Automatically shuts off burner, after delay, in a low water
condition to prevent dry firing.
CG470 Series
Low Water Cut-Offs
For Steam Boilers
120 VAC Operating Voltage
Max. Pressure 15 psi
U.S. Patent Nos. 5,739,504 & 6,390,027
MOUNTING THE CONTROL
The probe may be
installed in the boiler
above the lowest safe
water level established by
the boiler manufacturer.
Most manufacturers provide a suitable tapping in
the side of the boiler.
SAFE
WATER
LINE
Enhanced Intermittent Level Test technology – active only
when water is at boiling temperature. Provides added protection in foaming and volatile water conditions.
Time delay sequencing prevents burner short-cycling caused
by momentary dips in water level and allows a water feeder
to replenish water to a level above the probe.
Integral temperature sensor provides High Limit Lock-Out
feature for an unprecedented level of boiler protection.
STEP 1 Screw the probe
into the LWCO tapping in the boiler. Allow 1/4" clearance from the
probe to any boiler surface, tube
or baffle. NOTE: Excessive use of
Teflon tape to seal probe piping
threads may insulate the control
from boiler ground. This could
result in the control not operating.
1/4"
STEP 2 Loosen the two control cover screws and remove the cover.
Assemble the chassis to the probe flange and secure with the screws provided.
WARNING
installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.
WARNING
is recommended for unattended dwellings in climates subject to sustain below-freezing temperatures.
Electrical shock hazard. To prevent electrical shock, death or
equipment damage, disconnect power supply before
Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages,
safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.com
STEP 3 Plug the wire lead from the probe into the
mating connection on the circuit board.
1
CAUTION
should be thoroughly cooled before installing or
servicing control.
To prevent serious
burns, boiler
WIRING – Model CG470
1 2 3
Connect input voltage (120 VAC, 60 HZ) to
terminals 1 and 2.
4
Connect terminal 2 to burner circuit neutral.
Connect terminal P2 to burner Circuit in
series with other limit controls. Consult boiler manufacturer instructions for proper terminal connections. Control should be wired
in series with and before other limit controls.
Detail of SmartCycle Connection
Model CG470
Optional water feeder connection.
Connect feeder N to terminal 2. Connect Feeder
H to terminal 1. Connect feeder “FEED” or “W”
to terminal A. For water feeders with 2 leads,
connect feeder neutral to terminal 2 and feeder
hot to terminal A.
NOTE: Use of a solenoid valve or McDonnell &
Miller Model 101A water feeder may cause
flooding and is not recommended for use with
this low water cut-off.
OPTIONAL ACTIVATION
Connect “SMTCYC” terminal on the
CycleGard control to the orange burner wire
(120VAC) located under the primary. See
detail illustration at the right.
See SmartCycle description on next page.
2