Hydra Kool KGL-OF-50-S, KGL-OF-40-S, KGL-OF-40-R, KGL-OF-60-S, KGL-OF-60-R Installation And Operation Manual

...
Page 1
DOE
Compliant
KGL SERIES - INSTALLATION AND OPERATION MANUAL - V0
Page 2
2
MVP GROUP CORPORATION
5659 Royalmount Ave.
H4P 2P9
Telephone: (514) 737-9701
Toll Free Telephone: (888) 275-4538
Fax: (514) 342-3854
Toll Free Fax: (877) 453-8832
Email: sales@mvpgroupcorp.com
Website: www.mvpgroupcorp.com
Page 3
3
INDEX
1 General information 5
1.1 Case description 5
2 Getting started with your KGL series 26
2.1 Location 26
2.2 Uncrating 27
2.3 Check for damage 28
2.4 Control panel and main features 29
2.5 Check serial, model numbers and requested options 33
2.6 Warning/Caution labels 35
2.7 Check your electrical installation 41
2.7.1 Cord connected 41
2.7.2 Permanently connected (remotes only) 42
2.8 Electrical, drain and refrigeration connections (remotes only) 43
2.9 Joining 44
2.10 Plugging and start 50
3 Refrigeration 54
3.1 Self contained refrigeration equipment and defrost 54
3.2 Refrigeration loads (remotes only) 56
4 Electrical 56
4.1. Electrical specifications data 56
4.3. Electrical diagrams 58
4.4. Electronic controller 90
5 Maintenance 93
5.1 Cleaning 93
5.2 Shelf removing/adjustment 94
5.3 Light substitution 94
5.4 Panels and protection grille removal 95
5.5 Condenser cleaning 96
5.6 Evaporator cleaning 96
5.6.1 Evaporator back cleaning (KGL-DL/RS/RM only) 97
5.7 Evap Pan cleaning 98
5.8 Drain inspection 99
5.9 Electric shutter 99
5.9.1 Manual operation 99
5.9.2 Setting position 100
6 Troubleshooting/Service 100
6.1 Troubleshooting 100
6.2 Service 101
7 Warranty 103 8 Notes 104
Page 4
4
This page has been left blank intentionally.
Page 5
5
1 General information
1.1 Case description
KGL series model (number) system.
KGL RS 40 S AAA BB CC D
AAA
BB
CC
D
Model variation
RS-Rear doors and electrical shutter
OF-Open front
OS-Open front and electrical shutter
DL-Open front and rear doors
RM-Rear doors and manual shutter
Length
40''
50''
60''
Type of Unit.
S-Self Contained
R-Remote
Basic model
| | | | | |
| | | |
| | | |
Page 6
6
34''
60''
12''
16''
11''
12''
10''
23''
22''
KGL SERIES
KGL-OF-XX-S(R)
41''
KGL-OF-40-S(R)
Page 7
7
50''
61''
KGL-OF-50-S(R)
KGL-OF-60-S(R)
Page 8
8
KGL-RS/RM-XX-S(R)
KGL-RS/RM-40-S(R)
41''
36''
60''
12''
16''
11''
12''
10''23''
23''
Page 9
9
KGL-RS/RM-50-S(R)
KGL-RS/RM-60-S(R)
50''
61''
Page 10
10
KGL-DL-XX-S(R)
36''
60''
12''
16''
11''
12''
10''
23''
23''
KGL-DL-40-S(R)
41''
Page 11
11
KGL-DL-50-S(R)
50''
KGL-DL-60-S(R)
61''
Page 12
12
KGL-OS-XX-S(R)
34''
12''
16''
65''
22''
23''
12''
10''
11''
KGL-OS-40-S(R)
41''
Page 13
13
KGL-OS-50-S(R)
50''
KGL-OS-60-S(R)
61''
Page 14
14
KGL-OF-40-S(R)
Front
3''
2''
8''
5''
9''
12''
34''
21''
6''
2''
38''
5''
21''
Implantation
Drain outlet
Electrical board
Refrigeration piping
Page 15
15
Front
KGL-OF-50-S(R)
34''
6''
26'' 25''
5''
8''9''
5''
3''
2''
12''
47
2''
Page 16
16
KGL-OF-60-S(R)
34''
6''
31''
31''
5''
3''
2''
12''
57''
2''
8''9'' 5''
Front
Page 17
17
KGL-RS/RM-40-S(R)
34''
6''
26''
25''
5''
8''9'' 5''
3''
2''
8''
38''
2''
4''
2''
Drain outlet
Electrical board
Refrigeration piping
Electrical wiring
Front
Page 18
18
KGL-RS/RM-50-S(R)
34''
6''
26'' 25''
5''
8''9''
5''
3''
2''
12''
47''
2''
4''
2''
Front
Page 19
19
KGL-RS/RM-60-S(R)
34''
6''
31''
31''
5''
3''
2''
12''
57''
2''
8''9'' 5''
4''
2''
Front
Page 20
20
KGL-DL-40-S(R)
34''
6''
21'' 21''
5''
8''9'' 5''
3''
2''
8''
38''
2''
Drain outlet
Electrical board
Refrigeration piping
Front
Page 21
21
KGL-DL-50-S(R)
34''
6''
25'' 26''
5''
8''9'' 5''
3''
2''
12''
47''
2''
Front
Page 22
22
KGL-DL-60-S(R)
34''
6''
31'' 31''
5''
8''9'' 5''
3''
2''
12''
57''
2''
Front
Page 23
23
KGL-OS-40-S(R)
34''
6''
21''
21''
5''
8''
9''
5''
3''
2''
12''
2''
3''
2''
38''
Drain outlet
Electrical board
Refrigeration piping
Electrical wiring
Front
Page 24
24
KGL-OS-50-S(R)
34''
6''
25''
26''
5''
8''9''
5''
3''
2''
12''
2''
3''
7''
37''
Front
Page 25
25
KGL-OS-60-S(R)
34''
6''
31'' 31''
5''
8''9'' 5''
3''
2''
12''
57''
2''
12''
3''
Front
Page 26
26
KGL series intended for grab-n-go, beverage and produce, are type 1 equipment ­75°F/55%RH. Temperature of the KGL-OF/OS cases is set for 36°F. Temperature of the KGL-RS/DL/RM cases is set for 39°F.
All shelves of the KGL series have a 31 lb/ft loading limit.
Model
Dimensions
(LxDxH in inches)
Service
dimensions
(LxDxH in inches)
13,0 19,9 16,2 13,0 19,9 16,2 13,0 19,9 16,2 13,0 19,9 16,2
Volume (ft³)
40³'' x 591'' x 33'' 50'' x 591'' x 33'' 60'' x 591'' x 33'' 40³'' x 591'' x 35'' 50'' x 591'' x 35'' 60'' x 64'' x 35'' 40³'' x 64'' x 33'' 50'' x 64'' x 33'' 60'' x 64'' x 33'' 40³'' x 64'' x 35'' 50'' x 64'' x 35'' 60'' x 64'' x 35''
40³'' x 591'' x 35'' 50'' x 591'' x 35'' 60'' x 591'' x 35'' 40³'' x 591'' x 51'' 50'' x 591'' x 56'' 60'' x 64'' x 61'' 40³'' x 591'' x 35'' 50'' x 591'' x 35'' 60'' x 591'' x 35'' 40³'' x 64'' x 51'' 50'' x 64'' x 56'' 60'' x 64'' x 61''
KGL-OF-40-S(R) KGL-OF-50-S(R) KGL-OF-60-S(R) KGL-DL-40-S(R) KGL-DL-50-S(R) KGL-DL-60-S(R) KGL-OS-40-S(R) KGL-OS-50-S(R) KGL-OS-60-S(R) KGL-RS/RM-40-S(R) KGL-RS/RM-50-S(R) KGL-RS/RM-60-S(R)
| | | | | | | | | | | |
| | | | | | | | | | | |
| | | | | | | | | | | |
2 Getting started with your KGL series
2.1 Location
To your new equipment perform well please respect the following warnings:
This is type 1 equipment, inte nded to work with 75°F / 55%RH.
