Hydrolevel 170 User Manual

170 Series Low Water Cut-Off
120 VAC Operating Voltage
Heavy-duty electro-mechanical design for long life. Automatically shuts off burner in a low water condition to
prevent boiler damage. Low maintenance. No moving parts to wear stick or hang up,
as in float devices. Rugged construction. Designed for the heating professional.
WARNING: To prevent electrical shock or equip-
ment damage, power must be off during installation or servicing of the control. To prevent serious burns, the boiler should be thorough­ly cooled before installing or servic­ing control. Only qualified personnel may install or service the control in accordance with local codes and ordinances. Read instructions com­pletely before proceeding.
2. Tee Options
STANDARD
REDUCING TEE
(SV Models Only)
FABRICATED TEE
1. Where To Install
HOT WATER BOILER INSTALLATIONS
B
A
MINIMUM
WATER LEVEL
FOEM-TEE
(160psi)
1214C-2 TEE
(250psi)
C
D
HOT WATER BOILER
HOT WATER BOILERS: Probe must be installed at or above the minimum safe water level established by the boiler manufacturer. The probe may be installed directly in the boiler if a suit­able tapping is available (A), in the riser (B), or in the header (C) or (D).
IMPORTANT: To assure proper drainage, pipe diameter should be no less than 1" on installations in vertical piping and no less that 1 tions in horizontal piping.
3. Probe Installation
1
4" on installa-
TEE MOUNTING: If a field fabricated tee is used, make sure that the tee drains thoroughly when the water level falls below it, and that it conforms to the spacing requirements described in Step 3. Models equipped with the shorter EL1214-SV probe can be installed in most standard reducing tees. Safgard cast iron tees are also available to accommodate all probe models (See page 4).
4. Control Mounting
Loosen the two control box cover bind­ing head screws and remove the cover.
Slide keyhole slots over probe mounting screws and tighten screws (with either a 1/4" hex head driver or flat screwdriver).
Connect the ring terminal wire lead to the probe terminal stud and secure with the lock washer and wing nut provided. With the power removed, proceed with installation and wiring according to Method A or B described on next page.
Check to insure 1/4" clearance from probe to any surface within the boiler or tee. When installed in a tee, the probe tip should extend fully into the pipe run. Apply pipe sealing com­pound to threads. Note: Use of Teflon tape is not recommended.
P1 P2 A
+
0
LIMIT
CONTROLS
BURNER CIRCUIT
NEUTRAL
HOT
2
1
ALARM
P1 P2 A
HOT
BURNER CIRCUIT
NEUTRAL
2
1
BURNER
POWER
SOURCE
(
24 or
120VAC)
P1 P2 A
NEUTRAL
HOT
BURNER
+
0
LIMIT
CONTROLS
2
1
2
P1 P2
A
BURNER
POWER
SOURCE
24 V
AC
1
NEUTRAL
HOT
FACTORY
INSTALLED
JUMPER
1
P1P2 A
ALARM
2
P2 A
24V
AC
1
NEUTRAL
HOT
P1
P1 P2 A
+
0
LIMIT
CONTROLS
BURNER CIRCUIT
HOT
NEUTRAL
2
1
WIRING METHOD A: SAME POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.
A1
A3
A1 Connect the hot lead of the input volt-
age (24 VAC, 60 HZ) to terminal 1. Connect the neutral lead to terminal 2. 24 VAC, 60 HZ must be supplied to terminals 1 and 2 for internal operation of the control.
Connect terminal 2 to burner
A2
circuit neutral. Connect terminal P2 to burner circuit in series with other limit controls. Consult boiler manufacturer instructions for proper terminal connections. Control should be wired in series with and before other circuits.
A3 Optional alarm connection. Connect
alarm common to terminal 2. Connect alarm hot to terminal A.
Upon completion of wiring, replace control box cover.
A2
WIRING METHOD B: SEPARATE POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.
B1
B3
B1 WARNING! Remove the jumper
between 1 and P1. Connect the hot lead of the input voltage (24 VAC, 60 HZ) to terminal 1. Connect the neutral lead to terminal 2. 24 VAC, 60 HZ must be supplied to terminals 1 and 2 for internal operation of the control.
Connect hot lead from the 24 VAC
B2
or 120 VAC burner power source to terminal P1. This terminal supplies power to terminal P2 in normal operating conditions when water is at the probe. Connect neutral to burner circuit. Note: consult boiler manufacturer instructions for proper terminal connections.
B3 Connect terminal P2 to burner
circuit in series with and before other limit con­trols.
Optional alarm connection. Connect
B4
alarm hot to terminal A. Connect alarm common to neutral of the burner power source.
Upon completion of wiring, replace control box cover.
WARNING: Be sure to
remove the jumper between 1 and P1.
B2
B4
OPERATIONAL TEST PROCEDURE
Important: Do not run boiler unattended until the following procedure is completed.
