HydroMatik LPS, LPS45, LPS72, LPS110 Operating Manual

Page 1
LPS
Humidifies and Cools
ÁLPS.Ä4-&3Ö.ENhÈ
LPS.20130619.EN
Page 2
Page 2
Caution: Voltage: All work must be carried out by specialists. All electrical installa­tion work and work on the device's electrical components must be carried out by authorised electricians. Switch off devices and disconnect them from the ma ins sup­ply first!
Certain computer programs contained in this product [or device] were developed by HygroMatik GmbH ("the Work(s)").
Copyright © HygroMatik GmbH [2013.06.19] LPS All Rights reserved.
HygroMatik GmbH grants the legal user of this product [or device] the right to use the Work(s) solely within the scope of the legitimate operation of the product [or device]. No other right is granted under this licence. In particular and without prejudice to the generality of the foregoing, the Work(s) may not be used, sold, licensed, transferred, copied or reproduced in whole or in part or in any manner or form other than as expressly granted here without the prior written consent of HygroMatik GmbH.
Information in this manual is subject to change or alteration without prior notice.
Page 3
Page 3
1. Introduction ....................................................................................................................... 5
1.1 Typographic markings .......................................................................................................5
1.2 Documentation .................................................................................................................. 5
1.3 Intended use .....................................................................................................................6
2. Safety instructions ............................................................................................................8
2.1 General information ...........................................................................................................8
2.2 Operational safety instructions .......................................................................................... 8
2.3 Disposal upon disassembly ...............................................................................................9
3. Transport ............................................................................................................................ 10
3.1 General information ...........................................................................................................10
3.2 Packaging ..........................................................................................................................10
3.3 Temporary storage ............................................................................................................ 10
3.4 Inspecting for correctness and completeness ................................................................... 10
3.5 Scope of delivery ...............................................................................................................10
4. Function and design .........................................................................................................11
4.1 Functioning ........................................................................................................................11
4.2 Design and process ........................................................................................................... 11
4.2.1 Pump group ....................................................................................................................12
4.2.2 Dimension drawing of HygroMatik LPS nozzle system .................................................. 12
4.2.3 Vortex modules .............................................................................................................. 13
4.2.4 Atomising nozzles .......................................................................................................... 14
4.2.5 Droplet separators (optional) .......................................................................................... 15
4.2.6 Humidification section ....................................................................................................15
4.3 Partial and Full-Load .........................................................................................................16
5. Connnections .................................................................................................................... 17
5.1 Water .................................................................................................................................17
5.2 Waste water ......................................................................................................................17
5.3 Pressure water .................................................................................................................. 17
5.4 Electrical ............................................................................................................................18
6. Interfaces to the HygroMatik nozzle system LPS ........................................................... 19
6.1 Air ......................................................................................................................................19
6.2 Humidification chamber .....................................................................................................19
7. Mechanical assembly ........................................................................................................ 21
7.1 Overview of the humidification chamber ...........................................................................21
7.2 Vortex wall module assembly ............................................................................................ 22
7.3 Assembling the vortex module wall ................................................................................... 22
7.3.1 Guide rails for the vortex module wall: ...........................................................................22
7.3.2 Examplary design of guide rails for a vortex module wall .............................................. 23
7.3.3 Side rails for the vortex module wall: ..............................................................................23
7.3.4 Assembling of the side rails for the vortex module wall ..................................................23
7.4 Installation of the nozzles, distributor pipe and tubing .......................................................24
7.4.1 Nozzle Installation: ......................................................................................................... 25
7.4.2 Assembling the distributor pipe ......................................................................................26
Page 4
Page 4
7.4.3 Piping ............................................................................................................................. 27
7.5 Assembling the droplet separators .................................................................................... 32
7.5.1 Examplary design of guide rails for the droplet separators ............................................32
7.6 Pump station wall mounting ..............................................................................................35
7.7 Checking the installation ...................................................................................................36
8. Dimensions - Pump Station ..............................................................................................37
9. Water connection ..............................................................................................................38
9.1 Overview Water connection ..............................................................................................38
9.2 Water supply .....................................................................................................................39
9.3 Drainage ............................................................................................................................40
9.3.1 Water drain for the humidification chamber ....................................................................40
9.4 Water Quality ..................................................................................................................... 41
9.5 Inspection the water supply ...............................................................................................41
10. Hygiene ............................................................................................................................42
10.1 Ensuring hygiene (VDI 6022) ..........................................................................................42
10.2 Automatic flushing ...........................................................................................................42
11. Electrical connection ......................................................................................................43
11.1 Connection data .............................................................................................................. 44
11.2 System enabling / Safety chain .......................................................................................44
11.3 Circuit diagram ................................................................................................................ 45
11.4 Inspecting the electrical installation ................................................................................. 47
12. Commissioning ............................................................................................................... 48
13. Maintenance ..................................................................................................................... 49
13.1 Maintenance activities .....................................................................................................49
13.1.1 Inspection / replacement of the net-based water filter ..................................................50
13.1.2 Cleaning the atomizer nozzle ....................................................................................... 51
13.1.3 Cleaning the droplet separators ...................................................................................52
13.1.4 Cleaning the vortex module wall ..................................................................................52
13.1.5 Cleaning the humidification chamber ...........................................................................53
14. Control System ................................................................................................................54
14.1 Control and speed regulation ..........................................................................................54
14.1.1 Full load and part load ..................................................................................................55
14.1.2 Summer / winter mode .................................................................................................55
14.2 Description of the programmable controller (PLC) .......................................................... 56
14.2.1 General description ......................................................................................................56
14.2.2 Menu ............................................................................................................................ 58
14.2.3 Overview of error reports ..............................................................................................61
15. EC declaration of conformity ......................................................................................... 63
16. Spare parts ....................................................................................................................... 64
17. Fax Form - Order for spare parts ................................................................................... 66
18. Technical Specifications ................................................................................................ 67
19. Plant scheme ................................................................................................................... 68
Page 5
Page 5
1. Introduction
Dear Customer,
Thank you for purchasing a LPS nozzle system. The HygroMatik LPS nozzle system corresponds to the current
state of the art. It features exceptional operational reliability, ease of use and cost-effectiveness.
To ensure the proper, safe and economical operation of your HygroMatik LPS nozzle system, please read this operating man­ual.
Only use the HygroMatik LPS nozzle system if it is in perfect condition and only for its intended purpose, considering all safety and risk aspects as well as all instructions in this manual.
If you have further questions please contact us:
Tel.: +49 (0)4193 895 0 (Switchboard) Tel.: +49 (0)4193 895 293 (Technical Hotline) Fax: +49 (0)4193 895 33 Email: hot1@HygroMatik.de
Please have your device data ready for queries or spare part orders!
1.1 Typographic markings
lists with items beginning with bullets: general lists » lists with items beginning with arrows: work or operating
steps which should or must be carried out in the speci-
fied order installation steps which must be checked italics figure and plan names
1.2 Documentation
Storage
Please keep this operating manual in a safe place where it is accessible at all times. If you sell the product, be sure to include this manual. Please contact HygroMatik if the documentation is lost.
Language versions
This operating manual is available in different languages. Please contact your HygroMatik dealer or HygroMatik for details.
Page 6
Page 6
1.3 Intended use
The HygroMatik LPS nozzle system is used for air humidification and cooling with desalinated water having a conductivity of 5-20 µS/cm. The feed water should have a temperature of 5-15°C.
Caution: Proper use includes fulfilment of the assembly, disas­sembly, reassembly, start-up, operating and maintenance condi­tions specified by us as well as disposal measures.
Only appointed qualified staff may work on or with the system. Persons transporting or working on or with the system must have read and understood the relevant parts of this operating manual, particularly the 'Safety instructions' section. Staff must also be informed of possible hazards by the operating company. Please keep a copy of the operating manual at the location where the device is being used.
The HygroMatik LPS nozzle system is not frost-proofed and not suitable for outdoor installation.
The room temperature should be between 5 and 40°C. At an altitude of over 1000 meters please contact your Hyg roMa-
tik dealer or HygroMatik for details.
Applications:
The HygroMatik LPS nozzle system has a wide range of applica­tions. These systems are used wherever low-energy adiabatic humidification or cooling or systems with high-precision control are needed. They can be found in such places as offices, store­rooms, production halls, clean rooms, hospitals and concert halls.
