HydroMatik HeaterCompact User Manual

Page 1
Electric Heater Steam Humidifier
HeaterCompact
Installation yellow
Electrics red
Maintenance green
General Information white
ÁHC.EN0È
HC.EN
Manual
Page 2
Page 2
Warning, Hazardous Voltage: All work to be performed by trained personnel only. All electrical installation and servicing of the electrical components of this unit to be performed by qualified electricians only. Disconnect power supply before installation and servicing!
© Copyright HYGROMATIK GmbH; HeaterCompact 08.09.2015
Information in this manual is subject to change or alteration without prior notice.
Current version of this manual can be found at: www.hygromatik.co.uk
Page 3
Page 3
1. Introduction ....................................................................................................................... 5
1.1 Typographic Distinctions ...................................................................................................5
1.2 Documentation .................................................................................................................. 5
1.3 Directions for Use .............................................................................................................. 6
2. Safety Notes ....................................................................................................................... 7
2.1 Overview ........................................................................................................................... 7
2.2 Guidelines for Safe Operation ........................................................................................... 7
2.3 Disposal after Dismantling .................................................................................................8
3. Transport ............................................................................................................................ 9
3.1 Overwiew ........................................................................................................................... 9
3.2 Transport Size and Weigth ................................................................................................ 9
3.3 Packing .............................................................................................................................. 9
3.4 Interim Storage .................................................................................................................. 9
3.5 Check for Complete and Correct Delivery of Goods ......................................................... 9
3.6 Included in the Delivery ..................................................................................................... 10
4. Operation and Device Construction ................................................................................ 11
4.1 Mode of Action .................................................................................................................. 11
4.2 Installation and Method of Operation ................................................................................ 12
4.3 Internal Output Setting ...................................................................................................... 14
5. Mechanical Installation .....................................................................................................15
5.1 Steam Humidifier - environmental conditions .................................................................... 15
5.1.1 Equipment Dimensions HC ............................................................................................ 16
5.1.2 Fitting Measures ............................................................................................................. 18
5.2 Absorption Distance BN .................................................................................................... 19
5.2.1 Determining the Absorption Distance ............................................................................. 19
5.3 Fan Unit (option) ................................................................................................................ 21
5.3.1 Fan Unit Type VG ........................................................................................................... 21
5.3.2 Absorption Distance Nomogram .................................................................................... 23
5.4 Steam Manifold ................................................................................................................. 24
5.4.1 Notes on Installation ....................................................................................................... 24
5.5 Steam Line ........................................................................................................................ 28
5.6 Cover Plate ........................................................................................................................ 29
5.7 Drill Pattern ........................................................................................................................ 30
5.8 Condensate Hose .............................................................................................................. 32
5.9 Types of Installation .......................................................................................................... 32
5.10 Steam Solenoid Valves ................................................................................................... 34
5.11 Unit Installation Check ..................................................................................................... 34
6. Water Installation .............................................................................................................. 35
6.1 Water Quality ..................................................................................................................... 35
6.2 Water Supply (For Operation with Demineralized Water or Purified Condensate) ........... 36
6.3 Water Supply (For Operation with Tap Water or Partially/Fully Softened Water) ............. 37
6.3.1 Feed from Holding Tank ................................................................................................. 38
Page 4
Page 4
6.4 Water Treatment ............................................................................................................... 38
6.5 Water Discharge ............................................................................................................... 39
6.6 Checklist ............................................................................................................................ 40
7. Electrical Installation ........................................................................................................ 41
7.1 Electrical Installation .......................................................................................................... 41
7.2 Safety Interlock .................................................................................................................. 42
7.3 Control Connection ............................................................................................................ 43
7.4 Control Connection - Steam Bath Application ................................................................... 43
7.4.1 Temperature Sensor Connection ................................................................................... 43
7.5 Control Connection - Air Conditioning Application ............................................................ 43
7.5.1 1-step control .................................................................................................................. 44
7.5.2 Proportional Control with an external control signal ....................................................... 44
7.5.3 Proportional Control with Built-In PI-Controller .............................................................. 46
7.6 Cable Connections ............................................................................................................ 47
7.7 Fan Unit ............................................................................................................................. 47
7.8 Wiring Diagram .................................................................................................................. 48
7.9 Electrical Installation Checklist ..........................................................................................48
8. Maintenance ....................................................................................................................... 49
8.1 Maintenance for Operation with Demineralized Water / Condensate ............................... 50
8.2 Maintenance for Operation with Tap Water or Partially Softened Water ........................... 51
8.3 Access to Control Unit ....................................................................................................... 52
8.4 Removing and Cleaning the Steam Cylinder .................................................................... 53
8.5 Maintenance of the Control Cylinder ................................................................................. 58
8.5.1 Cleaning the nozzle in the steam hose adapter ............................................................. 58
8.6 Replacing Heater Elements ............................................................................................... 58
8.7 Replacing Thermo Sensor (for Heater Element) ............................................................... 59
8.8 Unlocking of a Released Thermo Sensor (for heater element) ......................................... 60
8.9 Unlocking of a Released Thermo Sensor (for Solid State Relay) ..................................... 60
8.10 Removing Inlet Solenoid Valve and Cleaning Fine Mesh Filter ...................................... 61
8.11 Cleaning Blow-Down Pump ............................................................................................. 62
8.12 Cleaning connection hoses and cylinder base ................................................................ 63
8.13 Checking Cable Screw Connections, Heater Element Wires .......................................... 64
8.14 Operational Check ........................................................................................................... 64
8.15 Dismantling ...................................................................................................................... 64
9. Commissioning ................................................................................................................. 65
10. EC-Declaration of Conformity ........................................................................................ 66
11. Spare Parts ...................................................................................................................... 67
12. Fax Form - Order for spare parts ................................................................................... 71
13. Index ................................................................................................................................. 72
14. Technical Specifications ................................................................................................ 74
15. Exploded View ................................................................................................................. 76
16. View of Cabinet ................................................................................................................ 77
Page 5
Page 5
1. Introduction
Dear Customer,
Thank you for choosing a HygroMatik steam humidifier.
HygroMatik steam humidifiers represent the latest in humidifica­tion technology.
They will impress you with their safety, ease of use and econo­mical operation.
In order to operate your HygroMatik steam humidifier safely, pro­perly and efficiently, please read these operating instructions.
Employ yo ur ste am hu midifier only in sound condition a nd as directed. Consider po tential hazards an d safety issues and fol­low all the recommendations in these instructions.
If you have additional questions, please contact us:
Tel.: +41 (0)31 932 01 11 (Main Number)
Tel.: +41 (0)31 932 01 11 (T
echnical Support Hotline)
Fax: +441 (0)31 931 08 67
e-mail: info@badgermeter.ch
For all technical questio
ns or spare parts orders, please be pre­pared to provide unit type and serial number (see name plate on the unit).
1.1 Typographic Distinctions
preceded by a bullet: general specifications.
» preceded by an arrow: Procedures for servicing or
maintenance which should or must be performed in the indicated order.
Installation step which must be checked off.
italics Terms used with graphics or drawings.
1.2 Documentation
Retention
Please ret ain th ese o perating instruction s in a secure, alwa ys accessible location. If the product is resold, turn the documenta­tion over to the new operator. If the documentation is lost, please contact HygroMatik.
Versions in Other Languages
These operating instructions are available in several languages. If interested, please contact HygroMatik or your HygroMatik dea­ler.
Page 6
Page 6
1.3 Directions for Use
The proven principle of heating wa ter by the use of electric immersion heate rs is exploited to generate steam. Usin g diffe­rent t ap water q ualities or p artial softened water (all hu midifier types) or fully demineralized wate r / condensate water (only for humidifier type HeaterLine, HeaterCompact/Kit and HeaterSlim).
Warning: HygroMatik steam humidifiers emit steam with a tem­perature o f 10 0°C. Th e steam may no t b e inhaled directly. Proper usage also entails following HygroMatik's instructions for installation, dismantling, reassembly, initial operation and opera­tion and maintenance, as well as disposal procedures.
Only qu alified a nd authorised personnel may opera te the unit. Persons transporting or working on the unit , must have read and unde rstood the corre sponding p arts of the Operation and Maintenance Instruct ion and especially the chapter 2. „Sa fety Notes“. Additionally, op erating personne l must be informed of any possible dangers. You should place a copy of the Operation and Maintenance Instruction at the unit‘s operational location (or near the unit).
The steam humidifier is not qualified for exterior application.
Page 7
Page 7
2. Safety Notes
2.1 Overview
These sa fety notes are required b y law . The y p romote work­place safety and accident prevention.
Warnings and Safety Symbols
The safety symbols be low identify sections containing warnings about hazards or pot ential da ngers. Please fa miliarize yourself with these symbols.
Warning: Failure to o bserve this warning ma y result in serious injury or death and/or damage to the unit.
Danger, Hazardous Voltage: Hazardous electrical current!
Fai-
lure to observe this warning may result in injury or even serious injury or death.
Warning: Failure to follow these instructions may resu lt in damage to the unit due to electrostatic discharge. The electronic components of the humidifier control a re very sensitive t o elec­trostatic discha rges. In orde r to safeguard these components during installation and servicing, steps must be taken to protect against ESD.
Reminder: Materials and consumables must be handled and/or disposed of as required by law.
Note: App ears before explanations o r cross-refere nces which refer to other sections of the operating instructions.
2.2 Guidelines for Safe Operation
Overview
Obey all safety notes and warnings present on the unit.
In case of a malfunction, switch off the unit immediately and pre­vent a re start. Rep air malfun ctions promptly. Af ter any rep air work, h ave qualified personnel check t he safe operation of the unit.
Use original spare parts only. Additional national safety regulati­ons also fully apply to the operation of this unit.
This unit is not designed for the use by persons (also children) with limited physical, sensory and mental abilities - or without knowledge and experience. Unless they are supervised or trai­ned by a person, who is responsible for their safety. Supervise children in order to ensure that they will not play with the unit.
The unit is only allowed to work with connected steam hose that safely leads the steam.
Caution
steam
Page 8
Page 8
Accident Prevention Regulations
Attention: In t he e vent of leaky or faulty components un con-
trolled hot steam may flow.
HygroMatik steam humid ifiers a re IP20 -protected. Make sure that the unit is protected from drips in its installed location.
Installing a humidifier in a room without water discharge requires safety devices to protect against water leakages.
Accident Prevention Regulations
Comply with the Accident Pr evention Regulatio n Electrical Systems and Equipment to prevent injury to yourself and others.
Operation of the Unit:
Do not pe rform any work which co mpromises the safety of the unit. Regularly check that all sa fety and monitoring devices are functioning normally. Do not remove or disable safety devices.
Installation, Di smantling, Maintenance and Re pair of the Unit:
Disconnect unit components from power supply prior to mainte­nance or repair work.
Attaching or installing additional components is permitted only with the written consent of the manufacturer.
