HydroTherm HC-65, HC-120, HC-85, HC-145, HC-165 Installation Operation & Maintenance

...
HCD2-501
42-9156 REV. 1
MODEL HC-D SERIES
OPERATION &
MAINTENANCE
MANUAL & REPLACE-
MENT PARTS MANUAL
Gas-Fired Cast Iron Water Boilers
65,000 to 165,000 Btuh Input
Intermittent Pilot & Vent Damper
SECTION 1: BOILER INSTALLATION
Introduction...............................................................2
Step 1: Locating & Setting the Boiler........................3
Step 2: Installing/Purging Water Piping.....................4
Step 3: Venting the Boiler..........................................6
Step 4: Installing/Testing Gas Piping ........................8
Step 5: Wiring the Boiler...........................................9
SECTION 2: START-UP & OPERATION
Safety Controls........................................................15
Start-Up & Adjustments...........................................15
HYDROTHERM
SECTION 3: MAINTENANCE
Water Treatment......................................................18
Freeze Protection....................................................18
Before Each Heating Season..................................18
How To Change Orifices..........................................19
Troubleshooting.......................................................19
Appendix A (French Vent Damper Translation)....... 20
Replacement Parts List......................................... 21
MEA# 90-77-E
IN UNITED STATES: 260 NORTH ELM ST., WESTFIELD, MA 01085 (413) 564-5515/FAX (413) 568-9613
IN CANADA: 5211 CREEKBANK ROAD, MISSISSAUGA, ONT. L4W 1R3 (905) 625-2991/FAX (905) 625-6610
ANSI/ASME CODE COMPLIANCE: Installation must conform to requirements of authority having jurisdiction or, in absence of such requirements, to National Fuel Gas Code ANSI Z223.1-latest edition and to National Electric Code NFPA-70-latest edition. Where required by authority having jurisdiction, installation must also con­form to Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME CSD-1-latest edition.
Part 2, and/or local codes. BOILER SHIPMENT: Each boiler is shipped in a single carton. There is a vent damper packed separately with the boiler.
WARNING: Installers must follow local regulations with respect to the installation of CO detectors and follow the manufacturer's stated maintenance schedule for this boiler!
For Canada, the installation must be in accordance with Standards CAN/CGA-B149.1 or .2 Installation Codes for Gas Burning Appliances and Equipment and with Stan­dard C.S.A. C22.1 Canadian Electrical Code, Par t 1 and
E
3 5/8"
C
SPILL SWITCH
D
A
A
BOILER
MODEL
HC-65 HC-85 HC-100 HC-120 HC-145 HC-165
HI-LIMIT AQUASTAT
A
19 1/2" 23 3/4" 23 3/4" 23 3/4" 27 1/4" 29"
DIMENSIONS
B
12 3/4" 12 3/4" 12 3/4" 12 3/4" 12 3/4" 16"
GAS VALVE
C
16 1/2" 16 1/2" 16 1/2" 30 1/2"
33- /4"
32 1/2"
1 1/2" SUPPLY HC-85, 100,120
ATTENTION: Observer les règlements règional à l'egard des détecteurs de monoxyde de carbone et observer entretien de manufacturier pour cette chaudière!
D
39 5/8" 43 7/8" 43 7/8" 57 7/8" 64 1/8" 65 1/8"
E
5" 5" 5" 6" 6" 7"
1 1/2" SUPPLY HC-65, 145, 165
PRESS./RELIEF VALVE HC-65, 145, 165
VENT DAMPER
PRESS./RELIEF VALVE HC-85, 100, 120
AIR ELIMINATOR TAPPING
EXPANSION TANK TAPPING
1 1/4"
RETURN
CIRCULATOR (PACKAGED BOILERS)
TEMP./PRESS. INDICATOR
ROLLOUT SWITCH
B
5 1/2"
21 3/4" 7 3/4"
MODEL HC-D BOILER DIMENSIONS
The following terms are used throughout this manual to bring attention to the presence of potential hazards
or to important information concerning the product:
DANGER: Indicates an imminently hazardous sit­uation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING: Indicates a imminently hazardous sit­uation which, if not avoided, could result in death, serious injury or substantial property dam­age.
