• UNIVERSAL COMPATIBILITY: The VXT feeder can be used with virtually
any probe or float-type low water cut-off.
• FEED COUNTER: Brightly illuminated feed cycle counter displays the
amount of water added to the boiler – essential in diagnosing water loss
problems that can severely shorten the life of a steam boiler. Built-in memory prevents power interruptions from clearing the counter.
• PROGRAMMABLE FEED DELAY SETTINGS: Helps prevent flooded boilers.
Allows time for condensate to return to the boiler before starting feed
cycle – ensuring that additional water is needed.
• PROGRAMMABLE FEED AMOUNT SETTINGS: Six settings provide two
ways to feed: 1-5 gallon settings feed
above
the Low Water Cut-Off to
restore boiler’s normal operating level. Or, select LWCO setting to end the
feed cycle when the Low Water Cut-Off re-energizes the burner.
• UNDERFEED PROTECTION: If one feed cycle is not sufficient to restore
boiler operation, the VXT will delay and feed one additional cycle.
• LOCKOUT FLOOD PROTECTION: The VXT locks-out to prevent steam sys-
tem flooding and costly water damage if burner operation does not
resume after two
consecutive feed cycles.
INSTALLATION
Step ➊– WarningStep ➋– Plumbing
WARNING – To
prevent electrical
shock or equipment
damage, power
must be off during
installation or servicing of the con-
serious burns, the boiler should be thoroughly cooled
before installing or servicing control. Only qualified
personnel may install or service the control in accordance with local codes and ordinances. Read instructions completely before proceeding.
We warrant products manufactured by Hydrolevel Company to
be free from defects in material and workmanship for a period
of two years from the date of manufacture or one year from
the date of installation, whichever occurs first. In the event of
any claim under this warranty or otherwise with respect to our
products which is made within such period, we will, at our
option, repair or replace such products or refund the purchase
price paid to us by you for such products. In no event shall
trol. To prevent
Feeder must be installed with a manual by-pass. Use isolation valves and
unions to allow easy removal for service or replacement.
Note: Arrow on VXT valve indicates direction of water flow.
LIMITED MANUFACTURER’S WARRANTY
Hydrolevel Company be liable for any other loss or damage,
whether direct, indirect, incidental or consequential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF
any other warranty or guarantee, express or implied, including, without limitation, any warranty of MERCHANTABILITY or
fitness for a particular purpose. This warranty may not be
assigned or transferred and any unauthorized transfer or
assignment thereof shall be void and of no force or effect.
Select the wiring diagram below that corresponds to the low water cut-off installed on the boiler. Consult boiler manufacturer’s
instructions for proper burner terminal connections.
Hydrolevel
Safgard Model 450 / CycleGard CG450
STANDARD WIRINGSTANDARD WIRING
ALTERNATE WIRING: If the power source for the low water
cut-off is separate from the burner circuit, remove the
jumper between 1 and P1, connect the red wire to A, connect the black wire to the burner circuit hot and the white
wire to the burner circuit common.
McDonnell & Miller
PS-800 Series
ALTERNATE WIRING: If the power source for the low water
cut-off is separate from the burner circuit, do not install
jumper between H and C. Connect the red wire to W, connect the black wire to the burner circuit hot and the white
wire to the burner circuit common.
Honeywell
Float Style Control
Model RW-700 Guard Ring
STANDARD WIRINGSTANDARD WIRING
ALTERNATE WIRING: If you choose to wire the feeder to a
separate power source from the burner circuit, do not install
jumper between 2 and 3. Connect the red wire to 4, the
black wire to the hot side of power source and the white
wire to common.
ALTERNATE WIRING: If you choose to wire the feeder to a
separate power source from the burner circuit, do not install
jumper between L1 and A. Connect the red wire to A, the
black wire to the hot side of power source and the white
wire to common.
Step ➍– Set the Feed Delay
30-Second2-Minute
(Factory Setting)
4-Minute6-Minute8-Minute10-Minute
NOTE: SELECT ONLY ONE DIPSWITCH CORRESPONDING TO THE DESIRED FEED DELAY.
The feed delay feature is designed to prevent boiler flooding by allowing time for condensate to return to the boiler prior to
feeding. If the returns and vents are in good condition, the 2-minute factory setting is usually sufficient. If for any reason condensate takes longer to return to the boiler (such as old return lines or long horizontal runs), a longer delay setting should be
selected.
Step
– Set the Feed Amount
➎
LWCO
(Factory Setting)
1-Gallon2-Gallon3-Gallon4-Gallon5-Gallon
NOTE: SELECT ONLY ONE DIPSWITCH CORRESPONDING TO THE DESIRED FEED AMOUNT.
CAUTION: BOILER FLOODING CAN OCCUR IF THE FEEDER IS NOT SET PROPERLY.
UNLIKE OTHER FEEDERS, THE 1-GALLON TO 5-GALLON SETTINGS WILL FEED THE FULL
CYCLE REGARDLESS OF WHEN THE WATER REACHES THE LOW WATER CUT-OFF.