This equipment is intended for maintaining temperature only.
Be sure products are not ambient temperature (must be cold)
This equipment must be located in an indoor environment.
Check for airdrafts and avoid them.
Air movement from ac units shouldn’t be directed to the equipment.
The equipment must not be directly or indirectly exposed to the sun.
Check for rejected heat from another refrigeration units and avoid that.
Page 27
27
Place the equipment in a levelled floor.
Do not obstruct the air way in front of the condenser.
Make sure there is a drain preparation (remotes only).
KGL series with shutter must be handled carefully. Open and close shutter only when needed.
Models to be positioned against a wall keep a safe distance of 2''.
This equipment should be handled by a qualified technician.
2.2 Uncrating
All operations must be done carefully.
All plastic protective films must be removed before using the equipment for
the first time.
2
1
Page 28
28
3
4
2.3 Check for damage
At the end of production HYDRA KOOL products are carefully inspected. No damaged units are sent out. HYDRA KOOL doesn’t take responsibility for damage between factory and client.
Possible damage on the unit must be checked to file a claim near the transportation company.
The unit must be checked in the following points:
Exterior panels
Doors
Shelves
Glasses
Paint job
Door handles
Base structure
Shutter
Page 29
29
CAUTION
DISCONNET ALL POWER.
MAY HAVE MORE THEN
ONE DISCONNET SWITCH
CAUTION
RISK OF ELECTRIC SHOK.
DISCONNECT ALL POWER BEFORE SERVICING UNIT
ATTENTION
DEBRANCHER TOUTE
COURANT.
IL PEUT AVOIR PLUS D’UN
INTERRUPTEUR
ATTENTION
RISQUE DE CHOC
ELECTRIQUE. AVANT TOUT TRAVAIL COUPER LE COURANT
Self contained control panel (KGL-OF/DL only)
Electronic controller
Light switch
Power signal
Condensing unit switch
Hot key connector
Electrical board
2.4 Control panel and main features
The pictures below, shows the main features and all necessary controls.
CAUTION
DO NOT OPEN MANUALLY.
IN CASE OF ELECTRICAL FAILURE
FOLLOW THE INSTRUCTIONS IN THE
INSTALLATION AND OPERATION
MANUAL.
ATTENTION
NE PAS OUVRIR MANUELLEMENT.
EN CAS DE PANNE ELECTRIQUE SUIVRE LES INSTRUCTIONS D’INSTAL­LATION ET DE FONCTIONNEMENT DU
MODE D’EMPLOI.
CAUTION
FOR THE SHUTTER CORRECT OPEN­ING AND CLOSING OPERATIONS, IT IS MANDATORY FOR ALL THE SHUTTERS
RAILS TO BE CLEAR AND
UNOBSTRUCTED.
ATTENTION
POUR OUVERTURE ET FERMETURE CORRECTE DU VOLET ROULANT, IL EST OBLIGATOIRE POUR TOUTES
LES COULISSES DU VOLET ROULANT
D’ETRE DEGAGEES ET
DEBARRASSEES.
CAUTION
DISCONNET ALL POWER. MAY HAVE MORE THEN
ONE DISCONNET SWITCH
CAUTION
RISK OF ELECTRIC SHOK.
DISCONNECT ALL POWER BEFORE SERVICING UNIT
Self contained control panel (KGL-RS only)
Electrical board
ATTENTION
DEBRANCHER TOUTE
COURANT.
IL PEUT AVOIR PLUS D’UN
INTERRUPTEUR
ATTENTION
RISQUE DE CHOC
ELECTRIQUE.
AVANT TOUT TRAVAIL
COUPER LE COURANT
Hot key connector
Electronic controller
Light switch
Power signal
Condensing unit switch
Shutter control
Page 30
30
CAUTION
DISCONNET ALL POWER.
MAY HAVE MORE THEN
ONE DISCONNET SWITCH
CAUTION
RISK OF ELECTRIC SHOK.
DISCONNECT ALL
POWER BEFORE SERVICING UNIT
ATTENTION
DEBRANCHER TOUTE
COURANT.
IL PEUT AVOIR PLUS D’UN
INTERRUPTEUR
ATTENTION
RISQUE DE CHOC
ELECTRIQUE.
AVANT TOUT TRAVAIL
COUPER LE COURANT
Self contained control panel (KGL-OS only)
CAUTION
FOR THE SHUTTER CORRECT OPEN­ING AND CLOSING OPERATIONS, IT IS MANDATORY FOR ALL THE SHUTTERS
RAILS TO BE CLEAR AND
UNOBSTRUCTED.
ATTENTION
POUR OUVERTURE ET FERMETURE CORRECTE DU VOLET ROULANT, IL
EST OBLIGATOIRE POUR TOUTES
LES COULISSES DU VOLET ROULANT
D’ETRE DEGAGEES ET
DEBARRASSEES.
CAUTION
DISCONNET ALL POWER.
MAY HAVE MORE THEN
ONE DISCONNET SWITCH
CAUTION
RISK OF ELECTRIC SHOK.
DISCONNECT ALL POWER BEFORE SERVICING UNIT
Self contained control panel (KGL-RM only)
Electrical board
ATTENTION
DEBRANCHER TOUTE
COURANT.
IL PEUT AVOIR PLUS D’UN
INTERRUPTEUR
ATTENTION
RISQUE DE CHOC
ELECTRIQUE. AVANT TOUT TRAVAIL COUPER LE COURANT
Hot key connector
Electronic controller
Light switch
Power signal
Condensing unit switch
Hot key connector
Electronic controller
Light switch
Power signal
Condensing unit switch
Shutter control
Electrical board
Page 31
31
CAUTION
DO NOT OPEN MANUALLY.
IN CASE OF ELECTRICAL FAILURE
FOLLOW THE INSTRUCTIONS IN THE
INSTALLATION AND OPERATION
MANUAL.
ATTENTION
NE PAS OUVRIR MANUELLEMENT.
EN CAS DE PANNE ELECTRIQUE SUIVRE LES INSTRUCTIONS D’INSTAL­LATION ET DE FONCTIONNEMENT DU
MODE D’EMPLOI.
CAUTION
FOR THE SHUTTER CORRECT OPEN­ING AND CLOSING OPERATIONS, IT IS MANDATORY FOR ALL THE SHUTTERS
RAILS TO BE CLEAR AND
UNOBSTRUCTED.
ATTENTION
POUR OUVERTURE ET FERMETURE CORRECTE DU VOLET ROULANT, IL
EST OBLIGATOIRE POUR TOUTES
LES COULISSES DU VOLET ROULANT
D’ETRE DEGAGEES ET
DEBARRASSEES.