CAUTION: Indicates a imminently hazardous situa­tion which, if not avoided, may result in minor injury or property damage.
NOTE: Used to notify of special instructions on installation, operation or maintenance which are important to equipment but not related to personal injury hazards.
DRAIN VALVE
2
SECTION 1: BOILER INSTALLATION
STEP 1: LOCATING & SETTING THE BOILER
PROCEDURE A: Check that provisions for combustion air are in accordance with National Fuel Gas Code
ANSI Z223.1-latest edition and all applicable local codes. In Canada, follow CAN/CGA B149.1 or .2 installation codes.
WARNING: This boiler must be supplied with com­bustion air in accordance with Section 5.3, Air for Combustion & Ventilation, of the latest revision of the National Fuel Gas Code, ANSI Z223.1 and all applicable local building codes. Failure to provide adequate combustion air for this appliance can result in severe personal injury or death!
If boiler is installed in an unconfined space, adequate air will be available via normal infiltration.
If boiler is installed in a confined space
(a space with a volume of less than 50 cubic feet per 1000 Btu/hr of gas input for all fuel burning equipment) or building construc­tion is unusually tight, adequate air for combustion must
PROCEDURE B: Check mini­mum clearances to com­bustibles are proper as shown. Local requirements may specify greater clear-
6"
VENT
DAMPER
6"
ances & must be adhered to.
Boiler shall be installed such that the gas ignition system components are protected from water (dripping, spray­ing, rain, etc.) during appli­ance operation and service (circulator replacement, con-
LEFT
6"
FRONT
VIEW
RIGHT
RECOMMEND MORE FOR ACCESS TO VENT DAMPER POSITION INDICATOR
densate trap, control replace­ment, etc.).
be provided by two openings: one located about 6" below the ceiling, the other about 6" above the floor. When communicating directly with the outside, each opening must have a minimum free area of one square inch per 4000 Btu/hr of gas input. When ventilation air is provided by openings in doors, etc. to adjoining spaces having adequate infiltration, each opening must have a minimum free area of one square inch per 1000 Btu/hr of gas input.
NOTE: Boiler employs atmospheric combustion. Combustion air must not be contaminated with halo­genated hydrocarbon vapors, aerosol propellants or freon; otherwise, heat exchanger will be subject to corrosion, reducing boiler life.
FIGURE 1.1
TOP
48"
REAR
(6")
W/O CIRC.
6"
FRONT
CLOSET
(6")
SIDE VIEW
24" WITH
CIRCULATOR (RECOMMENDED FOR SERVICING)
WARNING: Never install boiler on combustible flooring without combustible flooring pan or on carpeting as heat damage and/or fire may result.
NOTE: Do not loosen tie rods on absorption unit. They accommodate thermal expansion. Loss of boiler structural integrity and water leaks/damage may result.
CAUTION: Locate boiler so horizontal connecting flue pipe is as short as possible. Maximize height of verti­cal flue connector.
PROCEDURE C: Check component positioning.
1. Remove all packing material from boiler.
2. Check that burners and controls are in the proper position.
3. Check proper seating of baffle grid inside of dome opening (see Figure 1.2)
.
DOME
TOP VIEW
BAFFLE GRID
FIGURE 1.2
3
STEP 2: INSTALLING & PURGING WATER PIPING
NOTE: Boiler must not be used without forced circulation, as overheating or failure of cast iron sections may result.
PROCEDURE A: Install vent tapping assembly, components and relief valve discharge piping. For Models HC-65, 145 & 165, supply outlet is at rear of boiler and vent fitting assembly tapping is at front of boiler.
Relief Valve Discharge Piping: Must terminate 6" above floor & be same size or larger than valve out­let.
