Hydronix HD0333 User Manual

Page 1
Ethernet Adapter User Guide
Page 2
2
Ethernet Adapter User Guide HD0333 Issue 2.0.0
COPYRIGHT Neither the whole or any part of the information containe d in nor the product described in this documentation may b e
adapted or reproduced in any material form except with the prior written approval of Hydronix Limited, hereinafter referred to as Hydronix.
© 2008
Hydronix Limited 7 Riverside Business Centre Walnut Tree Close Guildford Surrey GU1 4UG United Kingdom
All rights reserved
CUSTOMER RESPONSIBILITY The customer in applying the product described in this documentation accepts that the product is a programmable
electronic system which is inherently complex and which may not be completely free of errors. In doing so the customer therefore undertakes responsibility to ensure that the product is properly installed commissioned operated and maintained by competent and suitably trained persons and in accordanc e with any instructions or safety precautions made available or good engineering practice and to thoroughly verify the use of the prod uct in the particular application.
ERRORS IN DOCUMENTATION The product described in this documentation is subject to continuous development and improvement. All information of a
technical nature and particulars of the product and its use i ncluding the information and particulars contained in this documentation are given by Hydronix in good faith.
Hydronix welcomes comments and suggestions relating to the product and this documentation
ACKNOWLEDGEMENTS Hydronix, Hydro-Probe, Hydro-Mix, Hydro-View and Hydro-Control are Registered Trade Marks of H ydro nix Limited
Page 3
3
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Revision history
Revision No. Date Description of change
1.0.0 December 2007 First Draft
2.0.0 January 2008 First edition released
Page 4
4
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Table of Contents
Chapter 1 Introduction ..........................................................................................................................7
Kit Contents.......................................................................................................................................8
Chapter 2 Connecting with Sensors .....................................................................................................9
Installation.............................................................................................................................................9
Ethernet Adapter Only (EA01)...........................................................................................................9
Power over Ethernet (EPK01).........................................................................................................10
Connections........................................................................................................................................11
Wiring Connections.........................................................................................................................11
RS-485 Wiring Recommendations..................................................................................................12
Indicator Lights ...................................................................................................................................13
Chapter 3 Connecting with Hydro-Control V.......................................................................................15
Introduction.........................................................................................................................................15
Installation...........................................................................................................................................15
Ethernet Adapter Only.....................................................................................................................15
Power over Ethernet (EPK01).........................................................................................................16
Connecting with Hydro-Control V........................................................................................................17
Programming......................................................................................................................................17
Chapter 4 Configuring the Ethernet Adapter.......................................................................................19
Ethernet Adapter defaults...................................................................................................................19
Finding an Ethernet Adapter automatically.........................................................................................19
Adding an Ethernet Adapter manually ................................................................................................20
Changing the Ethernet Adapter IP Address........................................................................................21
Remote (Internet) Connection.............................................................................................................21
Chapter 5 Technical Specifications ....................................................................................................23
EA01 Ethernet Adapter.......................................................................................................................23
EPA01 Ethernet Power Adapter .........................................................................................................23
EPI01 Ethernet Power Injector............................................................................................................23
Terminal Identification.........................................................................................................................24
Chapter 6 Fault Finding ......................................................................................................................27
Ethernet Adapter EA01.......................................................................................................................27
Ethernet Power Adapter EPA01 .........................................................................................................27
Ethernet Power Injector EPI01............................................................................................................28
Page 5
5
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Table of Figures
Figure 1: Ethernet Adapter Kit Connections.............................................................................................7
Figure 2: Connections for Ethernet Adapter only......................................................................................9
Figure 3: Connections for Ethernet Adapter and Power Adapter............................................................10
Figure 4: Maximum number of sensor connections................................................................................11
Figure 5: Connecting the Ethernet Adapter to Hydro-Control V..............................................................15
Figure 6: EA01 Terminal Identification ...................................................................................................24
Figure 7: EPA01 Terminal Identification.................................................................................................25
Page 6
6
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Page 7
7
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Chapter 1 Introduction
The Hydronix Ethernet Adapter provides a simple method of network enabl ing Hydronix products. The Adapter is a small DIN-rail mounted unit that converts packets received over an Ethernet (TCP/IP) network to RS485 or RS232. This enables a host PC elsewhere on the network to communicate with sensors using Hydronix Hydro-Com software. Remote configuration and control of a Hydro-Control V unit is also possible.