Electrical
Work on the e lectrical system must be p erformed by q ualified personnel.
Disconnect unit components from power supply prior to work.
It is not allowed to connect the unit to DC voltage supply.
In case of a malfunction in the electrical power supply, switch off the unit immediately. Use only original fuses with the appropriate amperage rating . Regularly check the unit's e lectrical e quip­ment. Promptly repair any damage, such as loose connections, burned wiring or defective electrical insulation. After proper elec­trical inst allation or repair, test all safety mechanisms (such as grounding resistance).
2.3 Disposal after Dismantling
Note: The operator is responsible for the disposal of unit compo-
nents as required by law.
Page 9
Page 9
3. Transport
3.1 Overwiew
Note:Proceed carefully when transporting the steam humidifier in
order to prevent damage from rough or careless loading and un­loading. If the transport of this unit is attempted by only one person there is a risk that the unit will drop down. We propose to transport the unit by two persons.
3.2 Transport Size and Weigth
* Dimensions and weigths can vary insignificantly
3.3 Packing
Note: Observe the symbols affixed to the box.
3.4 Interim Storage
Keep the unit dry and protect from frost.
3.5 Check for Complete and Correct Delivery of
Goods
Upon receipt of the unit, make sure that:
type and serial number on the name plate match what
is in the purchasing and delivery documents,
equipment is complete and in perfect condition.
Note: In case of damage during shipment and/or missing parts, immediately file a written claim with your carrier or supplier.
Type* depth
[cm]
higth
[cm]
width
[cm]
weigth
[kg]
HC02 33 47 46 14 HC03 36 65 51 16 HC06 36 65 51 16
HC09 36 65 51 16 HC06P 41 78 59 25 HC09P 41 78 59 25
HC12 41 78 59 26
HC18 41 78 59 26
HC27 41 78 59 27
Page 10
Page 10
Time limits for filing freight claims with shipping companies are*:
* Subject to change without prior notice.
3.6 Included in the Delivery
The delivery includes:
Unit of the selected humidifier type including selected con­trol.
Water installation hose.
Manuals for the steam humidifier and the control.
Ordered accessories (steam manifold, steam hose, con­densate hose, etc.).
Maintenance o-ring set for steam cylinder.
Transport Company After Receipt of Goods
Mail 24 hours at the latest Rail 7 days at the latest
Truck and railway compa-
nies
4 days at the latest
Parcel Service immediatly
Page 11
Page 11
4. Operation and Device Construction
4.1 Mode of Action
The Imersion Heater Principle
One to three heater eleme nts (Pos. 8 in the explo ded view, please see co ver foldout) a re pla ced in a close d cylin der and connected to a lternating current. The cylin der is filled with t ap water, fully demineralized water or partially softened water. Heat generated by the heater element increases water temperature to approx. 100°C.
When fully demineralized water is used, the feed water is practi­cally free of minerals. This ensures long life for the cylinder and heater elements since virtually no mineral deposits can settle or build up. Fully demineralized water minimizes the number of ser­vice / maintenance checks.
When tap water is used, some of the minerals dissolved in the water will settle in the cylinder as solids of various compositions. Most of these scale deposits are removed by periodic flushing or use of a h eavy-duty blow-down pump. See section "Se rvicing During Operation with Tap Water".
The gen erated steam has a temperatu re of abo ut 100°C and minimal po sitive pressure ("pressure less” steam). It is virtually demineralized and germ-free.
Page 12
Page 12
4.2 Installation and Method of Operation
By pressing the control switch („Pos. I”) the humidifier is turned on. Wh en th e hygrost at or controller signals a demand for humidification, the inlet solenoid valve (14) opens. The solenoid
valve is designed for pressures from 100 x 10
3
to 100 x 104 Pas-
cals (1 to 10 bar).
Water is fed into the cylinder.
The water level in the cylinder must be maintained within a spec­ified range. If the water level is to o high, the ellbow act s as a safety overflow for water drainage. If the water level is too low, it could cause the heat er elemen t (8) to overhea t. Th erefore, power supply to the heater element is shut off when water levels are too low.
The cylinder water level is controlled by a level control (27). The level control consists of a stainless steel cylinder with two float switches and three reed contacts. The float switches indicate the water level in the steam cylinde r: "Dry Run", "Humidification " and "Max. Level". The control capsule is pressure-equalized.
At the standard setting, the inlet solenoid valve (14) opens when the water level remains below “humidif ication” level for 10 sec­onds. The water level then rises again to “humidification” level.
The steam cylinde r consist s of a to p (16) an d lower (9) p art joined with a cylinder flange. The seal between the cylinder and cylinder base (11), as well as between the top and lower part of the cylinder, is maintained using an o-ring.
Page 13
Page 13
General survey
The heater elements are equipped with a mechanical high tem­perature sa fety. Th is mechanism provides a re dundant safety system in the event of excessively low water levels (“Dry Run”).
The cylinder water is periodically flushed out with a hea vy-duty blow-down pump (10).
Steam is fed into air-condition ing duct s through special steam hoses a nd steam ma nifolds. Under normal condition s, t his steam has virtually no heating effect on the air to be humidified. Accumulated condensate can be returned to the steam cylinder via a condensate hose.
Direct room humidification (without ducts) is performed using fan units (with blower and n ozzle). T he st eam g enerator is con­nected to the fan unit with steam and condensate hoses.
Page 14
Page 14
Steam lines in steam ba th cabin s employ special steam hoses and piping (if required). Accumu lated condensate is n ormally routed into the steam cabin. At a relative humidity of 100%, the supplied steam is used to heat the steam bath.
Warning: Leakage of the steam cylinder can cause a serious hazard, such as giving an electric shock.
Warning: During blow down hot wat er wit h a temperature of about 95°C is being drained. This can cause burns to the skin at direct contact.
4.3 Internal Output Setting
Continuous control of the HeaterCompact Type steam humidifier is achieved by proportional control of the heater elements. In this way th e hu midifier ca n be prop ortionally op erated across the entire output range of 5% - 100% nominal capacity.
Page 15
Page 15
5. Mechanical Installation
Warning: Installation of this unit should be performed by quali-
fied personnel only . HygroMatik accept no liability for d amage due to faulty installation.
Obey all safe ty instructions and wa rnings on the unit. Durin g installation the unit must be disconnected from its power supply.
Accessory equipment may not be installed on or in the unit with­out prior written co nsent from Hygro Matik. Otherwise the war­ranty is void.
Warning: If the installation of this unit is a ttempted by only one person there is a risk that the unit will drop down. We propose to carry out the installation by two persons.
5.1 Steam Humidifier - environmental con diti­ons
Note: When selecting the location for steam hu midifier installa-
tion, be aware of the following:
Ambient temperature must be between +5 and +40 °C.
Relative humidity may not exceed 80% RH.
Observe clearances specified in the diagrams below to
ensure adequate ventilation.
An Installation in a closed room requires aeration and if
neccessary temperature conditioning in order to reach the above mentioned environmental conditions.
HygroMatik humidifiers are not suitable for direct out-
door installation.
Install the steam humidifier as close as possible to the
steam manifold. Use only short lengths of steam and condensate hose to ensure optimal performance.
Hoses must be laid at a constant 5-10% grade to uni-
formly prevent sags and kinks.
The back surface of the steam humidifier heats up dur-
ing operation (to max. 70°C). Take care that the con­struction on which the unit is mounted is not made of temperature-sensitive material.
Place the steam humidifier so that the unit is easily
accessible with sufficient space to perform mainte­nance.
The unit’s protection class is IP20.
Page 16
Page 16
5.1.1 Equipment Dimensions HC
c
a
e
l
j
m
k
o
n
d
b
h
f
i
g
View from below
Rear view
View from top
Water inlet
Waste water connection
Steam outlet
Condensate inlet
Cable entries
Page 17
Page 17
HC02 HC03-09 HC06P-09P
HC12-HC27
a 390 562 707 b 394 427 490 c 260 257 306 d 320 382 445 e 351 513 657
f33 30 30 g 170 190 250 h48 35 50
i80 44 50
j 158 145 162 k 110 109 138
l 178 100 81
m 167 50 86
n43 56 56 o18 18 18
all dimensions in mm
General Survey
Page 18
Page 18
5.1.2 Fitting Measures
Wall Distance
Note: It is often advantageous to use existing water connections
(feed and drain) when selecting the steam humidifier.
Wall Mounting
Note: To function properly the steam humidifier must be installed
vertically.
Measures for drills for wall mounting please see table (measures d and e) in chapter „Equipment Dimensions”.If there is no suit­able wall, it is recommended that th e equipment is inst alled on brackets which can be embedded in the floor.
(all dimensions in mm)
B
B
Page 19
Page 19
5.2 Absorption Distance BN
The "ab sorption d istance" (BN) is defined as the dist ance from the steam feed to where the steam is completely absorbed in the
treated air. W ithin the ab sorption d istance, steam is visible as mist in the air stream.
Condensation ma y occur o n anythin g inst alled within the absorption distance.
Although st eam outside th e absorptio n dist ance (B
N
) is com-
pletely absorbed, it is not yet evenly diffused in the duct. If you plan to inst all a ny p arts or device s in side the a bsorption dis­tance, such a s sensors or elbows, we recommend increasing the absorption distance using the formulae below. The absorp­tion dist ances required for certain in stalled fittings are distin­guished by separate symbols a nd calcula ted a s a multiplier of the absorption distance B
N
.
The absorptio n dist ance has no fixe d value, but depe nds on many factors. T hese are dep icted in th e absorptio n dist ance nomogram below.
5.2.1 Determining the Absorption Distance
To determine the absorption distance, the following parameters are required:
Air humidity before humidification x
1
in g/kg.
Air temperature after humidification t
2
in °C (with steam
humidifiers the change in air temperature due to humid­ification may be disregarded t
1
or t2).
Specific increase in humidity x in g/kg (can be deter­mined in the h,x diagram)
quantity of steam introduced in kg/h.
air speed w
L
in m/s in air duct
Total length l
D
of the steam manifold installed in the air
duct
Absorption Distance
B
N
for normal obstructions, such as se n­sors, ventilators, outlets
B
c
= (1,5...2) x BNfor fine filters, heat registers
B
s
= (2,5...3) x BNfor particle filters
B
d
= (2,5...3) x BNfor humidity sensors, duct humidistats
o
D
m
Page 20
Page 20
Length ID of the usable steam manifold depends on the dimen­sions of the air duct. Th e length of the absorption distance can
be reduced by using multiple st eam manifolds (also see section on the steam manifold).
Method:
Graphically determine absorption distance B
N
using the absorp-
tion distance nomogram (also see Section „Absorption Distance Nomogramm“). Enter the va lue of the p arameters enumerated above into the respective quadrants. The resulting point of inter­section ind icates the value of the desired absorption dist ance B
N
.
