HVAC Partners R2A3, WCA3**2, R2AM Installation Instructions Manual

INSTALLATION INSTRUCTIONS
R22 Split System Air Conditioner
Product Family: R2A3, R2AM, WCA3**2
These instructions must be read and understood completely before attempting installation.
Safety Labeling and Signal Words
DANGER, WARNING, CAUTION, and NOTE
The signal words DANGER, WARNING, CAUTION, and NOTE are used to identify levels of
hazard seriousness. The signal word DANGER is only used on product labels to signify an immediate hazard. The signal words WARNING, CAUTION, and NOTE will be used on product labels and throughout this manual and other manuals that may apply to the product.
DANGER Immediate hazards which will result in severe personal injury or death.
WARNING Hazards or unsafe practices which could result in severe personal injury or death.
CAUTION Hazards or unsafe practices which may result in minor personal injury or product or
property damage.
NOTE − Used to highlight suggestions which will result in enhanced installation, reliability, or operation.
Signal Words in Manuals
The signal word WARNING is used throughout this manual in the following manner:
WARNING
!
The signal word CAUTION is used throughout this manual in the following manner:
!
Signal Words on Product Labeling
Signal words are used in combination with colors and/or pictures on product labels.
WARNING
CAUTION
TABLE OF CONTENTS
Inspect New Unit 2...............................
Safety Considerations 2...........................
Location 2.......................................
Clearances 2....................................
Unit Support 2...................................
Refrigeration System 3...........................
Electrical Wiring 7................................
Startup Procedure 8.............................
Refrigerant Charge 8.............................
Sequence of Operation 9..........................
Maintenance 9...................................
!
DEATH, PERSONAL INJURY, AND/OR PROPERTY DAMAGE HAZARD
Failure to carefully read and follow this warning could result in equipment malfunction, property damage, personal injury and/or death.
Installation or repairs made by unqualified persons could result in equipment malfunction, property damage, personal injury and/or death.
The information contained in this manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments.
Installation must conform with local building codes and with the National Electrical Code NFPA70 current edition or Canadian Electrical Code Part 1 CSA C.22.1.
WARNING
421 01 5203 02 5/23/14
INSTALLATION INSTRUCTIONS R22 Split System Air Conditioner
INSPECT NEW UNIT
After uncrating unit, inspect thoroughly for hidden damage. If damage is found, notify the transportation company immediately and file a concealed damage claim.
SAFETY CONSIDERATIONS
Consult a qualified installer, service agency, or the dealer/distributor for information and assistance. The qualified installer must use factory authorized kits and accessories when modifying this product. Refer to the individual instructions packaged with the kit or accessory when installing.
The weight of the product requires careful and proper handling procedures when lifting or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Follow all safety codes. Wear safety glasses, protective clothing, and work gloves. Use a heat sinking material such as a wet rag − during brazing operations. Keep a fire extinguisher available. Consult local codes and the National Electric Code (NEC) for special requirements.
Improper installation, adjustment, alteration, service or maintenance can void the warranty.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
!
CUT HAZARD
Failure to follow this caution may result in property damage.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
WARNING
CAUTION
LOCATION
Check local codes for regulations concerning zoning, noise, platforms, and other issues.
Locate unit away from fresh air intakes, vents, or bedroom windows. Noise may carry into the openings and disturb people inside.
Locate unit in a well drained area, or support unit high enough so that water runoff will not enter the unit.
Locate unit away from areas where heat, lint, or exhaust fumes will be discharged onto unit (as from dryer vents).
Locate unit away from recessed or confined areas where recirculation of discharge air may occur (refer to CLEARANCES section of this document).
Rooftop installation is acceptable providing the roof will support the unit and provisions are made for water drainage and noise/vibration dampening.
NOTE: Roof mounted units exposed to wind may require wind baffles. Consult the manufacturer for additional information.
CLEARANCES
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service. Allow 24 in. (610 mm) clearance to service end of unit and 48 in. (1219.2 mm) above unit. For proper airflow, a 6 in. (152.4 mm) clearance on one side of unit and 12 in. (304.8 mm) on all remaining sides must be maintained. Maintain a distance of 24 in. (609.6 mm) between units or 18 in. (457.2 mm) if no overhang within 12 ft. (3.66m). Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
UNIT SUPPORT
NOTE: Unit must be level ± 2 degrees [3/8 inch rise or fall
per foot of run (10 mm rise or fall per 305 mm of run)] or compressor may not function properly.