Remote control panel (KGL-OF/DL only)
Hot key connector
Electronic controller
Light switch
Power signal
Condensing unit switch
CAUTION
DO NOT OPEN MANUALLY.
IN CASE OF ELECTRICAL FAILURE
FOLLOW THE INSTRUCTIONS IN THE
INSTALLATION AND OPERATION
MANUAL.
ATTENTION
NE PAS OUVRIR MANUELLEMENT.
EN CAS DE PANNE ELECTRIQUE
SUIVRE LES INSTRUCTIONS D’INSTAL-
LATION ET DE FONCTIONNEMENT DU
MODE D’EMPLOI.
CAUTION
FOR THE SHUTTER CORRECT OPEN­ING AND CLOSING OPERATIONS, IT IS MANDATORY FOR ALL THE SHUTTERS
RAILS TO BE CLEAR AND
UNOBSTRUCTED.
ATTENTION
POUR OUVERTURE ET FERMETURE CORRECTE DU VOLET ROULANT, IL
EST OBLIGATOIRE POUR TOUTES
LES COULISSES DU VOLET ROULANT
D’ETRE DEGAGEES ET
DEBARRASSEES.
Electrical board
CAUTION
DISCONNET ALL POWER.
MAY HAVE MORE THEN
ONE DISCONNET SWITCH
CAUTION
RISK OF ELECTRIC SHOK.
DISCONNECT ALL
POWER BEFORE
SERVICING UNIT
ATTENTION
DEBRANCHER TOUTE
COURANT.
IL PEUT AVOIR PLUS D’UN
INTERRUPTEUR
ATTENTION
RISQUE DE CHOC
ELECTRIQUE. AVANT TOUT TRAVAIL COUPER LE COURANT
Remote control panel (KGL-RS only)
Hot key connector
Electronic controller
Light switch
Power signal
Condensing unit switch
Shutter control
Page 32
32
CAUTION
DO NOT OPEN MANUALLY.
IN CASE OF ELECTRICAL FAILURE
FOLLOW THE INSTRUCTIONS IN THE
INSTALLATION AND OPERATION
MANUAL.
ATTENTION
NE PAS OUVRIR MANUELLEMENT.
EN CAS DE PANNE ELECTRIQUE SUIVRE LES INSTRUCTIONS D’INSTAL­LATION ET DE FONCTIONNEMENT DU
MODE D’EMPLOI.
CAUTION
FOR THE SHUTTER CORRECT OPEN­ING AND CLOSING OPERATIONS, IT IS MANDATORY FOR ALL THE SHUTTERS
RAILS TO BE CLEAR AND
UNOBSTRUCTED.
ATTENTION
POUR OUVERTURE ET FERMETURE CORRECTE DU VOLET ROULANT, IL
EST OBLIGATOIRE POUR TOUTES
LES COULISSES DU VOLET ROULANT
D’ETRE DEGAGEES ET
DEBARRASSEES.
Remote control panel (KGL-OS only)
CAUTION
FOR THE SHUTTER CORRECT OPEN­ING AND CLOSING OPERATIONS, IT IS MANDATORY FOR ALL THE SHUTTERS
RAILS TO BE CLEAR AND
UNOBSTRUCTED.
ATTENTION
POUR OUVERTURE ET FERMETURE CORRECTE DU VOLET ROULANT, IL
EST OBLIGATOIRE POUR TOUTES
LES COULISSES DU VOLET ROULANT
D’ETRE DEGAGEES ET
DEBARRASSEES.
Electrical board
CAUTION
DISCONNET ALL POWER.
MAY HAVE MORE THEN
ONE DISCONNET SWITCH
CAUTION
RISK OF ELECTRIC SHOK.
DISCONNECT ALL
POWER BEFORE SERVICING UNIT
ATTENTION
DEBRANCHER TOUTE
COURANT.
IL PEUT AVOIR PLUS D’UN
INTERRUPTEUR
ATTENTION
RISQUE DE CHOC
ELECTRIQUE. AVANT TOUT TRAVAIL COUPER LE COURANT
Remote control panel (KGL-RM only)
Hot key connector
Electronic controller
Light switch
Power signal
Condensing unit switch
Hot key connector
Electronic controller
Light switch
Power signal
Condensing unit switch
Shutter control
Page 33
33
Shutter
Night curtain
Return air grille
Discharge air grille
Only for rear doors model.
2.5 Check serial, model numbers and requested options
Before starting your equipment, check the serial number, model numbers and requested options. This inspection should be made visually in the following items:
Page 34
34
Self contained numbers
Remote numbers
Page 35
35
Label 5 Label 3 Label 1 Label 11
Label 23
Label 12 Label 2 Label 4 Label 6
Label 9 Label 7 Label 8
Label 10
Label 9 Label 10
Label 7
Label 8
2.6 Warning/Caution labels
Before starting, HYDRA KOOL products have caution and warning labels to be respected.
Self contained labels
Self contained labels (RS/MR only)
Page 36
36
Label 9 Label 10
Label 7
Label 8
Label 13 Label 14
Remote labels
Self contained and remote labels (evaporator)
Label 23
Page 37
37
Self contained labels (OS/RS only)
KGL-OS-XX-S KGL-RS-XX-S KGL-RM-XX-S
Label 17 Label 18 Label 15 Label 16
Label 17 Label 18 Label 15 Label 16
Label 17
Label 18
Remote labels (OS/RS only)
KGL-OS-XX-R KGL-RS-XX-R KGL-RM-XX-R
Label 17 Label 18 Label 15 Label 16
Label 17 Label 18 Label 15 Label 16
Label 17 Label 18
Page 38
38
Shutter rails (OS/RS only)
Label 20
Label 22
Label 19 Label 21
ATTENTION
PIÈCES MOBILES.
NE FAIRE PAS
FONCTIONNER AVEC
DES PIÈCES ENLEVER
CAUTION
MOVING PARTS. DO NOT OPERATE UNIT WITH (PART) REMOVED
Label 1 Label 2
Label 20
Label 22
Label 19
Label 21
Shutter rails (RM only)
Page 39
39
Label 3 Label 4
-NOTE-
CETTE VITRINE TYPE 1 EST CONÇUE POUR FONCTIONNER SELON LES CONDITIONS DU
MAGASIN ET NE DOIT
DÉPASSER
75 F AND 55% R.H.
-NOTE-
THIS A TYPE 1 CASE AND IS
DESIGNED TO OPERATE AT
THE FOLLOWING STORE
CONDITIONS THAT DOES NOT
EXCEED
75 F AND 55% R.H.
Label 5 Label 6
-NOTE-
CET EQUIPEMENT EST PREVU
UNIQUEMENT POUR LE
STOCKAGE ET EXPOSITION DE
PRODUITS ALIMENTAIRES
EMBALLER
-NOTE-
THIS EQUIPMENT IS INTENDED
FOR THE STORAGE
AND DISPLAY OF PACKAGED
FOOD PRODUCTS ONLY
CAUTION
DISCONNET ALL POWER.
MAY HAVE MORE THEN
ONE DISCONNET SWITCH
Label 7 Label 8
ATTENTION
DEBRANCHER TOUTE
COURANT.
