HydroTherm KN-20 Field Assembly Instructions

Hydrother m
®
-Series
KN
Gas-fired direct vent Cast iron boilers
Model KN-20 only
Field assembly instructions
Also read and follow:
KN Series Gas Boiler Installation & Operating Instructions and KN HeatNet Control Manual
is manual is intended only for use by a qualied heating installer/technician. Read and follow this manual, all supplements and re-
lated instructional information provided with the boiler. Install, start and service the boiler only in the sequence and methods given in thi
s manual and the documents listed above. Failure to do so can result in severe personal injury, death or substantial property damage.
Do not use the boiler during construction. Construction dust and particulate, particularly drywall dust, will cause contamination
the burner, resulting in possible severe personal injury, death or substantial property damage. e boiler can only be operated with a
of du
op
eration with contaminated air, follow the instruction manual guidelines to clean, repair or replace the boiler if necessary.
P/N 42-9551 Copyright 2011 Mestek, Inc.
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Contents and information
Read before beginning the installation. . . . . . . . 5
Boiler ratings and specifications . . . . . . . . . . . . 6
Installation site preparation . . . . . . . . . . . . . . . 7
Prepare the boiler . . . . . . . . . . . . . . . . . . . . 10
Water piping. . . . . . . . . . . . . . . . . . . . . . . . 11
Gas piping . . . . . . . . . . . . . . . . . . . . . . . . . 18
Wiring a single boiler . . . . . . . . . . . . . . . . . . 20
Control setup . . . . . . . . . . . . . . . . . . . . . . . 25
Vent piping (and air piping when used) . . . . . . 28
Condensate drain line. . . . . . . . . . . . . . . . . . 29
Fill and test the system . . . . . . . . . . . . . . . . . 30
Hazard icons
You will find the following icons throughout this manual. (English/French)
The WARNING icon indicates a hazard that can cause severe
personal injury, death or substantial property damage.
The CAUTION icon indicates a hazard that will or can cause minor personal or property damage.
The NOTICE icon calls out special instructions that are important, but are not related to hazards.
Starting the boiler . . . . . . . . . . . . . . . . . . . . 32
Annual start-up . . . . . . . . . . . . . . . . . . . . . . 41
Maintenance . . . . . . . . . . . . . . . . . . . . . . . 42
Replacement parts. . . . . . . . . . . . . . . . . . . . 46
Appendix A — suggested wiring. . . . . . . . . . . 48
Other manuals
You must read and follow this manual, the KN Series Gas Boiler
Installation and Operating Instructions, the KN HeatNet Control manual and all additional
materials supplied with the boiler. Failure to do so can result in severe personal injury, death or substantial property damage.
Boiler/control installa­tion and setup
After completing assembly of the KN boiler, follow all instructions in the Installation and Operation Instructions and Control Manual for installation, start-up and testing.
2
P/N 42-9551
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Read before proceeding
Customer service and technical support
Direct all questions to your HydroTherm distributor or contact the HydroTherm Customer Service Department at:
260 North Elm Street Westfield, MA 01085.
Always include the model and serial numbers from the rating plate of the boiler in question.
Claims for damage or missing components must be filed immediately against the transportation company by the consignee.
Codes and standards
Code compliances
All aspects of the boiler installation must conform to the requirements of the authority having jurisdiction, or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223.1/NFPA 54-latest revision. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automati­cally Fired Boilers, ANSI/ASME CSD-1.
In Canada, the installation must be in accordance with the requirements of CSA B149.1 or .2, Installation Code for Gas Burning Appliances and Equipment.
Before assembling the boiler . . .
Verify boiler rating and gas supply
• Before assembling and installing the boiler, check the ratings to en­sure that the unit has been sized properly for the job.
• Ensure that the boiler will be set up for the type of gas available at the installation site.
Verify location is suitable
• Ensure the availability of an adequate electrical supply, uncontami­nated air for combustion, and that vent (and air) piping can be cor­rectly installed.