Note: Components installed in ventilation and air-conditioning systems must be suitable for the intended use; i.e. they must be corrosion-resistant, easy to clean, accessible and hygienic. Fur­thermore, they must not facilitate growth of micro-organisms.
Improper use:
Hardware and software may not be modified.
Page 7
Page 7
Exemptions of usage: The HygroMatik nozzle system LPS is not frost resistant and is
unsuitable for outdoor installation. The HygroMatik nozzle system LPS PLC control may not be
deviate from the preset programmed On-/Off Control (or only after consultation with HygroMatik).
The default constant pressure level of the HygroMatik LPS noz­zle system may not be changed (or only after consultation with HygroMatik).
The HygroMatik LPS nozzle system may only be used for the purpose of cold-water cooling after consultation with HygroMa­tik.
The HygroMatik LPS nozzle system or may not be used in a ver­tical flow (or only after consultation with HygroMatik).
Page 8
Page 8
2. Safety instructions
2.1 General information
The safety instructions are prescribed by law. They are intended to ensure health and safety at work and accident prevention.
Warnings and safety symbols
The following safety symbols are used in this manual to indicate hazard and risk warnings. Please familiarise yourself with these symbols.
Caution: Failure to heed this warning may result in injury or dan­ger to life and limb and/or damage to the device.
Caution: Voltage: Dangerous electrical voltage! Failure to heed this warning may result in injury or danger to life and limb.
Note: indicates materials and consumables which must be han­dled and/or disposed of in accordance with statutory require­ments.
Note: precedes explanations for or cross-references to other places in the text.
2.2 Operational safety instructions
General information
Observe all safety instructions and warnings found on the sys­tem.
If malfunctions occur switch the system off immediately and secure it to prevent it from being switched on. Eliminate the mal­functions immediately.
After maintenance work has been carried out, expert staff must ensure that the system is safe to operate.
Only use original spare parts. National regulations beyond the scope of this manual apply with-
out restriction for operation of this device. During operation of the HygroMatik LPS nozzle system it is not
allowed to stay in the humidification chamber. The desalinated water used for feeding the HygroMatik LPS
nozzle systemis unsuitable for drinking. Work on the high pressure components of the nozzle system is
only allowed if the unit is disconnected from the power supply. This unit is not designed for the use by persons (also children)
with limited physical, sensory and mental abilities - or without knowledge and experience. Unless they are supervised or trained by a person, who is responsible for their safety.
Page 9
Page 9
Supervise children in order to ensure that they will not play with the unit.
Accident prevention regulations Caution: Heed the HSW (Health and Safety at Work) regulations
for electrical installations and equipment (VBG4/BGVA3). By doing so you protect yourself and others from harm.
Operating the HygroMatik LPS nozzle system
Refrain from all work practices which compromise the safety of the system.
Check all protection and warning devices at regular intervals to ensure they are in perfect working order.
Do not remove or deactivate safety devices.
Assembling, disassembling, servicing and maintaining the device
Disconnect system parts from the mains supply before servicing or repairing them.
Mounting or insertion of additional devices is only permitted with the written consent of the manufacturer.
The HygroMatik LPS nozzle system is protected to IP20. Ensure that the devices are protected from dripping water and dust at the installation location.
If a HygroMatik LPS nozzle system is to be set up in an area without water drainage, safety measures which eliminate the possibility of water entering the system due to leaks must be taken.
Electrical equipment Caution: Only a qualified electrician is permitted to work on the
electrical system and the control cabinet. Disconnect system parts from the mains supply before working
on them. Switch off the system immediately if faults in the electri­cal energy supply occur. Only use original fuses with the speci­fied amperage. Inspect the system's electrical equipment at regular intervals. Promptly eliminate deficiencies, such as loose connections or melted cables. After carrying out the correspond­ing electrical assembly or maintenance work, test all protective measures used (e.g. earth resistance).
2.3 Disposal upon disassembly
Note: The operating company is responsible for disposal of the
system parts in accordance with statutory requirements.
Page 10
Page 10
3. Transport
3.1 General information
Note: Take care when transporting the HygroMatik LPS nozzle
system to prevent the device and packaging from being damaged by impact or accidental loading or unloading.
3.2 Packaging
Note: The HygroMatik LPS nozzle system is delivered on a pal-
let.
3.3 Temporary storage
Store the material in a clean dry place. The storage temperature should be 0-40°C.
Note: Only clean components may be installed in a ventilation duct.
3.4 Inspecting for correctness and complete-
ness
When you receive the goods, ensure that:
the equipment is complete and all parts are in perfect
condition. Note: Any transport damages and/or missing parts must be re-
ported immediately to the shipper or supplier. The periods in which notification of the transport company must occur for the purposes of identifying the damage are as follows*:
* Periods are subject to change without notice.
3.5 Scope of delivery
The following items are included in the delivery:
vortex modules
droplet separators (optional; Hygiene compliance
checks applies only to systems with droplet separators)
pump station
operating instructions for the system
bushing/s for duct
Note: Hoses and nozzles are delivered at the time of start-up.
Transport company Time after receipt of
goods
Post no later than 24 hours
Rail 7 days at the latest
Rail and road transport
companies
4 days at the latest
Parcel services immediately
Page 11
Page 11
4. Function and design
4.1 Functioning
The HygroMatik LPS nozzle system is based on atomisation of water.
Desalinated water is fed into a vane pump. With an operating pressure of up to 16 bar, the water then goes to the nozzles. These nozzles generate a very fine spray mist which is taken up by the air in the device chamber. The ambient air is cooled adia­batically in the process.
4.2 Design and process
1: Pump group 2: Water feed 3: Vortex module wall 4: Viewing window (necessary according to VDI 6022) 5: 2-stage droplet separator 6: Humidification chamber or duct with service doors and water
tray 7: Water drain, siphoned 8: SPS-control
Page 12
Page 12
4.2.1 Pump group
The vane pump generates a pressure of up to 16 bar. The main­tenance-free asynchronous motor with variable frequency ena­bles continuous operation up to 50 Hz.
4.2.2 Dimension drawing of HygroMatik LPS nozzle
system
Pump group Capacity [l/h] Max. speed
[rpm] LPS 45 45 1350 LPS 72 72 1350
LPS 110 110 1350
H T B Weight
LPS 45-110 700 230 600 30 Kg
T
B
H
Page 13
Page 13
4.2.3 Vortex modules
The vortex modules provide for effective mixing of the air and the water mist.
Due to their special design, they generate turbulence and shear zones which lead to a homogeneous distribution of moisture along the humidification section (0.9 m). The vortex modules (dimensions: 150 x 150 mm) are delivered individually and can be assembled to form a wall. For optimal moisture absorption, the air velocity is 1.0-2.5 m/s. The vortex module wall exhibits a low pressure drop of 10Pa at an air veloc­ity of 2.0 m/s.
Page 14
Page 14
4.2.4 Atomising nozzles
Desalinated water at a pressure of up to 16 bar reaches the noz­zles where the water is atomised to form ultra-fine mist-like aero­sols. The aerosols enter the area of the vortexed air stream downstream of the vortex modules. The air and aerosols are mixed intensively here.
The atomising nozzle generates a spray cone with a wide open­ing angle.
1: Nozzle opening 2: Nozzle body
Functioning: The nozzle sets the flowing water in rotation and thereby it can
leave at high speed. This enables a very fine water spray. The higher the operating pressure, the finer the droplets.
Material of the nozzle: corrosion-free stainless steel
2
1
Page 15
Page 15
4.2.5 Droplet separators (optional)
There are no more atomised water droplets in the air stream behind the HygroMatik LPS nozzle system (if the environmental parameter specifications are complied with). The two wire-mesh droplet separators arranged in series ensure this. The trap pads exhibit a low pressure drop (75 Pa at air velocity of 2.0 m/s and average air density of 1.2 kg/m³).
The air velocity should be between 0.9 m/s and 2.8 m/s. If it is outside this range it can cause moisture breakthrough down­stream of the droplet separators - in such cases please first con­tact HygroMatik.
The droplet separators are inserted into the humidification chamber via guide rails and are hence easy to remove for serv­icing.