IL PEUT AVOIR PLUS D’UN
INTERRUPTEUR
Label 9 Label 10
ATTENTION
RISQUE DE CHOC
ELECTRIQUE.
AVANT TOUT TRAVAIL
COUPER LE COURANT
CAUTION
RISK OF ELECTRIC SHOK.
DISCONNECT ALL
POWER BEFORE SERVICING UNIT
Page 40
40
Label 11 Label 12
CAUTION
HOT PARTS. DO NOT OPERATE UNIT WITH (PART) REMOVED
ATTENTION
PIÈCES BRULANTES.
NE FAIRE PAS
FONCTIONNER AVEC LES
PIÈCES ENLEVER
CAUTION
HAZARDOUS MOVING PARTS.
DO NOT OPERATE UNIT
WITH DECK PANS
ATTENTION
PIÈCES MOBILES DANGEREUSES. NE FAIRE PAS FONCTIONNER AVEC
DES PIÈCES ENLEVER
Label 13
Label 15
Label 14
Label 16
CAUTION
DO NOT OPEN MANUALLY.
IN CASE OF ELECTRICAL FAILURE
FOLLOW THE INSTRUCTIONS IN THE
INSTALLATION AND OPERATION
MANUAL.
ATTENTION
NE PAS OUVRIR MANUELLEMENT.
EN CAS DE PANNE ELECTRIQUE SUIVRE
LES INSTRUCTIONS D’INSTALLATION ET DE
FONCTIONNEMENT DU MODE D’EMPLOI.
Label 17
Label 18
CAUTION
FOR THE SHUTTER CORRECT OPEN-
ING AND CLOSING OPERATIONS, IT IS
MANDATORY FOR ALL THE SHUTTERS
RAILS TO BE CLEAR AND
UNOBSTRUCTED.
ATTENTION
POUR OUVERTURE ET FERMETURE
CORRECTE DU VOLET ROULANT, IL
EST OBLIGATOIRE POUR TOUTES
LES COULISSES DU VOLET ROULANT
D’ETRE DEGAGEES ET
DEBARRASSEES.
Page 41
41
2.7 Check your electrical installation
2.7.1 Cord connected
This equipment must be connected to an outlet with 115V/ 60Hz/ 1 phase.
For the wright connection check tension and frequency stated In the marking plate.
Label 23
Label 21 Label 22
KEEP SHUTTER RAILS CLEAR!
MAINTENIR LES
COULISSES du volet roulant dégagées !
Label 19
KEEP SHUTTER RAILS CLEAR!
Label 20
MAINTENIR LES
COULISSES du volet roulant dégagées !
Nema-5-15P
Nema-5-20P
Warning
- This appliance requires a properly grounded dedi­cated circuit using a NEMA rated wall receptacle do not remove the grounding prong on the plug or the risk of an injury due to shock from the ungrounded electrical service may occur.
- This product can expose an individual to chemi­cals that have been identied by the state of Cali­fornia to possibly be dangerous leading to various diseases birth defects or other human reproductive system harm. For more information go to www.p65warnings.ca.gov.
Page 42
42
2.7.2 Permanently connected (remotes only)
This equipment must be connected to an outlet with 115V/ 60Hz/ 1 phase or
220V/ 60Hz/ 1 phase
For the wright connection check tension and frequency stated In the marking plate.
To proceed to electrical to safe electrical connections follow the steps below:
-Check connections box behind protection grilles (use proper tool);
-Select wiring accordingly with labeling;
-Check ratings on the nameplate for the tension applicable;
-Open connections box and identify correct connector (check tension);
-Prepare wire through correct passage (hole) and connect the 3 wire cable correctly (check phase/neutral/earth labeling);
-Secure connections;
- Close box;
Page 43
43
Equipments for remote installation come with nitrogen under pressure and an easy prep kit (tubing connections needed only) for installation.
Prepare a drain installation
2.8 Refrigeration and drain assemblies (remotes only)
Installation and service must be performed by a qualified technician.
Equipments for remote installation come with nitrogen under pressure and an easy prep kit (tubing connections needed only) for installation.
Page 44
44
2.9 Joining
For joining follow the steps described (KGL-OF/DL only).
Page 45
45
2x - DIN933 M6x80
4x - DIN933 M6x25
12x- DIN9021 M6
6x - DIN934 M6
2X FIT00201301 (189'')
1x
1x 1x
1x
13 10
Page 46
46
KIT0004U01000
2x KGL-DL
Page 47
47
2x
1x
1x
10
10
Page 48
48
2X - FIT00201301 (189'')
G
G
Page 49
49
1x - DIN933 M6x80 2x - DIN9021 M6 1x - DIN934 M6
1x - DIN933 M6x25 2x - DIN9021 M6 1x - DIN934 M6
H
I
I
H
H
I
I
I
10
10
+
-
13
13
Page 50
50
2.10 Plugging and start
To start your equipment follow the steps:
1 - Check for page with parameters inside the manual.
2 - After uncrating and placed the equipment respecting all warnings set in 2.1 chapter, and all switches are set to off position, connect the equipment.
Make sure you have the correct outlet!
Page 51
51
Nema-5-20P
3 - Check lights, using button referenced on chapter 2.4. If not working consult the maintenance chapter. KGL-OF/DL/RM only.
3.1 - For KGL-OS/RS, lights and shutter are controlled by key referenced on 2.4 chapter. Turn the key to check lights and shutter. (Open shutter = lights ON)
Open or close shutter only when needed, to prevent motor burning.
4 - Check for shutter normal operation.
4.1 - Electrical shutter.
Keep the shutter rails clear for proper operation.
Turn the key to control the shutter.
Close
Open
Page 52
52
4.2 - Manual shutter.
5 - Turn ON power button referenced in 2.4 chapter.
Noise will be heard when compressor starts! If compressor doesn’t start, call a technician!
6 - Check for air movement in the discharge air grille.
7 - Before loading, leave the equipment working for about 30 min. With night curtain or shutter on.
Rear doors closed (KGL-RS/DL/RM only).
Page 53
53
8 - Load your KGL-Series.
Loading must be done respecting loading limits and weight per square foot mentioned in chapter 1. This equipment is intended for maintaining temperature, be sure the products are cold, and not ambient temperature.
After loading check for any obstruction in the discharge and return air grilles.
1
1
Maintain doors closed after loading. (KGL-DL/RS only)
When loading KGL-OS/RS, using the back doors, objects can fall into the evaporator. Remove them if any encountered there.
Page 54
54
Volumes inside the KGL must respect the refrigerated shelf area.
9 - If any problem encountered, see troubleshooting or call a technician!
3 Refrigeration
3.1 Self contained refrigeration equipment and defrost
The refrigeration equipment it’s laid out in the base of the equipment.
Page 55
55
Compressor
Evap pan
Fan
Condenser
Filter
Controller
Page 56
56
All self contained KBD series use the following equipment: capillary tube, finned coil ventilated systems (condenser/evaporator), hermetic compressor, electrical water evaporation system.