An option of using Power over Ethernet is available via a second small DIN-rail module to eliminate the need for a local 24V supply for the sensors.
Figure 1: Ethernet Adapter Kit Connections
Page 8
Chapter 1 Introduction
8
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Kit Contents
A – Ethernet Adapter – EA01 B – Ethernet Power Adapter – EPA01 C – Ethernet Power Injector – EPI01 D – IEC Mains Cable E – Ethernet Patch Cables x 3
Order Options: Ethernet Adapter Kit Part Number: EAK01
Comprises: Ethernet Adapter, Ethernet Patch Cable (0.5m), User Guide, CD with
Hydro-Com software and User Guide
Use: Use with external 24V power supply
Ethernet Power Adapter Kit: Part Number: EPK01
Comprises: All the above plus Ethernet Power Adapter, Power Injector, IEC
mains cable and 2 additional Ethernet Patch Cables
Use: Provides power and Ethernet connection over standard CAT5e cable
A
B
C
D
E
Page 9
9
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Chapter 2 Connecting with Sensors
Installation
Depending on the installation option chosen, the system should be set up as shown in the diagrams below. Terminal identification for each module is shown later in this chapter.
Ethernet Adapter Only (EA01)
The most basic setup uses only the Ethernet Adapter and is arranged as shown below:
Cable T o Sensor
Black
RS/485 A RS/485 B 0v DC 24v DC
Colour White
Black Red
MILSPEC F G B A
EA01 Ethernet Adapter
1
24v DC
Powe r Sup ply
0v 24v
10/100baseT
CAT5e
Ethernet
to network
Figure 2: Connections for Ethernet Adapter only
Location of the Ethernet Adapter (EA01)
The Ethernet Adapter should be mounted in the wiring junction box as close to the sensors as possible, and protected from water and excessive dust. Connect the Ethernet drop cable from the network connection to the Ethernet port of the Adapter. Connect a 24V dc supply to the 24V+ and 0V input terminals of the Ethernet Adapter, ensuring that the power supply and wire is of a sufficient power rating to carry the power for the number of sensors connected.
Connect the RS485 sensor cable to the Ethernet Adapter outputs, taking care to note the recommendations in the RS485 Wiring Recommendations in Chapter 3.
Page 10
Chapter 2 Connecting with Sensors
10
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Power over Ethernet (EPK01)
To eliminate the need for a local 24V supply for the adapter and sensors, the optional Power over Ethernet kit can be used. The arrangement is as shown below:
Junction box close to sensorsControl Room Cabinet
Cable To Sensor
Black
RS/485 A RS/485 B 0v DC 24v DC
Colour White
Black Red
MILSPEC F G B A
EPA01 Ethernet Power Adapter
1
EA01 Ethernet Adapter
1
10/100baseT
CAT5e
linking
EPA01 and
EA01
EPI01 Ethernet Power Injector
OUT IN
IEC Mains
Cable
100-240v
50-60Hz
10/100baseT
CAT5e Ethernet to EPI01
10/100baseT
CAT5e
Ethernet
to EP A0 1
10/100baseT
CAT5e
Ethernet
to Network
Figure 3: Connections for Ethernet Adapter and Power Adapter
Location of the Power Adapter (EPA01)
The Power Adapter Module (EPA01) should be mounted in the wiring junction box close to the sensors and beside the Ethernet Adapter, protected from water and excessive dust. Connect the Ethernet drop cable from the router to the IN port of the Power Adapter. This cable carries both the power and the Ethernet communications signals. Connect a short Ethernet cable from the OUT port of the Power Adapter to the Ethernet port on the Adapter. This cable carries only the Ethernet communications. Connect short insulated wires from the 24V+ and 0V outputs of the Power Adapter to the 24V+ and 0V inputs of the Ethernet Adapter, ensuring that the wire is of sufficient power rating to carry the power for the number of sensors connected.