A. GROUND LEVEL INSTALLATION
The unit must be level and supported above grade by beams, platform, or a pad. Platform or pad can be of open or solid construction but should be of permanent materials such as concrete, bricks, blocks, steel, or pressure treated timbers approved for ground contact. Soil conditions must be considered so that the platform or pad does not shift or settle and leave the unit partially supported. Minimum pad dimensions are shown in Figure
2. If beams or an open platform are used for support, it is
recommended that the soil be treated or area be graveled to reduce the growth of grasses and weeds.
To minimize vibration or noise transmission, it is recommended that supports not be in contact with the building structure. However, slabs on grade constructions with an extended pad are normally acceptable.
B. ROOF TOP INSTALLATION
This type of installation is not recommended on wood frame structures where low noise levels are required.
Supporting structure or platform for the unit must be level. If installation is on a flat roof, locate unit minimum 6 inches (152mm) above roof level.
Place the unit over one or more load bearing walls. If there are several units, mount them on platforms that are selfsupporting and span several load bearing walls. These suggestions are to minimize noise and vibration transmission through the structure. If the structure is a home or apartment, avoid locating the unit over bedrooms or study.
2 421 01 5203 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R22 Split System Air Conditioner
NOTE: When unit is to be installed on a bonded
guaranteed roof, a release must be obtained from the building owner to free the installer from all liabilities.
C. FASTENING UNIT DOWN
If conditions or local codes require the unit be attached in place, remove the knockouts in the base pan and install tie down bolts through the holes (refer to Figure 2).
Contact local distributor for hurricane holddown details and the P.E. (Professional Engineer) certification, when required.
!
CAUTION
PROPERTY DAMAGE HAZARD Failure to follow this caution may result in
property damage. Inadequate unit support may cause excessive
vibration, noise, and/or stress on the refrigerant lines, leading to refrigerant line failure.
Figure 2 Tie Down Knockouts
a(10mm) dia. Tie Down Knockouts In Base Pan (2 places)
View From Top
R22 outdoor units can only be used with R22 specific indoor coils. If there is a refrigerant mismatch, consult the indoor coil manufacturer to determine if a refrigerant conversion kit is available for the indoor coil.
This outdoor unit is designed for use only with indoor coils that utilize a TXV refrigerant metering device. If any other type of metering device is installed on the indoor coil, consult the indoor coil manufacturer to determine if a TXV conversion kit is available.
The compressors for these units are supplied with Polyol Ester (POE) Oil. If the existing line set and indoor coil has residual mineral oil (MO) there is no concern with percentage of oil mixtures as both are miscible with the R22. Mixtures of both oils at any percentage will lubricate and return with the R−22.
!
WARNING
EXPLOSION AND FIRE HAZARD Failure to follow this warning could result in
property damage, personal injury, or death. This unit is designed to use ONLY R−22
refrigerant. Use ONLY R22 refrigerant when charging or servicing this unit. DO NOT under any circumstances use any refrigerant other than R22 in this unit.
A
Base Pan
Width x Depth
23 x 23
(584 x 584)
25−11/16 x 25−11/ 16
(652 x 652)
31−1/8 x 31−1/8
(791 x 791)
Base Pan Width
Inches (mm)
Tie Down
Knockouts
A B C
7−3/4
4−7/16
(197)
9−1/16
(230)
9−1/16
(230)
(113)18(457)
4−7/16
(113)
6−1/2
(165)
211/4
(540)
245/8
(625)
Base
Pan
Depth
C
B
Minimum
Mounting Pad
Dimensions
23 x 23
(584 x 584)
26 x 26
(660 x 660)
31−1/2 x 31−1/2
(800 x 800)
When installing a TXV on an indoor coil, follow the instructions provided with the new TXV.
A typical TXV installation is shown in Figure 3.
Figure 3 Typical TXV Installation
INDOOR
EQUALIZER
COIL
TUBE
SENSING BULB
SUCTION TUBE
LIQUID TUBE
TXV
SENSING
STRAP
BULB (EITHER SIDE)
REFRIGERATION SYSTEM
A. COMPONENT MATCHES
Check to see that the proper system components are in place, especially the indoor coil.
