Hycontrol MINIFLEX LR Installation And Operation Manual

MINIFLEX LR PROGRAMMABLE LEVEL CONTROLLER
INSTALLATION AND OPERATION MANUAL
Rev 0
Hycontrol Limited, Larchwood House, Orchard Street,
Redditch, Worcestershire, B98 7DP, UK.
Email:
sales@hycontrol.com Web: www.hycontrol.com
MINIFLEX LR USER MANUAL - INDEX
Page Drawings
Introduction
1
SECTION 1 Installation
Transceiver Mounting 2 Fig. 1 Transceiver Wiring 3 - 4 Fig. 2 & 3 Transducer Mounting 5 Fig. 4 Transducer Alternative Mounting 6 Fig. 5 Transducer Mounting Faults 7 Fig. 6 Transducer Stand Pipe 7 Transducer Cable Extensions 8 Fig. 7 & 8 Temperature Sensor 9 Fig. 9
SECTION 2 Easy start for Miniflex LR
Quick Start Guide 10 Principle of Program ming 10 Keypad Definitions 10 - 11 To Enter Programme 11 To Enter the Password 11 To Change an Option 12 To Reset 13 Simulation Mode 13
SECTION 3 Programming the instrument
Parameter List 14 - 34
SECTION 4 Miniflex LR Default programs
1. Distance Measurement Mode 35
2. Level Measurement Mode 36
3. Contents, Volume Conversion 37
4. Pump Control 38
5. Open Channel Flow 39 - 40
6. Differential 41 - 42
SECTION 5 Commissioning fault finding APPENDIX 1 LINEARISATION OF SPECIAL
43 - 47 48 - 52
VESSELS OR FLUMES APPENDIX 2 SPECIFICATION APPENDIX 3 INSTALLATION INSTRUCTIONS
53 54 - 55
FOR ATEX TRANSDUCER IN HAZARDOUS AREA
APPENDIX 4 PARAMETER SETTINGS APPENDIX 5 PARSHALL FLUMES APPENDIX 6 WIRING DIAGRAM FOR
56 - 62 63 64
SYNCHRONISATION OF INSTRUMENTS
APPENDIX 7 MINIFLEX LR PROGRAMMING
65 - 74
CHARTS
SECTION 1
MINIFLEX LR PROGRAMMABLE LEVEL CONTROLLER

USER MANUAL

INTRODUCTION

Miniflex LR is a programmable multi-purpose level measurement and flow control instrument. It consists of two elements, a wall mounted transceiver, which has a display and an integral keypad for programming, and a transducer, which must be mounted directly above the surface to be monitored.
Ultrasonic pulses are transmitted by the transducer to the surface of the material to be monitored and are reflected back to the transducer. The time period between transmission and reception of the sound pulses is directly proportional to the distance between the transducer and the material.
Since speed of sound through air is affected by changes in temperature, a separate or integrated temperature sensor may be fitted to improve accuracy.
Miniflex LR is capable of the following functions:-
a) Distance Measurement (distance from a datum) b) Level Measurement (height above datum) c) Volume Measurement d) Pump Control e) Open Channel Flow Measurement (O.C.M.) f) Differential Level Measurement
WARNING
DO NOT OPEN THE TRANSCEIVER
TERMINAL COVER WHEN THE POWER IS ON TO
THE SUPPLY OR RELAY TERMINALS.
IMPORTANT INSTALLATION REQUIREMENTS
1: A SWITCH OR CIRCUIT BREAKER SHALL BE INCLUDED IN
THE INSTALLATION
2: IT SHALL BE IN CLOSE PROXIMITY TO THE EQUIPMENT AND
WITHIN EASY REACH OF THE OPERATOR
3: IT SHALL BE MARKED AS THE DISCONNECTING DEVICE FOR
THE EQUIPMENT
Ref: MINIFLEX LR MANUAL Rev. 0 1
SECTION 1

INSTALLATION

Transceiver For ATEX hazardous areas refer to Appendix 3.
Enclosure mounting
Secure one of the three fixing screws provided with the instrument 30mm below the centre of where the top of the instrument is to be located. This fixing screw will need to be left 4mm proud of the surface allowing the instrument to be hung from this point. The instrument is then secured in place by 2 more screws using the two mounting slots exposed when the terminal cover is removed. DO NOT use excessive force when tightening the fixings and avoid any distortion of the enclosure.
Ensure that the mounting surface is not subject to vibration and is not in close proximity to high voltage cables, contactors or drive controls. The unit should not be mounted in a confined space where temperatures may exceed the normal working temperature. If the unit is mounted outside, it must be protected from direct sunlight or severe weather conditions.