Connect the RS485 sensor cable to the Ethernet Adapter outputs, taking care to note the recommendations in the RS485 Wiring Recommendations in Chapter 3.
Sufficient ventilation and cooling should be employed to keep the air temperature around the unit to a suitable level for the number of sensors being powered. The diagram below shows the number of sensors that can be used at different air temperatures for each sensor type.
Page 11
Connecting with Sensors Chapter 2
11
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Figure 4: Maximum number of sensor connections
NOTE: Operation above these limits may cause premature failure of the unit.
Location of the Power Injector Module (EPI01)
The Power Injector Module (EPI01) should ideally be located in the computer room or network cabinet close to the router. Identify which drop cable runs to the sensor location, and using a short patch cable insert the Power Injector into that cable, connecting the port labelled IN to the router output and the port labelled OUT to the drop cable. Connect a 240V or 110V mains supply to the Power Injector.
Note: The Power Injector Module can supply sufficient power for up to four Hydronix Hydro­Probe II sensors or three Hydro-Mix VI, Hydro-Probe Orbiter or Hydro-Probe SE (Hydrotrac) sensors. If more sensors are to be connected to the network, then a separate power supply local to the sensors should be used instead of the Power over Ethernet solution.
Connections
Wiring Connections
Ethernet Adapter sensor connections:
Ethernet Adapter Terminal
Signal
Description
MIL Spec pin
number on sensor
Wire Colour in
standard Hydronix
0090A cable
1 24V + input 2 0V input 3 24V + to sensor A Red 4 0V to sensor B Black 5 RS485 B G Black 6 RS485 A F White
HydroMix / Orbite r / HydroProbe S E
0
1
2
3
4
0 1020304050607080
Maxim um Air Temperature
Number of Sensors
HydroProbe II
0
1
2
3
4
5
0 1020304050607080
Maximum Air Temperature
Number of Sensors
Page 12
Chapter 2 Connecting with Sensors
12
Ethernet Adapter User Guide HD0333 Issue 2.0.0
The white and black are from one twisted pair and the red and black from another.
Ethernet Power Adapter connections:
Ethernet Power Adapter Terminal Signal Description
1 0V output 5 24V + output
RS-485 Wiring Recommendations
The performance and reliability of a RS485 network can depend significantly on the quality and design of the wiring used. It is recommended to use 24AWG twisted pairs with a characteristic impedance (Zo) of 100R – 120R. Ideally, sensors on a RS485 network should be connected in a daisy chain arrangement, as shown here:
This arrangement uses just one of the sets of sensor outputs on the Ethernet Adapter. In practice, this arrangement is hard to achieve, so sensors may be wired using very short stubs:
Although the Ethernet Adapter has multiple sets of sensor outputs, wiring in a star configuration with each sensor wired to an output set should be avoided if at all possible.
Page 13
Connecting with Sensors Chapter 2
13
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Indicator Lights
The Ethernet Power Adapter unit (EPA01) has a single red indicator light on the top, which indicates that it is supplying power. It must be connected to an Ethernet cable with a 802.11af compliant Power Injector
supplying it.
The Ethernet Adapter (EA01) has three indicator lights on the top. The red indicator illuminates when a suitable 24V supply is connected. The transmit indicator light blinks when data is received by the Adapter and is being sent to the sensors. The receive indicator light blinks when data is received from the sensors and is being sent over the Ethernet to the host system.
Additionally, the green indicator light above the network connector indicates that a network connection has been established, and the yellow indicator blinks when network data is sent or received
Page 14
Chapter 2 Connecting with Sensors
14
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Page 15
15
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Chapter 3 Connecting with Hydro-Control V
Introduction
The serial port of a Hydro-Control V unit may be connected to the RS232 port of an Ethernet Adapter to allow remote access to recipe configuration and mix logs.
This cannot be done while an Adapter is communicating with sensors, as a different communications protocol is used. Installation will be similar to one of the options described above, except that the RS232 Tx, Rx and GND signals will be connected to the Hydro-Control V unit.
Installation
Depending on the installation option chosen, the system should be set up as shown in the diagrams below. Terminal identification for each module is shown later in this chapter.