421 01 5203 02 3
8 O’CLOCK 4 O’CLOCK
Specifications subject to change without notice.
SUCTION
TUBE
INSTALLATION INSTRUCTIONS R22 Split System Air Conditioner
B. REFRIGERANT LINE SETS
The refrigerant line set must be properly sized to assure maximum efficiency and proper oil circulation.
Refer to Product Specifications and Long Line Applications Guideline for line set sizing.
NOTE: Total line set length must not exceed 200 feet
(61m). A crankcase heater must be used when the refrigerant
line length exceeds 80 feet (24.4m). If outdoor unit is more than 10 feet (3m) higher than the
indoor coil, refer to the Long Line Applications Guideline manual for instructions.
When the outdoor unit is higher than the indoor coil, the vertical separation must not exceed 100 feet (30m).
When the outdoor unit is lower than the indoor coil, the vertical separation must not exceed 50 feet (15.2m).
If it is necessary to add refrigerant line in the field, use dehydrated or dry, sealed, deoxidized, copper refrigeration tubing. Do not use copper water pipe.
Do not remove rubber plugs or caps from copper tubing until connections are ready to be made.
Be extra careful when bending refrigeration tubing. Tubing can “kink” easily, and if this occurs, the entire length of tubing must be replaced.
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper product operation.
Do not leave system open to atmosphere any longer than absolutely required for installation. Internal system components especially refrigerant oils are extremely susceptible to moisture contamination. Keep ends of tubing sealed during installation until the last possible moment.
!
PERSONAL INJURY AND ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury or death.
Relieve pressure and recover all refrigerant before system repair or final unit disposal. Use all service ports and open all flowcontrol devices, including solenoid valves.
Federal regulations require that you do not vent refrigerant to the atmosphere. Recover during system repair or final unit disposal.
CAUTION
WARNING
C. ROUTING AND SUSPENDING REFRIGERANT
LINES
Run refrigerant lines as straight and direct as possible, avoiding unnecessary bends and turns. Always insulate the entire suction line. Both lines should be insulated when routed through an attic or when routed through an underground raceway.
When routing refrigerant lines through a foundation or wall, do not allow refrigerant lines to come in direct contact with the building structure.
Make openings large enough so that lines can be wrapped with extra insulation. Fill all gaps with RTV caulk. This will prevent noise transmission between the tubing and the foundation or wall.
Along floor or ceiling joists, suspend refrigerant lines so that they do not contact the building structure, water pipes, or ductwork. Use insulated or suspension type hangers. Metal straps must be at least 1” (25mm) wide to avoid cutting into the tube insulation. Keep the liquid and suction lines separate. Refer to Figure 4.
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in improper product operation.
Do not bury more than 36” (1m) of line set underground. Refrigerant may migrate to cooler buried section during extended periods of unit shutdown, causing refrigerant slugging and possible compressor damage at start−up. If ANY section of the line set is buried underground, provide a minimum 6” (152mm) vertical rise at the service valve.
D. OUTDOOR UNIT HIGHER THAN INDOOR UNIT
Proper oil return to the compressor should be maintained with suction gas velocity. If velocities drop below 1500 fpm (feet per minute), oil return will be decreased. To maintain suction gas velocity, do not upsize vertical suction risers.
E. LIQUID LINE FILTER−DRIER
NOTE: It is required that an approved filter drier (XH-6
with 25% activated alumina/75% molecular sieve desiccants) be installed in the liquid line due to the POE oil.
Leave the plugs in the tube ends until the filterdrier is installed. The optimal location for the filter−drier is close to the indoor coil. Install the filterdrier with the arrow pointing towards the indoor coil. Refer to Figure 5.