Select appropriate knockouts in the base of the enclosure and fit appropriate cable glands to maintain the IP65 rating.
106.5
31.00
MINIFLEX LR
LEVEL CONTROLLER
INCREASE
MOUNTING POINT 1
RELAY 1
FOUND ON REAR
RELAY 3
ECHO
HYCONTROL LTD, ENGLAND
TEL :+44(0) 1527 406800 Websi t e: www.hycontrol.com
BACK
DIGIT
M
ENT
(MODIFY)
OPTION
/ DIGIT
185.0
137.0
MOUNTING POINT 2 & 3
(REMOVE TERMINAL COVER)
10
198.0
213.0
5.4
KNOCKOUTS FOR 1 HOLE 16mm AND 5 HOLES 20mm
∅∅
NOTE: - All dimensions are shown in mm
Figure 1: Enclosure dimensional & mounting drawing
Ref: MINIFLEX LR MANUAL Rev. 0 2
SECTION 1
Electrical and Transducer Connections
The Miniflex LR has two-part screw terminals; the top part can be removed for ease of connection. It can be powered from either an AC or DC supply.
Power Supply Remove the terminal cover to expose the terminals shown below.
F4
T250mA
TB1
1 2 3 4 5 6 7 8 9 101112131415161718192021222324
TB2 TB3 TB4 TB5 TB6
95V
25
F3
T160mA
110V
230V
Figure 2: Terminals as seen in Miniflex LR.
The wiring instructions are on the inside of the terminal cover as shown below.
1
2 3 4 5 6 7 8 9 101112131415161718192021222324
+
DC POWER
21.6-30VDC
9W
SHIELD
-
RS485
+
TRANSDUCER
-
SHIELD
HOT
SYNC
SHIELD
+
-
ISOLATED ANALOG OUTPUT
RELAY 1
RELAY 3RELAY 2
E
L2
AC POWER
95/110/230V AC
+10%/-10%
50/60 HZ 12VA
25
LN
L1
Figure 3: Wiring diagram label inside MIniflex LR terminal cover
AC Supply The instrument will accept either 95V, 110V or 230VAC ±10%, 50Hz or 60Hz, 12VA. A time lag fuse T160mA is fitted.
Select the voltage required using the jumper link situated just above terminal TB6.
Pass mains cable through cable gland and - Connect:- Earth to terminal 23 Neutral to terminal 24 Live to terminal 25
DC Supply The instrument will accept 21.6 - 30VDC, 5W. A time lag fuse T250mA is fitted.
- Connect :- Positive +ve to terminal 1 Negative -ve to terminal 2
Relays
3 SPDT Relays - rated at 8A/250VAC 8A/30V DC resistive, are connected at terminals 14 to 22, for activating
external alarms, contactors, pumps etc..
Transducer Transducer RYV15 & RWV15 - is connected:- Black to terminal 6
Blue to terminal 7 Shield to terminal 9
Ref: MINIFLEX LR MANUAL Rev. 0 3
Temperature compensated transducer RYT15 & RWT15 - is connected: ­ Shield to terminal 6 Blue to terminal 7 Black to terminal 8
Analogue Output Analogue - is connected : - Shield to terminal 11
Positive +ve to terminal 12 Negative -ve to terminal 13
RS485 Output RS485 - is connected : - Shield to terminal 3
Negative –ve to terminal 4 Positive +ve to terminal 5
Note: - See Page 8 for transducer extension cables.
SECTION 1
Ref: MINIFLEX LR MANUAL Rev. 0 4
SECTION 1
Transducer Mounting
The transducer can be supplied as 'standard' or mounted in a flange. For applications requiring chemical compatibility the transducer is available fully enclosed in PVDF in a standard mounting or with flange. Figure 4 shows the dimensions:
10m cable 6.0 dia
50 dia
M20 x 1.5
M32 x 1.5
Isolation Kit Fit as shown
20
102
26
62
No. & size of bolts to suit flange selected
20
130
assembled
height
92 dia
Bolt hole PCD to suit
flange selected
Dia to suit flange selected
INTEGRAL FLANGE
Figure 4: Transducer mounting diagram
An isolation kit is provided with each transducer to minimise any ringing transmitted through the mounting structure.
The transducer must be mounted perpendicular to the monitored surface and, ideally, at least
0.5 metres above it.
The transducer has a 12° inclusive conical beam angle at -3dB and must be mounted with a clear unobstructed sight of the liquid to be measured over the complete measurement range.