The traps are standardly delivered with corrosion-resistant metal frames.
Note: Hygiene compliance checks applies only to systems with droplet separators.
4.2.6 Humidification section
The section between the vortex module wall and the droplet sep­arators is called the 'humidification section' in this system. It is unobstructed and hence easy to monitor and clean.
For a total standard installation length of 1.5 m for the HygroMa­tik LPS nozzle system the humidification section should have a length of at least 0.9 m. The exact dimensions are described in the schematic in the section entitled 'Overview of the humidifica­tion chamber'.
droplet separators
Page 16
Page 16
4.3 Partial and Full-Load
For optimal humidification control under various input conditions the HygroMatik nozzle system LPS can be equipped with a „Par­tial and Full-Load” control function.
At Full-load all nozzles are fed with water. At Partial-load a sole­noid valve switches off the water supply for approximately half of the nozzles.
Construction: The vane pump has to exits for water - one is the water supply
for the nozzles for Partial load and the othe one is the water sup­ply for the nozzles for Full load.
If the external control signal decreases below a special switching point, the HygroMatik nozzle system LPS switches off the water supply for half of the nozzles.
Page 17
Page 17
5. Connnections
5.1 Water
Connection: 3/4”-external thread (within the
system)
Conductivity: 5-20 µS/cm Pressure: 0.15-0.5 MPa (1.5-5 bar) Temperature: max. 15°C pH value: 7 +/- 1
Note: The supply water for the HygroMatik high-pressure nozzle
system must comply with VDI 6022; i.e. from a microbiological point of view it must be of drinking water quality.
5.2 Waste water
Connection: Connecting piece DN 12 for
plastic hose (resistant to low conductive water) Fitting: with constant fall and free outlet and siphon
5.3 Pressure water
Connection „Full-Load”: plug-in connection for 6/4
pressure hose
Connection „Cooling”: plug-in connection for 6/4
pressure hose
Connection „Partial-Load”: plug-in connection for 6/4
pressure hose
Page 18
Page 18
5.4 Electrical
Power supply: LNE 230 V AC, 50 Hz (a fixed
socket (16 A) at the installation
site is necessary)
External control signal: 0-10 V DC
4-20 mA DC
System enabling: via ext. potential-free contact Collective fault signal: potential-free contact (change
over contact)
Operating status signal: potential-free contact (NO)
Page 19
Page 19
6. Interfaces to the HygroMatik nozzle system LPS
6.1 Air
Air purity: A Class F7 pre-filter is to be
placed upstream of the HygroMatik nozzle system LPS. Air velocity: 0.9-2.8* m/s If the air velocity is outside this range please contact HygroMa-
tik. (*: under ideal conditions)
Pressure drop: Approx. 80 Pa (at an air velocity of 2.0 m/s and with use of a vortex module wall and two dry droplet separators).
Air volume flow (for 'partial-load / full-load switching' option):
If the HygroMatik nozzle system LPS is operated in systems with modifiable air volume flows (reduced air volume of less than 70% of the maximum air volume), the full-load solenoid valve is switched off and the partial-load mode is activated. This also applies for systems with multi-stage ventilators.
Note: For humidification of rooms the humidified air must exhibit a purity in terms of bacterial count in accordance with VDI 6022.
6.2 Humidification chamber
The humidification component should be designed with a floor tray that has an inclination of at least 1.5° towards the trap and to be waterproof.
The water drain must be at the end of the humidification section. The ideal humificiation section length (distance between vortex
module wall and droplet separators) is 0.9 m. This corresponds to a total installation length of 1.5 m (see schematic in section entitled 'Overview of the humidification chamber'). Should this installation length not be available please contact HygroMatik.
The humidification chamber should be aerosol-tight and it should be able to withstand desalinated water.
Note: The guide rails for the vortex module wall and droplet sep­arators are supplied by the manufacturer. The guide rails must already be installed for the system to be started. The vortex module wall and droplet separators must also already be installed.
Page 20
Page 20
Note: The guide rails must be designed such that
- the vortex module wall and droplet separators can be removed
(for servicing)
- there cannot be any stagnant water.
Note: When starting the system check again that the humidifica­tion chamber has been thoroughly cleaned. In particular the humidification chamber and the ventilation duct upstream of it must be free from metal swarfs to prevent corrosion.
Page 21
Page 21
7. Mechanical assembly
Caution: The device may only be assembled by qualified staff.
HygroMatik accept no liability for damages resulting from incor­rect assembly.
Observe all safety instructions and warnings found on the device. The device must be de-energised during assembly. Mounting or insertion of additional devices is only permitted with the written consent of the manufacturer. Otherwise the guaran­tee and warranty will become void.
7.1 Overview of the humidification chamber
1: Vortex module wall with spray system 2: Droplet separators 3: Upper guide rails for droplet separators 4: Lower guide rails for droplet separators 5: Collection tray 6: Drain with trap
7. Guide rails for vortex module wall
8. Humidification section, >/= 0.9 m
9. Two supplied bushings for the duct (for partial-load / full-load
switching) for connecting high-pressure hoses * Only one bush­ing is needed for the standard model.
10. Distribution pipe
Note: In front of the vortex module wall and from the droplet separators a minimum distance of 0.3 m to other installed com­ponents must be maintained (see above schematic). In case of an upstream installation of a fan in front of the vortex module wall, the minimum distance shall be 1 m or appropriate action has to be taken in order to ensure a laminar flow of the vortex module wall. Temperatures higher than 60°C may destroy the vortex modules.
Page 22
Page 22
7.2 Vortex wall module assembly
The vortex module wall provides firstly the air turbulence and secondly it holds the atomiser nozzles and water distributor.
The vortex module wall is supplied as specified (please note the number of vortex modules in width and height), assembled in the accompanying nozzle assembly data sheet:
» The Vortex modules are slotted together piece by
piece, starting at the bottom right
The bottom right vortex module must be so positioned that the right hand and lower side is flat surface up while the other two sides show the guide bars (1).
7.3 Assembling the vortex module wall
Two guide rails are required for assembly of the vortex module wall.
We recommend to have an air gap sideways between the vortex module wall and the housing wall as it generates a laminar air flow and prevents moisture build-up on the walls.
7.3.1 Guide rails for the vortex module wall:
In order to position the vortex module wall in the humidification chamber guide rails are required. The guide rails are fixed to the ceiling and the floor of the humidification chamber.
The guide rails must be installed in a way that makes it possible to either pull out of or lift up the vortex module wall and stagnant water is prevented.
Ensure that after installation the floor of the h umidification cham­ber is leackage-free.
1
Page 23
Page 23
7.3.2 Examplary design of guide rails for a vortex
module wall
Pos. 1: upper guide rail Pos. 2: vortex module wall Pos. 3: spacer or direct connection floor of chamber Pos. 4: lower guide rail Pos. 5: humidification chamber
Inner dimension of guide rail: 62 mm Hight: please see above sketch Material: 1.4301 stainless steel sheet, thickness: 1 mm
7.3.3 Side rails for the vortex module wall:
If the wall consists of 11 or more vortex module rows side rails are required in order to avoid bending of the vortex module wall.
Having more than 16 vortex modules in horizontal position the the vortex module wall has to be vertically separated into two halfs, that are separately fixed by side rails
Guide rail (cross section)
Page 24
Page 24
7.3.4 Assembling of the side rails for the vortex
module wall
Vortex module walls consisting of 11 or more vortex module rows are automatically equipped with side rails and self-tapping screws.
The side rails have to be adapted to the right lenght by the installer. The required lenght is the distance between the middle of the lowest and the middle of the top vortex module.
The side rail is an u-section and made of stainless steel. It is
1.5mm thick. For the assembling the open side of the u-section
has to be attached to the latteral edge of the vortex module wall (pos. 3). The lower end of the side rail is positioned in the middle of the lowest vortex module. The lowest drilling (pos. 2) of the side rail is used to screw in a self-tapping screw (M3.9X20). A second self-tapping screw is used for the upper end of the side rail.
The side rail for the other side of the vortex module wall has to be assembled in the same way.
1
2
3
Page 25
Page 25
7.4 Installation of the nozzles, distributor pipe
and tubing
7.4.1 Nozzle Installation:
» In accordance with the supplied nozzle assembly data
sheet locate the vortex module to be equipped with a nozzle.