Notes:
x
1
: _______________________________[g/kg]
t
2
: _______________________________[°C]
x:_______________________________[g/kg]
:_______________________________[kg/h]
w
L
: _______________________________[m/s]
l
D
: _______________________________[mm]
Air humidity before humidification
Air temperature after humidification
Specific increase in humidity
quantity of steam introduced
air speed t
Total length of the steam manifold
o
D
m
Page 21
Page 21
5.3 Fan Unit (option)
Note: The fan unit shou ld be positioned to avoid drafts. A mini-
mum height of 2 m is generally sufficient.
Install the fan unit directly on a wall.
Warning:
During operation and some time afterwards the steam nozzle is hot! This can cause burns to the skin at direct contact.
During operation the cross-flow fan rotates. Do not touch the fan during operation.
During operation hot steam discharges from the nozzle. In the field of the visible steam cloud contact can cause burns to the skin.
During operation the cross-flow fan rotates. Do not touch the fan during operation.
5.3.1 Fan Unit Type VG
The fan unit is installed above the steam humidifier.
When using multiple fan units, do not exceed a maxi-
mum distance of 5 m from the steam humidifier.
Observe the clearances specified in the diagrams below.
Type Fan Unit
HC02,HC03 HC06(P)
VG 08
HC09(P), HC12
VG 17
HC18 - 27 VG 30
(all dimensions in mm)
Page 22
Page 22
Fan unit, wall installation
Side view, wall-mounted fan unit
Technical Specifications Fan Unit VG Fan Unit VG08 VG17 VG30
Quantity of Steam [kg/h] 8 17 30 Steam Inlet [mmφ]25 25 40 Condensate Outlet [mmφ]12 12 12 Airflow Capacity [cbm/h] 150 185 350 Nominal Output [W] 26 35 67 Nominal voltage [V] 230 230 230
Dimensions W [mm] 441 507 550
H [mm] 171 171 171 D [mm] 180 237 277
Weight [kg] 3.6 6 7 Sound Level (1m dis-
tance to th e sou rce of noise)
[dB(A)] 52 54 57
Page 23
Page 23
5.3.2 Absorption Distance Nomogram
Source: Henne, Erich: Luftbefeuchtung (Air Humidification), 3rd Edition 1984 (Page 101), Olden­bourg Industrieverlag, Munich
Page 24
Page 24
5.4 Steam Manifold
5.4.1 Notes on Installation
These notes are based on a homogeneous
Standard steam manifold installation:
An even distribution of steam manifolds ensures a uniform steam distribution. Please use the total hight of the duct!
Minimum distances in order to avoid condensation:
L
min = 210mm: distance „ steam manifold - next ste am mani-
fold“
L4
min = 120mm: distance „lowest steam manifold - duct bot-
tom“:L5
min = 120mm: distance „highest steam manifold - duct
ceiling“Installations depending on special designs of air ducts:
Horizontal installation of steam manifold
Steam Manifold
L1=L2=L3
Duct
Steam Manifold
Air flow
Air flow direction
Page 25
Page 25
Steam manifold
placement:
Horizontal installation of the steam manifolds is preferred. Howe­ver, installation from below into the air duct is possible.
Air duct Positioning of steam manifolds Sample
flat Staggered vertically and laterally
Air flow
very flat By tilting t he steam manifo ld 30 - 45°
towards the air flow directio n, the mini­mum upper clearan ce ca n be reduced to 70mm.
min. distances: H1[mm] H2[mm]
30° 45°
DN25 182 168 225
DN40 193 179 230
very flat duct
narrow, high Identical lenghts one on top of the other.
Staggered laterally if possible.
square Identical leng hts, st aggered vertically
and laterally
low, very wide
facing each other
Vertical installation of steam manifold
Page 26
Page 26
Note:
Install the steam manifold horizontal with it ensure a clean
steam out.
Maximum allowable pressure in the air duct is 1200 Pa.
On the return side, th e ma ximum allowable nega tive air
pressure is 500 Pa. Placeme nt of the steam manifold on the supply side of the air duct is preferred.
With high-pressu re air-cond itioning systems, the un it's
drain ho se system must be modified depending on the over p ressure. W hen this is the ca se please consult HygroMatik.
Install t he steam m anifold as c lose as p ossible t o t he
steam humidifier in orde r to minimize steam loss t hrough condensation.
Depending on the design of the air duct, additional moun-
ting of the steam man ifold may be required. Shown instal­lation and position dimensions are based on experimental values. S pecial environment al con ditions could re quire adjustments.
We note that th e German Association of Engineers (VDI)
Guideline 6022 specifies a water drain within the absorp­tion distance inside the air duct.
For steam ba th ap plications: Install the ste am manifold
safe from contact with people in order to prevent injuries or burns. Do n ot install the steam manifold near a tempera-
ture sensor or inaccurate readings may result.
Air flow rates o ver 3m/s can possibly lead to conden sate
drainage problems at the steam ma nifolds which may require adaptation measures.
Length of steam manifold [mm]*:
* special lenght on request
Note: At len gths of 600 mm or mo re, st eam manifolds are shipped with an extra alternative mounting fixture (Nut, M8) on the closed end.
l 220 400 600 900 1200 1450
DN25xxxx x x
DN40xxxx x x
Page 27
Page 27
The nu mber and size of appropriate steam manif olds, as well the no minal wid th of the ir respective ste am a nd conden sate hoses, are found in the tables below.
HyLine:
CompactLine:
HeaterCompact/Kit:
CompactLine Kit:
HeaterLine:
* For units HL 6 - 12 and HC3-12 HygroMatik delivers one adapter DN40 / 25 (but not for SPA applications)..
** For units HL 36 - 45 HygroMatik delivers one t-connector for separating the steam on two steam manifolds.
Type Steam Manifold Stea m Hose Condensate hose
HY05-HY17 1xDN25 DN25 DN12
HY05DS - HY17DS (for SPA)
1xDN40 DN40 DN12
HY23-HY30 1xDN40 DN40 DN12
HY45-HY60 2xDN40 2xDN40 2xDN12
HY90-HY116 4xDN40 4xDN40 4xDN12
Type Steam Manifold Steam Hose Condensate Hose
C01-C17 1xDN25 DN25 DN12
C10-DS, C17DS (for SPA)
1xDN40 DN40 DN12
C22, C30 1xDN40 DN40 DN12
C45** 2xDN40 DN40 DN12
C58 2xDN40 2xDN40 2xDN12
Type Steam Manifold Steam Hose Condensate Hose
HC02/Kit 1 xDN25 DN25 DN12
HC03-12* 1xDN25 DN25 DN12
HC03-12/Kit 1xDN40 DN40 DN12
HC16-27/Kit 1xDN40 DN40 DN12
HC3-27 (for SPA) 1xDN40 DN40 DN12
Type Steam Manifold Steam Hose Condensate Hose
C01 Kit - C06 Kit 1x25 DN25 DN9
C10 Kit - C17 Kit 1x25 DN25 DN12
C22 Kit / C30 Kit 1x40 DN40 DN12
C45 Kit 2x40 DN40 DN12
Type Steam Manifold Steam Hose Condensate Hose
HL 6-12 * 1xDN25 DN25 DN12
HL 6-12 (for SPA)
1xDN40 DN40 DN12
HL 18-30 1xDN40 DN40 DN12
HL 36-45 ** 2xDN40 1xDN40 1xDN12
Page 28
Page 28
5.5 Steam Line
Note: Whe n inst alling the steam hose, please pay att ention to
the following:
The steam hose diameter may n ot b e smaller than the
steam ou tlet of th e HygroMatik steam humidifier (do not restrict the cross-section , otherwise back pressu re will increase).
The steam hose must be without sags and kin ks and be
laid with a continuous slope of 5-10% (otherwise sags will be formed).
The steam hose should be as short as possible. In case of
lengths of over 5 m the hose should be insulated to avoid excess condensation.
In the case that steam o utput is distributed on two steam
manifolds the Y-pieces for the steam and condensate hose should be installed near the manifolds. If the installation is carried out in this way only one st eam hose is necessary for the main part, loss of condensate will be decrease d. If the inst allation is carrie d out in th is way only o ne steam hose is necessary for the main part, loss of condensate will be d ecreased. In deviation of this the y-piece tha t is delivered ex works with a humidifier type C45, HL36, HL45 should be installed near the humidifier.
Depending on how the hose is laid, hose clips should be
set at intervals of approx. 500 mm.
Allow access to the steam hose, so th at it ca n be inspec-
ted later.
In case of straight lengths of several me ters, it is recom-
mended to pla ce the steam hose in temperature resistant plastic pipe (40 mm dia for hose DN25; 60 mm dia for hose DN40) or to use copper pipe.
Device outp ut, steam line inst allation, a nd th e duct influ-
ence pressure condition in the duct. In an exeptional case this could mean to optimize ths steam line installation.
Only genuine HygroMatik hoses are capable of withstan-
ding the operating conditions. Allow for minimum bending radii: Steam hose DN 25: Rmin = 200 mm Steam hose DN 40: Rmin = 400 mm
Page 29
Page 29
5.6 Cover Plate
HygroMatik flange plates may be used to neatly complete instal­lation of the steam humidifier in the air duct.
Two-piece flange plates are ava ilable for the DN2 5 and DN40 steam manifolds.
flange plate DN25 E-2604260
flange plate DN40 E-2604410
Page 30
Page 30
5.7 Drill Pattern
Drill Pattern DN25 (not to scale)
Note: Due to variable print med ia the dimension s are not to
scale.
Page 31
Page 31
Drill Pattern DN40 (not to scale)
Note: Due to variable print med ia the dimension s are not to
scale.
Page 32
Page 32
5.8 Condensate Hose
Note: When inst alling the conden sate hose, please pay atten-
tion to the following:
Warning: To ke ep cond ensate from accumula ting in the duct, make sure condensate can drain freely.
If the s team m anifold i s positio ned hig her than 5 00 mm above the steam humidifier:
» Remove the condensate plug (12) from the connection
fitting on the cylinde.
» Lay the condensate hose at an approximate incline of
5-10% to the steam cylinder connection fitting, to allow the condensate to drain freely.
Note: It is recommended to form a loop of 200 mm diameter as a vapour trap provided there is enough space. Possible operat­ing n oises can be re duced in t his manner. The loop should be filled with water before commissioning.
If the ste am ma nifold is position ed lower than 5 00 mm above the steam humidifier:
» The condensate must be drained separately.
» To prevent steam loss, lay a loop at least 200 mm in di-
ameter. The loop should be filled with water before commissioning.
» To ensure condensate drainage, place the loop (vapor
trap) as far away as possible below the steam manifold connection.
» The condensate connection on the steam cylinder must
be closed with a sealing cap.
» Place hose clamps at intervals of at least 500 mm, de-
pending on how the hose is laid.
