Hydrolevel VXT-120 User Manual

Model VXT-120
Programmable Water Feeder for Steam Boilers
120 VAC Operating Voltage
Patent Pending
SPECIFICATIONS MAXIMUM FLUID
TEMPERATURE: 150°F AMBIENT TEMPERATURE: 100°F FLOW RATE: 1 GPM MAXIMUM FEED: 10 Gallons (2 Cycles) ELECTRICAL: 120 VAC, 60 HZ
UNIVERSAL COMPATIBILITY: The VXT feeder can be used with virtually any probe or float-type low water cut-off.
FEED COUNTER: Brightly illuminated feed cycle counter displays the amount of water added to the boiler – essential in diagnosing water loss problems that can severely shorten the life of a steam boiler. Built-in mem­ory prevents power interruptions from clearing the counter.
PROGRAMMABLE FEED DELAY SETTINGS: Helps prevent flooded boilers. Allows time for condensate to return to the boiler before starting feed cycle – ensuring that additional water is needed.
PROGRAMMABLE FEED AMOUNT SETTINGS: Six settings provide two ways to feed: 1-5 gallon settings feed
above
the Low Water Cut-Off to restore boiler’s normal operating level. Or, select LWCO setting to end the feed cycle when the Low Water Cut-Off re-energizes the burner.
UNDERFEED PROTECTION: If one feed cycle is not sufficient to restore boiler operation, the VXT will delay and feed one additional cycle.
LOCKOUT FLOOD PROTECTION: The VXT locks-out to prevent steam sys- tem flooding and costly water damage if burner operation does not resume after two
consecutive feed cycles.
INSTALLATION
Step ➊– Warning Step ➋– Plumbing
WARNING – To prevent electrical shock or equipment damage, power must be off during installation or ser­vicing of the con-
serious burns, the boiler should be thoroughly cooled before installing or servicing control. Only qualified personnel may install or service the control in accor­dance with local codes and ordinances. Read instruc­tions completely before proceeding.
We warrant products manufactured by Hydrolevel Company to be free from defects in material and workmanship for a period of two years from the date of manufacture or one year from the date of installation, whichever occurs first. In the event of any claim under this warranty or otherwise with respect to our products which is made within such period, we will, at our option, repair or replace such products or refund the purchase price paid to us by you for such products. In no event shall
trol. To prevent
Feeder must be installed with a manual by-pass. Use isolation valves and unions to allow easy removal for service or replacement.
Note: Arrow on VXT valve indicates direction of water flow.
LIMITED MANUFACTURER’S WARRANTY
Hydrolevel Company be liable for any other loss or damage, whether direct, indirect, incidental or consequential. This war­ranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or guarantee, express or implied, includ­ing, without limitation, any warranty of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be assigned or transferred and any unauthorized transfer or assignment thereof shall be void and of no force or effect.
P.O. Box 1847 • New Haven, CT 06508 • Phone: (203) 776-0473 • FAX: (203) 773-1019 • www.hydrolevel.com
Step ➌– Wiring
Select the wiring diagram below that corresponds to the low water cut-off installed on the boiler. Consult boiler manufacturer’s instructions for proper burner terminal connections.
Hydrolevel Safgard Model 450 / CycleGard CG450
STANDARD WIRING STANDARD WIRING
ALTERNATE WIRING: If the power source for the low water
cut-off is separate from the burner circuit, remove the jumper between 1 and P1, connect the red wire to A, con­nect the black wire to the burner circuit hot and the white wire to the burner circuit common.
McDonnell & Miller PS-800 Series
ALTERNATE WIRING: If the power source for the low water cut-off is separate from the burner circuit, do not install jumper between H and C. Connect the red wire to W, con­nect the black wire to the burner circuit hot and the white wire to the burner circuit common.
Honeywell
Float Style Control
Model RW-700 Guard Ring
STANDARD WIRING STANDARD WIRING
ALTERNATE WIRING: If you choose to wire the feeder to a
separate power source from the burner circuit, do not install jumper between 2 and 3. Connect the red wire to 4, the black wire to the hot side of power source and the white wire to common.
ALTERNATE WIRING: If you choose to wire the feeder to a separate power source from the burner circuit, do not install jumper between L1 and A. Connect the red wire to A, the black wire to the hot side of power source and the white wire to common.
Step ➍– Set the Feed Delay
30-Second 2-Minute
(Factory Setting)
4-Minute 6-Minute 8-Minute 10-Minute
NOTE: SELECT ONLY ONE DIPSWITCH CORRESPONDING TO THE DESIRED FEED DELAY.
The feed delay feature is designed to prevent boiler flooding by allowing time for condensate to return to the boiler prior to feeding. If the returns and vents are in good condition, the 2-minute factory setting is usually sufficient. If for any reason con­densate takes longer to return to the boiler (such as old return lines or long horizontal runs), a longer delay setting should be selected.
Step
– Set the Feed Amount
LWCO
(Factory Setting)
1-Gallon 2-Gallon 3-Gallon 4-Gallon 5-Gallon
NOTE: SELECT ONLY ONE DIPSWITCH CORRESPONDING TO THE DESIRED FEED AMOUNT.
CAUTION: BOILER FLOODING CAN OCCUR IF THE FEEDER IS NOT SET PROPERLY.
UNLIKE OTHER FEEDERS, THE 1-GALLON TO 5-GALLON SETTINGS WILL FEED THE FULL
CYCLE REGARDLESS OF WHEN THE WATER REACHES THE LOW WATER CUT-OFF.