The transducer is provided with integral cable which can be extended up to 300 metres using a suitable junction box and RG62AU cable. The temperature compensated transducer requires an additional single core screen extension, or twin-ax cable. Refer to Page 8 for full details.
Transducer cables and temperature compensation cables can be run together but should be separated from power cables by at least 150mm and preferably installed in their own earthed steel conduit.
Ref: MINIFLEX LR MANUAL Rev. 0 5
SECTION 1
FLEXIBLE OR RIGID
CONDUIT.
BRACKET.
ISOLATION KIT.
INTEGRAL FLANGE
UNDER FLANGE.
OPTIONAL
ISOLATION KIT
ISOLATION KIT.
Figure 5: Alternative mounting arrangements for transducers
Do not mount transducers incorporating temperature compensation in direct sunlight.
Do not over-tighten the bolts on flange construction transducers.
Flange transducers are not pressure rated and are suitable only for atmospheric pressure.
ATEX approved transducers must be mounted and wired in accordance with the appropriate
National Standards concerning installation in hazardous environments.
For differential applications mount both transducers at the same height above the zero datum point. For open channel flow applications the transducer must be mounted upstream of the flume or weir as detailed in BS3680 (usually 3 or 4 times maximum head).
Ref: MINIFLEX LR MANUAL Rev. 0 6
SECTION 1
CAUTION: AVOID THE FOLLOWING TRANSDUCER INSTALLATION FAULTS
DO NOT AIM THROUGH
HOLES IN THE TANK
AVOID ROUGH EDGES
IN STANDPIPES
KEEP TRANSDUCERS AND
TEMPERATURE COMPENSATION
PROBES OUT OF DIRECT
SUNLIGHT
KEEP TRANSDUCER PERPENDICULAR
TO LIQUID.
AVOID INFLOWS OR
OTHER OBSTRUCTIONS
Figure 6: Transducer installation faults
Standpipe Installations
In many applications access to a vessel must be made via a standpipe. However, it is necessary to observe some basic rules when fitting transducers into standpipes.
BLANKING: Parameter 4.0 should always be set at least 150mm longer than the length of the standpipe.
STANDPIPE should be in accordance with the following table DIMENSIONS:
Flange size and minimum bore of Standpipe
of Standpipe
Maximum length
3" ( 80mm) 300mm 4" (100mm) 300mm
e.g. Using a 4" flanged transducer would require the standpipe length to be no more than 300mm and Pr.4.0 set at 450mm minimum.
The inside of the pipe and joint with vessel top must be clean and free of any obstructions, seams or welds.
Ref: MINIFLEX LR MANUAL Rev. 0 7
Transducer Cable Extensions Transducer cables may be extended using junction boxes as shown in Figure 7:
RWV15 / RYV15 Transducer
Transducer
Black
Shield
Blue
Junction
To Miniflex LR
Shield - Term 6
RG62AU
Core - Term 7
Temperature Compensation RWT15 / RYT15 Transducer
Junction
Black
Shield
Blue
To Miniflex LRTransducer
Copper core Term 8
Shield Term 6
Silver core Term 7
RWV15 / RYV15 Transducer- alternative
Black
Shield
Blue
Junction
To Miniflex LRTransducer
Copper core Term 6
Shield Term 9
Silver core Term 7
Beldon 9207
or equal
Figure 7: Transducer lead extension diagram
RWV15 / RYV15 Transducer
Upstream Transducer
Black
Shield
Blue
Downstream Transducer
Black
Shield
Blue
Junction
Junction
To Miniflex LR
Shield - Term 6
RG62AU
Core - Term 22
To Miniflex LR
Shield - Term 9
RG62AU
Core - Term 20
Extend transducer cable if necessary
with RG62AU as shown.
Wire unextended transducers as below
UP & DOWNSTREAM BLACKS
UP & DOWNSTREAM SHIELDS
Note Link
DOWNSTREAM - BLUE
UPSTREAM - BLUE
1
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
DC POWER
21.6-30VDC
9W
SHIELD
+
+
RS485
-
TRANSDUCER
-
SHIELD
HOT
SYNC
SHIELD
ISOLATED ANALOG OUTPUT
+
-
RELAY 1
RELAY 3RELAY 2
E
AC POWER
95/110/230V AC
+10%/-10%
50/60 HZ 12VA
Figure 8: Transducer Wiring for Differential Mode
SECTION 1
Beldon 9207
or equal
25
LN
L2
L1
Ref: MINIFLEX LR MANUAL Rev. 0 8
SECTION 1
Temperature Sensor
If a separate temperature sensor is to be used it must be mounted where it will monitor temperature changes of the air between the transducer and the liquid. This is usually adjacent to the transducer, but should not be in direct sunlight and should be protected from wind chill.
