711 Series
Low Water Cut-Off
Feeder Combination
for Steam Boilers
120 VAC Operating Voltage
WARNING: Power must be off during installation or servicing of the control. Only qualified personnel may install or service the
control in accordance with local codes and ordinances. Read instructions completely before proceeding. Caution – Disconnect power
supply before beginning installation to prevent electrical shock or equipment damage.
HOW TO INSTALL
1
No moving parts in water.
No floats to hang-up or foul.
Unique two probe design. Bouncing
water line wonʼt cause on-off burner
cycling or water valve slamming
noise.
Easy installation. Quick hook-up
fittings adapt control to all 8" to 14"
sight glasses.
Simple fast wiring. Can be used with
any standard automatic water feeder.
(2) 6" x 1/2" brass nipples
(1) 1/2" x 1/2" x 3/8" tee
(1) 1/2" x 1/2" x 1/2" tee
(1) 2" x 1/2" brass nipple
(1) 711C manifold casting
(1) 3/8" copper tube
(2) 3/8" compression fittings
(1) 3/4" nipple (not included)
(1) Blow down valve
(not included)
Remove gauge glass assembly and nipples replacing nipples with two 6" brass nipples provided.
Install 1/2" x 1/2" x 3/8" teeon top nipple.
2 34
Install 1/2" x 2" brass nippleand 1/2" x 1/2" x
1/2" teeto 1/2" threaded hole in casting.
Note: Casting is designed for either left or right
mounting on gauge glass. Be sure to plug hole on
opposite side.
Thread tee attached to casting into bottom 6" nipple. Tighten until casting is vertical.
Install compression fittingsinto casting and
top tee. Size copper tubingand tighten
between the two compression fittings.
5 67
Attach control to probes using No. 8-32 self tapping screws provided. Install blow down valve (by
others) in bottom 3/4" tapped hole. Be sure to
attach maintenance tag in prominent place near
valve.
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.com
Reattach gauge glass cocks and gauge glass into
end of 1/2" tees. Pressure-trol can be threaded
into 1/8" threaded hole on top of casting. If pressure-trol is not used, plug 1/8" hole on top of
casting.
Attach blue probe lead wire to upper probe and
white probe lead wire to bottom probe with wing
nuts and lock washers provided.
WIRING METHOD A:
SAME POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.
A1
must be supplied to terminals G and H for internal
operation of the control.
Install a jumper between terminal H
and terminal P(1). Power from terminal
P(1) is supplied to terminal P(2) when water
reaches the upper probe. Power to terminal P(2)
is removed when water falls below the bottom
probe.
A3 A4
burner circuit in series with other limit controls.
Consult boiler manufacturer’s instructions for
proper terminal connections. NOTE: Control is
wired in series with and before other limits.
Feeder Connection: Connect feeder
common to terminal G. Connect feeder
hot to terminal V. Whenever water falls below the
lower probe, power is supplied to the feeder terminal V. When water reaches the upper probe,
power to the feeder is removed.
Connect input voltage (120 VAC, 60HZ)
A1
to terminals G and H. 120 VAC, 60HZ
Connect terminal G to burner circuit
A3
neutral. Connect terminal P(2) to
A2
A2
A4
WIRING METHOD B:
B1 B2
B3 B4
SEPARATE POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.
Connect input voltage (120 VAC, 60HZ)
B1
must be supplied to terminals G and H for internal
operation of the control.
Connect hot lead from burner
control circuit to terminal P(1).
This terminal supplies power to terminal P(2) in
normal operating conditions when water is at the
probe. Connect neutral to burner circuit.
NOTE: Consult boiler manufacturer’s instructions
for proper terminal connections.
Consult boiler manufacturer’s instructions for
proper terminal connections. NOTE: Control is
wired in series with and before other limits.
Feeder Connection: Connect feeder
common to terminal G. Connect
feeder hot to terminal V. Whenever water falls
below the lower probe, power is supplied to the
feeder terminal V. When water reaches the upper
probe, power to the feeder is removed.
to terminals G and H. 120 VAC, 60HZ
Connect terminal P(2) to burner circuit
B3
in series with other limit controls.
B2
B4
NOTE: All schematic diagrams show all systems in
the off position. No power applied.