CAUTION
4 421 01 5203 02
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R22 Split System Air Conditioner
Figure 4 Routing and Suspending Refrigerant Lines
OUTDOOR WALL INDOOR WALL
CAULK
INSULATION
THROUGH THE WALL SUSPENSION
Figure 5
Liquid Line Filter−Drier Installed at Indoor Coil
LIQUID TUBE
SUCTION TUBE
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
1” (25mm) MIN
Figure 6 Service Valve
VALVE CORE
JOIST
INSULATION
SUCTION TUBE
LIQUID TUBE
SERVICE VALVE
FilterDrier (arrow points towards indoor coil)
F. SERVICE VALVES
Service valves are closed and tube stubs are plugged from the factory. Outdoor units are shipped with a refrigerant charge sealed in the unit. Leave the service valves closed until all other refrigerant system work is complete or the charge will be lost. Leave the plugs in place until line set tubing is ready to be inserted.
Service valve bodies are brass and tube stubs are copper.
NOTE: Remove valve core from schrader port on both Service Valves BEFORE brazing. This helps prevent overheating and damage to valve seals (refer to Figure 6). Replace valve core when brazing is completed.
421 01 5203 02 5
!
FIRE HAZARD
Failure to remove refrigerant and oil charge before brazing could result in personal injury, death, and/or property damage.
Refrigerant and oil mixture could ignite and burn as it escapes and contacts brazing torch. Make sure the refrigerant charge is properly removed from both the high and low sides of the system before brazing any component or lines.
Clean line set tube ends with emery cloth or steel brush. Remove any grit or debris.
3811 84
Insert line set tube ends into service valve tube stubs. Apply heat absorbing paste or heat sink product between
service valve and joint. Wrap service valves with a heat sinking material such as a wet cloth.
Braze joints using a SilFos or Phoscopper alloy.
G. BRAZING CONNECTIONS
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Braze with SilFos or Phoscopper alloy on coppertocopper joints and wrap a wet cloth around rear of fitting to prevent damage to TXV.
Specifications subject to change without notice.
WARNING
CAUTION
INSTALLATION INSTRUCTIONS R22 Split System Air Conditioner
H. EVACUATING LINE SET AND INDOOR COIL
The unit is shipped with a factory refrigerant charge. The liquid line and suction line service valves have been closed after final testing at the factory. Do not disturb these valves until the line set and indoor coil have been evacuated and leak checked, or the charge in the unit may be lost.
NOTE: Do not use any portion of the factory charge for purging or leak testing. The factory charge is for filling the system only after a complete evacuation and leak check has been performed.
!
CAUTION
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in product damage.
Never use the outdoor unit compressor as a vacuum pump. Doing so may damage the compressor.
Line set and indoor coil should be evacuated using the recommended deep vacuum method of 500 microns. If deep vacuum equipment is not available, the alternate triple evacuation method may be used by following the specified procedure.
If vacuum must be interrupted during the evacuation procedure, always break vacuum with dry nitrogen.
Deep Vacuum Method
The deep vacuum method requires a vacuum pump capable of pulling a vacuum to 500 microns and a vacuum gauge capable of accurately measuring this vacuum level. The deep vacuum method is the most positive way of assuring a system is free of air and water.
Watch the vacuum gauge as the system is pulling down. The response of the gauge is an indicator of the condition of the system (refer to Figure 7).
With no leaks in the system, allow the vacuum pump to run for 30 minutes minimum at the deep vacuum level.
Triple Evacuation Method
The triple evacuation method should only be used when system does not contain any water in liquid form and vacuum pump is only capable of pulling down to 28 inches of mercury (711mm Hg). Refer to Fig. 8 and proceed is as follows:
1. Pull system down to 28 inches of mercury (711mm Hg) and allow pump to continue operating for an additional 15 minutes.
2. Close manifold valves or valve at vacuum pump and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and fill with nitrogen until system pressure is 2 psig.
4. Close nitrogen valve and allow system to stand for 1 hour. During this time, dry nitrogen will diffuse throughout the system absorbing moisture.
5. Repeat this procedure as indicated in Figure 8.
6. After the final evacuate sequence, confirm there are no leaks in the system. If a leak is found, repeat the entire process after repair is made.
Figure 8 Triple Evacuation Sequence
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
BREAK VACUUM WITH DRY NITROGEN
WAIT
EVACUATE
Figure 7
5000
4500
4000
3500
3000
2500
2000
MICRONS
1500
1000
500
Deep Vacuum Gauge Response
and System Conditions
01
246
375
MINUTES
6 421 01 5203 02
CHECK FOR TIGHT, DRY SYSTEM
LEAK IN SYSTEM
I. OPENING SERVICE VALVES
Outdoor units are shipped with a refrigerant charge sealed in the unit. Opening the service valves releases this charge into the system.