5.9 Types of Installation
If the s team m anifold i s positio ned hig her than 5 00 mm above the steam humidifier:
» Lay the steam hose at a height of at least 400 mm
above unit and then connect to the steam manifold with a constant rise or fall.
» Lay condensate hose with a slope to the steam cylin-
der.
Page 33
Page 33
» If enough space is available, lay a loop as a vapor trap.
The steam manifold must be at least 500 mm from the loop.
If the ste am ma nifold is position ed lower than 5 00 mm above the steam humidifier:
» Lay steam hose at a height of at least 400 mm above
unit and then connect to the steam manifold with a con­stant fall.
» Lay condensate hose with a loop of 200 mm diameter
(vapour trap) to the drain. The distance between vapour trap and steam manifold should have at least 500mm.
» Lay the loop of condensate hose 200 mm directly
above the drain. Detail x
Page 34
Page 34
5.10 Steam Solenoid Valves
When humidifying a number of loads, which are to be controlled separately, using a sin gle steam hu midifier, steam solenoid valves can be included in the steam hoses. Valve control has to provided by the customer.
Install the vertical risers with flow from bottom to top.
The best position is just above the steam humidifier.
Installation of Steam Solenoid Valve
5.11 Unit Installation Check
Attention: This unit may only be operated by qualified and prop-
erly trained personnel.
Please check the installation using the following list:
Does unit hang vertically?
Are wall distances to the unit within the range
Does steam hose have a slope of 5-10%?
Is condensate hose installed with a loop of min. 200
mm?
Is steam manifold positioned correctly? Are all bolts and
clamps tightened?
Page 35
Page 35
6. Water Installation
Warning: For installation, note the following:
Have all work performed by a professional.
Disconnect power supply prior to installation.
Obey regulations of local public utilities. Verify that neces-
sary saf ety me asures have been t aken - in compliance with either German Technical and Scientific Association for Gas and Water (DVGW) guidelines (DIN EN1717) or local regulations - to eliminate backflow of pollute d wa ter into drinking water treatment facilities. This can mean installing a system sep arator an d a fre e discharge in the drainage system. W ithin the h umidifier, two do uble check valves (58) are located in the water supply lines. They prevent - in accordance with DIN EN 61770 - the backflow of water.
The water supply temperature may not exceed 40 °C.
Flushed-out water must be able to drain freely.
The water supply line must have a minimum diamet er of
DN 12 (3/8").
If (chemical) ad ditives are pre sent in th e humidification
water, health risks and/or imp aired unit opera tion cannot be ruled out. Use of additives is not advised unless specifi­cally recommended by the unit manufacturer.
When employing demineralized water or purified conden-
sate, do not use copp er or brass in the supp ly or drain lines of the HeaterCompact u nit. These materials ca n be corroded by demineralized wate r or pu rified condensate. Instead, use st ainless stee l or temp erature-resistant pla­stic pipes.
Water in stallation pre ssure: 1 to 10 ba r (10 0x10³ to
100x10
4
Pa)
For water inst allation ple ase use the water connecting
hose that is delivered with the unit.
6.1 Water Quality
The HeaterCompact Type steam humidifier is designed for use with:
tap water of different qualities up to 15°gH total hardness
demineralized water (min. conductivity 3µS/cm)
fully cleaned condensate (min.conductivity 3µS/cm)
partially or fully softened water
Boiling n ormal t ap water a lways pro duces lime. Lime deposits on the surface of the heater elements may reduce their lifetime. We recommend to use a water treatment device in order to pre­vent scaling.
In case of any questio ns regard ing water trea tment devices please contact HygroMatik.
Page 36
Page 36
6.2 Water Supply (For Operation with Demineral-
ized Water or Purified Condensate)
» Install a shut-off valve (AV) in the supply hose
» Install a water filter (WF) if the water quality requires it
» Make sure that a backflow preventer is installed in the
water supply line.
Note: Shut-o ff valve ( AV), wate r filter (W F) and backflow pre­venter are not provided by HygroMatik.
Install as follows:
» Check whether the valve strainer has been inserted in
the solenoid valve.
» Screw cap nut (Q) onto the supply connection. Tighten
by hand.
The supply connection protrudes from the intermediate tray.
Note: Excessive tightening will damage the threads.
» Slide 13mm inner diameter hose (SCH) over the pres-
sure clip (R) and secure with a hose clamp.
Page 37
Page 37
6.3 Water Supply (For Operation with Tap Water
or Partially/Fully Softened Water)
» Install a shut-off valve (SV) in the supply line.
» Install a water filter (WF) if water quality requires it. » Make sure that a backflow preventer is installed in the
water supply line.
Note: Shut-off valve (SV) and wate r filter (WF) are not supplied with the unit
» HygroMatik provides a water hose (56) with a cap nut at
both ends which can be used for water installation.
Install as follows:
» Screw and tighten th e cap n ut with it s inner seal ring
around the water su pply screw con nection t hat pro­trudes from the base.
Note: T ightening to o much will destroy the fitting . The va lve strainer must be placed inside the solenoid valve.
» Use a cap nut (interna l thread ¾“) with inner se al for a
customer-provided water installation.
Page 38
Page 38
6.3.1 Feed from Holding Tank
If a holding tank will be used to supply water, the „option sole­noid valve 0-1 0bar” must be ord ered. Make sure that th e feed height is at least 0.5 meter. If the height is less than 0.5 m, insert a feed pump or install the humidifier lower if possible.
6.4 Water Treatment
For water treatment system specifications, use the following
table. The figures below assume that the humidifier has been running for 24 hours at 100% output.
HeaterCompact Max. Water Consump-
tion in over24 h [l]
255 383 6 166
9 248 12 331 18 497 27 745
HeaterSlim Max. Water Consump-
tion in over24 h [l]
383
6 166 10 277
option: solenoid valve 0-10 bar
Page 39
Page 39
6.5 Water Discharge
Warning: Please pay attention to free a nd non-pressure drain-
age of the wate r! During blo w down up to 0,3 L/s is b eing drained. For wa ter discharg e, we recommend installation of a flexible water drain hose. Humidifier and waste water discharge must be on the same pressure level.
Please note:
Do not bend, shorten or lengthen the drain hose.
For the discharge line and drain pipe, select materials
temperature-resistant up to 95°C.
Install the water drain system as follows:
Install a drain hose 1 1/4 ", 250 -. 1000 mm long, into a pressure-free outlet according t o DIN EN 171 7. Please ensure that ascending vapor does n ot conde nsate on the humidifier`s housing.
Slide the drain hose over the pump discharge hose and secure to the cabinet drain connection.
A grounding clip is fixed on the inner surface of the cabinet drain connection.Slide the end of th e pump d rain hose onto this clip. During blow-down, the grou nding clip will be in direct cont act with the water and will conduct any residual currents which may appear away from the cabinet.
There is a 3mm-wide gap between the pump drain hose jacket and th e inn er surface of the cabinet dra in connection. If water collects on the base pla te, it will flow thro ugh this gap into the drainage system.
Type Drain Hose
HC 2-27
HS 3-10
1 x 1 1/4"
Page 40
Page 40
6.6 Checklist
Verify correct system installation using the checklist below:
Can flushed-out water drain freely?
Have all screws and clamps been properly tightened?
Is the water supply line properly flushed out?
Has the water installation been performed correctly?
Is the drainage system correctly installed?
Are the water supply and drain lines free of leaks?
Warning: Flush out the water supply line before connecting to the so lenoid va lve, espe cially wh en installing a ne w line. T his prevents dirt particles from damaging the solenoid valve.
Page 41
Page 41
7. Electrical Installation
Warning, Haza rdous V oltage! All work re lated to ele ctrical
installation may b e perfo rmed b y au thorized pe rsonnel o nly (electricians or professionals with equivalent training). The cus­tomer is resp onsible for checking qualifications.Warning, Haz- ardous V oltage! Do not connect the steam humidifier to the power grid un til after all inst allation work has bee n completed. Please obey all local re gulations concerning electrical inst alla­tion.
Warning: The electronic comp onents of the humidifier co ntrol are very sensitive to ele ctrostatic disch arges. In order to safe­guard these components during installation and servicing, steps must be taken to protect against ESD.
Warning: For installation, note the following:
Disconnect power supply prior to installation and secure
against restart.
Verify the absence of electric current.
Installation or removal of the display and control unit may
only be performed when the unit is switched off. See also section "Access to Control.”
Electrical connector cables must be wired by qualified per-
sonnel.
Install electrical connections as specified in the wiring
diagrams.
For units with power ratings over 33 kW, only a permanent
connection to a permanent installation is permitted (observe European Directives shown in chapter „EC Dec­laration of Conformity“).
Ensure that all terminals have been tightened.
We recommend to install a fault current circuit breaker.
7.1 Electrical Installation
» Breakers must have a contact gap of at least 3 mm per
pole.
» Each steam cylinder requires a separate main power
supply including main fuses, main breaker, etc.
» Connect potential equalization inside the unit to the
external ground bolt (located on the underside of the cabinet beside the cable connections).
Observe European Directives shown in chapter „EC Declaration of Conformity.
Page 42
Page 42
We recommend using a main f use with medium blow r ating (applies only to the mains voltages above.) See table below indi­cating maximum power consumption corresponding to each type of circuit protection:
The steam generator should be operated with a residual current circuit breaker (RCCB).
7.2 Safety Interlock
Between terminal 1 and 2 of the humidifier the so called safety interlock is located. If the safe ty interlock is not closed the humidifier is not allowed to work.
Any additional safety de vices (see be low) h ave to be installed between those terminals. The safety interlock is also used for an On/Off control mode (remote switch).
There is no jumper between terminal 1 and 2 ex works.
If neither a Remote Switch nor any safety devices are wired to terminal 1 and 2 an electrical bridge has to be set.
Note: Inst all co ntact interlo cks, i.e. max. hygrostat, vane relay, pressure controller, air interlock etc. in series between Terminals 1 and 2.
Warning: It is st andard practice for air-condition ing to in stall a max. hygro stat in the safety interlock (not valid for stea m bath applications). The ma x. hygrostat acts as a safety device in the event of a humidit y senso r malfunction and p rotects against overhumidification.
Warning: Contacts laid between Terminals 1 and 2 must be potential free and rated for 230V switches. Terminal 1 is supplied with 230V AC after switching on the humidifier.
Type Power Supply Power Con-
sumption
Fuses
HC02 230V/1Phases/N 6,5A 1x10A HC03 230V/1Phases/N 9,8A 1x10A HC06 230V/1Phases/N 19,6A 1x20A HC06(P) 400V/3Phases/N 11,3A 3x20A HC09(P) 400V/3Phases/N 16,9A 3x20A HC12 400V/3Phases/N 19,5A 3x25A HC18 400V/3Phases/N 29,3A 3x35A HC27 400V/3Phases/N 29,3A 3x35A
Terminals Humidifier
230V int.