75 dia.
60
50
33 a/f hex
M20 x 1.5
Cable entry
M20 x 1.5
110
HOUSING: POLYCARBONATE IP65
PROBE: 316SS
16
25
50
Process connection
10 dia.
blue red
no connection
Electrical connections
Note that the connections are not polarised
TEMPERATURE SENSOR RTS-2
35
175
25
12
50
POLARITY
+
UNIMPORTANT
-
LOCK
SCREW
30 dia
34 ref
52
85 dia
9 dia
HOUSING: CAST IRON BLACK EPOXY PAINT
CLASSIFICATION EEx e II T6/IP 65
PROBE: 316SS
EXTERNAL
EARTH
33 HEX
3/4" BSPP
INTERNAL
EARTH
TEMPERATURE SENSOR RTS 2B
Figure 9 Temperature sensor dimensional drawing
Ref: MINIFLEX LR MANUAL Rev. 0 9
SECTION 2

EASY START FOR MINIFLEX LR

The Miniflex LR system requires programming by the operator to obtain the required measurements and control. To create a basic working system, only the application type and parameters 2.0 to 5.0 need be programmed. To become familiar with the use of the system, it is suggested that the following QUICK START guide is used before the instrument is installed.
Quick Start Guide
1. Connect power and transducer cables as defined on the instrument.
Temperature
compensated dc Power Supply
Transducer ac Power Supply
Terminal Nos: [1 ] [2] [ 6 ] [ 7 ] [8 ] [ 23 ] [ 24 ] [ 25] +ve -ve Shield Blue Black E N L
2. Close the front cover and secure in position before switching on the power. The instrument is supplied factory set to work in distance measurement up to 10 metres from the transducer.
3. Hold the transducer approximately 1.5 metres from a flat surface and switch on.
After a short period, the display will show the distance (e.g. 1.50) between the transducer and the surface.
If the transducer is now moved slowly towards the surface, the reading should decrease. This shows that the unit is correctly wired and is operating as expected in response to the reduction in distance.
If the reading increases as the transducer is moved towards the surface, it indicates that the unit has been previously programmed to read level not distance.
Principle of Programming
The Miniflex LR has two modes:-
a) RUN (Normal operating)
In the 'RUN' mode, the instrument is monitoring the target, displaying values, and setting outputs as programmed by the operator.
b) Program Mode (Programming)
In the 'Program Mode' the operator uses the keypad in conjunction with the display to adjust the settings and to test that the unit is programmed correctly.
Keypad Definitions
The keypad consists of 5 keys, which are used to programme the operation of the transceiver. These keys also have secondary functions enabling the operator to view the results being obtained by the instrument during its normal 'RUN' cycle.
Ref: MINIFLEX LR MANUAL Rev. 0 10
SECTION 2
Primary Key Functions M = Mode Key - to go from "RUN" to "Program Mode”
- or to go from "Program Mode" to "RUN" Mode ENT = ENTER - to enter a value or option change or
start a simulation if parameter 12.5.2 is entered.
M
= In program mode to increase the selected digits value.
= To move back to the main sections of parameters.
ENT
= Scroll through options or move cursor to the right if there is a value.
Alternative Key Functions
The 4 peripheral keys have secondary functions which can be viewed without interrupting the instrument's operation. In the normal "RUN" mode:-
Press = Display will show head and flow values when in OCM mode.
Press = Display will show the echo distance in metres and "GAIN" with a value from 0.2 to 100, which represents strength of echo. Low numbers mean
strong echo.
Press = Display will show the operating temperature if using a temperature compensated transducer or 20ºC with standard transducer, and the analogue output value in mA.
Press ENT = Display will show the number of Alarms and Starts for relay 1, if the button is pressed again whilst displaying the value for relay 1 it will change to relay 2 and if pressed again relay 3.
NOTE:- The Miniflex LR comes with pre-programmed applications, which can be simply modified to meet your applications requirements. See
SECTION 4 for more details.
1
) To Enter Programme
Press M - Display will show "Program Mode" Press immediately - Display will show either Distance Measurement, Level
Measurement, Volume Measurement, Pump Control, Open Channel Flow Monitoring or Differential Measurement. If you wish to change the selected application press to move through the applications,
you will be asked to enter the password.
) To Enter the Password
2
The first time that you try to change the application, a value or a parameter option, you will be required to enter the password. The default for this is 1000. You use the and the to change the digits then ENT when you have finished, if you enter the wrong code the display
value will be cleared and you will need to try again.
