Hydrotech DLR-4M User Manual

INSTALLATION
OPERATION &
MAINTENANCE
MANUAL
WEDECO
SERIES
DLR
M
MODEL
4-M 7-M
ULTRAVIOLET
WATER
DISINFECTION UNIT
DLR SERIES
System Tested and Certified by NSF International against NSF/ANSI Standard 55 for Disinfection Performance, Class A.
Manufactured by:
WEDECO UV Technologies, Inc.
14125 South Bridge Circle
South Point Business Park
Charlotte, NC 28273
Main:704-716-7600
Fax: 704-409-9838
www.wedeco.us
CAUTION
IT IS VERY IMPORTANT THAT THOSE RESPONSIBLE FOR THE INSTALLATION OF THIS EQUIPMENT, AS WELL AS THE OWNER/OPERATOR, READ THIS MANUAL AND CAREFULLY FOLLOW THE INSTRUCTIONS AND GUIDELINES.
INSTALLATION OF THIS SYSTEM MUST COMPLY WITH ALL APPLICABLE STATE AND LOCAL REGULATIONS.
Table of Contents
Important Safety Instructions...................................................................................................................... 3
Pre-Installation Instructions ..................................................................................................................... 4-6
Installing the Disinfection Unit................................................................................................................... 7
Mounting Electrical Control Box................................................................................................................ 8
Installing the UV Lamp .........................................................................................................................9-10
Pre-Start Up Sequence .............................................................................................................................. 11
Start-Up Sequence .................................................................................................................................... 12
Maintenance.........................................................................................................................................13-16
Maintenance Log ...................................................................................................................................... 17
Parts List ................................................................................................................................................... 18
Alarms.................................................................................................................................................. 19-20
Troubleshooting ........................................................................................................................................ 21
Technical Specifications: DLR Series ................................................................................................. 22-23
Warranty ................................................................................................................................................... 24
O & M Manual DLR-M, 4-7 08/05 – Rev. 6
2
Important Safety Instructions
WARNING!
CAUTION! Use disinfection unit only for its intended purpose as described in the Owner’s Manual. The use
ELECTRIC SHOCK! To avoid possible electrical shock, take special care when using water with this
ELECTRIC SHOCK! Do not operate any disinfection unit if it has a damaged cord or plug, if it is
ELECTRIC SHOCK! Always unplug disinfection unit from outlet when not in use, before putting on or
CAUTION! Shut down system before servicing:
EYE PROTECTION MUST BE WORN! Never look at an operating UV light with the naked eye. The light
To guard against injury, basic safety precautions must be observed.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS AND SAFE THESE INSTRUCTIONS
CAUTION! Denotes a potentially dangerous situation. Failure to observe this
warning may lead to minor or serious personal injury and material damage.
CAUTION! Ultraviolet light (UV-C) is harmful to eyes and skin. Use UV lamps only inside the disinfection
chamber with the appropriate protective covering. Avoid exposure to UV-C radiation.
of attachments not recommended or sold by WEDECO may cause an unsafe condition.
CAUTION! Disinfection unit must be properly installed in accordance with the Owner’s Manual and in
compliance with all applicable local and state regulations before use. Read and observe all important notices on the disinfection unit.
CAUTION! The UV disinfection unit is intended for indoor use only.
equipment. Always shut off and disconnect power to the unit before:
Making repairs (We strongly recommend that a qualified individual who fully understands the Owner’s
Manual perform service and/or repairs.)
Cleaning
Replacing a UV lamp
malfunctioning, or if it is dropped or damaged in any way.
ELECTRIC SHOCK! The power cord of disinfection unit is equipped with a 3-prong grounding plug that
mates with a standard 3-prong grounded wall outlet to minimize the possibility of electric shock. Be sure the outlet for the disinfection unit is wired and grounded properly. remove the third prong from the power cord.
taking off parts, and before cleaning. Never unplug by pulling on the power cord. Always grip plug firmly and pull straight out of the outlet.
Turn off water supply to the UV disinfection unit.
Disconnect all power to the UV disinfection unit.
Drain water from the system.
will burn and irritate unprotected eyes and skin.
EYE PROTECTION MUST BE WORN! Never operate the UV lamp outside of the UV disinfection unit.
ELECTRIC SHOCK! Warning — Dangerous electric voltage. Failure to
observe this warning may lead to serious injury or death.
EYE PROTECTION MUST BE WORN!
IMPORTANT! Denotes a useful tip and other information.
Do Not under any circumstances, cut or
O & M Manual DLR-M, 4-7 08/05 – Rev. 6
3
Pre-Installation Instructions
Before you begin
Perform the following pre-installation steps:
Step Action
1 Ensure that your DLR-M system is correct for your flow capacity (see Flow Rate
Tables in Technical Specifications.)
2 Ensure that your water supply meets water quality standards as shown in the table
below. If any of the elements exceed the recommended maximum, we strongly suggest, at a minimum, that you install a 5-micron sediment filter as particles in the water can reduce UV light intensity and affect performance. Contact the distributor for additional information about testing and pretreatment equipment.