Page 43
Page 43
7.3 Control Connection
Within the scope of this manual there is only a short descrip­tion of the „Adjustment of th e Control to th e Control Signal” at this point. More detailed information please find in the technical
manual for the co ntrol that is also delive red with the Heater Compact.
The Heater Compact is used in both applications for steam bath and air conditioning. As the Heater Compact is controlled via the temperature in steam bath applications and via the air humiditiy in air conditioning ap plications different typ es of controls are used. Therefore the descriptions of the Control Connections are also different:
7.4 Control Connection - S team Ba th Applic a-
tion
Valid for Controls: Basic-DS (B-DS), Comfort-DS (C-DS) und ComfortPlus-DS (CP-DS).
7.4.1 Temperature Sensor Connection
Connect the temperature sensor cable to the designate d termi­nals 6 and 7 on the HygroMatik steam generator.
The factory settin g for the value for the set point of steam bath temperature is 45°C. After switching the main switch to I (=ON) the humidifier starts to produce steam if the cabin temperature is a) below setpoint of temperature and b) if the safety interlock is closed (please see also chapter „Safety Interlock).
Connection for other steam bad components is described in the technical manual for the DS-Control.
7.5 Control Connecti on - Air Conditioning
Application
Valid for Controls: Basic (B), Comfort (C) und ComfortPlus (CP).
Note: The factory setting for the controls is to an „External con­trol signal, 0-10 VDC“ if no other setting is described in the deliv­ery note of th e humidifier .Within th e scope of this technical manual there is only a short description of „Adjustment of Con­trol to the Control Signa l”. For more d etailed information please see the also delivered technical manual „Controls”.
Warning: Se t the cont rol to prevent ove rly freq uent activation and de activation o f the steam humidifier . Main cont actors are wearing p arts and are guaranteed by the manu facturer for 150,000 cycles. Operation which minimizes activation cycles will extend the life of the main contactors.
Page 44
Page 44
7.5.1 1-step control
With 1-S tep Controls, the external control hyg rostat or co ntrol switch is wired in series with the contacts of the safety interlock.
Warning: Cont acts laid between terminals 1 and 2 mu st be potentialfree and rated for 230V switches
By the use of a
Basic control: For 1 -step controls the jumpers
must be set as indicated below:
By the use of a
Comfort/Comfort-Plus control: For 1-step con­trols, Parame ter U6 must be set to “1-step,” a lso see Section „Parameter Se tting with Codes (P0=10) / Advan ced Customer Level“ in the technical manual for the Control.
7.5.2 Proportional Control wi th an external control
signal
The control can be adjusted to the following external control sig­nals:
0(2) - 5 V DC
0(2) - 10 V DC
0(4) - 20 V DC
0(4) - 10 mA DC
0(4) - 20 mA DC
0 - 140 Ohm
230V int.
Basic Control
A
B
C
JP1
Comfort Control
Page 45
Page 45
The factory setting is a control signal of 0-10V.
Controller
Humidifier Terminals
By the use of a
Basic control:
For a Proportional Control with an e xternal control signal the jumpers must be set as indicated below:
By th e use o f a
Comfort/Comfort-Plus contro l: F or a propor­tional control connected to an external control signal, Software­Parameters U6 and E3 must be set as indicated below.
Setting for External Control
Signall
Parameter
U6 E3
0(2) - 10V DC external control-
ler
0 - 10 V
0(4) -20 mA external control-
ler
0 - 20 mA
0 - 140 Ohm external control-
ler
0 - 140 Ohm
Basic Control
A
B
C
JP1
Setting fo r External Control Signal:
0(2) - 10 V DC
A
B
C
JP1
Setting for External Control Signal:
0(4)-20 mA
Setting for External Control Signal:
0-140 Ohm
A
B
C
JP1
Comfort Control
Page 46
Page 46
7.5.3 Proportional Control with Built-In PI-Controller
Upon reque st, Hygro Matik will provide an active sen sor with a control signal of 0 -10 V DC. Sensors with othe r control signals can also be used; the control (only available at Comfort or Com­fort-Plus Control) need only be set to them.
Humidifier Terminals
If other types of active sensors are used Paramter E3 has to be adjusted:
Humidifier Terminals
Note: The desired relative humidity value is set at Parameter P8 (factory setting: P8=50%).
Setting for Sensor Signall Parameter
U6 E3
0(2) - 10V DC PI-Control 0 - 10 V
0(4) -20 mA PI-Control 0 - 20 mA
0 - 140 Ohm PI-Control 0 - 140 Ohm
Connection: Active Se nsor, one-cylinder and double- cyl­inder humidifier; vo ltage out­put
active sensor
terminal block
Connection: active sensor; current out put, sin gle-cylin­der and double cylinder un its, two-wire system
Page 47
Page 47
7.6 Cable Connections
The t able belo w shows t he ca ble connectio ns pro vided in HeaterLine steam humidifiers:
Characteristics of metric cable connections:
7.7 Fan Unit
» Connect fan unit as specified in the wiring diagram.
The fan unit is activated/deactivated in parallel with humidif ica­tion.
Note:Terminals 37 und 38 are supplied with the unit only when the fan unit a nd humidifier a re purchased simult aneously. In other cases (i.e. re trofitting) the fan unit motor p hase can be connected to Terminal 2 guided via the a uxiliary contact of the main contactor.
Only cables with same diameter are alllowed to be connected to one common clamp.
Unit Connection
M16
Connection
M25
Connection
M32
HC02 - 09 4 2 0 HC06P-HC09P
HC12 - HC27
421
Thread
across-flats
dimensions [mm]
for cable diameter
[mm]
M16x1,5 19 4,5 - 10
M25x1,5 30 9 - 17
M32x1,5 36 11 - 21
Page 48
Page 48
7.8 Wiring Diagram
Please refer to th e wiring diagram in the technical manual sup­plied with th e con trol used wit h you r humidifier . Eve ry steam humidifier comes with a u nit-specific technical manual an d a manual fo r the control. I n add ition, you will find d ownloadable wiring diagrams and technical manuals at www.hygromatik.de.
7.9 Electrical Installation Checklist
Perform e lectrical inst allation checks in compliance with cus­tomer site requirements and public power utility regulations:
Does the mains voltage match the voltage on the name
plate?
Have all electrical connections been made according to
the terminal diagram?
Have all electrical cable and plug connections been
properly tightened?
Are all electrical plug connections secure?
Is the unit grounded?
After this check the unit can be switched on.
Warning: The unit must be closed and locked (only for humidifer type HeaterLine). This guarantees that the cover is grounded.
Note: For initial o peration, control, service, malf unctions, and circuit diagrams, consult the operation instructions for the Hygro­Matik-controls or at www.hygromatik.de.
Page 49
Page 49
8. Maintenance
The HygroMatik steam humidifier is easy to maintain. Neverthe­less, ina dequate or imp roper ma intenance can le ad to opera­tional ma lfunctions. Perfo rm reg ular main tenance to g ive your unit a long life span.
Since steam and co ndensate hoses are also subject to wear they have to be checked regularly. Seals are wearing parts and must there fore b e examined in the periodic mainte nance and replaced if required.
For maintenance the screw t erminals must be checked and retightened if necessary.
Warning: When performing maintena nce work, ple ase follow these instructions:
During operation and also for a while after switching off
the unit the steam cylinder is hot. Before touching the cylinder, check its temperature.
Drained cylinder water could have a temperature up to
95°C.
Before removing the steam cylinder make sure that it is
completely drained and that it does not contain any hot water.
During disassembling a steam hose hot steam could
leave the steam hose if several humidifiers are working on the same air duct, although the currently maintained unit is switched off.
Have the unit serviced only by qualified, authorized per-
sonnel.
Obey safety regulations.
Switch off the unit prior to maintenance and secure
against restart.
After maintenance work, have qualified personnel
check that the unit is operating safely.
If a defective cable is detected through a visual check
switch off the unit, secure it against restart and replace the cable.
The clamps that fix the steam cylinder halves have par-
tially sharp edges and could spring out uncontrolled during removement. Prevent springing out clamps by covering the clamps with one hand during removement.
During operation the fan for cooling the solid state relay is run­ning.
The steam humidifier’s performance and maintenance intervals depend primarily on the existing water quality and the quantity of steam generated. Variable water quality can lengthen or shorten the maintenance interval. Ongoing maintenance intervals can be estimated based on the amount and type of residue found in the steam cylinder.
Page 50
Page 50
Immediate cylinder maintenance is indicated by:
a green, blinking LED on the display and operating panel.
the
display reads Service (only with co ntrols of T ype Comfort and Comfort Plus).
8.1 Maintenance for Operation with Demineralized
Water / Condensate
Instructions f or maintena nce and clean ing intervals are b ased exclusively on typical, empirically determined values.
Cycle Maintenance Task
4 W eeks af ter Initial Operation
Visual check o f electrical and me chanical connections.
Visual check of water level control.
Visual check of steam cylinder interior.
Annually Visual check of electrical and mechanical
connections.
Visual check of water level control.
Visual check of heater elements / thermo sen­sor.
Visual inspection of interior of steam cylinder.
If needed, cleaning of steam cylinder, heater elements and thermo sensor.
Page 51
Page 51
8.2 Maintenance for Operation with Tap Water or Par-
tially Softened Water
No precise ma intenance intervals can be specified because these always de pend on water q uality an d quan tity of steam generated. It is advisable to adjust the frequency of maintenance to the specific operational application.
HYGROMATIK recommends to op en and check the steam cyl­inder two weeks af ter commissioning. Ongoing maintenance intervals can be estimated based on the amount and type of res­idue found in the steam cylinder.
Blow-Down Cycles
The vaporization process causes mineral (calcium) deposits of different compositions to settle in the steam cylinder. Part of this solid build-up is removed through periodic blow-downs and fresh tap water refills.
Water quality
When using t ap wa ter, not e that clean ing intervals short en as
the carbonate hardness level in the water increases. As a gen-
eral rule, it is prefera ble to operate the unit with fully demineral­ized water. Op eration will no t be affected by mineral depo sits and flushing losses will be minimized.
Note: If desired , maintena nce intervals can b e len gthened by moderately incre asing blow-down rate s. Please consult Hygro­Matik.
Page 52
Page 52
8.3 Access to Control Unit
» Remove cover (or electric compartment cover) and lift
display panel (A) out of its guide.
» Turn display panel (see drawing) and hang display
panel on the humidifier cabinet (B) by placing the two guide pins in the two front guides.
» The PCB (C) is now accessible.
Danger, Hazardous Voltage: Switch off unit before installing or removing the display plate.
Page 53
Page 53
8.4 Removing and Cleaning the Steam Cylinder
Warning: Please follow the detailed instructions in these operat-
ing in structions! The unit is only to be se rviced by qualified, authorized personnel. Note the warnings and safety notes in the operating instru ctions. F ailure to ob serve warnings a nd safety notes may result in injury, serious injury o r death, and/or dam­age to the unit. The stea m cylind er may still be hot wh en you begin maintenance work. Handle carefully!