Ref: MINIFLEX LR MANUAL Rev. 0 11
SECTION 2
3) To Accept the Current Selection press ENT
Continue to press
ENT - To accept the value or option and move to the
next applicable parameter.
4)
To Change the Value of a Number
Press - To increase value of flashing digit between 0 and 9. It will then roll over to its minimum and start again.
Press - To move the cursor right and select the next digit to be changed, then Press
to change its value as above.
Press ENT - To enter the new value. The display will then show the next parameter in the list.
To Change a Y or N Option
5)
Certain parameters have been put into sections to avoid stepping through numerous parameters that you may not need to change initially. Each of the sections will have a Yes or No option.
8.0 Edit relays No
To change the relay settings use the to change a ‘No’ to a ‘Yes’ or to skip that section just
press ENT.
8.0 Edit relays Yes
When you have made your selection press ENT to move to the next parameter.
6)
To Change an Option
A display which shows a label enclosed in brackets means that this is the currently selected value for this parameter, but it can be changed.
e.g. 8.1 Rly1 Options (Norm–Energised)
Press ENT
8.1.1 Relay 1 Norm - Energised
Press to change the option
8.1.2 Relay 1 Norm-DeEnergised
Press to change the option again
8.1.3 Relay 1 Temp Alarm
Ref: MINIFLEX LR MANUAL Rev. 0 12
SECTION 2
When you come to the option you want press ENT to accept the new selection and move on the next parameter in the list.
(Shortcut for more familiar users)
Alternatively if you don’t need to make a change to this parameter and its associated settings you can move to the next parameter in the top level by using the
key.
e.g. 8.1 Rly1 Options 8.2 Rly2 Options 8.3 Rly3 Options
(Norm-Energised) (Norm–Energised) (L.O.E. Alarm)
When you come to a parameter you want to adjust press ENT and follow step 4), 5) or 6) depending on whether there is a value to enter, a yes or no option or select an option.
To complete Programming and Return to RUN Mode
7)
Press M - The display will show “Storing Values” and “Data stored to memory”, if a value has been changed. Then "Searching for target" and then the measured value in the selected units.
8) To Reset all Parameters to Factory Default Press M if not already
in program mode - Displays "Program mode".
Press To display a parameter (it can be any one)
To reset the instrument you need to be in the first parameter of any application displaying Distance Measurement, Level Measurement, Volume Measurement, Pump Control, Open Channel Flow Monitoring or Differential Measurement. If you haven’t appeared here you can use the key to move back through the program to the first parameter.
Then press both instrument will reset the parameters, custom tables and totaliser, and reverts back to
displaying Distance Measurement.
and simultaneously and when prompted Enter the password. The
Simulation mode
To simulate a program go to parameter
12.5.2 Simulate then press ENT. Yes
Keys M = Exits simulation mode
ENT = Direction to decrease displayed value = Direction to increases displayed value
= Reduce speed by 2 from a maximum of 64x to 1x. The initial speed of 1x is set by the rate of change defined in parameter 6.0.
= Increase speed by 2. From 1x to a maximum of 64x.
Ref: MINIFLEX LR MANUAL Rev. 0 13
PARAMETER INDEX
Application Pr. 1.0 Basic Application
Basic Set-up
Pr. 2.0 Empty Distance Pr. 3.0 Operatio nal Span Pr. 4.0 Blanking Pr. 5.0 Rate Of Ch ange
Volume Measurement
Pr. 6.1 Vessel shape Pr. 6.2 Displ a y Units Pr. 6.3 Maximum Display x 100 Pr. 6.4 Displa y F orm at
Open Channel Flow Monitoring (O.C.M.)
Pr. 7.1 Flow device Pr. 7.2 Maximum Flow Value Type Pr. 7.3 Maximum Flow Pr. 7.4 Totaliser Units Pr. 7.5 External Totaliser Drive Pr. 7.6 Totaliser Reset
Relays
Pr. 8.1 Relay1 Options Pr. 8.2 Relay2 Options Pr. 8.3 Relay3 Op tio n s
Pump Control
Pr. 9.1 Pump Sequence Pr. 9.2 Duty Standby Pr. 9.3 Exerciser Pr. 9.4 Tolerance Pr. 9.5 Maintenance Pr. 9.6 Pump Run-on Interval Pr. 9.7 Pump Run-on Time

MINIFLEX LR

Failsafe
Pr. 10.1 Relay 1 Failsafe Pr. 10.2 Relay 2 Failsafe Pr. 10.3 Relay 3 Failsafe Pr. 10.4 Fail Time Pr. 10.5 mA Fail
Analogue
Pr. 11.1 Analogue Output Pr. 11.2 Analogue Value Pr. 11.3 Test mA Pr. 11.4 Analogue Scale
Miscellaneous
Pr. 12.1 Offset Pr. 12.2 Passcode Pr. 12.3 Number Of Decimals Pr. 12.4 Relay totaliser Pr. 12.5 Simulation Pr. 12.6 Station ID Pr. 12.7 Synchronisation Pr. 12.8 Check Search Pr. 12.9 Maximum gain
SECTION 3
Ref: MINIFLEX LR MANUAL Rev. 0 14
SECTION 3

PROGRAMMING THE INSTRUMENT

NOTE:- (D = ) factory default entry for that parameter.
