System Tested and Certified by NSF
International against NSF/ANSI Standard
55 for Disinfection Performance, Class A.
Manufactured by:
WEDECO UV Technologies, Inc.
14125 South Bridge Circle
South Point Business Park
Charlotte, NC 28273
Main:704-716-7600
Fax: 704-409-9838
www.wedeco.us
CAUTION
IT IS VERY IMPORTANT THAT THOSE RESPONSIBLE FOR
THE INSTALLATION OF THIS EQUIPMENT, AS WELL AS THE
OWNER/OPERATOR, READ THIS MANUAL AND CAREFULLY
FOLLOW THE INSTRUCTIONS AND GUIDELINES.
INSTALLATION OF THIS SYSTEM MUST COMPLY WITH ALL
APPLICABLE STATE AND LOCAL REGULATIONS.
Table of Contents
Important Safety Instructions...................................................................................................................... 3
Installing the Disinfection Unit................................................................................................................... 7
Mounting Electrical Control Box................................................................................................................ 8
Installing the UV Lamp .........................................................................................................................9-10
Pre-Start Up Sequence .............................................................................................................................. 11
Parts List ................................................................................................................................................... 18
CAUTION! Use disinfection unit only for its intended purpose as described in the Owner’s Manual. The use
ELECTRIC SHOCK! To avoid possible electrical shock, take special care when using water with this
ELECTRIC SHOCK! Do not operate any disinfection unit if it has a damaged cord or plug, if it is
ELECTRIC SHOCK! Always unplug disinfection unit from outlet when not in use, before putting on or
CAUTION! Shut down system before servicing:
EYE PROTECTION MUST BE WORN!Never look at an operating UV light with the naked eye. The light
To guard against injury, basic safety precautions must be observed.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS AND SAFE THESE
INSTRUCTIONS
CAUTION! Denotes a potentially dangerous situation. Failure to observe this
warning may lead to minor or serious personal injury and material damage.
CAUTION! Ultraviolet light (UV-C) is harmful to eyes and skin. Use UV lamps only inside the disinfection
chamber with the appropriate protective covering. Avoid exposure to UV-C radiation.
of attachments not recommended or sold by WEDECO may cause an unsafe condition.
CAUTION! Disinfection unit must be properly installed in accordance with the Owner’s Manual and in
compliance with all applicable local and state regulations before use. Read and observe all important notices
on the disinfection unit.
CAUTION! The UV disinfection unit is intended for indoor use only.
equipment. Always shut off and disconnect power to the unit before:
•Making repairs (We strongly recommend that a qualified individual who fully understands the Owner’s
Manual perform service and/or repairs.)
• Cleaning
• Replacing a UV lamp
malfunctioning, or if it is dropped or damaged in any way.
ELECTRIC SHOCK! The power cord of disinfection unit is equipped with a 3-prong grounding plug that
mates with a standard 3-prong grounded wall outlet to minimize the possibility of electric shock. Be sure the
outlet for the disinfection unit is wired and grounded properly.
remove the third prong from the power cord.
taking off parts, and before cleaning. Never unplug by pulling on the power cord. Always grip plug firmly
and pull straight out of the outlet.
• Turn off water supply to the UV disinfection unit.
• Disconnect all power to the UV disinfection unit.
• Drain water from the system.
will burn and irritate unprotected eyes and skin.
EYE PROTECTION MUST BE WORN! Never operate the UV lamp outside of the UV disinfection unit.
ELECTRIC SHOCK! Warning — Dangerous electric voltage. Failure to
observe this warning may lead to serious injury or death.
EYE PROTECTION MUST BE WORN!
IMPORTANT! Denotes a useful tip and other information.
Do Not under any circumstances, cut or
O & M Manual DLR-M, 4-7
08/05 – Rev. 6
3
Pre-Installation Instructions
Before you
begin
Perform the following pre-installation steps:
Step Action
1 Ensure that your DLR-M system is correct for your flow capacity (see Flow Rate
Tables in Technical Specifications.)
2 Ensure that your water supply meets water quality standards as shown in the table
below. If any of the elements exceed the recommended maximum, we strongly
suggest, at a minimum, that you install a 5-micron sediment filter as particles in the
water can reduce UV light intensity and affect performance. Contact the distributor for
additional information about testing and pretreatment equipment.
Suspended solids <5 mg/l
Color None
Iron 0.3 mg/l
Manganese 0.05 mg/l pH 6.5 to 9.5
Hardness <120 ppm
3 Check the pressure of the water supply. The WEDECO UV system is designed to
Less than 148 psi Proceed to step 4 Greater than 148 psi Install a suitable pressure-reducing valve in
Element Recommended
Note: All models are rated for a minimum UV transmittance of 70%. If your
transmittance is lower, consult the distributor.
operate at pressures up to 148 psi.