» Then plug the nozzle body (1), as shown in the picture,
on the upstream side of the vortex module, so that it protrudes about 1 cm on the other side
» Screw the nozzle (2) and copper washer (3) firmly into
the nozzle body.
1
2
3
Page 26
Page 26
7.4.2 Assembling the distributor pipe
The high-pressure water coming from pump station first enters a manifold and is routed from there to the nozzle.
The manifold is mounted according to the nozzle assembly sheet (project specific) produced by HygroMatik on the vortex wall.
Each nozzle in the vortex wall is connected to the manifold with a hose. Each nozzle must be higher than the corresponding port on the manifold - the water hose must have a constant slope
Installation:
» A manifold is mounted on the inlet side to at least two
vortex modules.
» Determine distributor pipe position (1) on vortex wall in
accordance with nozzle data sheet.
» Place retaining clips (3) on the appropriate position on
Vortex Modules. » Put screw (2) through by retaining clip Vortex Module. » Tighten nut (4) with washer (5) on the rear of the Vortex
Module where the screw stands proud. » Repeat this process for all the holding clamps. » Press manifold (1) into the holding clamps (see figure
C) and check for tightness.
1
C
4
5
2
B
2
2
3
A
Page 27
Page 27
7.4.3 Piping
Manifold - Nozzles
» The supplied 4 / 2 Hose pipe is firmly fitted into one of
the snap-connections on the manifold pipe. » Check connection by gently pulling on the hose. » Estimate the hose length (noting nozzle assembly plan)
to the nozzle by observation. Minimum bending radius
no less than 25mm.
» Cut the hose at right angles with a hose cutter.
» Insert hose into the nozzle snap-connector. » Check connection by gently pulling the hose.
Page 28
Page 28
The completed finished hose connection should look like this:
Manifold - Pump Station
In the standard version a 6/4 hose leads from the pump station to a manifold. However, if the LPS nozzle system is equipped with a partial/full load switch, then there is a 6/4 hose line lead­ing to two manifolds.
Since the 6/4 hose line goes through the air conditioning duct a duct wall grommet is provided (or two in the case of a partial/full load switch).
Page 29
Page 29
Assembly of the hose guide
» Drill a hole with a diameter of 15mm. through the wall of
the air conditioning duct, » Assemble snap connector (4), nut (3) and washer (2) to
hose opening (1) and insert through the duct wall from
the outside (see picture below).
» From the inside of the duct, assemble washer (5),
mother (6) and necessary snap-connectors (7) and
screw tight.
1 2
3 4
5
6
7
Page 30
Page 30
Hoses:
For standard version:
The pump station has a hose leading to a manifold at the vortex wall. From the manifold, it goes to all the nozzles of the LPS noz­zle system.
Additionally: » All hose assemblies are to be laid with a constant inc-
line. » Put a 6/4 hose line in the pump station outlet (I). » Check by gently pulling the tube. » Estimate the hose length to the ducting snap-connector
(external duct wall). Maximum bend radius 40mm. » Cut the hose at right angles with a hose cutter. » Put the 6/4 hose line into the ducting angled snap-con-
nector (external duct wall). » Check by gently pulling the tube. » Put a further 6/4 hose line into the straight snap-con-
nector (internal duct wall).
Connection I: Water supply for nozzles (for standard and partial load operation)
Connection II, Optional: Water supply for nozzles (only at full load operation)
Page 31
Page 31
» Check by gently pulling the tube. » Estimate the hose length from the snap-connector to
the duct opening (external duct wall) to the manifold.
Maximum bending radius 40mm. » Cut the hose at right angles with a hose cutter. » Put the 6/4 hose line into the angled snap-connector on
the duct opening (external duct wall). » Check by gently pulling the tube.
Partial / full load switching:
The tubing for partial/full load switching is initially in the same as described above for the standard version.
In addition, though, there is a further pump station hose for optional output II (for full load operation) to a second manifold on the vortex wall
Page 32
Page 32
7.5 Assembling the droplet separators
The guide rails must be installed in a way that makes it possible to either pull out or lift up the vortex module wall.
Detail B
Detail A
7.5.1 Examplary design of guide rails for the droplet
separators
Detail A:
Dimensions given in mm
A1: Trap guide rail: U-section with perforated 1.4301 stainless steel sheet
A2: Trap guide rail holder: U-section made from 1.4301 stain- less steel
A3: Several holes (at least 4 per metre) 8-10 mm in diameter distributed over the length of the trap holder
A4: Collection tray for humidification chamber A5: Fixation of guide rail with the floor of the humidification
chamber (ensure that condensate can freely run to the drain)
Page 33
Page 33
Dimensions of guide rails for droplet separators
Material used for upper guide rail: 1.4301 stainless steel sheet, thickness: 1 mm
Detail B:
Hight is variabel:
pushed in droplet separators: 55 lifted in droplet separatosr: 30 The upper guide rail is directly attache to the ceiling of the
humidification chamber (using screws, rivets or similar)
Assembling two droplet separators in a stack
For installation heights of above 1.5 m, two droplet separators must be mounted in a stack.
The waste water from the upper droplet separator is drained via an additional collector. For this the waste water from the upper trap is drained via a flexible hose either directly or into the collec­tion tray. This additional collector is to be provided for both the preliminary and the final droplet separator.
1. Upper guide rail
2. Detail C (please see next page)
3. Lower guide rail
Page 34
Page 34
Detail C (side view):
B1: Preliminary droplet separator B2: Final droplet separator B3: Angle bracket B4: Hose connection for drainage of waste water from upper
droplet separator Perforated sheet metal (material: 1.4301) should be used for the
lower guide rails for the droplet separators. Alternatively, sheet metal with several holes (at least 4 per metre) 8-10 mm in diam­eter can be used.The assembly must be made with 1.5% incline.
Page 35
Page 35
7.6 Pump station wall mounting
The installation of this unit must be carried out only by qualified personnel. We can assume no liability for damages caused by incorrect installation.
Please observe all the safety instructions and warnings on the equipment.
On the rear wall of the unit housing there are 4 mounting brack­ets (see also: Dimensions, pump station). There is a mounting kit supplied in which four screws, and rawlplugs are included for hanging the unit housing.
Firstly, holes are to be drilled according to the pump station dimensions (see pump station dimen­sions). Press rawlplugs into the drilled holes if dealing with stone or con­crete walls. Then screw the top two fittings to the wall (allowing a 12mm distance from the screw head to the wall) and hang up the pump station. Then attach and tighten the bottom two screws.
Note: If installing the system is done by a single person there is a danger that the unit can be dropped. Therefore we recom­mend that two qualified persons do the installation.
Hanging tab
Page 36
Page 36
7.7 Checking the installation
Assembling the vortex module wall
Have all electrical cable and plug connections been
properly tightened?Is the vortex module wall in accor-
dance with the nozzle arrangement data sheet? (please
note the number of modules in width and height)?
Vortex module wall assembly
Have all electrical cable and plug connections been
properly tightened?Are the guide rails built so that the
vortex wall module can be lifted or slid from the guide
rails? Is it ensured after assembly that the floor pan is sho-
wing no leaks? Have all electrical cable and plug connections been
properly tightened?With a wall height of 11 modules is
the Vortex-Vortex-module supported by two side rails.
With16 Vortex modules is it vertically split and sup-
ported individually by side rails?
Droplet separator assembly
Are the guide rails built so that separator can be lifted or
slid from the guide rails? Is it ensured after assembly that the floor pan is sho-
wing no leaks? Are all electrical plug connections
secure?
Mounting of the distributor pipe / tubing
Has the seating of the individual hoses on their connec-
tors been checked by pulling gently on them? Are all
electrical plug connections secure? Is the arrangement of the nozzles and tubing in accor-
dance with to the supplied nozzle arrangement data
sheet?
Pump station installation
Is the pump station fixed horizontally on a suitable wall?
Does the mains voltage match the voltage on the name
plate/delivery note?