Note: After a longer period of operation the steam cylinder could shrink a little. This doesn‘t matter but could lead to tightness dis­crepancies when o nly one h alf of the cylinder is b eing exchanged. The refore we recommend not to change only one half of the cylinder but a complete cylinder.
Removal:
on/off switch in position II
after cylinder draining switch off unit
open unit
disconnect unit from voltage supply and secure it against restarting
Page 54
Page 54
disconnect unit from water supply
check for voltage disconnection
check cylinder temperature
remove steam hose from adapter
lift steam cylinder out of base
push clip on adapter outside cabinet
Page 55
Page 55
Cleaning of Steam Cylinder and Cylinder base
When using minera l deposit removers or cleaners to clea n the cylinder and h eater e lements, ma ke sure you th oroughly rinse the unit before return ing reasse mbling it. Use mineral depo sit removers only for cylinder and heater elements.
Note: Overly strong mechanical cleaning can damage the cylin­der / heater elements.
detach connecting cable for heater element(s)
remove flange clamps
open cylinder
remove used O-ring
clean cylinder inside
clean the two strainers
Page 56
Page 56
» Remove all deposits. However, small amounts of scale
deposits on the heater elements (8) are harmless.
» Cylinder base (11) and the connections have also to be
checked for deposits and cleaned if necessary.
Cleaning of the Control Cylinder
The control cylinder (27, 28, 29) monitors the water level. When cleaning the steam cylinder the control cylinder should also be cleaned. Therefore:
» Loosen the four top screws that interconnect floating
switch (27) and control cylinder housing (29).
» Pull out floating switch and clean it carefully.
» Take off sealing (28) and clean it.
Note: The rod assembly may not be lubricated.
» Clean the sealing surface it the control cylinder housing
(28).
» For installation mount the a.m. components in reverse
order.
Assembly
connect upper and lower part with clamps
insert new O-ring
remove used O-ring
insert new O-ring
Page 57
Page 57
Note: When putting the cylinder back toge ther, the jo ints and reinforcements of both sections must fit together snugly.
Switch on t he un it and check for leaks af ter 15-30 minutes of operation.
install connecting cable for heater element(s)
remove old O-ring insert new O-ring
place cylinder vertically into cylinder base
reconnect to power supply
fix adapter with clip
push adapter onto steam outlet
Page 58
Page 58
8.5 Maintenance of the Control Cylinder
When clea ning the steam cylinder th e co ntrol cylinder sh ould also be cleaned.
As the access to the control cylinder is only possible if the steam cylinder is remo ved o ne can fi nd the sub chapte r „Cleaning of the Control Cylinder” in chapter „Cleaning the Steam Cylinder”.
8.5.1 Cleaning the nozzle in the steam hose adapter
From the top of the control cylinder a hose is laid to the connec­tor at the steam ho se adapter. Within this connector there is an integrated nozzle that has to be cleaned regularly as it could be blocked by lime.
8.6 Replacing Heater Elements
Removal
» Remove and open the steam cylinder as described
above in section “Removing and Cleaning the Steam Cylinder.”
» Detach connecting cable for the heater element in
question. Mark these two terminals.
» If necessary, remove the capillary tube from the thermo
sensor by detaching the retainer clips.
» Detach the heater element from the cover by removing
the nut and adjusting washer.
» If present detach cable lug for grounding.
» Pull heater element downward out of the steam cylin-
der.
» Clean the sealing surface on the underside of the cover
around the area where the new heater element will be installed.
Installation
» Install new heater element (with sealing), replacing the
parts in the correct sequence, and screw nut.
» Insert the heater element’s connecting cable into the
two marked terminals and tighten. Polarity of (heater element) connecting cable is not important.
» If necessary: Install capillary tube on the thermo sensor
using retainer clips.
» To proceed further, follow the steps described above in
section “Removing and Cleaning the Steam Cylinder”.
Page 59
Page 59
8.7 Replacing Thermo Se nsor (for Heater Ele-
ment)
Removal
» Remove and open the steam cylinder as described
above in section “Removing and Cleaning the Steam Cylinder.”
» Loosen clips of capillary tube (T).
» Disconnect capillary (T) tube from the heater elements
(8).
» Remove the etwo screws (S) of thermo sensor (O).
» Remove thermo sensor.
O: Thermo Sensor P: Unlocking Button for Thermo Sensor Q: Seal R: Steam Cylinder S: Screw T: Capillary tube
Warning: Do not bend the capillary tube of the thermo sensor! Installation
» Install thermo sensor with new sealing. Do not fix the
screws too tightly!
» Neatly connect the capillary tube to the heater element.
Having humidifiers with two or more heating elements the capillary tube is connected to two heating elements.
» To proceed further, follow the steps described above in
section “Cleaning Coarse Strainer in Cylinder Base ­Assembly” .
O
P
Q
R
S
T
Page 60
Page 60
8.8 Unlocking of a Re leased Ther mo S ensor
(for heater element)
If a thermo sensor (for heater element) has released due to a too high temperature the red release button (P) is some millimetres above the level of the top of it s holder . Additiona l the co ntrol reports a failure „thermo sensor activated“. After the system has cooled down the release button (P) can be unlocked by pressing it down a few millimetres.
8.9 Unlocking of a Re leased Ther mo S ensor
(for Solid State Relay)
If a th ermo sensor (for solid state relay) has release d due to a too high temperature (>100°C +/- 5°K) the con trol reports a fail­ure „thermo sensor activated“. After the system has cooled down the release pin (that lays between the bot h pla in connectors) can be released by pressing it carefully down until there is a klick sound.
Release button
Page 61
Page 61
8.10 Removing Inlet Sole noid Valve and Clean-
ing Fine Mesh Filter
Removal
» Remove and open the steam cylinder as described
above in section “Removing and Cleaning the Steam Cylinder - Removal.”
» Seal off water supply and remove screw joint from fresh
water connection.
» Detach connector hose from base.
» Remove electrical connectors from solenoid.
» Remove solenoid valve mounting screws.
» Take the solenoid valve out of hole.
Cleaning
» Remove fine mesh filter from the solenoid valve and
clean.
Installation
» Place solenoid valve with seal in the hole in the unit
cabinet.
» Secure solenoid valve tightly with screws .
» Attach fresh water connection.
» Connect elecrical cable to the solenoid valve.
» Attach connector hose to the base by using clamps .
» Install cylinder as described above in section “Cleaning
Steam Cylinder - Assembly”.
» Open water supply.
» Switch on unit and check for leakage after 15-30 min-
utes of operation.
If leakage occurs, switch off power supply and repair the leaks, following safety instructions for work on live components!
Page 62
Page 62
8.11 Cleaning Blow-Down Pump
Removal
» Remove and open the steam cylinder as described
above in section “Removing and Cleaning the Steam Cylinder - Removal.”
» Detach electrical connector from the pump (10).
» Detach union adapter (E) from the pump.
» Remove screws (G) and take the pump out of the base
(11).
» Open pump (bayonet lock).
» Remove all residue from the drain hoses and pump
(possibly replace o-ring (A)).
» Assemble pump.
» Moisten o-ring (C) and place in the side connection of
the base.
» Push pump into the base and secure tightly with screws
(G).
» Moisten o-ring (D) and place on the side connection of
the pump.
» Slide union adapter (E) over the side connection of the
pump.
» Connect electrical connector to the pump (polarity not
specified).
» Open water supply.
» Switch on unit and check for leaks after 15-30 minutes
of operation.
If leakage occurs, switch off power supply and repair the leaks, following safety instructions for work on live components!
Page 63
Page 63
8.12 Cleaning c onnection hose s a nd c ylinder
base
All connection hoses should be free of deposits and under good conditions.
As well check all conne ctions of the cylinder base (11) and the steam hose adapter (2) for deposits and remove if neccessary.
G
Page 64
Page 64
8.13 Checking Cable Screw Connections,
Heater Element Wires
» Check that all cable screw connections are securely
tightened
» Ensure that heating element cable is not dammaged.
Warning: Lo ose cable connection s cause excessive cont act resistance and overheating of contact surfaces.
8.14 Operational Check
» Start up the unit and operate for a few minutes, ideally
at maximum output..
» Check safety devices.
» Check hose connections for possible leaks.
8.15 Dismantling
Once the steam humidifier will no long er be used, dismantle (demolish or scrap) it b y following the installation procedures in reverse order.
Warning: Dismantling of th e unit may on ly be performed by qualified pe rsonnel. Electrical d ismantling may only be per­formed by trained electricians.
Obey the safety guidelines in section “Safety Instructions,” espe­cially the guidelines for disposal.
Page 65
Page 65
9. Commissioning
Warning: This unit is only to be started by qualified personnel.
Switching off steam humidifier
Warning: Before starting up the unit, make sure you know h ow
to switch it off.
» Switch off unit by setting control switch to “0”
» Close water supply stopcock valve.
Check of electrical wire connections
» » Check that all electrical wire connections, including
heater element wire connections, are tight and secure.
» Check cylinder seating, and if necessary steam and
condensate hose clamps.
Switching on Steam Humidifier
» Switch on main breaker.
» Open water supply stopcock valve. Operating pressure
100 x 10
3
to 100 x 104 Pa (1 to 10 bar overpressure).
» Switch on unit by setting control switch to “I”.
» Set control of initial operation check to humidity
demand.
The following functions are operating:
The unit performs a self-test. If the control includes a
display, the message “self-test“ is displayed.
If the safety interlock (see also chapter „Safety inter-
lock”) is closed, the water inlet solenoid valve opens and feeds water into the steam cylinder.
If there is a demand for humidity, the main contactor is
switched and a few minutes later steam production starts.Initiation of steam production can take up to 20 minutes.
Further checks:
Let all electrically-driven operations run to completion.
As so on as the solen oid valve be gins replenishing the water periodically, th e ste am hu midifier operates at steady nominal output and the cold start sequence is complete.
» Monitor the unit and let it operate for 15 to 30 minutes.
If leaks appear, switch off the unit.
» Repair leaks, and in doing so:
Attention, Hazardous V oltage! Follow safe ty instructio ns for work on live components.