Step 1: - Select application (Pr.1.0)
Application (D = Distance Measurement)
This will automatically load the applicable default program which can then be modified to suit your application. At initial start up display will show one of below listed options: -
Distance Measurement (Page 35) Level Measurement (Page 36) Volume Measurement (Page 37) Pump Control (Page 38) Open Channel Flow Monitoring (Pages 39 – 40) Differential Measurement (Pages 41 – 42)
For more details see Pr.1.0 Application Selection Guide (Page 16)
Step 2: - Enter Basic Set-up parameters
Complete Basic Set-up section - Page 17
Step 3: - Dependent on application, go to appropriate section in manual.
For Distance Measurement go to Page 35. For Level Measurement go to Page 36. For Volume Measurement go to Page 37. For Pump Control go to Page 38. For Open Channel Flow Monitoring go to Pages 39 - 40. For Differential Measurement go to Pages 41 - 42.
Step 4: - Set any relay conditions
Relay section go to Pages 24 - 26
Step 5: - Set any failsafe conditions
Failsafe section go to Page 30
Step 6: - Set any analogue conditions
Analogue section go to Pages 31 - 32
Step 7: - Set any miscellaneous conditions
Miscellaneous section go to Pages 33 - 34
Step 8: - Exit program mode and return to run mode
Go to Section 7 Page 13
Ref: MINIFLEX LR MANUAL Rev. 0 15
SECTION 3
Pr.1.0 APPLICATION SELECTION GUIDE
Miniflex LR can be programmed for Distance measurement, Level measurement, Volume measurement, Pump control, OCM and Differential measurement. Each application selected will allow access to only parameters associated with that application.
Distance Measurement
Displays a distance measurement; relay set and reset points can be programmed and a relay can be programmed for Loss Of Echo indication. A 4-20mA output proportional to the displayed distance is provided.
Level Measurement
Displays a level; relay set and reset points can be programmed and a relay can be programmed for Loss Of Echo indication. A 4-20mA output proportional to level is provided.
Volume Measurement
Displays contents, ullage or both contents and ullage. Choose from a variety of vessel shapes including vertical and horizontal cylinders or a 24-point custom table. Display in Litres, Gallons, Tons, Tonnes, Kg, m3 or %. Provide a 4-20mA output proportional to contents or ullage.
Pump Control
For pump control applications; can include pump sequencing, duty standby, pump maintenance and pump run on.
Open Channel Flow Monitoring (O.C.M.)
For flow measurement, using BS3680 flumes and weirs, Parshall flumes, or custom table for non-standard devices. Displays flow rate in litres/sec or gallons/sec and totalises in a variety of units. Provides a pulse output to drive an external totaliser and a 4-20mA output proportional to level or flow.
Differential Measurement
Uses two transducers switched automatically. The display indicates the difference between two levels and gives a 4-20mA output proportional to the reading. Relay set and reset points can be programmed and a relay can be programmed for Loss Of Echo indication.
Ref: MINIFLEX LR MANUAL Rev. 0 16
Basic Set-up
Pr.2.0
Pr.3.0
Pr.4.0
Pr.5.0
Empty Dist Empty Distance in Metres
Distance Level Volume Pump OCM Differential
Default 10.00 6.000 6.000 6.000 1.200 2.000
The approximate distance from the face of transducer to the furthest point away, usually the bottom of the container or channel. Enter the distance in metres.
Resolution is a function of this parameter.
Span Operational Span in Metres
Distance Level Volume Pump OCM Differential
Default 10.00 5.500 5.500 5.500 0.280 0.500
The distance between the furthest and nearest points over which measurement is required. Enter the distance in metres. For OCM, span = maximum head. For differential applications, the value required is the maximum difference in the levels to be measured.
Blanking (D = 0.500 Metres)
Blocking or Blanking Zone.
Minimum distance from transducer face to target, within which no return echoes will be processed. It is important to ensure that the target material does not enter this zone.
Enter in metres.