• Ensure the boiler can be connected to system water piping and gas supply.
• e boiler must not be exposed to dripping or spraying water or to rain.
• If replacing an existing boiler, nd out what caused the boiler to fail before installing a new boiler. Correct the problems that led to failure, or the failure may happen to the new boiler.
Attention:
Use of an approved dust respirator is strongly
recommended when handling the insulating com­ponents of the boiler
Electrical shock hazard — Disconnect all electrical
power sources to the boiler before making any electrical connections.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation! Verif y proper operation aer servicing.
Failure to comply with the above could result in severe
personal injury, death or substantial property damage.
e electrical connections to this boiler must be made in
accordance with all applicable local codes and the latest revision of the National Electrical Code, ANSI /NFPA-70. Installation should also conform to CSA C22.1 Canadian Electrical Code Part I if installed in Canada. Install a sepa­rate 120 volt 15 amp circuit for the boiler. A properly rated shut-o switch should be located at the boiler. e boiler must be grounded in accordance with the authority having jurisdiction, or if none, the latest revision of the National Electrical Code, ANSI/NFPA-70.
Line voltage eld wiring of any controls or other devices
must use copper conductors with a minimum size of #14awg. Use appropriate wiring materials for units installed outdoors.
DO NOT open any gas valve, or aempt to re the boiler,
until all boilers have been set up and veried following the instructions in the KN Series Gas Boiler Installation & Operating Instructions.
Failure to comply could cause a boiler failure, leading to
possible severe personal injury, death or substantial prop­erty damage.
.
P/N 42-9551
3
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Components and special tools required
Special equipment/materials required for assembly
1. One quart 30-wt motor oil
2. Rubber and leather gloves
3. Rubber or leather mallet
4. Two 2”x4”x12” boards (used for cushioning when seating push nipples)
5. Two 18-inch pipe wrenches
6. Torque wrench (at least 30 foot-pound capacity)
7. Deep socket, 11/16” for use with torque wrench
8. Standard hand tools, wire, nuts, electrical hand tools
9. 2”x2” steel square stock x 6 inches long, for driving square-socket pipe plugs (supplied with boiler in hardware box)
Sealants, lubricants and adhesives supplied with boiler (in hardware box)
Use gloves when working with
these products as specied in these instructions and in the product instructions.
1. Silicone RTV-6500 HiTemp: (3) 10­oz caulk tubes (for sealing between sections)
2. Loc-Tite 30557 pipe dope: (1) 16-oz can (for water and gas piping connections)
3. Hercules Pro Dope: (1) 8-oz jar (for
mixing with 30-wt motor oil, used as lubricant for push nipples)
4. Res Bond 2300: (1) 11-oz caulk tube (for sealing burner assembly)
5. Fast-Tack 87: (1) 13-oz spray can (for securing flue baffles to sections)
Boiler components and shipping information
Skid 1
Cast iron sections (front, rear and intermediate)
Push nipples
3” x 8” supply nipple and return nipple
Pipe plugs
Draw rods and hardware
All-thread rods (7/8”) and cast-iron draw-up plates for assembling boiler block
Ceramic flue baffles
Hardware box (bolts, nuts, etc., indi­vidually packed/labeled by usage)
Base
Burner kit
Ceramic combustion chamber
Drain pan (with inspection cover plate pre-attached)
Upper casting
4” x 6” boards for section assembly
Skid 2
Jacket components
Jacket insulation
Blower and filter box assembly
Control box assembly
Gas train assembly
Gas train shroud
Components box (igniter, sight glass, supply and return sensors, LWCO assembly, etc.)
Flue adapter assembly
Condensate trap assembly
Skid 3
4
P/N 42-9551
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Step 1 Place 4x6 boards on base
Ignore the palee under the
boiler in the manual images — it is le in place during assembly for demonstration purposes only.