VACUUM TIGHT TOO WET
TIGHT DRY SYSTEM
NOTE: Open the Suction service valve first. If the Liquid service valve is opened first, oil from the compressor may be drawn into the indoor coil TXV, restricting refrigerant flow and affecting operation of the system.
Remove Suction service valve cap and insert a hex wrench into the valve stem. Hold the valve body steady with an end−wrench and back out the stem by turning the hex wrench counterclockwise. Turn the stem until it just contacts the rolled lip of the valve body.
Specifications subject to change without notice.
(IF IT HOLDS DEEP VACUUM)
CHARGE SYSTEM
INSTALLATION INSTRUCTIONS R22 Split System Air Conditioner
After the refrigerant charge has bled into the system, open the Liquid service valve.
NOTE: These are not back−seating valves. It is not necessary to force the stem tightly against the rolled lip.
The service valve cap is a primary seal for the valve and must be properly tightened to prevent leaks. Make sure cap is clean and apply refrigerant oil to threads and sealing surface on inside of cap.
Tighten cap finger tight and then tighten additional 6 of a
turn (1 wrench flat) to properly seat the sealing surfaces.
J. GAUGE PORTS
Check for leaks at the schrader ports and tighten valve cores if necessary. Install plastic caps finger tight.
ELECTRICAL WIRING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing, modifying or servicing system, main electrical disconnect switch must be in the OFF position. There may be more than 1 disconnect switch. Lock out and tag switch with a suitable warning label.
The supply voltage must be 208/230 volts (197 volt minimum to 253 volts maximum) 60 Hz single phase.
Outdoor units are approved for use with copper conductors only. Do not use aluminum wire.
WARNING
Refer to unit rating plate for minimum circuit ampacity and circuit protection requirements.
Grounding
Permanently ground unit in accordance with the National Electrical Code and local codes or ordinances. Use a copper conductor of the correct size from the grounding lug in control box to a grounded connection in the service panel or a properly driven and electrically grounded ground rod.
Wiring Connections
Make all outdoor electrical supply (Line Voltage) connections with raintight conduit and fittings. Most codes require a disconnect switch outdoors within sight of the unit. Consult local codes for special requirements.
Route electrical supply (Line Voltage) wiring through knockout hole in bottom of Control Box. Connect wires to Contactor and Ground Lug according to Wiring Diagram on unit. Also refer to Figure 9.
Route thermostat wiring through rubber grommet in bottom of Control Box. Low voltage lead wires are provided in the control box for connection to thermostat wires (use wire nuts). Refer to Wiring Diagram on unit and Figure 10 for low voltage wiring examples.
NOTE: Use No. 18 AWG (American Wire Gage) colorcoded, insulated (35 ° C minimum) wire. If thermostat is located more than 100 feet (31m) from unit as measured along the control voltage wires, use No. 16 AWG colorcoded wires to avoid excessive voltage drop.
Figure 9 Electrical Supply (Line Voltage) Connections
DISCONNECT
PER NEC AND/OR
LOCAL CODES
CONTACTOR
11
23 or 13
LUG
FIELD POWER
WIRING
FIELD GROUND
WIRING
L1
L2
GROUND
421 01 5203 02 7
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R22 Split System Air Conditioner
Figure 10 Typical Thermostat Connections
THERMOSTAT FURNACE
24 VAC HOT
24 VAC COM
COOL STAGE 1
INDOOR FAN
THERMOSTAT FAN COIL
24 VAC HOT
24 VAC COM
COOL STAGE 1
INDOOR FAN
R
C
W/W1
Y/Y2
G
R
C
W/W1
Y/Y2
G
R
C
WHEAT STAGE 1
Y
G
R
C
W2HEAT STAGE 1
Y
G
AIR CONDITIONER
C
AIR CONDITIONER
C
STARTUP PROCEDURE
1. Set indoor thermostat selector switch to OFF.
2. Turn ON all electrical disconnect devices.
3. If unit has a crankcase heater, energize the heater and wait 24 hours before proceeding.
4. Set indoor thermostat at desired temperature. Be sure setpoint is below indoor ambient temperature or thermostat will not call for cooling.