Page 37
Page 37
8. Dimensions - Pump Station
View from below
Side view
Rear view
Page 38
Page 38
9. Water connection
9.1 Overview Water connection
1: Water supply 2: Water drainage 3: 12mm plastic tube (1.5 meter ): included 4: plastic hose DN12: on site 5: Water filter (input side: 3/4 external thread output side: 12mm snap-connector) 6: Mounting Bracket 7: Pump Station 8: External drain, siphoned (free entry must be assured) 9: Manometer, 0-10 bar
7
1
2
5
4
3
6
8
9
Page 39
Page 39
Note: There must be a stopcock and a sampling valve in the immediate vicinity of the HygroMatik LPS nozzle system pro­vided.
9.2 Water supply
Attention: Please observe during installation:
All work must only be performed by qualified personnel.
System must be switched off and voltage free.
Please observe local waterworks and utilities regulations
When using de-mineralized water we recommend the use of stainless steel or plastic pipes.
Water supply:
» Locate water Filter (position 5 in the graph above) near
the pump station (7). » Transfer mounting bracket hole pattern (6) to a suit a ble
location on wall. » Then drill using rawplugs and mounting brackets inclu-
ding water filters. » An 8mm plastic tube is supplied (length 1.5 m, shorten
if necessary). Connect this to the snap-connector on
the output side of the water filter. Gently pull on the
hose to check for tight fit. » Attach other end of the 8mm plastic tube into the snap-
connector to the pump station water supply. Gently pull
on the hose to check for tight fit. » Connect the external feed water line to the input side of
the water filter (3/4 "external thread).
Page 40
Page 40
9.3 Drainage
At the bottom of the housing, a DN12 spout is sticking out. This is a drain and is used to:
empty and relieve the pressure lines to the vortex wall
after removal of the module enable signal
drain the flush water after flushing
Water drainage
» A DN12 water hose (position 4 on the graph above) is
attached to the DN12spout on the bottom and made
fast with a clamp. » The tube is then siphoned off and installed on the slope
to the drain (8).
9.3.1 Water drain for the humidification chamber
Note: The water drain in the collection tray must be at the lowest
point in the humidification chamber. It is recommendable to have the water drain positioned behind
the droplet separators with respect to the direction of air flow. Only in this way can the waste water drain completely.
Page 41
Page 41
9.4 Water Quality
Conductivity: 5-20 µS/cm Pressure: 0,15-0,5 MPa (1,5-5 bar) Flow rate greater than max output of the
nozzle sytem Temperature: 5-15°C PH value: 7 +/-1
9.5 Inspection the water supply
Water supply
Is the supplied water filter installed to the water inlet for
the pump station?
Is the feed water quality within the specified range? Is the hose that lies between the water filter and pump
station waterproofed?
Drainage
Is the drain hose siphoned and installed wit h a constant
incline to the drain?
Can the flushing water drain off freely?
Humidification chamber
Is the humidification chamber provided with a drain at
the lowest point?
Page 42
Page 42
10. Hygiene
10.1 Ensuring hygiene (VDI 6022)
The regulations require that only inert materials must be used and biocides should only be used as a last option.
Prior to humidification the supply air is to be purified using a Class F7 filter.
A metal filter made of mesh wire is used as a droplet separator. The droplet separators can, as far as is necessary, be easily
cleaned and reused. Addition of a biocide is not required. All components must be easily accessible to perform a cleaning
in accordance with VDI6022. In order to carry out a visual inspection according to VDI 6022
sufficiently large windows / removable panels have to be pro­vided in the area of the droplet separators and the vortex mod­ules.
10.2 Automatic flushing
If the HygroMatik nozzle system LPS is in „stand by mode” and there is no demand for work for 24 hours the system will periodi­cally run (every 24h) flush cycles.
Hereby the growth of bacteria in standing water is obviated. During flushing the inlet water solenoid valve and the flushing
valve are simultaneously open. Thus the water in the pump sta­tion is being exchanged and directly led into the drain without reaching the humidification chamber.
Page 43
Page 43
11. Electrical connection
Caution: Voltage! All electrical installation work must be carried
out by qualified specialist staff (electricians or skilled workers with equivalent training) only. It is the customer's responsibility to monitor qualifications.
Caution: Voltage! All installation work must be completed before the HygroMatik nozzle system LPS is connected to the mains supply.
Please observe all local regulations for electrical installation work.
Caution: The electronic components of the HygroMatik nozzle system LPS control system are sensitive to electrostatic dis­charge. To protect these components from damage by electro­static discharge, special measures must be taken during all installation work.
Caution: During installation please perform the following steps:
Disconnect the system from the mains supply and secure
it to prevent it from being switched on again.
Ensure that the system is de-energised.
Installation and removal of the control system may only be
performed if the device is switched off.
Lay electrical cables properly.
Make the electrical connections according to the circuit
diagrams.
Ensure that all terminals are tight.
Connect the system via socket to the supply network. The
back-up fuses specified in the technical data must be used.
The mains plug of the nozzle system HygroMatik LPS is
the network point of separation according to VDE and is therefore absolutely necessary.
Page 44
Page 44
11.1 Connection data
Power supply: LNE 230 V AC, 50 Hz External control signal: 0-10 V DC
4-20 mA DC
System enabling: via ext. potential-free contact Group fault signal: potential-free contact (change
over contact)
Operating status signal: potential-free contact (NO)
Note: If a residual current device should be installed up stream of
the system a universal-current-sensitive circuit-breaker should be selected.
Note: When sizing the connection lines, observe that the supply impendance must be low! If a short circuit occurs the circuit­breaker must switch off automatically within 0.4 s. The magnetic short circuit trigger for the circuit-breaker (type B) acts immedi­ately when the flowing short circuit current is more than five times the rated current.
11.2 System enabling / Safety chain
Note: Interlock contacts, such as max. hygrostat, air flow relay,
duct pressure switch, ventilator interlock etc., are placed in series between series terminals X2.1 and X2.2 (= safety chain).
Caution: If the ventilation system fails or the supply air face velocity is too low (less than 0.9 m/s) the built-in control must switch off the humidifier via the safety chain. Otherwise unde­sired condensate build-up behind the droplet separator may occur.
Caution: Integration of a max. hygrostat into the safety chain is state-of-the-art. The max. hygrostat serves as a safety element in case of malfunction of the humidity sensor and protects against over-humidification.
Caution: The contacts which are placed on terminals X2.1 and X2.2 must be potential-free and suitable for switching 24 V DC / 100 mA. After the HygroMatik nozzle system LPS has been started, a standard voltage of 24 V DC is applied to terminal X2.1.
Pump group Rated power [kW] Rated current [A] Fuse [A]
LPS 45 0.15 1.9 1 x 16 LPS 72 0.16 2.1 1 x 16
LPS 110 0.18 2.7 1 x 16
Page 45
Page 45
11.3 Circuit diagram
S-103801
S-103801B.001
HYGROMATIK
Lise-Meitner-Str. 3
D-24558 Henstedt-Ulzburg
Germany
Telefax
+49-(0)4193 / 895 - 33
Phone
+49-(0)4193 / 895 - 0
15.09.2011
Schl
3 2
V
W
U
N L
3x 0,75 qmm
1.5 qmm
Motor
230V/3ph
L
24
25
6
8
K1
13
14
A01
F1
S1
F3
GND
1,6AF
SMP5500/C
N
N
PE
N PE
PE
N
PE
PE
X4
PE
PE
PE
L
L'
5AF
N
PE
N
PE
16
1718
1011
1213
14
15
0,75 qmm
Supply
Supply
GND
LAN
DI2
DI3
DI5
AI3AI4
DI4
12687
354
5GND
3
G
4
A03
DO6
12V
DO1
DO2
DO3
DO4
AO
Supply
Supply
LAN
10
798
A04
DO1 DO2
DO3
A02
0V
+12V
L
N
L'
N'
C1
F2
5AF
N
PE
50°C
B1
DI6
DI1
1
2
K1
K1
K2
20
A1
A1
A2
A2
19
21
SE632
origin Ers.dErs.f
page 1
of 1 p.