WARNING: No valve of any type may be installed between boiler & relief valve to prevent accidental explosion from over-pressure.
CAUTION: Piping must be installed from relief valve discharge so there will be no danger of scalding per­sonnel.
1/2" NPT TAPPING
VERTICAL EXPANSION TANK ARRANGEMENT (PREFERRED)
MAY BE PIPED TO EITHER SIDE OF BOILER
RELIEF VALVE DISCHARGE PIPING
PRESS. RELIEF VALVE
AIR VENT
VENT FITTING ASS'Y.
HORIZONTAL EXPANSION TANK ARRANGEMENT
MAY BE SCREWED INTO TAPPING
FIGURE 1.3
PROCEDURE B: Install supply and return water pip­ing. For Models HC-65, 145 & 165, supply outlet is at rear of boiler and vent fitting assembly tapping is at front of boiler.
SHUT-OFF VALVE
DRAIN VALVE
SHUT-OFF VALVE
SHUT-OFF VALVES
If boiler is installed above level of radiation, a low water cut-off must be used.
ALL EXTERNAL PIPING MUST BE SUPPORTED BY HANGERS, NOT BY BOILER OR ACCESSORIES.
SHUT-OFF VALVE
CIRCULATOR
PRESS. REDUCING (FILL) VALVE
FIGURE 1.4
4
CAUTION: To prevent damage due to excessive con­densation, one of the following piping options should be used.
SUPPLY
RETURN
SYSTEM BYPASS
For systems using a circulator on the return as either a sin­gle zone, or multiple zones with zone valves, install a sys­tem bypass line between the supply and return on the suc­tion side of the circulator (see Figure 1.5). Install a metering valve in this bypass line to regulate the amount of flow that will be diverted to the return. A plug valve offers the best control for this application. Although other valves may be less expensive , a plug v alv e will be easier to set accurately.
In the absence of a flow indicator, set the metering valve using temperature as a guide. The accompanying dia­gram suggests one scenario. This addition requires only two tees, a plug valve, and a small amount of pipe and offers the simplest approach to reliably control condensa­tion. For this system and those that follow, be aware that you are using a percentage of the pump capacity to blend, but the friction loss for the entire pump flow has been reduced. In most cases, the standard pump pack­aged with the boiler has enough capacity to feed the baseboard distribution system and the bypass line.
PUMP AWAY BYPASS
For systems that use a single circulator to pump away from the boiler, the bypass should be installed on the dis­charge side of the circulator (see Figure 1.6). Full tem­perature water supplies the baseboard distribution sys­tem as before. Half of the circulator’s volume moves through the bypass, blending and heating the cooler return water. Again, the cost of installing the bypass is small and setting it by temperature can be accomplished with a contact thermometer.
PUMPED BLEND
An additional circulator can also be used to provide a return water temperature blend. This method works well with systems with multiple zones with circulators (see Figure 1.7). The dedicated bypass circulator provides a strong blending flow without diminishing the flow avail­able to any heating zone. Any residentially sized circula­tor is adequate for this purpose.
50%
160° F
100%
160° F
50%
160° F
100%
160° F
100%
160° F
200%
160° F
50%
160° F
SYSTEM BYPASS
SUPPLY
50%
160° F
RETURN
PUMP AWAY
BYPASS
SUPPLY
100%
160° F
RETURN
50%
120° F
100%
140° F
50%
120° F
100%
140° F
100%
120° F
200%
140° F
FIGURE 1.5
FIGURE 1.6
Each of these bypass solutions also has the added ben­efit of increasing circulation in the boiler which will maxi­mize tankless coil output and increase the accuracy of temperature sensing controls.
REVERSE ACTING AQUASTATS
An alternative for existing systems experiencing condensa­tion that does not require re-piping the boiler utilizes a reverse acting aquastat, one that makes on temperature rise. This approach works best in single zone systems. Wired in series with the circulator, this control holds the cir­culator off until the boiler reaches an acceptable tempera­ture and then starts system circulation (see Figure 1.8).
