Combination Low Water
Cut-Off & Universal
Temperature Limit Control
for Oil-Fired Boilers
PATENT NO. 7,891,572
Dual Function
Design
Temperature Limit Control
Designed for cold start and tankless
coil boilers.
• Replaces Common Aquastat*Models – Can be installed on existing immersion
wells to replace both cold-start and triple-action Aquastats
designations make change-outs quick and easy.
• Digital Display – Easy to read LED continually displays boiler temperature. Also displays
temperature limit and differential settings during adjustment.
• Easy to Set – Dials for setting temperature limits and differentials eliminate complicated
programming.
• Thermal Pre-Purge Feature – Conserves fuel and meets 2012 DOE regulations by
circulating latent heat in the boiler to the heating zone before firing the burner.
• *Aquastat is a registered trademark of Honeywell International, Inc.
®
. Industry standard wiring
Low Water Cut-Off
Provides protection against potentially
dangerous low water conditions
when installed with the Hydrolevel
Electro-Well™ (see page 2 for details).
WARNING
installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.
WARNING
is recommended for unattended dwellings in climates subject to sustain below-freezing temperatures.
Electrical shock hazard. To prevent electrical shock, death or
equipment damage, disconnect power supply before
Frozen pipes/water damage. Central heating systems are prone to shut down as a result of power or fuel outages,
safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions
CAUTION
should be thoroughly cooled before installing or
servicing control.
To prevent serious
burns, boiler
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 • www.hydrolevel.com
1
IMMERSION WELLS
Fuel Smart HydroStat can be installed on a Hydrolevel Electro-Well™ or on an existing immersion well already in the boiler.
IMPORTANT: The control will only provide low water cut-off protection when installed on an Electro-Well™.
Installing HydroStat
with Hydrolevel Electro-Well™
When installed on an Electro-Well™ (sold separately), the Low Water Cut-Off
function is automatically activated. Heat transfer grease should not be used.
NOTE: For proper operation, there must be 1/2" clearance between the copper well tube and any furnace within the boiler.
See Electro-Well™ models on page 11.
When installing on a standard immersion well, the LWCO function should
be turned off (see page 6 for instructions). A buildup of heat transfer grease
or other coatings in older wells can interfere with continuity between the
sensor and the well causing a false low water shutdown. Turning off the
LWCO function will prevent this from occurring.
Installing HydroStat
with Standard Immersion Well
MOUNTING THE CONTROL
IMPORTANT Make sure that the immersion well or Electro-Well™ is installed in the boiler manufacturer’s designated
temperature limit control tapping.
NNOOTTEE::
If installing an Electro-Well, pipe sealing compound should be used. Tef
lon tape is not recommended.
STEP 1
are available on the back of the control
(Fig. 1). Select which of the two positions
(2 knockouts) is best for the location of
the control. Remove the knockout.
FIG. 1FIG. 3FIG. 2
NOTE: In the case of space restrictions, the Fuel Smart HydroStat control may be mounted in a horizontal orientation without any
loss of function. Hydrolevel recommends vertical mounting, when possible, for proper orientation of LED display.
REMOTE MOUNTING KITS are available separately for mounting the Fuel Smart HydroStat control box in a remote location.
Each kit includes mounting hardware and a remote sensor. See page 12 for kit options.
Two mounting positions
BACK OF
HYDROSTAT BOX
STEP 2 Place control on the well.
While holding box against well nut,
tighten well clamp screw. (Fig. 2)
STEP 3 Insert sensor ALL THE
WAY into well through the knockout (A
or B) you have chosen. (Fig. 3)
2
WIRING
WARNING
STEP 1
terminal L1. Connect 120 VAC Neutral
to terminal L2. Disconnect means and
overload protection as required (provided by others).
Connect 120 VAC Hot to
Electrical shock hazard. To prevent electrical shock, death or equipment damage, disconnect power supply before
installing or servicing this control.
STEP 2 Connect the circulator to
C1 and C2. (C2 is neutral.)
STEP 3 Connect the burner cir-
cuit to B1 and B2. (B2 is neutral.)
STEP 4 Connect the thermostat to
T and T.
SCHEMATIC/LADDER DIAGRAM
Multi-Zones Adding additional zones.
3
SETTING THE CONTROL
Dynamic
Display
Water Temperature
and Real Time
Verification of
Setting Adjustments.
Low Temperature
Limit Setting
(OFF or 110°-200°F)
Factory OFF
Low Temperature
Differential Setting
(10°-30°F)
Factory 10°F
NOTE: Be careful not to select overlapping temperature settings.
For example: If the HIGH TEMPERATURE LIMIT is set at
190°F with a HIGH TEMPERATURE DIFFERENTIAL set at 20°F,
then the LOW TEMPERATURE LIMIT needs to be set at 170°F
(190°F - 20°F = 170°F) or below.
IMPORTANT: To prevent flue gas condensation and reduce
fatigue caused by thermal cycling on conventional (non-condensing) boilers, both HIGH and LOW LIMIT set points should be
150°F or above (Limit Setting - Differential Setting ≥ 150°F).
Boiler manufacturerʼs temperature requirements supercede these
recommendations.
Diagnostic LEDs
Test/Settings Button
Jumper
High Temperature
Limit Setting
(100°-220°F)
Factory 190°F
High Temperature
Differential Setting
(10°-30°F)
Factory 10°F
To set COLD START operation
Operates on call for heat only.
Low Temperature Limit
Make sure Low Temperature Limit is turned fully
counter-clockwise (OFF position).
Low Temperature Differential
No change is required.
High Temperature Limit
(factory setting = 190°F)
Adjust setting until desired temperature is displayed.
High Temperature Differential
(factory setting = 10°F)
Using a small screwdriver, adjust setting until
desired differential is displayed.
To set WARM START operation
Maintains temperature for domestic hot water.
Low Temperature Limit
Adjust setting until desired temperature is displayed. Prior to adjusting, remove the jumper
located at the top right corner of the circuit board
(not equipped on all units).
IMPORTANT: If low limit temperature cannot
be set above 140°F, remove jumper.
Low Temperature Differential
Using a small screwdriver, adjust setting until
desired differential is displayed.
High Temperature Limit
(factory setting = 190°F)
Adjust setting until desired temperature is displayed.
High Temperature Differential
(factory setting = 10°F)
Using a small screwdriver, adjust setting until
desired differential is displayed.
OPERATION
4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.