Page 66
Page 66
10. EC-Declaration of Conformity
Page 67
Page 67
11. Spare Parts
*
HC02
HC 0 3
HC06
HC09
HC06P
HC 09P
HC 1 2
HC18
HC27
Arti c le No. D esc ri pt ion
Cabinet HC
Stea m Gen era ti on
1
B-2 205 493 C ylin de r c ompl ., wit h 1 h ea ter e lem ent 1 ,5k W, 1 ther mal se nsor and
termina l, 2 30V
1
B-2 205 483 C ylin de r c ompl ., wit h 1 h ea ter e lem ent 2 ,25kW , 1 t herm al sen sor
an d t erminal , 23 0V
1
B-2 205 455 C ylin de r c ompl . Inc l 1 h ea ter e lemen t 4. 5 kW , 1 th ermal senso r an d
termina l
1
B-2 20545 9
Cylinder compl. Incl 1 heater element 6.75kW, 1 thermal sensor and
termina l
1
B-2 205 463 C ylin de r c ompl . Inc l 1 h ea ter e lemen t 4. 5 kW , 1 th ermal senso r an d
termina l
1
B-2 20546 7
Cylinder compl. Incl 1 heater element 6.75kW, 1 thermal sensor and
termina l
1
B-2 205 471 C ylin de r c ompl . Inc l 2 h ea ter e lemen ts 4.5kW, 1 th ermal s enso r an d
termina l
1
B-2 205 47 5 Cylin de r c om pl . Inc l 2 hea ter e lem en ts 6.7 5kW , 1 the rma l sen sor
an d t erminal
1
B-2 205 47 9 Cylin de r c om pl . Inc l 3 hea ter e lem en ts 6.7 5kW , 1 the rma l sen sor
an d t erminal
16 1
B-3216046 top part of cylinder Cy2, empty
16 1 1 1
B-3 216 050 to p par t of c yli nder, empt y fo r 1 h ea ter e lemen t and 1 th . Sen sor,
including strainer
16 1 1
B-2 206 051 to p par t of c yli nder, empt y fo r 1 h ea ter e lemen ts and 1 th . Sen sor,
including strainer
16 1 1
B-2 206 059 to p par t of c yli nder, empt y fo r 2 h ea ter e lemen ts and 1 th . Sen sor,
including strainer
16 1
B-2 206 061 to p par t of c yli nder, empt y fo r 3 h ea ter e lemen ts and 1 th . Sen sor,
including strainer
191111
B-3 216 052 l ower p art o f cyl ind er Cy08 , in clud ing straine r
19 11111
B-2 206 053 l ower p art o f cyl ind er Cy17 , in clud ing straine r
1
B-2 209 031 he ater ele me nt 230V / 1, 5k W with se aling and moun ting se t, big
diameter
81
B-2 209 029 he ater ele me nt 230V / 2, 25 kW wi th sealin g a nd mou nt ing set, big
diameter
81
B-2 20902 5
he ate r ele ment
23 0V
/ 4.5kW with sealing and mounting set, big
diameter
81
B-2 209 021 he ater ele me nt
40 0V
/ 4,5kW with sealing and mounting set, big
diameter
81
B-2 209 023 he ater ele me nt 400V / 6. 75 kW wi th sealin g a nd mou nt ing set, big
diameter
812
B-2 209 001 he ater ele me nt 400V / 4. 5k W with se aling and moun ting se t
8123
B-2 209 003 he ater ele me nt 400V / 6. 75 kW wi th sealin g a nd mou nt ing set
262222
E-2 205 138 Ga sket for h ea ter e lemen t
252222
E-2205140 Mounting nut for heater
26 22446
E-2 204 006 Ga sket for h ea ter e lemen t
25 11223
E-2204007 Mounting nut for heater
151111
E-3 216 010 O- rin g se al f or cy l ind er fl a ng e
15 11111
E-2 206 050 O- rin g se al f or cy l ind er fl a ng e
1
B-3 216 015 O- rin g se t f ür HC 02
111
B-3 216 095 O- rin g se t f or HC 06-0 9
11111
B-3 216 097 O- rin g se t f or HC 06P- 27
59 1
B-2 209 035 pr otec ti ve tube incl m e lt ing fu se
5111111111
B-2 205 03 1 The rma l s ensor 1po le
6666668810
E-2 205 012 C lam p for ther mal se nsor 1p ole
6111111111
E-2 205 010 ga sket for the rma l sen sor 1 po le
21
E-2 209 000 ad apter for ste am h ose D N25
1
E-2 209 014 ad apter for ste am o utle t D N40/DN25
24 1
E-3 221 004 C lip for stea m ho se adap ter D N25
1
E-2 204 022 O- rin g f or cy lind er ba se an d st eam ho se adapt er
2 11111111
B-2 205 025 ad apter for ste am h ose D N40
24 11111111
E-2 209 002 C lip for stea m ho se adap ter D N40
4 11111111
E-2 204 022 O- rin g f or ste am h ose ada pter DN 4 0
1 22222222
E-2205088 star knob screw, fixation for steam hose adapter
12 11111111
E-2 204 03 5 conde nsa te pl ug
Page 68
Page 68
*
HC02
HC 0 3
HC06
HC09
HC06P
HC 09P
HC 1 2
HC18
HC27
Arti c le No. D esc ri pt ion
Water feed
14 1
B-2 304 059 do uble so leno i d va lve, 0. 2-10 ba r, 2 00-2 40V AC, 1.2 l /m in
14 1 1 1
B-2 304 061 do uble so leno i d va lve, 0. 2-10 ba r, 2 00-2 40V AC, 2.5 l /m in
14 11111
B-2 304 069 do uble so leno i d va lve, 0. 2-10 ba r, 2 00-2 40V AC, 3.5 l /m in
111111111
E-2304024 fine filter in solenoid valve inlet
111111111
E-2 304 103 c ap ti ve c ou pling rin g f or so leno id va lve 3 /4"
111111111
E-2 30410 7 ga sket for in let screwed fittin g, sole noid
111111111
E-8 501 034 ho se col lar f o r inlet screw ed fi ttin g, 3/ 4" so len oid
56111111111
B-2 304 031 ho se for w at er co nnec ti o n, 0,6 m 3/ 4" ca p nut s o n b ot h sid es, sea l
inc lud ed
32111111111
E-2 304 036 ru bber se al so len oid valv e - c abin et
111111111
B-2 304 040 m ounti ng se t f or so leno id va lve
31 0,9 1, 2 1 ,2 1,2 1,4 1,4 1,4 1 ,4 1, 4
E-2 604 00 2 hose s ol en oi d valv e - c yl in de r
33 0,9 0, 7 0 ,7 0,7 0,7 0,7 0,7 0 ,7 0, 7
E-2 604 00 2 hose s ol en oi d valv e - s up er flu sh
211111111
E-2 604 044 bu ckl in g pr ot ectio n f or ho se
1111
B-2504121 water level control, compl with flow switch, consisting of pos. 27, 28,
29 , va lid s i nce 06/2 014
11111
B-2504141 water level control, compl with flow switch, for HC06P/09P, HC12-27
291111
E-2 504 142 wa ter lev el co ntrol , wi tho ut fl ow sw itch , va lid sinc e 0 6/2 014
29 11111
E-2 504 174 wa ter lev el co ntrol , wi tho ut fl ow sw itch , f or HC0 6P/0 9P/ 12 -2 7,
before 06 /2014 for: HC03 -09
27 11111
B-2 50416 7 fl ow sw itch incl. Seal ing s, b efore 06/201 4 for : HC03- 27, sin ce
06 /20 14 fo r: H C06P/0 9P/12 -27
1111
B-2 504 171 fl ow sw itch incl . sea lin gs, si nce 06/ 2 01 4 f or: H C03 -0 9
28111111111
E-2 304 038 ru bber se al f or w ate r level control
30 0,2 0, 3 0 ,3 0,3 0,4 0,4 0,4 0 ,4 0, 4
E-2 604 004 ho se, cylin der ba se - c ontrol c yl ind er
3 0 ,3 0, 5 0,5 0,5 0,6 0 ,6 0,6 0 ,6 0, 6
E-2 604 002 ho se, wate r level co ntro l- stea m ho se ad apt er
1111111
E-2604021 T-piece condensate manif old, type TS12, DN12 E-2 604 029 ho se nozz le DN 2 5 - R 3 /4"
58222222222
E-2 604 094 D ouble c hec k v alv es
34 1 0 10 1 0 1 0 10 1 0 10 1 0 10
E-2 304 01 5 hose c la m p DN12
39222222222
E-8 501 06 4 hose c la m p DN14 ,2
Water Drain
11111111111
E-2 206 086 c yl inde r ba se for C , Hy, HC, DN40
13111111111
E-2 204 022 O- Ring f or cyli nder b ase DN40
10111111111
B-2 404 027 D rain p ump 230V / 50- 60Hz with ou t mo unt ing set
111111111
B-2 424 014 Mo unti ng se t fo r dr ain pu m p
111111111
E-2 404 026 D rain p ump housing
18111111111
E-3 220 005 O- rin g cy lind er b ase - dra in p ump
211111
E-3 425 002 ad apter , pum p - dra in h ous e, ang led DN25/ 13
11111
E-2 425 002 ad apter , pum p - dra in h ous e, str aigh t, DN2 5/ 13
17111111111
E-3 220 005 O- rin g f or dr a in p um p
7111111111
E-2 425 004 El bow wit h ve nt pip e
22 0,3 0, 5 0 ,5 0,5 0,6 0,6 0,6 0 ,6 0, 6
E-2 604 002 ho se, drain pum p-elbo w
23 0,4 0, 6 0 ,6 0,6 0,6 0,6 0,6 0 ,6 0, 6
E-2 604 004 dr ain ho se, elb ow - ou tlet
57111111111
B-2 304 03 1 hose wa ter co nn ec t io n 3/4 "
1
B-3401053 drain hose system for HC02, consisting of pos. 7 , 17, 21, 22, 23
111
B-3401035 drain hose system for HC03-09, consisting of pos. 7, 17, 21, 22, 23
11111
B-3401037 drain hose syste m for HC06(P)-27, consi sting of pos. 7,17,22,23,
ad ap er st raig ht
Page 69
Page 69
*
HC02
HC 0 3
HC06
HC09
HC06P
HC 09P
HC 1 2
HC18
HC27
Arti c le No. D esc ri pt ion
Control
1
E-2 501 005 m ain con tact or 1 6A, ( ABB) , co il v ol ta ge.23 0VAC
111111
B-2 507 041 m ain con tact or 2 0A, D ILM7 , c o il volt a ge .230V AC
11
B-2 507 061 m ain con tact or 3 5A, D ILM1 7, coil vo ltag e 2 30VAC
51111111111
E-2 502 412 c on tr ol b utt on 2 pole B asi c, L3/ DS, middle 0
1
E-2 205 110 s olid sta te re lais 2 5 A , wit ho ut co oler
11111
B-2 602 001 s olid sta te re lay 2 5 A, 1 ph., cooli n g d evi ce 15 0 x 50 mm, th erm al
circuit breaker
11
B-2 602 103 s olid sta te re lay 5 0 A, 2 ph., cooli n g d evi ce 15 0 x 50 mm, th erm al
ci rcu it b re ak er (not at Sl a ve- unit s
1
B-2 602 009 s olid sta te re lay 7 5 A, 1 ph., cooli n g d evi ce 15 0 x 80 mm, th erm al
ci rcu it b re ak er (not at Sl a ve- unit s)
111 1
B-2 602 107 s olid sta te re lay 2 5 A, 1 ph.