Model
Circuit
pressure
(psig)
Refrigerant
and charge
(OZ)
Defrost
R 404A 24,7 R 404A 26,5 R 404A 33,5 R 404A 35,62 R 404A 31,04 R 404A 46,91
Automatic 4/day Automatic 4/day Automatic 4/day Automatic 4,8/day Automatic 4,8/day Automatic 4,8/day
High side Low side
174 174 174 174 174 174
331 331 331 331 331 331
KGL-OF/OS-40-S KGL-OF/OS-50-S KGL-OF/OS-60-S KGL-DL/RS/RM-40-S KGL-DL/RS/RM-50-S KGL-DL/RS/RM-60-S
| | | | | |
| | | | | |
| | | | | |
3.2 Refrigeration loads (remotes only)
Installation of remote equipment must be done by a qualified technician.
Model
BTU*/h
4125
4897
5141
4190 4982 5835
TS2 TS2 TS2 TS2 TS2 TS2
00 00 00 00 00 00
Expansion
valve type
*values presented are indicative for 14°F evap, and 90°F ambient.
KGL-OF/OS-40-R KGL-OF/OS-50-R KGL-OF/OS-60-R KGL-DL/RS/RM-40-R KGL-DL/RS/RM-50-R KGL-DL/RS/RM-60-R
| | | | | |
| | | | | |
4 Electrical
4.1. Electrical specifications data
Electrical data can be found on the marking plate.
Standard equipment includes led lighting in all shelves and top, and anti sweat heaters. (RS/DL/RM only)
Page 57
57
Model
Fans
EVP CND
0,28
0,28 0,30 0,20
0,42
0,40
0,45
0,9 0,9
0,45
0,9 0,9
6,67 6,67 6,67 6,67 6,67 6,67
0,52 0,52
0,86
16,42
24
24,06
16,86 24,66 25,02
Lights (all shelves
and top)
0,12
0,54
0,19 0,12 0,15 0,19
Compressor
F.L.A./L.R.A.
8,9/47
16/64 16/64
8,9/47
16/64 16/64
Anti sweat heaters
Evap pan
REAR
Total amps
(self contained)
115V/60Hz/1 phase-self contained amps
The data regards to standard options only.
KGL-OF/OS-40-S KGL-OF/OS-50-S KGL-OF/OS-60-S KGL-DL/RS/RM-40-S KGL-DL/RS/RM-50-S KGL-DL/RS/RM-60-S
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
| | | | | |
Model
Total amps
(remote)
0,40
0,43 0,49 0,84
1,09 1,45
KGL-OF/OS-40-R KGL-OF/OS-50-R KGL-OF/OS-60-R KGL-DL/RS/RM-40-R KGL-DL/RS/RM-50-R KGL-DL/RS/RM-60-R
| | | | | |
115V/60Hz/1 phase-remote amps
Page 58
58
KGL-OF/RM-40-S
4.3. Electrical diagrams
IR33F0AHE0
7
1
8
R3
POWER
N
SUPPLY
67
R2
54R12163
5
2
a
1
4
7
6
8 9
10
27
3
5
c
10987
5
6
4
M
M
M
32
12
21
22
9
3 4
20
9
11
N
L
31
29
30
3 A
13
24
2111
A2
A1
14
4
5
1
2
3
11
11109
DI
2
L
N
2
3
1
4
5
M
M
8
Page 59
59
Discription
1 2 3 4 5 6 7 9
11 12 13
20
21
22 27 29
30
31
32
Compressor Overload Relay Start capacitor Condenser fan Controller Temperature probe Terminal block Ground connection Evaporator fan Compressor relay Lamp switch Pilot light Switch Run capacitor Transformer Led lighting Socket Evaporative condensate pan
| | | | | | | | | | | | | | | | | | |
Page 60
60
KGL-OF/RM-50(60)-S
14
A1
A2
11 21
24
13
3 A
30
29
31
L
N
11
9
20
43
9
22
21
12
32
M
M
M
4
M
M
5
65789 10
c
5
3
27
10
9
8
6 7
4
1
a
4
1
2
5
1
32N
L
2
361 2R14 5R276
SUPPLY
N
POWER
R3
7
DI
8 9 10 11
1 1
IR33F0AHE0
4
5
1
2
3
Page 61
61
Discription
1 2 3 4 5 6 7 9
11 12 13
20
21
22 27 29
30
31
32
Compressor Overload Relay Start capacitor Condenser fan Controller Temperature probe Terminal block Ground connection Evaporator fan Compressor relay Lamp switch Pilot light Switch Run capacitor Transformer Led lighting Socket Evaporative condensate pan
50 Inch 60 Inch
1 1 1 1 1 1 1
2
1
3
1 1 1 1 1 1
3
1 1
1 1 1 1 1 1 1
2
1
4
1 1 1 1 1 1
5
1 1
Number
for length
| | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | |
Page 62
62
KGL-RS-40-S
31
30
L
N
29
3 A
32
12
M
M
M
5
M
M
27
10
37
5
3
9
8
6 7
1
1
4
4
5
2
a
c
2 1
4 3 N
L
2
9
11
9
43 65789 10
A2
13
A1
4
3
3
3
3
BA
4
4
0
11 21
14 24
1
5
2
43
M
34
C
44
21
7
DI
22
6
3R11 2
R2
64 5
IR33F0AHE0
R3
SUPPLY
POWER
87
N
1 1
91011
8
Page 63
63
Discription
1 2 3
4
5
6
7
8 9
11 12 13 21
22 27 29
30
31
32 37
43
44
Compressor Overload Relay Start capacitor Condenser fan Controller Temperature probe Earth two pin plug Terminal block Ground connection Evaporator fan Compressor relay Pilot light Switch Run capacitor Transformer Led lighting Socket Evaporative condensate pan Anti sweat heater Electrical shutter A key switch shutter
| | | | | | | | | | | | | | | | | | | | | |
Page 64
64
KGL-RS-50(60)-S
14
A1
A2
11 21
24
13
3 A
30
29
31
L
N
11
9
43
9
12
32
M
M
M
4
M
M
5
65789 10
c
5
3
27
10
9
8
6 7
4
1
a
4
1
2
5
1
32N
L
2
34
0
3
3
3
C
B
A
4
4
43
44
M
37
7
1DI1
1
5
4
3
2
6
R3R1 R2
IR33F0AHE0
SUPPLY
POWER
31 2 64 5 87
N
91011
21
22
Page 65
65
Discription
50 Inch 60 Inch
Number
for length
1 2 3 4 5 6 7 9
11 12 13 21
22 27 29
30
31
32
37 43 44
1 1 1 1 1 1 1
2
1
3
1 1 1 1 1
3
1 1
2
1 1
1 1 1 1 1 1 1
2
1
4
1 1 1 1 1
5
1 1
2
1 1
Compressor Overload Relay Start capacitor Condenser fan Controller Temperature probe Terminal block Ground connection Evaporator fan Compressor relay Pilot light Switch Run capacitor Transformer Led lighting Socket Evaporative condensate pan Anti sweat heater Electrical shutter A key switch shutter
| | | | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | | | |
Page 66
66
M
30
31
32
M
12
M
M
M
29
L
3 A
N
9
8
11
4
20
3
21
9
22
7
5
5
6
3 4 1098
1
6
2
27
3
4
10
7 8 9
4
1
L
2 1
13
A2
A1
1
6
5
5
a
c
2
N3
4
24
2111
14
5
IR33F0AHE0
11
DI
5
2
R1
1 42 3
R27R3
POWER
N
SUPPLY
67 811109
37
KGL-DL-40-S
Page 67
67
Discription