LWCO Setting: The VXT feeder is shipped in the LWCO feed setting. When operating in this setting, the VXT will feed only
until the low water cut-off re-energizes the burner circuit (or a maximum of 5 gallons). This will restore boiler operation, but on some applications may only be enough water to satisfy the boiler’s
complete, regardless of when the low water cut-off is satisfied. These settings should be used only when the LWCO setting does not provide adequate water to restore the boiler to a these settings:
Boilers with probe-type cut-offs:
1. With power to the system on and the thermostat off, lower
2. Press the FEED button on the water feeder and, using a
3. Round the time to the nearest minute and set the feeder
Example:
rise from 1/2" below the probe to the normal operating level, round to 1 minute and set the feeder for 1-Gallon.
normal
1 Gallon to 5 Gallon Settings: When the 1 to 5 Gallon settings are used, the feeder will continue to feed until the cycle is
the water level to approximately 1/2" below the probe.
watch with a second hand, time how long it takes boiler water to reach the middle of the gauge glass unless otherwise specified by the boiler manufacturer).
for the corresponding number of gallons.
operating level, the 1-Gallon to 5-Gallon settings should be selected using the instructions below.
normal
If it takes 1 minute and 15 seconds for water to
operating level (Usually the
minimum
normal
requirements. If additional water is needed to reach the
operating level. Use the following instructions when choosing
Boilers with float-type cut-offs:
1. With power to the system on and the thermostat off, lower the water level until 1/4" is visible in the gauge glass.
2. Press the FEED button on the water feeder and, using a watch with a second hand, time how long it takes boiler water to reach the middle of the gauge glass unless otherwise specified by the boiler manufacturer).
3. Round the time to the nearest minute and set the feeder for the corresponding number of gallons.
Example:
rise from 1/4" in the gauge glass to the normal operating level, round to 2 minutes and set the feeder for 2-Gallons.
If it takes 2 minutes and 10 seconds for water to
normal
operating level (Usually the
Step ➏– Attach Service Tag
Complete the information at the top of the service tag provided and attach tag near the VXT Water Feeder.
Feed Counter
The VXT’s built-in feed counter records the number of gallons that enter the boiler during automatic feed cycles FEED button is pressed.* To determine how much water has been added to the boiler since the last service, the counter should be checked, recorded, and reset each time the boiler is serviced. The counter reset (DISPLAY RST) button is located in the bottom right corner of the circuit board.
The addition of water to a boiler raises the oxygen level and accumulates lime and other mineral deposits over time. Excessive feed cycles, resulting from leaks in the system, can cause cast iron boilers to oxidize (rust) internally, significantly reducing the life of the boiler. Lime and sediment build-up can impede heat transfer causing damage and/or premature failure of the boiler.
Recommended Limits on Make-Up Water
Many factors, such as the water capacity of the boiler, feed water con­ditions and boiler design can impact the amount of water that can safe­ly be added to a steam boiler. As a general guideline for late model boilers, Hydrolevel recommends the monthly limits in the table at the right for boiler operation during the heating season. If feed amounts significantly exceed these levels, the system should be checked for leaks by a qualified technician. Note: Any feed limits provided by the boiler manufacturer supercede Hydrolevel recommendations. Please check the boiler manufacturer’s instructions carefully.
*The VXT Feeder is equipped with an orifice to regulate flow rates over a wide range of water pressures. The Feed Counter readings are designed to be accurate to ±15% with water pressures between 20 to 90 PSI.
Recommended Make-Up Water Limits
Net IBR Rating Gal/month
MBH Limit
Up to 90,000 6
91,000 - 120,000 8 121,000 - 150,000 10 151,000 - 185,000 12
185,000 & Higher 15
Note: The above limits are based on normal boiler operation during the heat­ing season. They do not include water added as a result of boiler and/or low water cut-off maintenance.
or
when the
Service / Maintenance
Check Feeder Operation: Feeder operation should be checked annually during boiler servicing to ensure proper operation and feed amount.
Record and Reset Feed Counter: The feed counter should be checked annually. If the feed amount falls within the recom­mendations provided in the table above, record this amount on the card provided and press the reset button (DISPLAYRST) on the bottom right corner of the circuit board. Note: If the feed amount significantly exceeds the recommendations above, the system should be checked for leaks by a qualified technician.
Trouble Shooting
If LOC appears in the digital counter, this indicates that the safety lockout feature is activated. This feature
gized the burner. The feeder can be reset by briefly interrupting power to the heating system. Important: The following trouble shooting steps should be taken to determine the cause of the lockout condition before restoring normal operation.
1. If the boiler is overfilled, the low water cut-off is not functioning properly. Using the manufacturer’s instructions, check the low water cut-off operation.
2. If the boiler is in low water:
a. Check boiler and return piping for leaks. b. If no leaks are detected, check to determine if the flow of the feeder is restricted. Check isolation valves around feeder
c. Check the feeder setting to ensure that it is set to feed adequate water in the event of a low water condition.
engages only when the feeder completes two consecutive feed cycles and the low water cut-off does not re-ener-
to ensure they are fully opened.
If ERR appears in the digital counter, this indicates that more than one or no delay or feed button has been select­ed. See Step 4 and Step 5 for DELAY and FEED setting instructions.
P.O. Box 1847 • New Haven, CT 06508 • Phone: (203) 776-0473 • FAX: (203) 773-1019 • www.hydrolevel.com
Loading...