MODEL 3200
INSTALLATION INSTRUCTIONS
and OPERATING MANUAL
Temp Limit / LWCO Control
with Thermal Targeting
™
for Water Boilers
120 VAC Input / 24 VAC Burner Circuit
PATENT PENDING
• Saves Fuel – Features Thermal Targeting™ technology and
• Universal Design – Replaces common cold-start and triple-action
• Easy to Install – Industry standard wiring, dial-type settings,
• Operating Indicators – LEDs, Dynamic Display and Test Button provide
• Prioritizes Hot Water – Gives priority to low limit setting or to calls from
• Reduces Condensation – Holds circulator off until boiler reaches 120°F
•
Three Function
Design
Temperature Limit Control
Designed for cold start and tankless
coil boilers.
Low Water Cut-Off
Provides protection against potentially
dangerous low water conditions
when installed with the Hydrolevel
Electro-Well™ (see page 2 for details).
hermal Pre-Purge capability
T
quastats*
A
o external sensors
n
continual and on-demand status checks
indirect water heater
*Aquastat is a registered trademark of Honeywell International, Inc.
Boiler Reset Control
Utilizes
technology to conserve fuel by
monitoring heating demand and
establishing target boiler temperatures
below the high limit setting (see page 4
for details).
WARNING
installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.
Thermal Targeting
Electrical shock hazard. To prevent electrical shock, death or
equipment damage, disconnect power supply before
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.com
™
CAUTION
should be thoroughly cooled before installing or
servicing control.
To prevent serious
burns, boiler
1
IMMERSION WELLS
Fuel Smart HydroStat can be installed on an existing immersion well already in the boiler or on a Hydrolevel Electro-Well™
(sold separately). The low water cut-off function is automatically activated when installed on an Electro-Well™.
IMPORTANT: The control will not provide low water cut-off protection when installed on a standard immersion well.
NOTE: Do not use heat-conducting grease.
Fuel Smart HydroStat installed
with Hydrolevel Electro-Well™
IMPORTANT: For proper operation of the low water cut-off function, there
must be a minimum of ½" clearance between the copper well tube and any
surface within the boiler.
See Electro-Well models on page 8.
NOTE: When installed on a standard immersion well, the “LWCO Active”
LED will not illuminate.
Fuel Smart HydroStat installed
with standard immersion well
MOUNTING THE CONTROL
IMPORTANT Make sure that the immersion well or Electro-Well™ is installed in the boiler manufacturer’s designated
temperature limit control tapping.
NNOOTTEE::
If installing an Electro-Well, pipe sealing compound should be used. Teflon tape is not recommended.
STEP 1
are available on the back of the control
(Fig. 1). Select which of the two positions
(2 knockouts) is best for the location of
the control. Remove the knockout.
Two mounting positions
STEP 2 Place control on the well.
While holding box against well nut,
tighten well clamp screw. (Fig. 2)
STEP 3 Insert sensor ALL THE
WAY into well through the knockout (A
or B) you have chosen. (Fig. 3)
BACK OF
FUEL SMART HYDROSTAT BOX
FIG. 1 FIG. 3FIG. 2
NOTE: In the case of space restrictions, the Fuel Smart HydroStat control may be mounted in a horizontal orientation without any
loss of function. Hydrolevel recommends vertical mounting, when possible, for proper orientation of LED display.
REMOTE MOUNTING KITS are available separately for mounting the Fuel Smart HydroStat control box in a remote location.
Each kit includes mounting hardware and a remote sensor. See page 8 for kit options.
2
WIRING
WARNING
STEP 1
terminal L1. Connect 120 VAC Neutral
to terminal L2. Disconnect means and
overload protection as required (provided by others).
Connect 120 VAC Hot to
Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before
installing or servicing this control.
STEP 2 Connect the burner
circuit to B1-B2. (B2 is neutral.)
STEP 3 Connect the circulator
to C1-C2. (C2 is neutral.)
ZONE VALVE WIRING
MPORTANT: Use a separate transformer to
I
power zone valves. Connecting zone valves to
Z-TV may overload the HydroStat and cause a
lock-out condition (see
for more information). The total load, including the
burner circuit, vent damper, and Z-TV connections
must not exceed 1.2 amps (30 VA). Connect zone
valve end-switch to T-TV as shown below.
Troubleshooting
on page 6
STEP 4 Connect the thermostat
to T-TV.
STEP 5
with a plug-in style vent damper, unplug
the factory installed jumper from the
receptacle on the circuit board and
replace it with the vent damper plug.
NOTE: Once a vent damper plug is
connected to the HydroStat, the control
is permanently altered and will no
longer function when the vent damper
plug is disconnected
If the boiler is equipped
.
STEP 6 For Systems with Indirect Water Heaters
When installing with an indirect water heater, the signal from the indirect must be
separated from the heating zone signals and wired to I1 and I2 as shown above.
Calls to I1 and I2 will bypass the Thermal Targeting feature and allow the boiler to
fire to the high limit setting to heat the indirect tank.
NOTE: If you choose not to separate the indirect signal from the heating zones,
the Economy Feature should the turned OFF to insure that the boiler supplies adequate temperature to heat the indirect tank (see page 4).
3