Ethernet Adapter Only
The most basic setup uses only the Ethernet adapter and is arranged as shown below:
Black
Connections to HydroControl V
RS/23 2 Rx RS/232 Tx 0v DC 24v DC
23
29 27
EA01 Ethernet Adapter
1
21 22
RS/232 Gnd
24v DC
Powe r Sup ply
0v 24v
10/100baseT
CAT5e
Ethernet
to network
Figure 5: Connecting the Ethernet Adapter to Hydro-Control V
Location of the Ethernet Adapter (EA01)
The Ethernet Adapter should be mounted in the wiring junction box as close to the Hydro-Control as possible, and protected from water and excessive dust. Connect the Ethernet drop cable from the network connection to the Ethernet port of the Adapter. Connect a 24V dc supply to the 24V+ and 0V input terminals of the Ethernet Adapter,
Page 16
Chapter 3 Connecting with Hydro-Control V
16
Ethernet Adapter User Guide HD0333 Issue 2.0.0
ensuring that the power supply and wire is of a sufficient power rating to carry the power for the number of sensors connected.
Power over Ethernet (EPK01)
A single Hydro-Control V unit (with attached Hydro-Mix sensor) can be powered using the Power over Ethernet kit. Connect one of the Sensor 24V and 0V connections to the Hydro-Control V power input pins. The arrangement is as shown below:
Junction box close to Hydro-Control
Black
Connections to Hydro-Control V
RS/232 Rx RS/232 Tx 0v DC 24v DC
23
29 27
21 22
RS/232 Gnd
Control Room Cabinet
EPA01 Ethernet Power Adapter
1
EA01 Ethernet Adapter
1
10/100baseT
CAT5e
linking
EPA01 and
EA01
EPI01 Ethernet Power Injector
OUT IN
IEC Mains
Cable
100-240v
50-60Hz
10/100baseT
CAT5e Ethernet to EPI01
10/100baseT
CAT5e
Ethernet
to EP A0 1
10/100baseT
CAT5e
Ethernet
to Network
Figure 6: Connecting the Ethernet Adapter to Hydro-Control V with Power Over Ethernet Option
Location of the Power Adapter (EPA01)
The Power Adapter Module (EPA01) should be mounted in the wiring junction box with the Hydro-Control and beside the Ethernet Adapter, protected from water and excessive dust. Connect the Ethernet drop cable from the router to the IN port of the Power Adapter. This cable carries both the power and the Ethernet communications signals. Connect a short Ethernet cable from the OUT port of the Power Adapter to the Ethernet port on the Adapter. This cable carries only the Ethernet communications. Connect short insulated wires from the 24V+ and 0V outputs of the Power Adapter to the 24V+ and 0V inputs of the Ethernet Adapter, ensuring that the wire is of sufficient power rating to carry the power for the Hydro-Control V and it’s sensor.
Connect RS232 cables between the Ethernet Adapter and the Hydro-Control V.
Page 17
Connecting with Hydro-Control V Chapter 3
17
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Location of the Power Injector Module (EPI01)
The Power Injector Module (EPI01) should ideally be located in the computer room or network cabinet close to the router. Identify which drop cable runs to the Hydro-Control’s location, and using a short patch cable insert the Power Injector into that cable, connecting the port labelled IN to the router output and the port labelled OUT to the drop cable. Connect a 240V or 110V mains supply to the Power Injector.
Note: The Power Injector Module can supply sufficient power for a Hydro-Control V and a sensor attached to it.
Ethernet Adapter Hydro-Control V connections
Ethernet Adapter
Terminal
Signal Description Signal Function Hydro-Control V
Pin
3 24V + to sensor 24v to Hydro-Control V 27 4 0v to sensor 0v to Hydro-Control V 29 8 RS232 RTS RS232 Ready To Send Not used 9 RS232 Tx
Data from Ethernet Adapter to
Hydro-Control V
21
10 RS232 Rx
Data from Hydro-Control V to
Ethernet Adapter
22
11 RS232 CTS RS232 Clear To Send Not used 12 RS232 GND Ground connection 23
Connecting with Hydro-Control V
To communicate with a Hydro-Control V unit, start a terminal emulation program such as HyperTerminal and set the connection properties as shown, substituting the correct IP Address. Note specifically that the Port number should be set to 10001.