PUMPED BYPASS
FIGURE 1.7
5
The most commonly available reverse acting aquastat is a Honeywell L4006B. The aquastat should be mounted in an immersion well directly installed in the boiler. The use of heat conductive grease (Honeywell part #
972545) in the immersion well is strongly recommended for fast and accurate temperature response. Set this adjustable aquastat to make at no less than 130° F. While this method can cause the circulator to cycle more frequently, setting the aquastats differential to the maxi­mum (25-30°F) will minimize short cycling.
115 volts
reverse
aquastat
N.O.
24 volts
T
t'stat
T
circulator
REVERSE
AQUASTAT
SET AT 120° F
PROCEDURE C: For combination heating and cooling installations only.
If a hot water boiler is installed in connection with a water chiller, the chilled water must be piped in parallel with the boiler, using appropriate valves to prevent the chilled medium from entering the boiler (see Figure 1.9). When boilers are connected to heating coils located in air han­dling units where they may be exposed to refrigerated air circulation, such boiler piping system shall be equipped with flow-control valves or other automatic means to pre­vent gravity circulation of the boiler water during the cool­ing cycle.
PROCEDURE D: Completely fill & purge heating system. Make sure that all heat­ing system manual air vents are closed.
DRAIN
VALVE “B”
NOTE: VALVES "H" OPENED ON HEATING WITH "C" VALVES CLOSED REVERSE PROCEDURE ON COOLING.
RELIEF VALVE
FILL VALVE
EXP. TANK
BOILER
BOILER
VALVE “A”
operating
aquastat
N.C.
VENT
PUMP
H
C
CHILLER
ROOM UNIT
H
C
DRAIN
GV
FIGURE 1.8
FIGURE 1.9
1. Check flow direction arrows on hydronic components are facing in proper direction.
2. Attach hose to drain valve "B" and close valve "A". Open valves "C", "D", "E" and "F" and drain valve "B". Fill system with water until water runs out of the hose in a steady stream (no visible air bubbles).
3. Close valves "C" and "D". Open valve "A". When water runs out of the hose in a steady stream (no visible air bubbles), close drain valve "B".
4. Open valves "C" and "D".
FOR WATER TREATMENT & FREEZE PROTECTION REQUIREMENTS,
SEE "SECTION 3: MAINTENANCE" IN THIS MANUAL
VALVE “C”
VALVE “E”
VALVE “D”
VALVE “F”
FIGURE 1.10
6
STEP 3: VENTING THE BOILER
DANGER: Draft hood and vent outlet must not be altered, as proper operation would be jeopardized;
flame rollout, fire or carbon monoxide poisoning will result.
NOTES: Additional venting and chimney requirements are provided on page 8.
For boilers equipped with intermittent pilot install plug supplied in damper package into damper vane hole. For standing pilot boilers discard plug.
PROCEDURE A: Mount draft hood and spill switch
on boiler.
1. Install draft hood on boiler. If draft hood shroud has a hole near the relief opening, mount draft hood so hole faces to the front of the boiler.
2. HC-D boilers are equipped with factory-mounted spill switch harness/mounting bracket assembly; spill switch is provided in bag on boiler front.
3. Install mounting bracket on outside surface of draft hood shroud with the screws provided (HARNESS MUST BE ON OUTSIDE OF SHROUD). Install spill switch in hole in shroud (on outside surface) with the screws provided.
INSTALL SWITCH
IN OPENING
ON DRAFTHOOD
CONNECT
WIRE
LEADS
4. Plug wiring leads from harness/bracket assembly onto flat terminals on spill switch.
NOTE: Boiler will not operate unless wiring leads to spill switch are connected.
INSTALL
MOUNTING
BRACKET
ON DRAFTHOOD
FIGURE 1.11
PROCEDURE B: Install vent damper. (For French version, see Appendix A at rear of manual.)