1 2 3 4 5 6 7 9
11 12 13
20
21
22 27 29
30
31
32 37
Compressor Overload Relay Start capacitor Condenser fan Controller Temperature probe Terminal block Ground connection Evaporator fan Compressor relay Lamp switch Pilot light Switch Run capacitor Transformer Led lighting Socket Evaporative condensate pan Anti sweat heater
| | | | | | | | | | | | | | | | | | | |
Page 68
68
M
5 4
30
31
32
12
M
M
M
M
5
3
27
4
10
9
8
6 7
4
5
1
2
1
32N
L
8
29
3 A
L
N
9
20
11
4
22
21
3
9
5
4356 7
1
1
A2
11 21
13
a
c
2
7
IR33F0AHE0
9 10
2
6
1 2
R1
14A124
3 4 5R276
SUPPLY
N
POWER
R3
8DI9 10 11
1 1
37
KGL-DL-50(60)-S
Page 69
69
Discription
50 Inch 60 Inch
Number
for length
1 2 3 4 5 6 7 9
11 12 13
20
21
22 27 29
30
31
32 37
1 1 1 1 1 1 1
2
1
3
1 1 1 1 1 1
3
1 1
2
1 1 1 1 1 1 1
2
1
4
1 1 1 1 1 1
5
1 1
2
Compressor Overload Relay Start capacitor Condenser fan Controller Temperature probe Terminal block Ground connection Evaporator fan Compressor relay Lamp switch Pilot light Switch Run capacitor Transformer Led lighting Socket Evaporative condensate pan Anti sweat heater
| | | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | | |
Page 70
70
43
3
C
7
3
3
B
4
6 3
0
44
9 10 11
SUPPLY
N
R2
POWER
R3
6
R1
4
4
21
24
2
A2
11
A1
14
10
13
1 2 3 4 5 76 8
A
IR33F0AHE0
5
1
7 86
5
394
22
21
9
M
3
2
1
4
N L
1
3 2
2
M
5
c
5
a
5
1
9
10
8
6 7
4
2
3
1
4
M
12
27
M
M
M
4
9
N
L
11
32
31
3 A
29
30
7
1DI1
8
KGL-OS/RM-40-S
Page 71
71
Discription
1 2 3 4 5 6 7 8 9
11 12 13 21
22 27 29
30
31
32
37 43 44
Compressor Overload Relay Start capacitor Condenser fan Controller Temperature probe Earth two pin plug Terminal block Ground connection Evaporator fan Compressor relay Pilot light Switch Run capacitor Transformer Led lighting Socket Evaporative condensate pan Anti sweat heater Electrical shutter A key switch shutter
| | | | | | | | | | | | | | | | | | | | | |
Page 72
72
31
32
11
L
N
9
4
M
M
M
27
12
M
4
1
3
2
4
7
6
8
10
9
1
5
a
5
c
5
M
2
2
3
1
L
N
4
1
2
3
M
9
21
22
493
5
6
87
1
5
IR33F0AHE0
A
86754321
13
10
14
A1
11
A2
2
24
21
4
4
R1
6
R3
POWER
R2
N
SUPPLY
11109
44
0
36
4
B
3
3
7
C
3
43
30
29
3 A
1DI1
7
KGL-OS/RM-50(60)-S
Page 73
73
Discription
50 Inch 60 Inch
Number for
length
1 2 3 4 5 6 7 9 11
12 13
21 22 27 29
30
31 32 37 43
44
1 1 1 1 1 1 1
2
1
3
1 1 1 1 1
3
1 1
2
1 1
1 1 1 1 1 1 1
2
1
4
1 1 1 1 1
5
1 1
2
1 1
Compressor Overload Relay Start capacitor Condenser fan Controller Controller Temperature probe Terminal block Ground connection Evaporator fan Compressor relay Pilot light Switch Run capacitor Transformer Led lighting Socket Evaporative condensate pan Anti sweat heater Electrical shutter A key switch shutter
| | | | | | | | | | | | | | | | | | | | |
| | | | | | | | | | | | | | | | | | | | |
Page 74
74
IR33F0AHE0
7
R3
POWER SUPPLY
R2R1
6
M
M
M
12
21
22
9
20
9
11
N
L
29
30
3 A
4
5
1
2
3
11
DI
5
M
M
39
8
N
675421 3
10987
5
6
34
11109
KGL-OF-40-R
Page 75
75
Discription
1 7 9 11
12
20
21 22 29
30
39
Compressor Temperature probe Terminal block Ground connection Evaporator fan Lamp switch Pilot light Switch Transformer Led lighting Solenoide valve
| | | | | | | | | | |
Page 76
76
KGL-OF-50(60)-R
3 A
30
29
L
N
11
9
20
43
9
22
21
12
M
M
M
M
M
5
65789 10
361 2R14 5R276
SUPPLY
N
POWER
R3
7
DI
8 9 10 11
1 1
IR33F0AHE0
4
5
1
2
3
39
Page 77
77
Discription
50 Inch 60 Inch
Number for
length
6 7 9 11
12
20
21 22 29
30
39
1 1
2
1
3
1 1 1 1
3
1
1 1
2
1
4
1 1 1 1
5
1
Controller Temperature probe Terminal block Ground connection Evaporator fan Lamp switch Pilot light Switch Transformer Led lighting Solenoide valve
| | | | | | | | | | |
| | | | | | | | | | |
Page 78
78
KGL-RS-40-R
30
M
12
M
29
3 A
L
N
9
11
M
5
M
M
37
4
3
34
3A4
3
B
34
C
0
M
43
44
10
5
9
43 6 789
R1
2
1
5
6
1 32R24 65
R3
SUPPLY
POWER
7
N
7
21
22
DI
11
11
8 910
IR33F0AHE0
39
Page 79
79
Controller Temperature probe Earth two pin plug Terminal block Ground connection Evaporator fan Pilot light Switch Transformer Led lighting Anti sweat heater Solenoide valve Electrical shutter A key switch shutter
Discription
6 7 8 9
11 12 21
22 29
30
37 39 43
44
| | | | | | | | | | | | | |
Page 80
80
KGL-RS-50(60)-R
30
29
L
N
9
3 A
11
5
M
12
M
M
M
M
37
4
3
4
A
4
M
44
3
C
43
3
B
3
0
43
4396578910
2
1
5
6
R1 R2
312 4
7
21
22
SUPPLY
POWER
R3
65 7
N
1
8 910
DI
1
11
IR33F0AHE0
39
Page 81
81
Controller Temperature probe Terminal block Ground connection Evaporator fan Pilot light Switch Transformer Led lighting Anti sweat heater Solenoide valve Electrical shutter A key switch shutter
6
7
9
11 12 21
22 29
30
37 39 43
44
1 1
2
1
3
1 1
1 3 2
1
1
1
1 1
2
1
4
1 1
1 5 2
1
1
1
| | | | | | | | | | | | |
| | | | | | | | | | | | |
Discription
50 Inch 60 Inch
Number for
length
Page 82
82
KGL-DL-40-R
M
30
M
12
M
M
M
29
L
3 A
N
9
11
4
20
3
21
9
22
7
5
5
6
3 4 1098
1
6
37
5
IR33F0AHE0
11
DI
5
2
R1
1 42 3
R27R3
POWER
N
SUPPLY
67 811109
39
Page 83
83
Discription
Controller Temperature probe Terminal block Ground connection Evaporator fan Pilot light Switch Transformer Led lighting Anti sweat heater Solenoide valve