The same “ * “ commands can be used as would normally be used over a serial link, and the responses will provide the same information. Refer to Chapter 4 of the Hydro-Control V Users Guide for more details of the commands available.
Programming
An installation using the Ethernet Adapter packs the messages sent from a Host to the Sensor into an Ethernet data packet, which is then unpacked by the Ethernet Adapter and converted into RS485 voltage levels. If a custom application is being written to communicate with Hydronix sensors over the Ethernet, then the Hydro-Link communications protocol should be implemented and the resulting message string sent over the network to the Ethernet Adapter (instead of a serial port). In Visual Basic (VB6) this is done using a WinSock control and in Visual Studio .NET this can either be done using a Sockets control or a TCPClient control. A connection should be made from the Winsock or TCPClient control to port 10001 on the Adapter. Further information on these controls can be found in the programming system documentation, but please note that Hydronix are unable to provide technical support for developing custom software applications
Page 18
Chapter 3 Connecting with Hydro-Control V
18
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Hydronix are currently developing a Class Library for .NET to implement all of the communications functionality including support for the Ethernet Adapter, which will be available upon request. For details of this and more information on the Hydro-Link Communications Protocol please contact Hydronix Technical Support ([email protected]).
configuring the two Ethernet Adapters. Power for both units may optionally be provided over the Ethernet cables, as described above
Page 19
19
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Chapter 4 Configuring the Ethernet Adapter
Ethernet Adapter defaults
By default, the Ethernet Adapter will use an automatically generated IP Address, which will be allocated by the network DHCP server. As this may change after a few days or weeks, it is recommended that a fixed IP Address is used for the Ethernet Adapter. The allocated address should be on the same subnet as the address allocated by DHCP, but outside the range of DHCP addresses. Contact the Network Administrator to find a suitable address.
Finding an Ethernet Adapter automatically
Communication with Hydronix sensors is carried out with the Hydro-Com Utility. To start go to the Communications->TCP/IP menu in Hydro-Com and select “Search for Ethernet Adapters”.
The program will display a search window and query the network for any sensors attached.
The adapter will be added to the list, select it to connect.
Page 20
Chapter 4 Configuring the Ethernet Adapter
20
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Adding an Ethernet Adapter manually
In order to manually enter an Ethernet Adapter’s IP Address select Communications->TCP/IP->Add Ethernet Adapter.
In the dialog that is shown, enter the IP Address and Port Number (usually 10001) of the Ethernet Adapter
The adapter will be added to the list, select it to connect.
Page 21
Configuring the Ethernet Adapter Chapter 4
21
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Changing the Ethernet Adapter IP Address
Once Hydro-com is connected to an Ethernet Adapter, go to the “Diagnostics” tab, login then click on the button “Settings” in the Ethernet Adapter frame
To fix the IP Address, click on “Use fixed IP Address” and enter the IP Address in the box provided. It is recommended to leave the Port Number and Gateway set to the defaults. Click “Set” and then after the progress bar has completed and the new information has been written, click “Exit” to close the dialog and go back to the main screen.
When a fixed IP Address has been assigned, it is recommended to write the address on the front of the Ethernet Adapter in the space provided.
Remote (Internet) Connection
Sensors connected to an Ethernet Adapter can also be accessed remotely over the Int ernet. In order to do this, it is necessary to open up a port in the Firewall of the network on which the Ethernet Adapter is installed. Contact the Network Administrator for details of doing this. When opening the Port, all incoming traffic to that port should be directed to the IP Address of the Ethernet Adapter and port 10001. Make a note of the network’s IP Address on the Internet and the number of the port opened up. The table below shows the settings used in this example:
Company Network Settings Ethernet Adapter Settings IP Address Opened Port IP Address Port Number
123.456.78.901 7011 192.168.10.61 10001
Page 22
Chapter 4 Configuring the Ethernet Adapter
22
Ethernet Adapter User Guide HD0333 Issue 2.0.0
The port 7011 on the Firewall is opened up and all traffic to this port is forwarded to 192.168.10.61 port
10001.