DANGER: Only the boiler may be served by the vent damper. Do not use it to vent an additional appliance; this will cause fire or carbon monoxide poisoning.
1. Mount damper on top of draft hood.
FLOW DIRECTION ARROW POINTS UP
MAKE SURE MOTOR IS LOCATED ON LEFT SIDE
MOUNT VENT DAMPER OVER DRAFTHOOD
FIGURE 1.12
2. Secure damper to draft hood.
ATTACH LOWER PORTION OF VENT DAMPER TO DRAFTHOOD WITH 1/2" OR SHORTER SCREWS OR POP RIVETS
PLUG INTO MOLEX RECEPTACLE INSIDE DAMPER MOTOR
3. Connect wire harness.
VENT DAMPER WIRE HARNESS
PLUG INTO MOLEX RECEPTACLE ON FRONT OF BOILER
FIGURE 1.14
FIGURE 1.13
7
PROCEDURE C: Install flue pipe between vent damper and chimney (6" minimum clearance required between flue pipe and combustibles).
ADDITIONAL VENTING REQUIREMENTS: When con-
necting to gas vents or chimneys, vent installations shall be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1-latest edition, or applicable provisions of the local building codes.
Vent connectors serving appliances vented by natural draft shall not be connected into any portion of mechani­cal draft systems operating under positive pressure.
When two or more appliances vent into a common flue, the area of the common flue should be at least equal to the area of the largest flue plus 50% of the areas of the additional flue or vent connectors.
SINGLE WALL OR TYPE B FLUE PIPE HC-65 = 5" HC-85 = 5" HC-100 = 5" HC-120 = 6" HC-145 = 6" HC-165 = 7"
USE VENT SUPPORT(S) AS REQUIRED TO PREVENT SAGGING
MAXIMUM
6-FT
APART
PITCH 1/4" PER FOOT
SECURE FLUE PIPE TO VENT DAMPER
INSTALL
FLUSH
WITH
INSIDE
CHIMNEY
LINER
SEAL WITH
FURNACE
CEMENT
FIGURE 1.15
When an existing boiler is removed from a common vent­ing system, common venting system is likely to be too large for proper venting of appliances remaining connect­ed to it. At time of removal of existing boiler, following steps shall be followed with each appliance remaining connected to the common venting system placed in oper­ation, while other appliances remaining connected to common venting system are not in operation:
1. Seal all unused openings in common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and win­dows and all doors between the space in which the appli­ances remaining connected to the common venting sys­tem are located and other spaces of the building. Tur n on clothes dryers and any appliance not connected to the common venting system. Tur n on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being in-spected. Fol­low the lighting instructions. Adjust thermostat so appli­ance will operate continuously.
6. After it has been determined that each ap-pliance remaining connected to common venting system properly vents when tested as outlined above, return doors, win­dows, exhaust fans, fireplace dampers and any other gas-burning appliance to previous conditions of use.
7. Any improper operation of the common venting system should be corrected so installation conforms with the National Fuel Gas Code, ANSI Z223.1-latest edition. When resizing any portion of the common venting sys­tem, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1-latest edition. For Canada, the provisions of CAN/CGA B149.1 or .2 shall apply.
ADDITIONAL CHIMNEY REQUIREMENTS: Chimney condition is of paramount importance for a safe and effi­cient boiler installation. All installations must include a chimney inspection by a qualified individual or agency. Chimney construction materials must be compatible with the fuel being used.
Particular attention should be paid on all oil-to-gas con­versions.Soot may have accumulated in chimney and/or degraded chimney liner. Most utilities require complete chimney cleaning. Others may require installation of new liner, spill switches or other chimney upgrades. Check with local utility for required safety precautions.
5. Test for spillage at draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from cigarette, cigar or pipe.
DANGER: A chimney which does not meet modern safety standards will result in a fire or deadly carbon monoxide poisoning of the building residents.
8
Loading...
+ 16 hidden pages