6 7 9
11 12 21
22 29
30
37 39
| | | | | | | | | | |
Page 84
84
KGL-DL-50(60)-R
M
30
12
M
M
M
M
5
8
29
3 A
L
N
9
20
11
4
22
21
3
9
5
4356 7
1
37
7
IR33F0AHE0
9 10
2
6
1 2R13 4 5R276
SUPPLY
N
POWER
R3
8DI9 10 11
1 1
39
Page 85
85
Controller Temperature probe Terminal block Ground connection Evaporator fan Lamp switch Pilot light Switch Transformer Led lighting Anti sweat heater Solenoide valve
6
7
9
11 12
20
21
22 29
30
37 39
1 1
2
1
3
1 1 1
1 3 2
1
1 1
2
1
4
1 1 1
1 5 2
1
| | | | | | | | | | | |
| | | | | | | | | | | |
Discription
50 Inch 60 Inch
Number for
length
Page 86
86
44
3
IR33F0AHE0
DI
1
1110987
R3
POWER
N
SUPPLY
1
0
4
B
3
3
A
4
4
7
543R221
R1
2
6
C
6
9 104
5
6
87
1
22
21
9
5
3
M
43
7
5
M
1
2
3
36
M
4
L
N
3 A
29
30
M
M
12
M
9
11
39
KGL-OS-40-R
Page 87
87
Controller Temperature probe Terminal block Ground connection Evaporator fan Pilot light Switch Transformer Led lighting Solenoide valve Electrical shutter A key switch shutter
6 7 9
11 12 21
22 29
30
39 43
44
| | | | | | | | | | | |
Discription
Page 88
88
30
29
3 A
L
N
9
4
M
M
M
12
M
M
5
2
1
3
3
6
7
M
43
21
22
9
43
5
6
7
5
IR33F0AHE0
8
4
4
7
2
1
98 10
2
1
R1
6
543
R267R3
POWER
N
SUPPLY
44
A B
3
3
0
4
C
3
1DI1
11109
11
39
KGL-OS-50(60)-R
Page 89
89
Controller Temperature probe Terminal block Ground connection Evaporator fan Pilot light Switch Transformer Led lighting Solenoide valve Electrical shutter A key switch shutter
6 7 9
11
12 21
22 29 30 39 43 44
1 1
2
1
3
1 1 1
3
1 1 1
1 1
2
1
4
1 1 1
5
1 1 1
| | | | | | | | | | | |
| | | | | | | | | | | |
Discription
50 Inch 60 Inch
Number
for length
Page 90
90
4.4. Electronic controller
Carel - IR33F0AHE0
Power supply
Model Voltage Power
Insulation guaranteed by the power supply
Inputs
Probe type
IRxxxxExxxx
Maximum ditance of probes and digital inputs less than 10 m.
IRxxxxExxxx
S1 (probe 1)
230 V~, 50/60 Hz 3 VA, 25 mA~max.
reinforced
reinforced
basic
IRxxxxAxxxx
Note: during installation keep the power and loads connection separate from probe cables,
IRxxxxAxxxx
S2 (probe 2)
115V~, 50/60 Hz 3 VA, 50 mA~max.
6mm clearance, 8 mm creepage
6mm clearance, 8 mm creepage
externally guaranteed by safety
1 ºC in the - 50T50 ºC range
10 kΩ at 25 ºC, - 50T90 ºC range
50 kΩ at 25 ºC, - 40T150 ºC range
985 Ω a 25 ºC, range da - 50T150 ºC
1,5 ºC in the - 20T115 ºC range
2 ºC in the - 50T50 ºC range
3mm clearance, 4 mm creepage
IRxxxxHxxxx
digital inputs, repeater display and supervisory system.
IRxxxxHxxxx
measurement error:
measurement error:
measurement error:
DI 1
DI 2
S3 (probe 3)
S4 (probe 4)
115 to 230 V~, 50/60 Hz 6 VA, 50 mA~max.
3750 V insulation
3750 V insulation
transformer (SELV power supply)
3 ºC in the - 50T90 ºC range
4 ºC in the - 20T115 ºC range
4 ºC in the - 50T150 ºC range
1250V insulation
IRxxxxLxxxx
IRxxxxLxxxx
Std. CAREL NTC
NTC high
PTC std. CAREL
12 to 24V~, 50/60 Hz, 12 to 30 Vdc
insulation in reference
insulation in reference
NTC (IRxxx0xxxxx) o NTC e PTC (IRxxx7xxxxx)
free contact, contact resistance < 10 Ω, closing current 6 mA
free contact, contact resistance < 10 Ω, closing current 6 mA
insulation from relay outputs
insulation from relay outputs
3 VA, 300 mA~/mAdc max.
IRxxxx0xxxx
IRxxxx0xxxx
temperature
(specic model)
12V~, 50/60 Hz, 12 to 18 Vdc
to very low voltage parts
to very low voltage parts
NTC (IRxxx0xxxxx) o NTC e PTC (IRxxx7xxxxx)
NTC (IRxxx0xxxxx) o NTC e PTC (IRxxx7xxxxx)
NTC (IRxxx0xxxxx) o NTC e PTC (IRxxx7xxxxx)
Use only SELV power supply
TECHNICAL SPECIFICATIONS
Page 91
91
Controller must be handled by a qualified technician.
Relay outputs
SSR outputs
Connessioni
depending on the model
Model Relay P. Supply Probes for wires from 12 A
EN 60730-1 UL 873
model
IRxxxxxx0xx screw screw screw 0.5 a 2.5 mm²
IRxxxxxx2xx removable removable removable
IRxxxx(E,A)x5xx vertical screw vertical screw vertical screw
IRxxxx(E,A)x1xx faston faston removable
IRxxxx(E,A)x3xx faston faston screw
relay
R2 (*)
R3 (*)
R1,R2
R1
R2,R3
R1 (*)
R4 (*)
250 V~ 250 V~
5(1)A 5 A resistive 1FLA
5 A resistive 1FLA
8 A resistive 2FLA
12 A resistive 5FLA
6 LRA C 300
6 LRA C 300
5(1)A
8 (4)A N.O.
6 (4)A N.C. 12 LRA
2 (2)A N.O./N.C. C300
30 LRA C300
12 (2)A N.O./N.C.
operating operating
100000 300000
100000 300000
100000 300000
100000 300000
(*): Relay not suitable for uorescent loads (neon lights, ...) that use starters (ballasts) with phase-shift
the installer has to provide the correct dimensioning of the power supply and cable connection between the
cycles cycles
capacitors. Fluorescent lamps with electronic control devices or without phase-shift capacitors can be used,
instruments and the loads. Depending on the model, the maximum current in the common terminals 1, 3 or 5 is
Type of connection
Cross-section Max. current
IRxxxx(E,A)
IRxxxx(E,A)
IRxxxx(E,A)
IRxxxx(E,A)
IRxxxx(O,L,H)
IRxxxx(O,L,H)
(N,R,C,B,A,M,L,T)xxx
(N,R,C,B,A,M,L,T)xxx
(P,Q,S,U,V,X,Y,Z)xxx
(N,R,C,B,A,M,L,T)xxx
(N,R,C,B,A,M,L,T)xxx
(P,Q,S,U,V,X,Y,Z)xxx
within the operating limits specied for each type of relay.