Step 2 Oil top surface of runner
boards
1. Use a brush to spread 30-wt motor oil on the runner boards. This will allow sections to move easily during draw-up.
1. Remove base from skid.
2. Place a 4x6 board (supplied) against each side as a runner shown.
3. Space runner boards with about even amounts off of each end of the base.
4. The runner boards will be used to support the boiler block during as­sembly, then removed afterward.
Step 3 Position the rear section
Use leather gloves when li-
ing or moving boiler sections. Sections are heavy and can cause severe personal injury or death if mishandled.
Li section using two
people, following the recommendations shown in Step13,page8.
Step 4 Bolt rear section to base
1. Use 3/8 x 3½” bolts, wedges, split lock washer and nut on each side as shown.
2. Point the wedge narrow edge toward the section.
1. Identify the rear section — its lower nipple port is on the right side when looking at the inside of the section, as in this photo.
2. Slide the rear section to the end of the base. Have someone support the section during the next step.
Tighten bolt rmly, but DO
NOT over-tighten — the cast iron ange could be bro­ken if too tight. Tighten only until the split lock washer has just aened.
P/N 42-9551
5
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Step 5 Prepare section for baffle
Use of an approved dust
respirator is strongly recom­mended when handling the insulating components of the boiler.
Step 6 Install baffle
Do not use baes if they
have been broken, cracked, folded or frayed. Obtain re­placements before proceed­ing with the boiler assembly.
Step 7 Apply RTV to perimeter
1. Spray cast iron heat pin section liber­ally with spray adhesive supplied with the boiler.
2. Avoid spraying on the nipple port machined surfaces.
1. Place a baffle in the heat pin area of the front section as shown.
2. The cut-off corner must go to the lower right.
3. Press into place.
4. Make sure the baffle does NOT overlap onto the perimeter surfaces of the section. This would prevent the section from drawing up correctly.
Rubber gloves are recom-
mended for this procedure.
1. Apply a bead of silicone RTV (sup­plied with boiler) on the perimeter surfaces of the section and around the INSIDE edges of the nipple ports.
2. This is necessary to form a seal be­tween the sections. The seal prevents flue gases from escaping.
3. Extend the bead all the way from the top of the section to the bottom.
4. Keep the bead of silicone close to the INSIDE edge of the nipple ports.
5. This will protect the machined nipple port surfaces from condensation that may occur in the flueways.
6
P/N 42-9551
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Step 8 Push nipple lubricant
Rubber gloves are recom-
mended for this procedure.
Step 9 Lubricate nipple ports
Step 10 Lubricate push nipples
1. In a disposable container, mix some 30-wt motor oil with some of the Hercules Pro Dope supplied with the boiler.
2. The consistency should be similar to thick paint and should flow easily.
3. You will need enough to lubricate all nipple ports and all push nipples — probably about ½ pint is enough.
1. Brush the pipe dope/oil mixture on the inner machined surfaces of the nipple ports.
2. Avoid getting lubricant on the sili­cone RTV or on the face of the nipple ports.
Step 11 Insert push nipples
Avoid scarring or damaging
the push nipple or nipple port surfaces. e push nip­ple makes a metal-to-metal seal with the nipple port. Any surface defects could cause a leak.
1. Brush the entire outside surface of each nipple port with the lubricant.
1. Insert a push nipple into each of the two nipple ports.
2. Seat each nipple firmly but squarely.
3. Make sure the nipple face is parallel to the section surface as closely as possible.
4. DO NOT attempt to assemble sec­tions if any nipple port is mis-aligned.
P/N 42-9551
7
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Step 12 Seat the push nipples
Step 13 Lifting the sections
1. Place a 2x4 board across the nipple and strike firmly with a mallet.
2. Do this with several strokes, just so the push nipple is firmly started.
3. Make sure the board is parallel to the nipple port surface to prevent rolling the push nipple.
Use leather gloves when li-
ing or moving boiler sections. Sections are heavy and can cause severe personal injury or death if mishandled.
Li section using two
people, following the recommendations shown in Step13,page8.
