Hydrolevel OS-100 User Manual

MODEL OS-100
Outdoor Sensor Kit
for Model 3200-Plus and Model 3250-Plus Fuel Smart HydroStats
manufactured after 0/0/11
Kit Includes
• Outdoor Reset Sensor with 9-foot cable
• Sensor mounting bracket with 2 screws and 1 wire clip
• Two spade connectors
• Knockout wire bushing
installing or servicing control. Only qualified personnel may install or service this control in accordance with local codes and ordinances. Read instructions completely before proceeding.
This document provides instructions for connecting the Hydrolevel Outdoor Sensor Kit to an installed Fuel Smart HydroStat control. For information on installing the HydroStat control, please refer to the installation instructions provided with the control or log onto www.hydrolevel.com.
Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before
CAUTION
should be thoroughly cooled before installing or servicing control.
To prevent serious burns, boiler
Before installation, determine the proper location for the sensor
• Sensor should be mounted on the northern outside wall of the house, shielded from direct sunlight.
• Sensor should be installed high enough off the ground to protect it from accidental damage or drifting snow.
• Sensor should be installed away from potential heat sources such as exhaust fans, windows, or doors.
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.com
1
INSTALLING THE SENSOR
STEP 1 Using the
two screws and wire clip provided, attach the sensor bracket to the side of the house.
STEP 3 Using an extended wood
or masonry bit, drill a ¼" hole through the side of the house at a location giving the best access to the boiler and the HydroStat control.
WARNING: Use caution to select the hole location away from wires or piping within the house wall.
WIRING
STEP 2 Secure the
sensor on the bracket by pressing it down into the slotted hole as shown above.
STEP 4 Feed the sensor cable
through the hole and into the house. Seal the hole with a bead of silicone or other appropriate caulking material.
STEP 5 Inside the house, route
the sensor cable to the HydroStat control. Splice in an additional length of wire as needed and, using a crimping tool or pliers, terminate with the two spade connectors pro­vided.
NOTE: To avoid interference with the sensor signal, do not run the sensor cable close to any other wiring such as telephone, cable, power, etc.
Locate the three quick connect posts on the HydroStat circuit board. The sensor cable will plug into two of these terminals depending on the features to be used.
OUTDOOR RESET AND WARM WEATHER SHUTDOWN Attach the spade connectors to the right and center spade posts (OR and C) for full outdoor reset
functionality including warm weather shutdown protec­tion. Wiring this way overrides the Thermal Targeting function of the Fuel Smart HydroStat control.
WARM WEATHER SHUTDOWN ONLY
Connect the wire ends to the left and center spade connectors (WWSD and C) to add warm weather shut­down functionality only. When wired this way, the Fuel Smart HydroStat control will utilize its internal Thermal Targeting function to reset the boiler temperature.