LWCO Setting: The VXT feeder is shipped in the LWCO feed setting. When operating in this setting, the VXT will feed only
until the low water cut-off re-energizes the burner circuit (or a maximum of 5 gallons). This will restore boiler operation, but on
some applications may only be enough water to satisfy the
boiler’s
complete, regardless of when the low water cut-off is satisfied. These settings should be used only when the LWCO setting
does not provide adequate water to restore the boiler to a
these settings:
Boilers with probe-type cut-offs:
1. With power to the system on and the thermostat off, lower
2. Press the FEED button on the water feeder and, using a
3. Round the time to the nearest minute and set the feeder
Example:
rise from 1/2" below the probe to the normal operating level,
round to 1 minute and set the feeder for 1-Gallon.
normal
1 Gallon to 5 Gallon Settings: When the 1 to 5 Gallon settings are used, the feeder will continue to feed until the cycle is
the water level to approximately 1/2" below the probe.
watch with a second hand, time how long it takes boiler
water to reach the
middle of the gauge glass unless otherwise specified by
the boiler manufacturer).
for the corresponding number of gallons.
operating level, the 1-Gallon to 5-Gallon settings should be selected using the instructions below.
normal
If it takes 1 minute and 15 seconds for water to
operating level (Usually the
minimum
normal
requirements. If additional water is needed to reach the
operating level. Use the following instructions when choosing
Boilers with float-type cut-offs:
1. With power to the system on and the thermostat off, lower
the water level until 1/4" is visible in the gauge glass.
2. Press the FEED button on the water feeder and, using a
watch with a second hand, time how long it takes boiler
water to reach the
middle of the gauge glass unless otherwise specified by
the boiler manufacturer).
3. Round the time to the nearest minute and set the feeder
for the corresponding number of gallons.
Example:
rise from 1/4" in the gauge glass to the normal operating
level, round to 2 minutes and set the feeder for 2-Gallons.
If it takes 2 minutes and 10 seconds for water to
normal
operating level (Usually the
Step ➏– Attach Service Tag
Complete the information at the top of the service tag provided and attach tag near the VXT Water Feeder.
Feed Counter
The VXT’s built-in feed counter records the number of gallons that enter the boiler during automatic feed cycles
FEED button is pressed.* To determine how much water has been added to the boiler since the last service, the counter should
be checked, recorded, and reset each time the boiler is serviced. The counter reset (DISPLAY RST) button is located in the
bottom right corner of the circuit board.
The addition of water to a boiler raises the oxygen level and accumulates lime and other mineral deposits over time. Excessive
feed cycles, resulting from leaks in the system, can cause cast iron boilers to oxidize (rust) internally, significantly reducing the
life of the boiler. Lime and sediment build-up can impede heat transfer causing damage and/or premature failure of the boiler.
Recommended Limits on Make-Up Water
Many factors, such as the water capacity of the boiler, feed water conditions and boiler design can impact the amount of water that can safely be added to a steam boiler. As a general guideline for late model
boilers, Hydrolevel recommends the monthly limits in the table at the
right for boiler operation during the heating season. If feed amounts
significantly exceed these levels, the system should be checked for
leaks by a qualified technician. Note: Any feed limits provided by the
boiler manufacturer supercede Hydrolevel recommendations. Please
check the boiler manufacturer’s instructions carefully.
*The VXT Feeder is equipped with an orifice to regulate flow rates over a wide range of
water pressures. The Feed Counter readings are designed to be accurate to ±15% with
water pressures between 20 to 90 PSI.
Note: The above limits are based on normal boiler operation during the heating season. They do not include water added as a result of boiler and/or low
water cut-off maintenance.
or
when the
Service / Maintenance
Check Feeder Operation: Feeder operation should be checked annually during boiler servicing to ensure proper operation
and feed amount.
Record and Reset Feed Counter: The feed counter should be checked annually. If the feed amount falls within the recommendations provided in the table above, record this amount on the card provided and press the reset button (DISPLAYRST)
on the bottom right corner of the circuit board. Note: If the feed amount significantly exceeds the recommendations above, the
system should be checked for leaks by a qualified technician.
Trouble Shooting
If LOC appears in the digital counter, this indicates that the safety lockout feature is activated. This feature
gized the burner. The feeder can be reset by briefly interrupting power to the heating system. Important: The following trouble
shooting steps should be taken to determine the cause of the lockout condition before restoring normal operation.
1. If the boiler is overfilled, the low water cut-off is not functioning properly. Using the manufacturer’s instructions, check the
low water cut-off operation.
2. If the boiler is in low water:
a. Check boiler and return piping for leaks.
b. If no leaks are detected, check to determine if the flow of the feeder is restricted. Check isolation valves around feeder
c. Check the feeder setting to ensure that it is set to feed adequate water in the event of a low water condition.
engages only when the feeder completes two consecutive feed cycles and the low water cut-off does not re-ener-
to ensure they are fully opened.
If ERR appears in the digital counter, this indicates that more than one or no delay or feed button has been selected. See Step 4 and Step 5 for DELAY and FEED setting instructions.