Hydrolevel 450 User Manual

Low maintenance. No moving parts to wear stick or hang up, as in float devices.
Solid state circuitry. Designed for the highest level of perfor-
450 Series
mance and reliability. Automatically shuts off burner, after delay, in a low water
Low Water Cut-Offs For Steam Boilers
120 VAC Operating Voltage Max. Pressure 15 psi
condition to prevent dry firing. Time delay allows water to feed above the probe to a safe
operating level.
HOW TO INSTALL
1 2 3
SAFE WATER LINE
1/4"
WARNING – To prevent electrical shock or equipment damage, power must be off during installation or servicing of the control. To pre­vent serious burns, the boiler should be thor­oughly cooled before installing or servicing con­trol. Only qualified personnel may install or ser­vice the control in accordance with local codes and ordinances. Read instructions completely before proceeding.
The probe may be installed in the boiler above the lowest safe water level established by the boiler manufacturer. Most manufacturers pro­vide a suitable opening in the side of the boiler.
R E M O T E M O U N T E D M O D E L S O N L Y
BA
A. To secure mounting plate to boiler jacket,* pre-drill two 3/32" pilot holes using the mount­ing plate as a template. Secure plate with sheet metal screws provided. Attach control to mounting plate by slipping keyholes in back of chassis over pre-mounted screws on plate. Tighten screws.
B. Using a wire nut, attach a wire (min 90°C) to the pigtail lead in the control box. Attach the other end to the probe terminal in the remote probe housing. Attach a second wire between the ground screw on the control chassis and one of the four screws in the remote probe housing. Note: Wires and wire nuts not provided.
*Or other suitable surface
P.O. Box 1847 New Haven, CT 06508 Phone: (203) 776-0473 FAX: (203) 773-1019
Allow 1/4" clearance from the probe to any boiler surface, tube or baffle. NOTE: Excessive use of Teflon tape to seal probe piping threads may insulate the control from boiler ground. This could result in the control not operating.
4
Loosen the two control cover binding head screws and remove the cover. Assemble the chassis to the probe flange and secure with the screws provided with the probe.
5
Connect the ring terminal wire lead to the probe terminal stud and secure with the lock washer and wing nut provided. With the power removed, proceed with installation and wiring according to the instructions on page 2. Upon completion of wiring replace control cover.
+
0
LIMIT
CONTROLS
AP2P112
BURNER CIRCUIT
HOT
NEUTRAL
FEEDER
OR ALARM
HOT
NEUTRAL
BURNER CIRCUIT
AP2P112
BURNER
POWER
SOURCE
(24 or
120VAC)
BURNER
POWER
SOURCE
120VAC
AP2P112
FACTORY INSTALLED JUMPER
NEUTRAL
HOT
BURNER
POWER
SOURCE
120VAC
+
0
LIMIT
CONTROLS
AP2P112
HOTNEUTRAL
BURNER CIRCUIT
120V
AC
AP2P112
REMOVE JUMPER
NEUTRAL
HOT
+
0
LIMIT
CONTROLS
AP2P112
BURNER CIRCUIT
HOT
NEUTRAL
BURNER
POWER
SOURCE
120VAC
+
0
LIMIT
CONTROLS
AP2P112
BURNER CIRCUIT
WATER
FEEDER
WIRING METHOD A: SAME POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.
A1
A1 Connect input voltage (120 VAC, 60 HZ)
to terminals 1 and 2. 120 VAC, 60 HZ must be supplied to terminals 1 and 2 for internal opera­tion of the control.
A2 A3
A2 Connect terminal 2 to burner circuit neu-
tral. Connect terminal P2 to burner Circuit in series with other limit controls. Consult boiler manufacturer instructions for proper terminal connections. Control should be wired in series with and before other limit controls.
WIRING METHOD B: SEPARATE POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.
B1
B1Remove jumper between terminals 1
and P1. Connect input voltage (120 VAC, 60 HZ) to terminals 1 and 2. 120 VAC 60 HZ must be supplied to terminals 1 and 2 for inter­nal operation of the control.
A3 Optional water feeder connection.
Connect feeder N to terminal 2. Connect Feeder H to terminal 1. Connect feeder “FEED” or “W” to terminal A. For water feeders with 2 leads, connect feeder neutral to terminal 2 and feeder hot to terminal A. Note: Use of a solenoid valve
or McDonnell & Miller Model 101A water feeder may cause flooding and is not recommended for use with this low water cut-off.
B2
B3
Connect hot lead from the burner
B2
control circuit to terminal P1. This terminal sup­plies power to terminal P2 in normal operating conditions when water is at the probe. Connect neutral to burner circuit. Note: consult boiler manufacturer instructions for proper terminal connections.
B3 Connect terminal P2 to burner circuit
B4
in series with and before other limit controls.
Optional water feeder connection.
B4
Connect feeder H to terminal P1. Connect feeder “FEED” or “W” to terminal A. Connect terminal N to neutral of the burner circuit supply. For feeders with two leads, connect feeder hot to terminal A and connect feeder neutral to neutral of the burner circuit supply. Note: Use of sole-
noid valve or McDonnell & Miller model 101A water feeder may cause flooding and is not rec­ommended for use with this low water cut-off.
Loading...
+ 2 hidden pages