(drawing Nr.)(description)
(file)
modification date name
edit
Norm
date
LPS + Options
Supply
230VAC
control signal
HP-sensor
0...20mA
water
supply
pressure
switch
interlock
potential
free
input
winter-/
summer
Mode
operation
message
collective
fault
Fan 230V
MV 230V
water inlet
valve
MV 230V
full load
winter
MV 230V
flushing
MV 230V
part load
winter
OPTION
winter-/ summer
Mode
winding
motor
MV 230V
full load
summer
power
supply
+12VAC
OPTION
Full-/ Partload
OPTION
controler
Frequency
converter
Extension module
A
15.09.2011
Schl
release
+24V
X1
X3
PE
PE
7 6 5
PE
4
2
1
21
PE
X2
5
6
K2
K1
22
30
2829
4
3
(+)
(-)
+24V
(-)
PE9 8PEPE
A
B
05.01.2012
Schl
ATTENTION:
Plug in position
without black
marker.
If ELCB was
activated, set the
plug to <3.5mA!
Page 46
Page 46
S-103802
S-103802B.001
HYGROMATIK
Lise-Meitner-Str. 3
D-24558 Henstedt-Ulzburg
Germany
Telefax
+49-(0)4193 / 895 - 33
Phone
+49-(0)4193 / 895 - 0
25.10.2011
Schl
A
25.10.2011
Schl
origin Ers.dErs.f
page 1
of 1 p.
(drawing Nr.)(description)
(file)
modification date name
edit
Norm
date
LPS 3-Step control
release
3 2
V
W
U
N L
3x 0,75 qmm
1.5 qmm
Motor
230V/3ph
L
24
25
6
8
K1
13
14
A01
F1
S1
F3
GND
1,6AF
SMP5500/C
N
N
PE
N PE
PE
N
PE
PE
X4
PE
PE
PE
L
L'
5AF
N
PE
16
1718
1011
1213
14
15
0,75 qmm
Supply
Supply
GND
LAN
DI2
DI3
DI5
AI3AI4
DI4
12687
354
5GND
3
G
4
A03
DO6
12V
DO1
DO2
DO3
DO4
AO
Supply
Supply
LAN
10
798
A04
DO1 DO2
DO3
A02
0V
+12V
L
N
L'
N'
C1
F2
5AF
N
PE
50°C
B1
DI6
DI1
1
2
K1
K1
K2
20
A1
A1
A2
A2
19
SE632
Supply
230VAC
control signal
HP-sensor
0...20mA
water
supply
pressure
switch
interlock
potential
free
input
winter-/
summer
Mode
operation
message
collective
fault
Fan 230V
MV 230V
water inlet
valve
MV 230V
3rd Step
MV 230V
flushing
MV 230V
2nd Step
winding
motor
power
supply
+12VAC
controler
Frequency
converter
Extension module
+24V
X1
X3
PE
PE
7 6 5
PE
4
2
1
21
PE
X2
5
6
K2
K1
22
30
2829
4
3
(+)
(-)
+24V
(-)
PE9 8PEPE
ATTENTION:
Plug in position
without black
marker.
If ELCB was
activated, set the
plug to <3.5mA!
B
20.03.2012
Schl
Page 47
Page 47
11.4 Inspecting the electrical installation
The electrical installation must be checked by an electrician in accordance with customer requirements and the regulations set out by the public electricity supply company:
Does the mains voltage match the voltage specified on
the nameplate / delivery note?
Have all electrical connections been carried out accord-
ing to the connection diagrams?
Have all electrical screw and plug cable connectors
been attached properly?
Are the switch-off conditions for protection in case of
faults complied with?
Has the system been earthed?
The system can then be switched on.
Page 48
Page 48
12. Commissioning
Note: The LPS nozzle system may only be operated by qualified
personnel.
Turning the LPS nozzle system off Note: Before the LPS nozzle system is put into operation, it
must be clear how to switch the system off. » Switch off Nozzle system using control switch (Pos.0).
» Shut off water supply shut-off valve.
Check all cable connections
» Check all cable connections for tightness.
Activating the LPS nozzle system
» Operate main switch. » Set manometer to „open“ » Open up water shut-off valve » Switch on unit using control switch (Pos.I). » Set commissioning control to permanent demand
steam production.
The following functions begin: A self-test. When humidity is demanded, the pump vane is operated and
directs the water at a pressure of up to 16 bar to the nozzle. The water is atomized at the nozzle. All nozzles should not drip
and show an even spray pattern.
Further tests:
All electrically-powered functions must function.
» Observe LPS nozzle system and let it run for 15-30
minutes. The air conditioning duct fan should be in ope­ration so that the moisture produced can be blown away. Should any leakages be evident then turn the LPS nozzle system off.
» Eliminate the leaks: Attention, voltage! Please observe all safety instructions while
working on live components.
Page 49
Page 49
13. Maintenance
The HygroMatik nozzle system LPS is maintenance-friendly. However, operational faults which can be traced back to inade­quate or improper maintenance may occur.
Regular maintenance of the HygroMatik nozzle system LPS is indispensable for ensuring long service life.
Caution: For maintenance work please bear in mind that:
the system must be serviced by qualified appointed staff
only;
safety instructions must be followed;
the system must be taken out of operation and secured to
prevent it from being switched (take the plug out of the socket) on before maintenance work is performed;
after maintenance work has been completed the device
must be inspected by qualified staff to determine whether it is safe to operate.
13.1 Maintenance activities
For the system to operate without any problems the following checks and maintenance tasks must be carried out regularly:
1 x per month:
» Check housing for contamination and clean if neces-
sary.
» Carry out a visual inspection of droplet separators and
clean if necessary.
» Check the water filter cartridge upstream of the pump
for contamination and replace if necessary; flush the mains water system if necessary.
» Check the resulting spray cone of the nozzles and
clean or change nozzles if necessary.
1 x per year (or after 2500 h)
» Nozzles should be checked as part of annual mainte-
nance and cleaned if necessary (see "Cleaning nozzle).
If required, the nozzles to be replaced. » Water filter cartridge change » Visual inspection of the vortex module wall, if necessary
clean. » Check shutdown function, such as a "Max-Hygrostat".
Page 50
Page 50
13.1.1 Inspection / replacement of the net-based
water filter
Water filter check
Water filter must be checked for cont amination 1 x monthly and if necessary replaced. If the white water filter cartridge changes its colour this means it is polluted.
Pollution causes a higher flow resistance. This reduces the water pressure at the pump. Too little pressure can cause the nozzle system to switch off (dry-run protection).
Replacing the water filter:
1
2
3
1. Filter housing holder
2. Filter cartridge (inside­ lying
3. Filter housing
4. Mounting plate
4
Page 51
Page 51
1. Set the main switch on the control panel of the HygroMatik nozzle system LPS to '0'.
2. Close the (external) stopcock.
3. Relieve the line pressure.
4. Open the filter housing by hand. The threads may be dam­aged if pliers are used.
5. Clean the filter housing.
6. Replace the filter cartridge (if necessary).
7. Screw the filter housing into the seat by hand. Note: Do not pinch the sealing ring.
8. Open the external stopcock.
9. Set the main switch to 'I'.
13.1.2 Cleaning the atomizer nozzle
1. Switch the HygroMatik LPS Nozzle System power supply to 0
2. Unscrew the nozzle from nozzle holder. Take care not to touch the impact pin.
3. Unscrew the nozzle by screwing the inside part out.
4. Clean the nozzle components in an ultrasonic bath for about 10 minutes, if necessary use a lime remover in low concentra­tion (less than 10%).
5. Put nozzle components back together.
6. Screw nozzle in the nozzle holder.
7. Switch power switch back to I
8. Finally check spray pattern
Caution: Make sure that the pressure reduces by, for instance, activating the wash cycle.
Caution: Wear eye protection when cleaning the nozzle.
Caution: Use only an appropriate tool to remove the nozzles.
Page 52
Page 52
13.1.3 Cleaning the droplet separators
The droplet separators should be checked every 4 weeks for possible contamination and cleaned if necessary. The droplet separators should be thoroughly cleaned at least once a year.
13.1.4 Cleaning the vortex module wall
The vortex module wall should be checked for contamination and damage as part of annual maintenance. Any contaminants must be removed with a cleaning agent.
Cleaning the droplet separators:
1. Pull or lift the droplet separators out of the guide rails.
2. Clean the droplet separators with a cleaning agent and then rinse and dry them.
3. Carry out a visual inspection of the droplet separators, repeat the cleaning step if necessary and replace the droplet separa­tors if damaged.