DO NOT REDUCE THE FACTORY SET VALUE WITHOUT REFERENCE TO HYCONTROL.
RateOfChange Rate Of Change in Metres/Min
Distance Level Volume Pump OCM Differential
Default 10.00 1.000 1.000 1.000 1.000 1.000
This value should be as small as possible but greater than the maximum rate of change of level. Do not greater than 1.0m/min or that the system continually 'tracks' a level lower than the actual level.
If it is necessary to change the value, enter the new value in m/min; the suggested range is 0.1 to 10.
SECTION 3
change this value unless you know that the rate of change is
Ref: MINIFLEX LR MANUAL Rev. 0 17
Volume Measurement
The following main parameters set up a volume measurement application.
6.0 Edit Volume No
No
Pr.6.1
Vessel shape (D = Linear)
Options displayed
6.1.1 Linear Vessel Linear vessel
6.1.2 Vertical Pyramid Bottom Vertical cylindrical tank with pyramid bottom
6.1.3 Vertical Conical Bottom Vertical cylindrical tank with conical bottom
6.1.4 Vertical Spherical Bottom Vertical cylindrical tank with half spherical bottom
6.1.5 Vertical Dished Bottom Vertical with dished bottom
6.1.6 Horizontal Cylind Flat Ends Horizontal cylinder with flat ends
6.1.7 Horizontal Cylind Dish Ends Horizontal cylinder with dished ends
6.1.8 Custom table – 24point 2 4 point linearisation table – See appendix 1
Additional parameters may be required dependent on vessel shape selection.
6.1.1 LINEAR VESSEL
6.1.2 VERTICAL PYRAMI D BO TT OM
6.1.3 VERTICAL CONICAL BOTTOM
6.1.4 VERTICAL SPHERICAL BOTTOM.
Yes
6.1 Vessel shape (Linear)
Pr.3.0
Pr. 6.1.2.1 Pyramid h
Pr.6.1.3.1
Cone h
Pr. 6.1.4.1
Sphere h
6.2 Display Units (Litres)
6.3 MaxDisp x100 (001.0)
Description
No additional parameters
Pr 6.1.2.1 Pyramd h (D = 0.00)
Pr.3.0
Pr.3.0
Pr.3.0
Enter pyramid h in metres.
Pr 6.1.3.1 Cone h (D = 0.00) Enter cone h in metres.
Pr 6.1.4.1 Sphere h (D = 0.00) Enter sphere h in metres.
6.4 Display Format (Contents)
SECTION 3
Ref: MINIFLEX LR MANUAL Rev. 0 18
SECTION 3
Pr.6.1.5.2
Radius R
Pr.3.0
Pr.6.1.5.1
Dish h
6.1.5 VERTICAL DISHED BOTTOM.
Pr 6.1.5.1 Dish h (D = 0.00) Enter dish h in metres.
Pr 6.1.5.2 Radius R (D = 0.00) Enter radius R in metres.
Pr.3.0
6.1.6 HORIZONTAL CYLINDER FLAT ENDS.
6.1.7 HORIZONTAL CYLINDER DISHED ENDS.
Pr.6.1.7.2
Cylndr L
Pr.6.1.7.1
Dish L
Pr.3.0
No additional parameters
Pr 6.1.7.1 Dish L (D = 0.00)
Enter dish L in metres.
Pr 6.1.7.2 Cylndr R (D = 0.00) Enter cylinder R in metres.
Pr. 6.2
DisplayUnits Display Units (D = %)
Options displayed
6.2.1 Units Litres Un its label displayed in Litres
6.2.2 Units Gallons Units label displayed in Gallons
6.2.3 Units Tons Units label displayed in Tons
6.2.4 Units Tonnes Units label displayed in Tonnes
6.2.5 Units Kg Units label displayed in Kg
6.2.6 Units m3 Units label displayed in m3
6.2.7 Units % Units label displayed in %
Description
Pr. 6.3 MaxDsp x 100 Maximum display x 100 (D = 1.0)
Enter - full scale display ÷ 100 e.g. if 100% = 2000 litres and display required in litres then set Pr. 6.3 to 2000 ÷ 100 = 20.
This parameter should not be adjusted in conjunction with 6.2.7 Units % as it will
invalidate the % reading.
Pr. 6.4
Disp. Format Display Format (D = Contents)
Options displayed Description
6.4.1 Display Contents Display contents only
6.4.2 Display Ullage Display ullage only
6.4.3 Display Ullage &Conte nts Display both ullage and contents
Ref: MINIFLEX LR MANUAL Rev. 0 19
SECTION 3
Open Channel Flow Monitoring (O.C.M.)