1. After wiring is complete and prior to raising the water level above the probe set the thermostat to call for heat. The burner should not fire. IMPORTANT: If the boiler fires with no water at the probe, immediately shut down the boiler and refer to Trouble Shooting Instructions below.
2. Proceed to fill the system with water. When water reaches probe position burner should fire. If burner does not fire with water at the probe refer to Trouble Shooting Instructions below.
MAINTENANCE
When installed on a residential hot water heating system, the probe should be removed and cleaned every five years. When installed on a commercial application, the probe should be removed and cleaned annually. After cleaning the probe, perform the Operational Test Procedure described above.
TROUBLE SHOOTING
IF THE BURNER DOES NOT SHUT DOWN WHEN WATER DROPS BELOW THE PROBE.
1. Remove power immediately and re-check wiring.
2. Remove power and check for adequate clearance from the probe to any surface within the boiler or tee.
IF THE BURNER DOES NOT FIRE.
1. Make sure water is at the probe and probe lead wire is properly secured to probe.
2. Check for proper ground between probe and boiler shell. Excessive use of Teflon tape or sealing compound may insulate the probe from the boiler shell.
3. Check to insure probe is not surrounded by an air pocket. Slowly loosen, but do not remove, the probe with a wrench. Allow any air to escape. When water begins to seep past probe threads, retighten probe.
4. Re-check wiring and test for correct incoming voltage.
A
NEW
VXT Water Feeder with
Digital Feed Counter
D
B
Hydrolevel... The Safe Choice
C
E
for Every Boiler!
Hydrolevel offers a complete line of electronic low water cut-offs and liquid level controls, including the NEW VXT water feeder with digital feed counter… everything to give you peace of mind on all Whether it’s hot water or steam, residential or commercial, Hydrolevel makes the right control to complete your installation with safety.
P.O. Box 1847 • New Haven, CT 06508 (203) 776-0473 • Fax (203) 773-1019 TOLL FREE 800-654-0768
www.hydrolevel.com
AA..
el 550 Low Water Cut-Off for hot water boilers,
Mod dential hot water boilers, DD..
el VXT-24 Programmable Water Feeder,
Mod
your installations.
BB..
CC..
CG400 foam-compensating Low Water Cut-Off for steam boilers,
Model
Model 170SV Low Water Cut-Off for resi-
EE ..
Model 250WC Pump Contoller/Low Water Cut-Off.
FITTINGS
2"
SQUARE
17/8"
313/16"
15
/16"
1"
3
/4" NPT
5
/16"
2"
SQUARE
11/16"
3"
15
/16"
1"
3
/4" NPT
5
/16"
2"
SQUARE
17/8"
49/16"
1"
3
/4" NPT
5
/16"
111/16"
59/16
11/16
51/2
31/16
BACK
37/8
15/8
11/8
15/8
23/8
BOTTOM
Controls equipped with the EL1214-SV Probe can be mounted in standard reducing tees (supplied by others). Safgard manifolds, listed below, can be used with all probe models.
MODEL PSI SIZE
FOEM-1 160 1 1/2" x 1 1/2" x 3/4"NPT
FOEM-2 160 1" x 1" x 3/4"NPT
FOEM-3 160 1 1/4" x 1 1/4" x 3/4"NPT
1214C-2 TEE 250 1" x 1" x 3/4"NPT
FOEM MANIFOLD 1214C-2 TEE
PROBE DATA
Test Pressure: 1000 PSI, All Models
EL1214 – STANDARD MODEL – 3/4" NPT
For 1/2", order Model EL1220
EL1214-SV – 3/4" NPT
For 1/2", order No. EL1220-SV
EL1214-P – 3/4" NPT
CAUTION: When installing probe, make sure there is a minimum of 1/4" clearance from probe tip to any surface.
DIMENSIONS SPECIFICATIONS
MAXIMUM PRESSURE: 160 PSI INPUT VOLTAGE: 24 VAC, 60 HZ SWITCH RATINGS: 5.8 FLA, 34.8 LRA SWITCH CONTACTS: SPDT ALARM CIRCUIT: 50 VA @ 24 VAC
LIMITED MANUFACTURERʼS WARRANTY
We wa rra nt pro duc ts man ufa ctu red by Hydrolevel Company to be free from defects in material and workmanship for a period of two years from the date of manufacture or one year from the date of installation, whichever occurs first. In the event of any claim under this warran­ty or otherwise with respect to our products which is made within such period, we will, at our option, repair or replace such products or refund the purchase price paid to us by you for such products. In no event shall Hydrolevel Company
be liable for any other loss or damage, whether direct, indirect, incidental or consequential. This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or guarantee, express or implied, including, without limitation, any warranty of MERCHANTABILITY or fitness for a particular purpose. This warranty may not be assigned or transferred and any unauthorized transfer or assignment thereof shall be void and of no force or effect.
P.O. Box 1847 New Haven, CT 06508 Phone: (203) 776-0473 FAX: (203) 773-1019
Pilot Duty
45-2400
Loading...