4. Place the droplet separators back on the guide rails. While doing so ensure that the trap frame drain holes are facing down­wards to guarantee free drainage.
Page 53
Page 53
13.1.5 Cleaning the humidification chamber
Clean the humidifier housing and the base tray as required with a cleaning agent, then rinse and dry them.
For cleaning and disinfection we recommend INCIDUR pro­duced by Ecolab.
When using other cleaning and disinfection agents please check material compatibility with all plastic materials used in the humid­ification chamber.
Caution: Do not aim the water jet at the droplet separators. Any upstream or downstream heating or cooling units must not become wet during cleaning.
Page 54
Page 54
14. Control System
14.1 Control and speed regulation
The electrical components and terminals are located in the system cabinet under the removable cover. A programmable logic controller PLC (Item 1 in the illustration below) is responsible for the control function.
Important operating data are depicted in the control system display. A frequency inverter (Item 2) supplies different frequencies and voltages for the asynchronous motor of the pumping station located in the lower part of the system cabinet.
Depending on the speed of the pump, it is possible to vary the water pressure and thereby the quantity of water atomized. The water pressure may range between 5 and 16 bars.
The main switch (Item 3), which is located at the top left-hand side, is for switching off the HygroMatik low-pressure nozzle system LPS.
HygroMatik low-pressure nozzle system LPS
2
3
1
Page 55
Page 55
14.1.1 Full load and part load
The HygroMatik low-pressure nozzle system LPS is controlled by a 0-10V control signal.
In the 5-10V range, all the nozzles are charged with pressurized water. If the control signal falls below a value of 5 volts, the system switches to part load operation. In this case, approx. 50% of the nozzles are no longer supplied with water. The rotary vane pump then works with a higher pressure, whereby an improved spray pattern is produced.
14.1.2 Summer / winter mode
The HygroMatik low pressure nozzle system can be operated in summer or winter mode.
In winter mode, the HygroMatik low pressure nozzle system is used to regulate air humidity, whereas summer mode is used for exhaust air cooling.
Changeover between summer and winter modes is made by potential-free contact between connecting terminals 6 and 7:
Contact open = Winter mode Contact closed = Summer mode In summer mode, regulation of the HygroMatik low pressure
nozzle system LPS is made solely by means of the safety chain (Terminals 1 and 2) in single-stage switching mode; as long as the safety chain is closed, the system operates at 100% humidification performance.
Page 56
Page 56
14.2 Description of the programmable
controller (PLC)
14.2.1 General description
The HygroMatik low pressure nozzle system LPS controller regulates the complete atomizing operation. The user interface for operating and regulating the function of the appliance is on the face of the PLC controller.
Functions of keys:
(F1): - increase value
- to the next identifier
(F3): - decrease value
- to previous identifier
(F2): - exit without saving the setting
- return to previous level
(F4): - confirm value / exit and setting save
- to the next level (select menu, submenu, parameter, value)
- select reading level
Page 57
Page 57
Functional description of the display and LED:
The display consists of 14 icons in 3 categories:
1. Operating modes
2. Values and dimensional units
3. Switching states
Icon Description Color
Error red (Error codes F1...F8 are displayed;
detailed description see below)
Summer mode green (cooling)
Winter mode green (humidify) No demand green
(the safety chain is closed, the demand is however below the activation threshold)
Pressure [bars] red
Relative humidity [%] red
Control signal error red
(control signal wrong or missing ­humidification is interrupted)
Page 58
Page 58
Description of switching states:
Condition Description LED color
1 Mode (nozzle system operating) orange 2 Maintenance/fault orange 3 Magnetic valve drain enabled orange 4 Magnetic valve full load enabled orange 5 Magnetic valve water inlet enabled orange 6 Magnetic valve winter mode part load
enabled orange
7 Magnetic valve summer mode full load
enabled orange
14.2.2 Menu
System start
After switching on the Hygromatik low pressure nozzle system LPS at the main switch, an initial flushing operation is carried out (default setting 10 sec.).
The system is then in the main menu, i.e. the actual pressure is displayed.
From here one can navigate to the reading level and read off current reading parameters (L1 ... L15) or to the programming level, where parameters can be set or changed.
A detailed description of the programming steps can be found in the following subsection "Menu structure and parameter setting”.
Page 59
Page 59
14.2.2.1 Reading level:
The following reading parameters can be selected in the reading level:
L01 Actual value of pressure [bars] L03 Actual value of the control signal L04 Setpoint control signal L05 Set value of performance limiter [%] L06 Set value for the target humidity (only valid
with PI control [%]
L07 Actual value of current humidity (only valid
with PI control [%] L11 Total running time of pump [h] L13 Total running hours [h] L14 Remaining running time before next service
reminder [h] L15 Remaining time until standby-draining [hh:mm]
14.2.2.2 Programming level:
The following parameters can be changed in the programming level:
Parameter Designation Option Factory setting U6 Controls 0 = external controller 0
1 = single-stage/ On-Off 2= PI control
L06 Setpoint rel. humidity 10-100% 50%
(only activ if U6=2) L05 Output limitation 25-100% 100% r_S Reset „Service” message ON/OFF OFF C12 Integral part, 50-500 100
with PI humidity controller C11 Proportional part, 50-200 100
with PI humidity controller E03 External control signal 4 = 0-10V DC 4
3 = 4-20mA DC
Page 60
Page 60
14.2.2.3 Operation
If the HygroMatik low pressure nozzle system LPS is enabled, (i.e. the safety chain is closed) and a control signal greater than the activation threshold is put in, the system atomizes water.
The LED 1 for status "Operating" is illuminated. At the same time the current working pressure in bars is shown
on the display. In addition, the topmost line of the display shows whether the
HygroMatik low pressure nozzle system LPS is operating in summer or winter mode.
14.2.2.4 Function of the safety chain
It is possible to read off from the main display window whether the system is enabled for operation. It is essential that a potential-free normally closed contact for enabling (= closing the safety chain between terminals X2.1 and X2.2) is provided on site. Here, several safety contacts (NO / NC) can be connected in series.
No demand:
Should the PLC controller show the safety chain is closed, however the requirement is below the activation threshold.
There is no demand for humidification.
Ready for use:
If is not displayed and if the display indicates 0.0 bars the safety chain is open (terminals X2.1 and X2.2 are not bridged).
The HygroMatik low pressure nozzle system LPS is ready for use.
14.2.2.5 Accumulated malfunction
If a fault is detected in the HygroMatik low pressure nozzle system LPS by the controls, the dedicated changeover relay is de-energized (terminals X2.28-30 NC, terminals X2.29-30 NO). Simultaneously a specific error report (F1 ... F8) is shown in the
display and the icon is illuminated red. The HygroMatik low pressure nozzle system LPS is deactivated. If no fault exists, the changeover relay is energized. You will find a detailed description of the errors and their
possible elimination in the following table.
Page 61
Page 61
14.2.3 Overview of error reports
Fault No.
Malfunction report
Description Possible cause Remedial action
F1 Water inlet
Pressure < 1bar
Water supply inadequate. Inlet pressure must be between 1 to 5 bars.
Water supply not connected.
Connect water supply with adequate pressure.
F2 Temperature
in control cabinet
The temperature sensor in the control cabinet is recording a temperature in excess of 50°C +/­10%
The ventilator in the control cabinet failed
Air inlets blocked
Check ventilator and replace if necessary
Clean out air inlets
F3 FU
defective
Frequency inverter reports a malfunction. This is shown in the frequency inverter display.
Overload of motor Motor cable short
circuited Fault in electronics
frequency inverter Earthing fault of output
terminals
For remedial action please observe the instructions in the documentation for the frequency inverter.
F4 Motor
winding
Temperature control of the motor winding activated due to excess temperature.
Failure of external ventilator
Air inlets of the external ventilator blocked.
Check external ventilator and replace if necessary.
