• Universal Design – Replaces common cold-start and triple-action
• Operating Indicators – LEDs, Dynamic Display and Test Button provide
• Prioritizes Domestic Hot Water – Gives priority to low limit setting or to
• Reduces Condensation – Holds circulator off until boiler reaches 125°F
•
Three Function
Design
Temperature Limit Control
Designed for cold start and tankless
coil boilers.
Low Water Cut-Off
Provides protection against potentially
dangerous low water conditions
when installed with the Hydrolevel
Electro-Well™ (see page 2 for details).
Thermal Pre-Purge capability
Shut-Down capability with the addition of Hydrolevel OS-100 Outdoor
Sensor Kit (sold separately)
Aquastats*
continual and on-demand status checks
calls from indirect water heater
*Aquastat is a registered trademark of Honeywell International, Inc.
Boiler Reset Control
Thermal Targeting – On-board micro-
•
processor adjusts boiler temperature
based on heating demand.
Outdoor Reset Ready – Compatible with
•
Hydrolevel OS-100 Outdoor Sensor Kit
(sold separately) for outdoor reset and
warm weather shut-down functionality.
WARNING
installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.
WARNING
is recommended for unattended dwellings in climates subject to sustain below-freezing temperatures.
Electrical shock hazard. To prevent electrical shock, death or
equipment damage, disconnect power supply before
Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages,
safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.com
CAUTION
should be thoroughly cooled before installing or
servicing control.
To prevent serious
burns, boiler
1
IMMERSION WELLS
Fuel Smart HydroStat can be installed on a Hydrolevel Electro-Well™ or on an existing immersion well already in the boiler.
IMPORTANT: The control will only provide low water cut-off protection when installed on an Electro-Well™.
Installing HydroStat
with Hydrolevel Electro-Well™
When installed on an Electro-Well™ (sold separately), the Low Water Cut-Off
function is automatically activated. Heat transfer grease should not be used.
NOTE: For proper operation, there must be 1/2" clearance between the copper well tube and any furnace within the boiler.
See Electro-Well™ models on page 15.
When installing on a standard immersion well, the LWCO function should
be turned off (see page 10 for instructions). A buildup of heat transfer
grease or other coatings in older wells can interfere with continuity between
the sensor and the well causing a false low water shutdown. Turning off the
LWCO function will prevent this from occurring.
Installing HydroStat
with Standard Immersion Well
MOUNTING THE CONTROL
IMPORTANT Make sure that the immersion well or Electro-Well™ is installed in the boiler manufacturer’s designated
temperature limit control tapping.
NNOOTTEE::
If i
nstalling an Electro-Well™, pipe sealing compound should be used. Teflon tape is not recommended.
STEP 1
are available on the back of the control
(Fig. 1). Select which of the two positions
(2 knockouts) is best for the location of
the control. Remove the knockout.
FUEL SMART HYDROSTAT BOX
FIG. 1FIG. 3FIG. 2
NOTE: In the case of space restrictions, the Fuel Smart HydroStat control may be mounted in a horizontal orientation without any
loss of function. Hydrolevel recommends vertical mounting, when possible, for proper orientation of LED display.
REMOTE MOUNTING KITS are available separately for mounting the Fuel Smart HydroStat control box in a remote location.
Each kit includes mounting hardware and a remote sensor. See page 16 for kit options.
Two mounting positions
BACK OF
STEP 2 Place control on the well.
While holding box against well nut,
tighten well clamp screw. (Fig. 2)
STEP 3 Insert sensor ALL THE
WAY into well through the knockout (A
or B) you have chosen. (Fig. 3)
2
WIRING
WARNING
STEP 1 Connect 120 VAC Hot to terminal L1. Connect
120 VAC Neutral to terminal L2. Disconnect means and
overload protection as required (provided by others).
Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before
installing or servicing this control.
STEP 2 Connect the burner circuit to B1-B2.
(B2 is neutral.)
Select the Diagram that
Matches your System Configuration
on Pages 4, 5 or 6
3
WIRING
WARNING
NOTE: For proper operation of the boiler reset function, all heating thermostats must input to T-T or ZC-ZR terminals as indicated below.
Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before
installing or servicing this control.
Jumping the T-T terminals and wiring the thermostat to the primary will override the economy feature.
STEP 3A: HEATING ONLY – No Indirect Water Heater
CHOOSEORBELOW
SINGLE CIRCULATORMULTIPLE CIRCULATORS
Connect thermostat or end switch from zone relay or multizone panel to T-T. Connect circulator to C2-C1. Move
Zone/Indirect Switch up to Z.
ZONE/
INDIRECT
SWITCH
POSITION
ZONE/
INDIRECT
SWITCH
POSITION
Connect end switch from circulator relay or multi-zone panel to
ZC-ZR. Move Zone/Indirect Switch up to Z.
STEP 3B: HEATING and Indirect Water Heater
IMPORTANT:
bypass the Thermal Targeting feature and allow the boiler to fire to the high limit setting to heat the indirect tank. The indirect signal must be separate from all
heating zone signals. If you choose not to separate the indirect signal from the heating zones, the Economy Feature should be turned OFF to ensure that the
boiler supplies adequate temperature to heat the indirect tank (see page 7).
Connect thermostat or end switch from zone relay or multi-zone
panel to T-T. Connect circulator to C2-C1. Connect end switch
from indirect zone relay to ZC-ZR. Move
down to I.
When installing with an indirect water heater, the Zone/Indirect Switch must be set in the I position. When set in the I position, calls to ZC-ZR will
CHOOSE FROM
THROUGHBELOW OR ON PAGE 5 OR 6
SINGLE CIRCULATORMULTIPLE CIRCULATORS
Zone/Indirect
ZONE/
INDIRECT
SWITCH
POSITION
Switch
Connect end switch from heating circulator relays or multi-zone
panel to T-T. Connect end switch from indirect circulator relay toZC-ZR. Move Zone/Indirect Switch to I.
ZONE/
INDIRECT
SWITCH
POSITION
4
WIRING
WARNING
NOTE: For proper operation of the boiler reset function, all heating thermostats must input to T-T or ZC-ZR terminals as indicated below.
Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before
installing or servicing this control.
Jumping the T-T terminals and wiring the thermostat to the primary will override the economy feature.
STEP 3B: HEATING and Indirect Water Heater – continued
MULTIPLE CIRCULATORS — Typical Zone Panel with Priority Zone
ZONE/
INDIRECT
SWITCH
POSITION
NOTE: The wire from ZR to the hot terminal of the indirect circulator will ensure
that indirect calls will fire to limit and receive priority over heating calls.
SINGLE CIRCULATOR — Multiple Zone Valves including Indirect, No Zone Control Panel
NOTE: When using zone valves for both heat and indirect, the calls must be separated in order to prioritize indirect calls. This can
be accomplished by using a general purpose relay as shown above. However, for ease of installation, a zone control panel is recommended (see wiring diagram 7 on next page).
ZONE/
INDIRECT
SWITCH
POSITION
MORE
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.