12 A. When using the controller at maximum operating temperature and full load, use cables featuring a maximum operating temperature of 105 ºC at least.
reinforced
basic
3 mm clearance, 4 mm creepage
1250 V insulation
6 mm clearance, 8 mm creepageinsulation from very low voltage parts
insulation between the relay outputs indipendent
Max output voltage : 12 Vdc, Output resistance: 600 Ω, Max output current: 20 mA
3750 V insulation
Page 92
92
Controller must be handled by a qualified technician.
Normal operation
Buttons on the keypad
· if pressed for more than
if pressed for more than
if pressed for more than
if pressed for more than
· if pressed for more than 5 s together
· if pressed for more than 5 s together with DOWN/DEF button, enables/disables
· if pressed for more than 5 s together with PRG/MUTE button, accesses the
· if pressed for more than 5 s together with UP/AUX button, enables/disables
· if pressed for more than 5 s with SET button, starts the procedure for printing
· if pressed for more than 1 s together with DOWN/DEF button, displays a
· if pressed for more than 1 s together with SET button, displays a submenu
Star t-up : if Automatic address pressed for assignment: more than if pressed for 1 s enters 5 s at start-up, the automatic serial starts the address assigning
default procedure
parameter
setting
· in the event of alarm:
parameters
active alarm with manual reset
printing the report (function available, with management to be implemented)
silences the audible · if pressed for more than 5 s together
· if pressed for more than 5 s together with PRG/MUTE button, resets any
· if pressed for more than 5 s together with UP/AUX, starts the procedure for
alarm (buzzer) and with the UP/AUX button resets any disables the alarm relay alarm with manual reset
5 s accessed the menu
1 s, enables/disables
Button Press. the button alone Pressing together with other buttons
5 s, enables/disables a
1 s, displays and/or set
with the SET button, accesses the
the continuous cycle operation
menu for setting the type “C“ parameters “C“ (configuration) or downloading the parameters
the continuous cycle operation
for setting type “F”
the auxiliary output
manual defrost
the set point
menu for setting the type “C“
(frequent) parameters
(configuration) or downloading the
the reports (function available, with management to be implemented)
submenu with the HACCP alarm parameters (HA, HAn, HF, HFn)
with the HACCP alarm parameters (HA, HAn, HF, HFn)
Set
Prg
mute
aux
def
Signals on the display
The blinking status indicates a request for activatuin that cannot be implemented until the end of the corresponding delay times.
compressor ON comp. OFF compressor request fan ON fan OFF fan request
defrost in progress auxiliary output
delayed externalALARM
CLOCK
LIGHT
SERVICE
HACCP
CONTINUOUS
CYCLE
DEFROST
Function
COMPRESS.
FAN
ONIcon OFF blink Startup
AUX
AUX
sent
HACCP
at least one timed
auxiliary output auxiliary output
no malfunction
HACCP fu n ct ion HACCP a l arm ( HA an d/or HF)HACCP fu n ct ion enabled
not enabled request
not enabled
no timed defrost is ON if Real-Timeclock alarm
anti-sweat heater function active
malfunction (eg. EEPROM error
or probe fault)
present Clock present
no alarm present
alarm (before the
defrost has been
LIGHT ACTIVE LIGHT NOT ACTIVE
set
expiry of the time “A7“ )
auxiliary output anti-sweat heater function active
alarms in normal operation (eg. high/low temp.) or alarm from ext. digital input immediate or delayed
AUX ac t ive AUX not active
defrost not required defrost request
enabled
Page 93
93
/3 Probe display response MSYF
MSYF MSYF
SYF SYF
SYF SYF
MSYF
YF
MS
-
ºC/ºF ºC/ºF ºC/ºF
min
hours
min
ag
-
-
C
C F F
C F
F
C
C C
0
-20 rl
0,1
0 0
1
0
0 0
0
0,0 0,0 2,0
0 8
30
0
2 2
15
20
r2 20 15
250 250
1
4 4
/5
/A2
/c1
Select ºC or ºF 0: ºC 1: ºF
Conguration of probe 2 (S2)
0: Probe absent 1: Product probe (display only) 2: Defrost probe 3: Condenser probe
4: Antifreeze probe
Calibration of probe 1 Temperature set point Control delta
Minimum compressor OFF time
Interval between defrosts Maximum defrost duration, evaporator
St rd c2 dl
dP1
Symbol Code Parameter Models UOM Type Min Max Def.
Main parameters
5 Maintenance
5.1 Cleaning
All operations must be done with the unit disconnected.
Clean surfaces (glass/metal/plastic) with soft detergents or warm water. Do not use abrasive cleanser.
Page 94
94
5.2 Shelf removing/adjustment
All operations must be done with the unit disconnected.
To remove or adjust shelves take care with light connections.
2
1
5.3 Light substitution
To replace lights follow the steps:
Turn off power and unplug the equipment.
Page 95
95
- Disconnect the light
- Unscrew the light and remove the light
- Insert a new light in the same place of the old one
- Screw the light and connect it
- Plug and turn on the light
2
1
5.4 Panels and protection grille removal
Page 96
96
5.5 Condenser cleaning
This operation must be performed by a qualified technician.
All operations must be done with the unit disconnected.
Condenser must be regularly cleaned (every month). Use a brush or vacuum it. To get to the condenser must remove frontal protection.
5.6 Evaporator cleaning
This operation must be performed by a qualified technician.
All operations must be done with the unit disconnected.
To access the evaporator:
- Lift and remove exposition panels
- Use tool for the screws and clean
Page 97
97
5.6.1 Evaporator back cleaning (KGL-DL/RS/RM only)
The back of the evaporator must be checked for obstruction every day.
This operation must be performed by a qualified technician.
All operations must be done with the unit disconnected.
Page 98
98
5.7 Evap Pan cleaning
This operation must be performed by a qualified technician.
All operations must be done with the unit disconnected.
Pan can be hot!
This operation must be done weekly.
To access the evap pan:
- Remove protection grille.
- Unplug the evap pan.
- Relieve the screws and take the evap pan off.
- Clean with soft detergent or warm water.
Page 99
99
5.8 Drain inspection
Check for drain obstruction and correct position every month (Remotes only).
5.9 Electric shutter
5.9.1 Manual operation
This operation must be performed by a qualified technician.
Manual opening of the shutter only for no power situation.
Make sure to insert the key in the correct place.
For more informations go to www.somfy.com
Open
Close
Page 100
10 0
5.9.2 Setting position
This operation must be performed by a qualified technician.
For more informations go to www.somfy.com
6 Troubleshooting/Service
6.1 Troubleshooting
Service must be performed by a qualified technician.
Doors not closing: Check for leveled floor.
Check for obstruction.
Remove doors and check the bearings.
Lights not working: Check light switch position.
Check light connections.
Warm case temperature: Check for air return grille obstruction.
Check for air drafts.
Check store temperature.
Check for condenser obstruction and cleaning.
Check for frozen evaporator.
Check set point.
Display area is over filled.
Fans not working: Check electrical connections.
Check for any debris.
Case not aligning: Check for leveled floor.
Check instructions for joining.
Display not working: Check main power switch position..
Check electrical connections.
Compressor not starting: Disconnect switch open.
Blown fuse.
Overload protective tripped.
Loading...