If the Firewall does not allow a completely flexible configuration of port forwarding then either open up port 10001 on the Firewall and leave the Ethernet Adapter port set as 10001, or alternatively alter the port of the Ethernet Adapter to be the same as the port opened in the Firewall. This is done by entering the new value in the Port Number box when setting the fixed IP Address:
Certain port numbers are reserved for internal use by the Ethernet Adapter and should not be used:
Port Number Function
1 – 1024
Commonly used Internet Ports
9999
14000 – 14009
30704 30718
Ethernet Adapter Reserved functionality
Hydro-Com prevents you from setting these port numbers.
Install Hydro-Com on the remote machine. As before, select Communications->TCP/IP->Add Ethernet Adapter. In the Add Ethernet Adapter window, enter the IP Address of the Firewall and the Port opened.
Page 23
23
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Chapter 5 Technical Specifications
EA01 Ethernet Adapter
Dimensions: 70mm (w) x 86mm (h) x 57mm (d)
Environment: Operating Temperature 0-70°C
Modules should be used indoors in dry environments only. The enclosures are rated to IP31.
Interfaces: Ethernet IN: Standard 10/100baseT Ethernet RJ45 socket
RS485: Can connect to a maximum of 16 Hydronix Sensors
RS232: Standard RS232 interface
Weight: 160g
EPA01 Ethernet Power Adapter
Dimensions: 35mm (w) x 86mm (h) x 57mm (d)
Environment: Operating Temperature:0-70°C
Modules should be used indoors in dry environments only. The enclosures are rated to IP31.
Power Output: 24V, 630mA – see notes in Chapter 2 on number of sensors that can be powered.
Interfaces: Ethernet IN: Standard 802.11af 10/100baseT Power over Ethernet RJ45 socket
Ethernet OUT: Standard 10/100baseT Ethernet RJ45 socket
Weight: 123g
EPI01 Ethernet Power Injector
Dimensions: 65mm (w) x 140mm (h) x 36mm (d)
Environment: Operating Temperature: 0-40°C
Modules should be used indoors in dry environments only.
Interfaces: Mains In: IEC320 inlet 3 pin
Ethernet IN: Standard 10/100baseT Ethernet RJ45 socket
Ethernet OUT: Standard 802.11af 10/100baseT Power over Ethernet RJ45 socket
Weight: 246g
NOTE: Allow space for cables to be fitted on all units
Page 24
Chapter 5 Technical Specifications
24
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Terminal Identification
The Ethernet Adapter terminals are wired as follows:
EA01 Ethernet Adapter
1 12
13 24
IN
Figure 6: EA01 Terminal Identification
Ethernet
Adapter
Terminal
Signal
Description
Notes
IN CAT5e Network cable
1 24V + input 2 0V input 3 24V + to sensor 4 0V to sensor 5 RS485 B 6 RS485 A 7 No connection 8 RS232 RTS
9 RS232 Tx 10 RS232 Rx 11 RS232 CTS 12 RS232 GND 13 24V + to sensor 14 0V to sensor 15 RS485 B 16 RS485 A 17 24V + to sensor 18 0V to sensor 19 RS485 B 20 RS485 A 21 24V + to sensor 22 0V to sensor 23 RS485 B 24 RS485 A
It is not recommended to wire RS485
using a star topology
Please refer to chapter 3 on RS485
wiring recommendations
Page 25
Technical Specifications Chapter 5
25
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
The Ethernet Power Adapter EPA01 terminals are wired as follows. Particular care must be taken to identify the top and bottom of the unit, as both sides look similar.
