent connectors.
When an existing boiler is removed from a common venting system, common venting system is likely to be too large for proper venting of appliances remaining connected to it. of removal of existing boiler
, following steps shall be followed
with each appliance remaining connected to the common vent-
ing system placed in operation, while other appliances remain­ing connected to common venting system are not in operation:
At time
6. After it has been determined that each ap-pli­ance remaining connected to common venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas-burning appliance to previous conditions of use.
7. Any improper operation of the common vent­ing system should be corrected so installation conforms with the National Fuel Gas Code, ANSI Z223.1-latest edition. When resizing any portion of the common venting system, the
common venting system should be resized to approach the minimum size as determined using the appropri­ate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1-latest edition. For Canada, the provisions of CAN/CGA B149(.1 or .2) shall apply.
AADDDDIITTIIOONNAALLCCHHIIMMNNEEYYRREEQQUUIIRREEMMEENNTTSS:
:
Chimney condi­tion is of paramount importance for a safe and efficient boiler installation.
All installations must include a chimney inspection by a qualified individual or agency. Chimney construction mate­rials must be compatible with the fuel being used.
Particular attention should be paid on all oil-to-gas conversions. Soot may have accumulated in chimney and/or degraded chim ney liner. Most utilities require complete chimney cleaning. Others may require installation of new liner, spill switches or other chimney upgrades. Check with local utility for required safety precautions.
DDAANNGGEERR:: AAcchhiimmnneeyy wwhhiicchh ddooeess nnoott mmeeeett mmooddeerrn ssaaffeettyy ssttaannddaarrddss wwiillll rreessuulltt iinn aa ffiirree oorr ddeeaaddllyy ccaarrbboon mmoonnooxxiiddee ppooiissoonniinngg ooff tthhee bbuuiillddiinngg rreessiiddeennttss.
9
-
n n
.
Loading...
+ 19 hidden pages