Step 14 Draw up sections
1. Carefully slide the first intermediate section up to the front.
2. Before pulling the intermediate section up fully, brush lubricant on the inside machined surfaces of the nipple ports as in Step 9, page 7.
3. Use a 2x4 board and mallet to start the section in place as shown in Step 17, page 9.
Step 15 Pull sections together
1. Lift section, with each person holding at the bottom of the section.
2. Handlers should lift with their legs to avoid back strain.
4. Wipe a small amount of motor oil on the ¾-inch all-thread rods supplied with the boiler to make pull-up easier.
5. Place a ¾” nut and washer plus a cast iron plate (supplied with boiler) on the ¾” rod on each side as shown.
6. Snug finger tight.
1. Use box wrenches (preferred) to pull
2. Alternate from one side to the other
3. When the sections are properly
8
the sections together.
during pull-up to avoid cocking the nipple ports.
pulled up, they will be nearly metal­to-metal.
P/N 42-9551
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Step 16 Install baffle
Do not use baes if they
have been broken, cracked, folded or frayed. Obtain re­placements before proceed­ing with the boiler assembly.
Step 17 Use 2x4 and mallet
1. Before adding additional sections, install a baffle in the flueway as in Step 5, page 6 and Step 6, page 6.
2. Place a baffle in the heat pin area of the front section as shown.
3. The cut-off corner must go to the lower right.
4. Press into place.
5. Make sure the baffle does NOT overlap onto the perimeter surfaces of the section. This would prevent the section from drawing up correctly.
1. To initially seat the push nipple into the next section, rap with a mallet and 2x4 at each nipple port.
2. Repeat, alternating from right nipple port to left to avoid cocking the push nipples.
Step 18 Install draw rods
e draw rods ARE NOT
used to pull the sections together, only to keep them rmly in position.
Step 19 Use a torque wrench
DO NOT exceed 30foot-
pounds when tightening nuts. Higher torque could cause breakage of the cast iron.
1. When the section assembly is com­pleted, slide a draw rod through each of the four draw rod holes.
2. Apply a washer and nut on each end and pull up finger tight.
1. Use a torque wrench to tighten the nuts on the draw rods.
2. Start with the upper left corner rod first.
3. Tighten the nut to 15 foot-pounds.
4. Move to the lower right rod. Tighten the nut to 15 foot-pounds.
5. Repeat with the lower left, then the upper right rod, both tightened to 15 foot pounds.
6. Repeat this sequence again, but finish the tightening to 30 foot-pounds for each nut.
P/N 42-9551
9
KN Series Gas-fired direct vent cast iron boilers Field assembly instructions
Step 20 Bolt boiler to base
Before bolting the boiler to
the base, knock the two 4x6 boards out from under the block. If necessary, loosen the two bolts that secure the back section to the base.
Step 21 Inspection port plugs
Step 22 Prepare condensate pan
1. Install a bolt, wedge, washer and nut on side of the front section as done in Step 4, page 5.
2. Tighten only until the split lock washer has just flattened.
3. Make sure the back section bolts are tightened as well.
1. Apply pipe dope (supplied with boiler) to plugs (supplied) and install in each of the inspection ports at the lower right side of each section.
Rubber gloves are recom-
mended for this procedure.
e condensate drain pan
is shown here with the inspection plate and gasket installed. is can be done before or aer the conden­sate drain pan is bolted to the boiler.
Step 23 Install condensate drain
pan
1. This procedure requires two people to do correctly.
2. Guide the condensate drain pan through the front of the base as shown.
3. When in position, lift the pan straight up and hold firmly against the bot­tom of the section assembly.
1. Use the silicone RTV supplied with the boiler to apply a bead on the condensate pan flange around the complete perimeter.
2. At each of the four corners, apply a bead on the flange where the sheet metal edges meet.
4. Install each bolt with two flat washers, one split lock washer and nut (pro­vided). Insert the bolts from the top.
5. Tighten just until the split lock washer has flattened.
10
P/N 42-9551
Loading...
+ 22 hidden pages