If the pressure is… Then…
4
5 Select a location that meets the following guidelines.
Fill in the following information and retain for future reference.
Series________________ Model_____________________
Date Purchased:_______________ Date Installed:_________________
Water pressure (psi):___________ Water flow rate (gpm):__________
• The unit must be installed between the cold water source and the water heater as
inlet temperature must not exceed 100
sequence.)
• The disinfection unit can be installed either horizontally or vertically. (See Figure
3 for water flow direction.)
• There must be enough clearance to remove the UV lamp and the quartz sleeve for
replacement and regular maintenance. Recommended clearance is length of unit
plus four inches. (See Figure 4 for additional clearance requirements.)
• The unit must be within 7 feet of a properly grounded, dedicated 110V electrical
outlet. A 7'5" cord is included with the unit.
• The unit must be protected from freezing. Freezing damage will void the warranty.
• The unit should be placed where a potential leak will not cause water damage.
WEDECO is not responsible for water damage.
Actual
maximum levels
(1mg/l = 1ppm)
the water inlet pipe to the disinfection unit.
o
F. (See Figure 1 for proper installation
O & M Manual DLR-M, 4-7
08/05 – Rev. 6
4
Pre-Installation Instructions, Continued
Figure 1:
Installation
Sequence
HOT W ATER
Figure 2:
Installation
Planning
HEATER
Figure 1 shows a typical installation sequence. Note that all items may not be
necessary for water treatment.
OPTIONAL EQUIPMENT
UV DISINFECTION
UNIT
OPTIONAL EQUIPMENT
SUCH ASSOFTENER,
SUCH AS SOFTENER, OR
OR ODORFILTER
OTHER FILTER
You must determine how to run pipes in and out of your disinfection unit.
Figure 2 shows one method of installation (with chamber mounted control
box). Use this diagram to determine the materials needed for your installation.
WATER
SEDIM ENT
FILTER
NOTE: PRETREATMENT EQUIPM ENT
MUST BE INSTALLED PRIOR TO
UV DISINFECTION UNIT
SOURCE
! IMPORTANT!
Check local plumbing codes
for sizes and types of pipes
to be used.
ELECTRIC SHOCK!
Check for hidden electrical
wiring before drilling holes.
The disinfection chamber must
be properly grounded prior to
powering up the system. Refer
to the section “Installing the
Disinfection Unit” on page 7 of
this manual for details.
O & M Manual DLR-M, 4-7
08/05 – Rev. 6
Installation of this system must comply
with all applicable state and local
regulations.
5
Pre-Installation Instructions, Continued
Figure 3: Unit
Positioning
Figure 3 shows proper water flow for horizontal or vertical installation. Make
certain that your unit and the inlet and outlet pipes are in the right position for
either horizontal or vertical installation.
Correct Installation
IMPORTANT!
For vertical
installation, the
inlet is at the
bottom and the
outlet is near the
top of the
disinfection
chamber. For
horizontal
installation pay
careful attention to
the diagram for
flow direction.
Figure 4:
Clearance
Requirements
OUTLET
FLOW
DIRECTION
INLET
INLETINLET
DIRECTION
FLOW
OUTLETOUTLET
DIRECTION
DIRECTION
OUTLET
FLOW
INLET
FLOW
OUTLET
FLOW
DIRECTIONDIRECTION
DIRECTION
FLOW
OUTLET
INLET
INLET
INLET
INLET
OUTLET
FLOW
DIRECTION
FLOW
OUTLET
Incorrect Installation
Figure 4 provides the clearance requirements needed for proper installation of
the disinfection chamber.
Model Min. Clearance
M-1 22.5
M-2 30.4
M-4 30.4
M-7 44.5
The disinfection chamber must
be properly grounded prior to
powering up the system. Refer
to the section “Installing the
Disinfection Unit” on page 7 of
this manual for details.
O & M Manual DLR-M, 4-7
08/05 – Rev. 6
6
Installing the Disinfection Unit
Attaching unit
to wall
Follow these steps to attach WEDECO UV disinfection chamber to the wall.
Step Action Diagram
1 Install the two wall mount brackets on the
wall using the proper screws for your wall
type (screws not included).
2 Place disinfection chamber in the brackets
and secure with the wall mount bracket
straps. Use the wall mount bracket strap
screws provided to tighten the wall mount
bracket straps to the wall mount brackets.
3 The disinfection chamber must be properly
grounded prior to powering up the system.
Attach the ground wire to the stud and nut
located on the lower area of the
disinfection chamber and connect it to the
earth strap that is located at the bottom left
of the electrical box. (Grounding wire
included.)
O & M Manual DLR-M, 4-7
08/05 – Rev. 6
Installation of this system must comply
with all applicable state and local
regulations.
7
Loading...
+ 16 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.