Hydrotech DLR-A User Manual

W
INSTALLATION
OPERATION
EDECO
AND
MAINTENANCE
MANUAL
DLR-A
SERIES NO'S
1 2 4
DLR A SERIES
ULTRAVIOLET
WATER
DISINFECTION UNIT
Sold by:
Manufactured by:
WEDECO Ideal Horizons, Inc.
3520 Westinghouse Blvd.
Charlotte, NC 28273 TEL: (704) 716-7600 FAX: (704) 716-7601
www.wedecouv.com
CAUTION
IT IS VERY IMPORTANT THAT THOSE RESPONSIBLE FOR THE INSTALLATION OF THIS EQUIPMENT, AS WELL AS THE OWNER/OPERATOR, READ THIS MANUAL AND CAREFULLY FOLLOW THE INSTRUCTIONS AND GUIDELINES.
Table of Contents
Important Safety Instructions...................................................................................................................... 3
Pre-Installation Instructions ..................................................................................................................... 4-6
Installing the Disinfection Unit................................................................................................................... 8
Mounting Electrical Control Box................................................................................................................ 9
Installing the UV Lamp .......................................................................................................................10-10
Pre-Start Up Sequence .............................................................................................................................. 12
Start-Up Sequence .................................................................................................................................... 13
Maintenance.........................................................................................................................................14-15
Maintenance Log ...................................................................................................................................... 16
Parts List ................................................................................................................................................... 18
Alarms....................................................................................................................................................... 19
Troubleshooting ........................................................................................................................................ 20
Technical Specifications: DLR Series ................................................................................................. 21-21
Warranty ................................................................................................................................................... 23
2
Important Safety Instructions
WARNING!
CAUTION! Use disinfection unit only for its intended purpose as described in the Owner’s Manual. The use
ELECTRIC SHOCK! To avoid possible electrical shock, take special care when using water with this
ELECTRIC SHOCK! Do not operate any disinfection unit if it has a damaged cord or plug, if it is
ELECTRIC SHOCK! Always unplug disinfection unit from outlet when not in use, before putting on or
CAUTION! Shut down system before servicing:
EYE PROTECTION MUST BE WORN! Never look at an operating UV light with the naked eye. The light
To guard against injury, basic safety precautions must be observed.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS AND SAFE THESE INSTRUCTIONS
CAUTION! Denotes a potentially dangerous situation. Failure to observe this
warning may lead to minor or serious personal injury and material damage.
CAUTION! Ultraviolet light (UV-C) is harmful to eyes and skin. Use UV lamps only inside the disinfection
chamber with the appropriate protective covering. Avoid exposure to UV-C radiation.
of attachments not recommended or sold by WEDECO may cause an unsafe condition.
CAUTION! Disinfection unit must be properly installed in accordance with the Owner’s Manual and in
compliance with all applicable local and state regulations before use. Read and observe all important notices on the disinfection unit.
CAUTION! The WEDECO DLR Series UV disinfection unit is intended for indoor use only.
equipment. Always shut off and disconnect power to the unit before:
Making repairs (We strongly recommend that a qualified individual who fully understands the Owner’s
x
Manual perform service and/or repairs.) Cleaning
x
Replacing a UV lamp
x
malfunctioning, or if it is dropped or damaged in any way.
ELECTRIC SHOCK! The power cord of disinfection unit is equipped with a 3-prong grounding plug that
mates with a standard 3-prong grounded wall outlet to minimize the possibility of electric shock. Be sure the outlet for the disinfection unit is wired and grounded properly. remove the third prong from the power cord.
taking off parts, and before cleaning. Never unplug by pulling on the power cord. Always grip plug firmly and pull straight out of the outlet.
x Turn off water supply to the UV disinfection unit. x Disconnect all power to the UV disinfection unit. x Drain water from the system.
will burn and irritate unprotected eyes and skin.
EYE PROTECTION MUST BE WORN! Never operate the UV lamp outside of the UV disinfection unit.
ELECTRIC SHOCK! Warning — Dangerous electric voltage. Failure to
observe this warning may lead to serious injury or death.
EYE PROTECTION MUST BE WORN!
IMPORTANT! Denotes a useful tip and other information.
Do Not under any circumstances cut or
3
Pre-Installation Instructions
IMPORTANT
Please read before installing your Ultraviolet System
When this unit is wired in conjunction with another electrical devise you may experience a drop in voltage. It is recommended that your Ultraviolet System NOT share a circuit with another electrical device. The maximum voltage threshold for this system is 130V. The minimum voltage threshold for this system is 105V. Please ensure that proper voltage requirements are meet before installing your Ultraviolet System.
Please read before installing your Ultraviolet System
IMPORTANT
Before you begin
Perform the following pre-installation steps:
Step Action
1 Ensure that your DLR system is correct for your flow capacity (see Flow Rate Tables
in Technical Specifications.)
2 Ensure that your water supply meets water quality standards as shown in the table
below. If any of the elements exceed the recommended maximum, we strongly suggest, at a minimum, that you install a 5-micron sediment filter as particles in the water can reduce UV light intensity and affect performance. Contact the distributor for additional information about testing and pretreatment equipment.
Suspended solids <5 mg/l Color None Iron 0.3 mg/l Manganese 0.05 mg/l pH 6.5 to 9.5 Hardness <120 ppm
3 Check the pressure of the water supply. The WEDECO UV system is designed to
Less than 125 psi Proceed to step 3 Greater than 125 psi Install a suitable pressure-reducing valve in
Element Recommended
maximum levels
(1mg/l = 1ppm)
Note: All models are rated for a minimum UV transmission of 90%. If your
transmission is lower, consult the distributor.
operate at pressures up to 125 psi.