EPA01 Ethernet Power Adapter
6 10
1 5
IN
OUT
Figure 7: EPA01 Terminal Identification
Ethernet Power Adapter
Terminal
Signal
Description
IN CAT5e Network cable from EPI01
OUT CAT5e Network cable to EA01
1 0V output 2 0V output 3 No connection 4 24V + output 5 24V + output 6 0V output 7 0V output 8 No connection 9 24V + output
10 24V + output
Page 26
Chapter 5 Technical Specifications
26
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Page 27
27
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Chapter 6 Fault Finding
Ethernet Adapter EA01
Symptom: 24V light not on
Possible Explanation Check Required Result
Action required on
failure
24V not connected
DC power on terminals 1 and 2
+24v DC
Locate fault in power supply
Symptom: Not found on network using the Hydro-Com Search function
Possible Explanation Check Requir ed Result
Action required on
failure
Not connected to network
Ethernet link Ethernet link light lit
Locate fault in network cabling
No DHCP address DHCP server IP address assigned
Unplug and replug the network cable
Ethernet Power Adapter EPA01
Symptom: 24V light not on
Possible Explanation Check Required Result
Action required on
failure
Ethernet Power Injector not connected
Ethernet Power Injector EPI01 as above
24V light on
Ethernet cables plugged in wrong way round
Try swapping the cables – the Power Injector should go to IN and the OUT should go to the Ethernet Adapter
24V light on
Symptom: Computer does not communicate with the Ethernet Adapter
Possible Explanation Check Required Result
Action required on failure
Not properly registered on network
Search for the Ethernet adapter using the Hydro­Com ‘Search’ function.
If that fails then try pinging the IP address of the Ethernet Adapter
Ethernet Adapter found
Ping response
Investigate network – try power cycling EA01
Check IP Address
Invalid IP address
If the subnet mask is
255.255.255.0 then if the adapter’s IP address x.y.z.a then the PC’s must be x.y.z.b (b <> a) try changing the PC’s to match and try again
Connection from HydroCom to Ethernet Adapter – then the IP Address can be changed
Contact local network administrator or Hydronix Technical Support
Page 28
Chapter 6 Fault Finding
28
Ethernet Adapter User Guide HD0333 Issue 2.0.0
Symptom: Computer does not communicate with the sensor
Possible Explanation Check Required Result
Action required on
failure
Not wired correctly to sensor
Wiring connections of EA01
Transmit and receive lights blink
Check sensor connections, try a different sensor
Ethernet Power Injector EPI01
Symptom: ON light not illuminated
Possible Explanation Check Required Result
Action required on
failure
Ethernet Power Injector not plugged in
Power supply to Ethernet Power Injector
ON light illuminated Try a different EPI01
Symptom: CONNECT light not illuminated
Possible Explanation Check Required Result
Action required on
failure
Ethernet cable to Ethernet Power Adapter faulty or not connected
Cable between EPI01 and EPA01
CONNECT light illuminated
Replace cable or try a different EPA01
Page 29
Index
29
Ethernet Adapter User Guide
HD0333 Issue 2.0.0
Index
Connections 13
Internet / Remote 25 Custom Application 21 Defaults 23 DHCP 23 Dimensions 27 Ethernet Adapter
Connections 30
Connections for Sensor 13
Defaults 23
Fault Finding 33
Hydro-Control V Connections 21
Indicator Lights 15
Installation 9
IP Address 23
Location 9, 17
Terminals 30 Ethernet Adapter Kit
Contents 8 Ethernet Power Adapter
Connections 14, 31
Fault Finding 33
Indicator Lights 15
Location 10, 20
Terminals 31
Ventilation 10 Ethernet Power Adapter Kit
Contents 8 Ethernet Power Injector
Fault Finding 34
Indicator Lights 15
Location 13, 21
Number of Sensors 13 Hydro-Control V
Connections 17, 21
Ethernet Adapter Location 17
Ethernet Power Adapter 20
Installation 17 Hydro-Link 21 Indicator Lights 15 Installation 9
Ethernet Adapter 9
Ethernet Power Adapter 10
Hydro-Control V 17 Interfaces
Ethernet Adapter 27
Ethernet Power Adapter 27
Ethernet Power Injector 27 Internet Connection 25 IP Address 23 Kit Options 8 Operating Temperature 27 Port Numbers 26 Power Injector Module
Sensor Connections 21 Power Output 27 Power over Ethernet
Installation 10, 20 Programming 21 Remote Access 25 Remote Connection 25 RS-485
Wiring 14 TCP/IP Menu 23 Temperature 27
Number of Sensors 10 Terminal Identification 30 Ventilation 10 Weight 27 Wiring 13
RS-485 14
Loading...