The following main parameters set up an Open Channel Flow Monitoring application.
7.0 Edit OCM No
No
Yes
7.1 Flow Device (Rect.Flume 3/2)
7.2 Max Flow Val (Auto calculate)
7.3 Maximum Flow (50.00)
7.4 Total. Units (in m3)
7.5 Ext. Tot. Drv. (0.000)
7.6 Total Reset (No)
Pr.7.1
Flow device (D = Rect. Flume 3/2)
The instrument provides options for three standard ratio-metric flow devices, three BS3680 flow devices, a variety of Parshall flumes or a custom 24-point table. Select the flow device from the following list.
Options displayed
7.1.1 Std. Ratio Rect. Flume 3/2 Standard Ratio Rectangular flume 3/2
7.1.2 Std. Ratio Rect. Weir 3/2 Standard Ratio Rectangular weir 3/2
7.1.3 Std. Ratio V-Notch Weir 5/2 Standard Ratio V-notch weir 5/2
7.1.4 BS3680 Rect. flume BS3680 Rectangular flume * Follow BS3680 set-up at step A
7.1.5 BS3680 Rect. weir BS3680 Rectangular weir * Follow BS3680 set-up at step B
7.1.6 BS3680 V-notch weir BS3680 V-notch weir * Follow BS3680 set-up at step C
7.1.7 Parshall Flumes Parshall Flumes * Follow PARSHALL set-up step D
7.1.8 Custom table 24-point linearization table. Refer to appendix 1
Description Action
BS3680 set-ups Rectangular flume Rectangular weir V-notch weir
Step A Step B Step C
7.1.4 BS3680 Rect. Flume
ENT
7.1.5 BS3680 Rect. Weir
ENT
Throat Width
0.000 Metres
Crest Width
0.000 Metres
ENT
ENT
Channel Width
0.000 Metres
ENT
Throat Length
0.000 Metres
ENT
Channel Width
0.000 Metres
ENT
Crest Height
0.000 Metres
Crest width (Metres)
Throat width (Metres)
Hump Height
0.000 Metres
Throat length (Metres)
Channel
width
(Metres)
Channel width (Metres)
Crest
height
(Metres)
7.1.6 BS3680 V-Notch Weir
ENT
Angle
000.0 Degrees
ENT
Channel Width
0.000 Metres
ENT
Vertex Height
0.000 Metres
Angle (Degrees)
Channel width (Metres)
Vertex
height
(Metres)
Ref: MINIFLEX LR MANUAL Rev. 0 20
Pr. 7.2
SECTION 3
Step D: -
Select from one of the following options if a Parshall flume is required (See also Appendix 5)
Options displayed
7.1.7.1 Parshall 1,2,3,24 inches 1, 2, 3 or 24 inches
7.1.7.2 Parshall 6 inches 6 inches
7.1.7.3 Parshall 9 inches 9 inches
7.1.7.4 Parshall 12 inches 12 inches
7.1.7.5 Parshall 18 inches 18 inches
7.1.7.6 Parshall 36 inches 36 inches
7.1.7.7 Parshall 48 inches 48 inches
7.1.7.8 Parshall 72 inches 72 inches
7.1.7.9 Parshall 96 inches 96 inches
7.1.7.10 Parshall 10 – 50 feet 10 to 50 feet
Max Flow Val
Description - Parshall flume type
* Only applies if 7.1 set to BS3680
Maximum Flow Value (D = Auto calculation)
There are two types of calculation either Auto calculate, if you want the instrument to calculate the flow automatically or Input by User if you want to enter the flow value manually.
7.2 Max Flow Val (Auto calculate)
ENT
7.3 Maximum Flow (50.00)
ENT
7.3.1 Max. Flow
50.00
Calculates flow and Manually enter flow stores in Pr.7.3 in Pr.7.3.1
7.2.1 Automatic calcul a tion
7.2.2 User sets maximum flow
Options displayed
7.2.1 Automatic Calculation
7.2.2 User sets maximum flow
Description Action following selection
This option calculates maximum flow based on the entered flume or weir values and the maximum head in metres @ Pr.3.0 Span. The calculated flow is stored in litres/sec @ Pr.7.3.1.
Selecting this option requires you to enter manually the maximum flow in litres/sec @ Pr.7.3.1 and the maximum head in me tres @ Pr.3.0.
Calculates a new flow value based on entered parameters and rewrites this flow in litres/sec then displays this value in Pr.7.3
Displays Pr.7.3.1. does not modify the existing entered value.
Ref: MINIFLEX LR MANUAL Rev. 0 21
Loading...
+ 53 hidden pages