If the pressure is… Then…
the water inlet pipe to the disinfection unit.
Actual
4
Fill in the following information and retain for future reference.
Unit Model No.________________ Serial No._____________________
Date Purchased:_______________ Date Installed:_________________
Water pressure (psi):___________ Water flow rate (gpm):__________
4
5 Select a location that meets the following guidelines.
x The unit must be installed between the cold water source and the water heater as
inlet temperature must not exceed 100
o
F. (See Figure 1 for proper installation
sequence.)
x The disinfection unit can be installed either horizontally or vertically. (See Figure
3 for water flow direction.)
x There must be enough clearance to remove the UV lamp and the quartz sleeve for
replacement and regular maintenance. Recommended clearance is length of unit plus four inches. (See Figure 4 for additional clearance requirements.)
x The unit must be within 7 feet of an 110V electrical outlet. A 7'5" cord is included
with the unit.
x The unit must be protected from freezing. Freezing damage will void the warranty. x The unit should be placed where a potential leak will not cause water damage.
WEDECO is not responsible for water damage.
5
Pre-Installation Instructions, Continued
p
Figure 1: Installation Sequence
Figure 2: Installation Planning
Figure 1 shows a typical installation sequence. Note that all items may not be necessary for water treatment.
WEDECO
HOT WATER
HEATER
U V D ISIN F E CT IO N
UNIT
OPTIONAL EQUIPMENT
SUCH AS SOFTENER,
OR ODOR FILTER
You must determine how to run pipes in and out of your disinfection unit. Figure 2 shows one method of installation (with chamber mounted control box). Use this diagram to determine the materials needed for your installation.
WATER
SEDIMENT
FILTER
NOTE: PRETREA TMENT EQUIPM ENT MUST BE INSTALLED PRIOR TO
U V D ISIN F E CT IO N U N IT
SOURCE
IMPORTANT!
Check local plumbing codes for sizes and types of pipes to be used.
ELECTRIC SHOCK!
Check for hidden electrical wiring before drilling holes.
The disinfection chamber must be properly grounded to a suitable electrical ground. Check local electrical codes for
roper location. Attach ground wire (not included) to stud and nut located on lower area of disinfection chamber.
ELECTRICAL
OUTLET
SHUTOFF VALVES SHOULD BE
INSTALLED BEFORE AND AFTER
THE DISINFECTION CHAMBER
UV DISINFECTION CHAMBER
ELECTRICAL
**
CONTROL BOX
DRAIN
SHUTOFF
VALVE
MINI MUM CLEARA NCE
IS LENGTH OF UNIT
PLUS 4"
FLOW
DIRECTION
SHUTOFF
*
VALVE
OUTLET
SOLENOID POWER CORD
INLET
SHUTOFF VALVE MAY BE REQUIRED
*
TO MEET LOCAL PLUMBING CODES
CAN BE MOUNTED ON THE UNIT OR SEPARATEL Y
**
ON THE WALL. CHECK YOUR LOCAL ELECTRI CAL
OPTIONAL SOL ENOID VALVE
CODES.
FLOW RESTRICTOR
6
Pre-Installation Instructions, Continued
p
Figure 3: Unit Positioning
Figure 3 shows proper water flow for horizontal or vertical installation. Make certain that your unit and the inlet and outlet pipes are in the right position for either horizontal or vertical installation.
Correct Installation
IMPORTANT!
For vertical installation, the inlet is at the bottom and the outlet is near the top of the disinfection chamber. For horizontal installation pay careful attention to the diagram for flow direction.
Figure 4: Clearance Requirements
OUTLET
FLOW
DIRECTION
INLET
INLET INLET
DIRECTION
FLOW
OUTLET OUTLET
DIRECTION
DIRECTION
OUTLET
FLOW
INLET
FLOW
OUTLET
FLOW
DIRECTION DIRECTION
DIRECTION
FLOW
OUTLET
INLET
INLET
INLET
INLET
OUTLET
FLOW
DIRECTION
FLOW
OUTLET
Incorrect Installation
Figure 4 provides the clearance requirements needed for proper installation of the disinfection chamber.
ELECTRICAL
CONTROL BOX
ELECTRICAL
OUTLET
POWER CORD
(7' 5" LO N G )
The disinfection chamber must be properly grounded to a suitable electrical ground. Check local electrical codes for
roper location. Attach ground wire (not included) to stud and nut located on lower area of disinfection chamber.
LAMP CORD
(42" LONG )
SENSOR CORD
(42" L ON G)
MINIMUM CLEARANCE
IS L ENG TH O F U N IT
PLUS 4"
FLOW
DIRECTION
UNIT
DLR 1 DLR 2 DLR 4 DLR 7 44.6"
FLOW RESTRICTOR
WEDECO UV D ISINF EC TION CHAMBER
OUTLET
SENSOR (DL R-M ONL Y)
INL ET
MIN. CLEARANCE
22.5"
30.4"
30.4"
MINIMUM
20.00"
LOCA TION
OPTIONAL SOLENOID VALVE
SOLENOID POW ER CORD
(8' LO NG )
INS TAL L F LOW RE S TR ICTO R W ITH AR RO W
*
IN DIRECTION OF WATER FLOW.
FLOW
*
RESTRICTOR
7