Suspended solids <5 mg/l Color None Iron 0.3 mg/l Manganese 0.05 mg/l pH 6.5 to 9.5 Hardness <120 ppm
3 Check the pressure of the water supply. The WEDECO UV system is designed to
Less than 148 psi Proceed to step 4 Greater than 148 psi Install a suitable pressure-reducing valve in
Element Recommended
Note: All models are rated for a minimum UV transmittance of 70%. If your
transmittance is lower, consult the distributor.
operate at pressures up to 148 psi.
If the pressure is… Then…
4
5 Select a location that meets the following guidelines.
Fill in the following information and retain for future reference.
Series________________ Model_____________________
Date Purchased:_______________ Date Installed:_________________
Water pressure (psi):___________ Water flow rate (gpm):__________
The unit must be installed between the cold water source and the water heater as
inlet temperature must not exceed 100 sequence.)
The disinfection unit can be installed either horizontally or vertically. (See Figure
3 for water flow direction.)
There must be enough clearance to remove the UV lamp and the quartz sleeve for
replacement and regular maintenance. Recommended clearance is length of unit plus four inches. (See Figure 4 for additional clearance requirements.)
The unit must be within 7 feet of a properly grounded, dedicated 110V electrical
outlet. A 7'5" cord is included with the unit.
The unit must be protected from freezing. Freezing damage will void the warranty.
The unit should be placed where a potential leak will not cause water damage.
WEDECO is not responsible for water damage.
Actual
maximum levels
(1mg/l = 1ppm)
the water inlet pipe to the disinfection unit.
o
F. (See Figure 1 for proper installation
O & M Manual DLR-M, 4-7 08/05 – Rev. 6
4
Pre-Installation Instructions, Continued
Figure 1: Installation Sequence
HOT W ATER
Figure 2: Installation Planning
HEATER
Figure 1 shows a typical installation sequence. Note that all items may not be necessary for water treatment.
OPTION AL EQUIPM ENT
UV DISINFECTION
UNIT
OPTIONAL EQUIPMENT
SUCH AS SOFTENER,
SUCH AS SOFTENER, OR
OR ODOR FILTER
OTHER FILTER
You must determine how to run pipes in and out of your disinfection unit. Figure 2 shows one method of installation (with chamber mounted control box). Use this diagram to determine the materials needed for your installation.
WATER
SEDIM ENT
FILTER
NOTE: PRETREATMENT EQUIPM ENT MUST BE INSTALLED PRIOR TO
UV DISINFECTION UNIT
SOURCE
! IMPORTANT!
Check local plumbing codes for sizes and types of pipes to be used.
ELECTRIC SHOCK!
Check for hidden electrical wiring before drilling holes.
The disinfection chamber must be properly grounded prior to powering up the system. Refer to the section “Installing the Disinfection Unit” on page 7 of this manual for details.
O & M Manual DLR-M, 4-7 08/05 – Rev. 6
Installation of this system must comply with all applicable state and local regulations.
5
Pre-Installation Instructions, Continued
Figure 3: Unit Positioning
Figure 3 shows proper water flow for horizontal or vertical installation. Make certain that your unit and the inlet and outlet pipes are in the right position for either horizontal or vertical installation.
Correct Installation
IMPORTANT!
For vertical installation, the inlet is at the bottom and the outlet is near the top of the disinfection chamber. For horizontal installation pay careful attention to the diagram for flow direction.
Figure 4: Clearance Requirements
OUTLET
FLOW
DIRECTION
INLET
INLET INLET
DIRECTION
FLOW
OUTLET OUTLET
DIRECTION
DIRECTION
OUTLET
FLOW
INLET
FLOW
OUTLET
FLOW
DIRECTION DIRECTION
DIRECTION
FLOW
OUTLET
INLET
INLET
INLET
INLET
OUTLET
FLOW
DIRECTION
FLOW
OUTLET
Incorrect Installation
Figure 4 provides the clearance requirements needed for proper installation of the disinfection chamber.
Model Min. Clearance M-1 22.5 M-2 30.4 M-4 30.4 M-7 44.5
The disinfection chamber must be properly grounded prior to powering up the system. Refer to the section “Installing the Disinfection Unit” on page 7 of this manual for details.
O & M Manual DLR-M, 4-7 08/05 – Rev. 6
6
Installing the Disinfection Unit
Attaching unit to wall
Follow these steps to attach WEDECO UV disinfection chamber to the wall.
Step Action Diagram
1 Install the two wall mount brackets on the
wall using the proper screws for your wall type (screws not included).
2 Place disinfection chamber in the brackets
and secure with the wall mount bracket straps. Use the wall mount bracket strap screws provided to tighten the wall mount bracket straps to the wall mount brackets.
3 The disinfection chamber must be properly
grounded prior to powering up the system. Attach the ground wire to the stud and nut located on the lower area of the disinfection chamber and connect it to the earth strap that is located at the bottom left of the electrical box. (Grounding wire included.)
O & M Manual DLR-M, 4-7 08/05 – Rev. 6
Installation of this system must comply with all applicable state and local regulations.
7
Loading...
+ 16 hidden pages