Remove blockage
F5 Low
pressure
No pressure can be built up after activating the rotary vane pump for 30 seconds
Pressure pipe leaking Water deficiency Signal cable pressure
sensor not connected
Check pressurized water pipe and replace
if necessary
Check cable connection and correct
F6 Excess
pressure
The supply of pressurized water exceeds a pressure of 16 bars for 30 seconds
Nozzles blocked Pressure-relief valve
not set correctly
Clean nozzles or replace
Please contact HygroMatik
F7 Sensor fault
pressure
The value of the pressure sensor is outside the normal range
Pressure sensor defective
Burst pipe
Replace pressure sensor
Renew pipe
F8 Sensor fault
humidity
The value of the humidity sensor fitted (optional) is outside the normal range
Humidity sensor defective
Burst pipe
Replace humidity sensor
Renew pipe
Page 62
Page 62
14.2.3.1 Menu structure and parameter setting
4
3
Page 63
Page 63
15. EC declaration of conformity
Page 64
Page 64
16. Spare parts
Article no. pump station
E-7800100 Motor LPS s
y
stems, 230V, 0,37kW
E-7800202 Rotar
y
vane pumpe LPS-100; LPS110
E-7800204 Rotar
y
vane pumpe LPS72
E-7800206 Rotar
y
vane pumpe LPS45
E-3720010 fan, axial, 230VAC
E-7702200 protection grill, cabinet fan HDS, incl. filter inlay 120 x 120 mm B-7800400 Solenoid valve water inlet, incl.
p
ressu re switch 1b a
r
E-7800300 3/2 Solenoid valve, incl. coil 230V/50-60Hz E-7800310 Plu
g
for solenoid valve
E-7800610 High pressure sensor LPS
E-7800436 pipe fitting G3/8, 12mm hose E-7800438
pip
e fitting G3/8, 90°, turnable, 12mm hose
E-7800416
pip
e fitting G1/8, 6mm hose
E-7800444 female pipe fitting G1/8, 6mm hose
E-7621028
Filter element 10" filter quality 10 µm for water-prefilter HP­pumpstation
E-7705200
Water filter housing, 10" bothside connection 3/4" iD blue sump,
p
ressure release button
B-2504021
A
uxiliary relay 230V AC 2 switching contact
E-2505206 Safety fuse 1,6A 5x20mm E-2504039 Safety fuse 1,6A 5x20mm
E-7704870
Thermal circuit breaker ; NC with automatic reset, switching point at
50°C ± 5
K
E-7800544 Transformer 230V/12V 11V
A
E-7800500 Frequenzy converter 0,37kW
E-7800540 Display CPU unit
E-2501005 main contactor 16A(AC1)coil 230V AC
Page 65
Page 65
Artikel -Nr . Article no.Vortex-wall
E-770 1000 E-770 1000 Vortex module E-780 0400 E-780 0400 LPS wa ter distributi on tub e E-7601630 E-7601630 T-
p
iece female 1/8"
E-760 1586 E-760 1586 Double ni
pp
le G1/8" - G1/8"
E-780 0410 E-780 0410 Sealing plug M5 E-780 0412 E-780 0412 Sealing plug male 1/8"
E-7800414 E-7800414 Pipe fitting M5, 4mm hose E-7800416 E-7800416 Pi
p
e fitting G1/8, 6mm Hose
E-7800472 E-7800472 Fixin
g
cli
p
E-7800452 E-7800452 Mountin bracket for nozzle
E-7621020 E-7621020 O -ring for nozzle mounting bracket E-7800450 E-7800450 Nozzle HY 0,27/120°
E-7800454 E-7800454 Nozzle HY 0,27/60° E-7601572 E-7601572 O-Rin
g
, 10 x 1.5, 70° Shore
E-7800424 E-7800424 Pipe fitting male 1/8", 90°, turnable, 4mm hose E-7800428 E-7800428 Hose PA, 6mm
E-7800426 E-7800426 Hose PA, 4mm B-780 0301 B-780 0301 LPS duct inlet fittin
g
Page 66
Page 66
17. Fax Form - Order for spare parts
Lise-Meitner-Str. 3
24558 Henstedt-Ulzburg
Tel. +4904193/895-0
Order of spare parts
unit type *______________ serial no.* ___________________
commission: ______________ order no.: __________________
date of delivery ____________forwarder _____________ shipment by ___________ delivery address (if different
from invoice address)
__________________________ __________________________ __________________________ __________________________
* Order can only be processed if unit type and unit serial no. are filled in.
quantity article article no.
Fax Form
Please copy, fill in and fax to
Fax.No. +49(0)4193/895-33
company stamp (delivery adress)
date/signature
Page 67
Page 67
18. Technical Specifications
LPS 45 LPS 72 LSP 110
Effective humidification capacity [l/h] 45 72 110
Nominal power rating [kW] 0,15 0,16 0,18
Amps [A] 1,9 2,1 2,7 Volts [V/Ph/Hz] 230/1/50 Control signals 0-10V / 4-20mA
(other control signal levels on request)
Nozzle number 15 22 32
Humidification path, ideal [m] 0,9
Installation lenght, ideal [m] 1,5
Flow velocity [m/s] 0,9 - 2,8
Pressure drop in duct [Pa] 80 at 2.0m/s air speed
Dimensions H, D, W [mm] 700, 230, 600
Weight [kg] 30
D
W
H
Page 68
Page 68
19. Plant scheme
Lise-Meitner-Str. 3 24558 Henstedt-Ulzburg Tel.: +49/(0)4193/895-0
Fax: +49/(0)4193/895-33
)UHLPDWROHUDQ]
JHP',1
'DWXP 1DPH
%HDUE *HSU 1RUP
=HLFKQXQJVQXPPHU
%H]HLFKQXQJ
%ODWW
YRQ
0DVWDE
*HZLFKW
5HY QGHUXQJ 'DWXP 1DPH
+<*520$7,.
0DWHULDO
7
 0DU
$QODJHQVFKHPD/36
PLWWHO
FU: Frequenzumrichter frequency converter
SPS: Speicherprogrammierbare Steuerung programmable logic controller
PID: Drucksensor pressure sensor
3ODQWVFKHPH/36
FU
SPS
PID
5 - 16 bar
VE-Wasser Deionised water
1 - 5 bar 5 - 20μs/cm
Pumpe pump
Wassereinlassfilter
water filter
MV
Wassereinlass-
Magnetventil
water solenoid
valve
PID
MV
MV
Spülmagnetventil
flushing solenoid valve
Volllast-Magnetventil
full load valve
Teillast
partial load
Option: Teil-/ Volllast part-/ full load
MV
MV
Spülmagnetventil
flushing solenoid valve
Winter Teillast-Magnetventil winter part load valve
Option: Sommer-/ Winterschaltung summer-/ winter contr ol
MV
Winter Volllast-Magnetventil winter full load valve
MV
Sommer Magnetventil
summer valve
A Blatt 2 eingefügt Mar
22.10.12
Lise-Meitner-Str. 3 24558 Henstedt-Ulzburg Tel.: +49/(0)4193/895-0
Fax: +49/(0)4193/895-33
)UHLPDWROHUDQ]
JHP',1
'DWXP 1DPH
%HDUE *HSU 1RUP
=HLFKQXQJVQXPPHU
%H]HLFKQXQJ
%ODWW
YRQ
0DVWDE
*HZLFKW
5HY QGHUXQJ 'DWXP 1DPH
+<*520$7,.
0DWHULDO
7
 0DU
$QODJHQVFKHPD/36
PLWWHO
FU: Frequenzumrichter frequency converter
SPS: Speicherprogrammierbare Steuerung programmable logic controller
PID: Drucksensor pressure sensor
FU
SPS
PID
5 - 16 bar
VE-Wasser Deionised water
1 - 5 bar 5 - 20μs/cm
Pumpe pump
Wassereinlassfilter
water filter
MV
Wassereinlass-
Magnetventil
water solenoid
valve
PID
MV
Spülmagnetventil
flushing solenoid valve
Option: Zuluftbefe uchtung 3-stufig humidification 3-step control
MV
MV
3ODQWVFKHPH/36
1. Stufe
1st step
2. Stufe
2nd step
3. Stufe
3rd step
A Blatt 2 eingefügt Mar
22.10.12
Page 69
Page 69
4
3
Page 70
12/2004
Lise-Meitner-Str.3 D-24558 Henstedt-Ulzburg Phone +49(0)4193/ 895-0 Fax -33 eMail hy@hygromatik.de www.hygromatik.com A member of the Group
Loading...