11
B-2 602 109 s olid sta te re lay 5 0 A, 2 ph. B-2 602 111 s olid sta te re lay 7 5 A, 1 ph.
11
E-2 205 102 Pr otec ti o n c ap ag ainst co ntact w ith cut out
1111111
E-2 205 116 c oo l ing de vi ce 1 50 x 50 m m
1
E-2 205 118 c oo l ing de vi ce 1 50 x 80 m m
111111111
E-2205108 Thermal circuit breaker with manual reset, 100°C ± 5K
11111
E-3 720 010 F an , 2 30VA C
Basic
111111111
B-2 526 203 El ekt ro nic pcb typ e B asic B-2 526 203 El ekt ro nic pcb typ e B asic f or S lav e-un its
(1) (1) (1) (1) (1) (1) (1) (1) (1)
B-2 526 213 El ekt ro nic pcb typ e B asic f or H C ste am b ath
1
B-2120915 Mounting plate with foil for Basic (without display), small
11111111
B-2120901 Mounting plate with foil for Basic (without display)
(1)
B-2120919 Mounting plate with foil for Basic DS
(without display), sma ll
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2120909 Mounting plate with foil for Basic DS
(without display)
(1) (1) (1) (1) (1) (1) (1) (1) (1)
B-2 526 301 R elais p cb for B asi s pcb
Comfort
111111111
B-2 526 203 El ekt ro nic pcb typ e B asic
B-2 526 203 El ekt ro nic pcb typ e B asic f or S lav e-un its
(1) (1) (1) (1) (1) (1) (1) (1) (1)
B-2 526 213 El ekt ro nic pcb typ e B asic f or H C ste am b ath
1
B-2 526 489 C omfo rt disp la y C 01/0 2 HC02 , sm all
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2 526 401 C omfo rt disp la y i ncl. mou ntin g p late with foil
1
B-2 526 487 C omfo rt Dis play DS C01 /02 HC 02
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2 526 445 C omfo rt disp la y i ncl. mou ntin g p late with foil st eam bath
1
B-2 120 917 m ounti ng p late wit h foi l fo r Comf o rt un i t ( wit hout displa y), sm all
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2 120 903 m ounti ng p late wit h foi l fo r Comf o rt un i t ( wit hout displa y)
1
B-2 120 919 m ounti ng p late wit h foi l fo r Comf o rt un i t fo r ste am b ath DS (wi thout
display), small
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2 120 911 m ounti ng p late wit h foi l fo r Comf o rt un i t fo r ste am b ath DS (wi thout
display)
Comfort Plus
11111111
B-2 526 203 El ekt ro nic pcb typ e B asic
B-2 526 203 El ekt ro nic pcb typ e B asic f or S lav e-un its
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2 526 213 El ekt ro nic pcb typ e B asic f or H C ste am b ath
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2 526 403 C omfo rt Pl u s Dis play in cl . Mou ntin g plat e
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2 120 905 m ounti ng p late wit h foi l fo r Comf o rt Pl u s un it ( wit ho ut displ ay)
(1 ) ( 1) (1 ) ( 1) ( 1) ( 1 ) ( 1) (1 )
B-2 526 447 C omfo rt plu s di spl ay in cl. mou ntin g pl ate w i th foil st eam bath
Page 70
Page 70
*
HC02
HC 03
HC06
HC09
HC06P
HC 09P
HC 12
HC18
HC27
Arti c le No. D esc ri pt ion
Accessories
E-2 604 034 R educi ng pi e ce DN4 0/D N 25 fo r ste am h ose E-2 604 012 Ste am hos e DN25 , p er m E-2 604 013 Ste am hos e DN40 , p er m E-2 604 002 C onden sate h ose DN 12 , p er m E-2 404 004 Ste am hos e cla mp D N25 E-2 604 016 Ste am hos e cla mp D N40 E-2 304 015 C onden sate h ose clam p D N 12
57 E-2 420 423 D rain h ose 1 1/4"
E-2 604 042 Ste am mani fol d p i ece DN25, sta inl ess ste el E-2 604 023 Ste am mani fol d p i ece DN40, sta inl ess ste el E-2 604 021 C onden sate c onnect or T- piece DN12 B-2 604 025 s te am so leno id va lve 0-0, 4 b ar, c ompl . for st eam ho se DN 2 5
B-2 604 040 s te am so leno id va lve 0-0, 4 b ar, c ompl . for st eam ho se DN 4 0
If you order any spar e part s , sp eci fy ty pe a nd se ria l num be r of the u nit, plea se.
* see exploded view
Page 71
Page 71
12. Fax Form - Order for spare parts
Badgermeter Swiss AG
Mittelholzerstrasse 8
3006 Bern
Tel. +41 (0)31 932 01 11
Order of spare parts
unit type *______________ serial no.* ___________________
commission: ______________ order no.: __________________
date of delivery ____________forwarder _____________ shipment by ___________
delivery address (if different from invoice address)
__________________________ __________________________ __________________________ __________________________
* Order can only be processed if unit type and unit serial no. are filled in.
quantity article article no.
Fax Form
Please copy, fill in and fax to
Fax.No. +41 (0)31 931 08 67
company stamp (delivery adress)
date/signature
Page 72
Page 72
13. Index
A
Absorption Distance
................................................................. 19
Determining the Absorption Distance ................................ 19
C
Commissioning
......................................................................... 65
Condensate Hose Installation .................................................. 32
E
EC-Declaration
......................................................................... 66
Electrical Installation ................................................................ 41
Environmental Conditions ........................................................ 15
Exploded View.......................................................................... 76
F
Fan Unit
.................................................................................... 21
I
Installation
Equipment Dimensions HC
................................................ 16
Fitting Measures................................................................. 18
Installation of a HeaterCompact............................................... 15
Internal Output Setting ............................................................. 14
M
Maintenance
............................................................................. 49
Blow Down Pump............................................................... 62
Control Cylinder.................................................................. 56
Heater Elements................................................................. 58
Steam Cylinder................................................................... 53
Thermo Sensor................................................................... 59
Method of Operation ................................................................ 12
Mode of Action ......................................................................... 11
S
Safety Interlock
......................................................................... 42
Setting for Control Signal ......................................................... 43
Spare Parts............................................................................... 67
Steam Line ............................................................................... 28
Steam Manifold ........................................................................ 24
Notes on Installation........................................................... 24
Page 73
Page 73
T
Technical Specification
............................................................ 74
U
Unlocking Thermo Sensor (for heater element)
...................... 60
Unlocking Thermo Sensor (for Solid State Relais).................. 60
V
View of Cabinet
........................................................................ 77
W
Water Installation
...................................................................... 35
Water Supply............................................................................ 36
Page 74
Page 74
14. Technical Specifications
HeaterCompact HC
Type HC02 HC03 HC06 HC06 HC09 HC06P HC09P HC12 HC18 HC27
Steam Output [kg/h] 2 3 6 6 9 6 9 12 18 27 Electrical Supply* 230V/1/N 400V/3/N 50-60Hz Power Rating [kW] 1,5 2,25 4,5 4,5 6,8 4,5 6,8 9,0 13,5 20,3 Power Consumption [A]**
6,5 9,8 19,6 11,3 16,9 11,3 16,9 19,5 29,3 29,3
Circuit Protection [A] 1 x 10 1x10 1x20 3x16 3x20 3x16 3x20 3x25 3x35 3x35 Control Type Basic, Comfort and Comfort Plus Number of Steam Cylinder
1
Number of Heater Elements
111111122 3
Steam Hose Con­nection
1x25mm*** 1x40mm
Condensate Hose Connection
1x12mm
Net Weight [kg] 12 16 16 16 16 22 22 23 23 24 Operating Weight [kg]
15 20 20 20 20 36 36 37 37 38
Height [mm]**** 390 562 704 Width [mm]**** 394 427 490 Depth [mm]**** 260 260 309 Water Supply Fully Demineralized Water / Cleaned Condensate: 1 to 10 bar, 13mm Hose
Partially Softened Water / Tap Water (different qualities): 1 to 10 bar, for 3/4” exter-
nal thread Fan Unit, Wall­Mounted
VG08 VG08 VG08 VG08 VG17 VG08 VG17 VG17 VG30 VG30
Airflow Capacity of Fan Unit [m
3
/h]
150 150 150 150 185 160 185 185 350 350
* Other voltages upon request. ** Current load of phases is not uniform. See table below. *** incl. reducing piece DN40/DN25 **** Outer dimensions of width and depth.
Max. current load [A] according to phase:
Phase HC06(P) HC09(P) HC12 HC18 HC27 Electrical Supply* 400V/3/N 50-60Hz L1 11,3 16,9 11,3 16,9 29,3 L2 11,3 16,9 19,5 29,1 29,3 L3 0,2 0,2 11,3 16,9 29,3
Page 75
Page 75
HeaterCompact HC for SPA
HC03..-DS - HC27..-DS
Type HC03 HC06 HC06 HC09 HC06P HC09P HC12 HC18 HC27
Steam Output [kg/h] 3 6 6 9 6 9 12 18 27 Electrical Supply* 230V/1/N 400V/3/N 50-60Hz Power Rating [kW] 2,25 4,5 4,5 6,8 4,5 6,8 9,0 13,5 20,3 Power Consumption [A]**
9,8 19,6 11,3 16,9 11,3 16,9 19,5 29,3 29,3
Circuit Protection [A] 1x10 1x20 3x16 3x20 3x16 3x20 3x25 3x35 3x35 Control Type Basic-DS, Comfort-DS and ComfortPlus-DS Number of Steam Cylinder
1
Number of Heater Elements
1 1111122 3
Steam Hose Con­nection
1x40mm
Condensate Hose Connection
1x12mm
Net Weight [kg] 16 16 16 16 25 25 26 26 27 Operating Weight [kg]
18 18 18 18 43 43 44 44 45
Height [mm]*** 562 707 Width [mm]*** 427 490 Depth [mm]*** 257 306 Water Supply Fully Demineralized Water / Cleaned Condensate: 1 to 10 bar, 13mm
Hose
Partially Softened Water / Tap Water (different qualities): 1 to 10 bar, for 3/
4” external thread
* Other voltages upon request. ** Current load of phases is not uniform. See table below. *** Outer dimensions of width and depth. Hight incl. drain connection.
Max. current load [A] according to phase:
Phase HC06(P) HC09(P) HC12 HC18 HC27 Electrical Supply* 400V/3/N 50-60Hz L1 11,3 16,9 11,3 16,9 29,3 L2 11,3 16,9 19,5 29,1 29,3 L3 0,2 0,2 11,3 16,9 29,3
Page 76
Page 76
15. Exploded View

































Page 77
Page 77
16. View of Cabinet
56
57
51
Page 78
12/2004
Loading...