5. Set indoor thermostat selector switch to COOL. Operate unit for minimum 15 minutes, then check system refrigerant charge.
REFRIGERANT CHARGE
Outdoor units are shipped with a refrigerant charge to match a specific indoor coil and 15 feet (4.6m) of refrigerant line. If shorter or longer refrigerant lines or a different indoor coil are used, the charge will have to be adjusted.
For different line lengths, add or remove charge based on
0.6 ounces (17g) charge per foot (305mm) of difference. For example, a 25 foot (7.6m) line set is 10 feet (3m) longer than the specified 15 feet (4.6m). Add 0.6 ounces (17g) charge for each of the extra 10 feet (3m):
10 x 0.6 = 6.0 ounces additional charge (3m x 17g = 51g additional charge) This outdoor unit is designed for use only with indoor coils
that utilize a TXV refrigerant metering device. With an indoor TXV, use the subcooling method to make final charge adjustments:
8 421 01 5203 02
NOTE: Only use subcooling charging method when
S outdoor ambient temperature is between 70_F and 100_F (21_C and 38_C) S indoor temperature is between 70_ and 80_F (21_C and 27_C) S line set is less that 80 feet (24.4m).
1. Operate unit a minimum of 15 minutes before checking charge. NOTE: If outdoor unit has a 2−speed fan motor, motor will operate in low speed when outdoor ambient temperature is below 82_F (28_C). Pull one of the yellow low voltage wires off the fan control and the unit will default to high speed fan for servicing. Reconnect wire after servicing.
2. Measure liquid service valve pressure by attaching an accurate gauge to service port.
3. Measure liquid line temperature by attaching an accurate thermistor type sensor or electronic thermometer to liquid line near outdoor coil.
4. Refer to unit rating plate for required subcooling temperature.
5. Refer to Figure 11. Find the required liquid line temperature where the rating plate subcooling temperature intersects measured liquid service valve pressure.
6. If the measured liquid line temperature is higher than the chart number, add refrigerant to lower the measured temperature. NOTE: When adding refrigerant, charge in liquid form, using a flow restricting device, into the suction port. If the measured liquid line temperature is lower than the chart number, reclaim refrigerant to raise the measured temperature. Tolerance is ± 3° F (± 1.7°C) .
Specifications subject to change without notice.
INSTALLATION INSTRUCTIONS R22 Split System Air Conditioner
Figure 11 Rating Plate (required) Subcooling Temperature ° F (° C)
° F (° C) ° F (° C) ° F (° C) ° F (° C)
Measured Liquid
5 3 10 6 15 8 20 11
Pressure (psig)
R22 Required Liquid Line Temperature ° F (° C)
163 83 28 78 26 73 23 68 20 171 86 30 81 27 76 24 71 22 179 89 32 84 29 79 26 74 23 187 92 33 87 31 82 28 77 25 196 95 35 90 32 85 29 80 27 205 98 37 93 34 88 31 83 28 214 101 38 96 36 91 33 86 30 223 104 40 99 37 94 34 89 32 233 107 42 102 39 97 36 92 33 243 110 43 105 41 100 38 95 35 253 113 45 108 42 103 39 98 37 264 116 47 111 44 106 41 101 38 274 119 48 114 46 109 43 104 40 285 122 50 117 47 11 2 44 107 42 297 125 52 120 49 115 46 110 43 309 128 53 123 51 118 48 113 45
SEQUENCE OF OPERATION
With power supplied to indoor and outdoor units, transformer is energized.
On a call for cooling, the thermostat makes circuits R−Y and RG. Circuit RY energizes contactor, starting outdoor fan motor and compressor. Circuit R−G energizes indoor unit blower relay, starting indoor blower motor.
When thermostat is satisfied, its contacts open, deenergizing contactor and blower relay. Compressor and motors stop.
NOTE: If indoor unit is equipped with a time−delay relay circuit, the blower runs an additional length of time to increase system efficiency.
MAINTENANCE
Condensate Drain
During the cooling season, check monthly for free flow of drainage and clean if necessary.
Cleanliness
These tips will help keep the air conditioner looking better and working more efficiently:
1. Free flow of air is essential. Keep fences, shrubs, trash cans, and other obstructions at least 18 inches (0.5m) from all coil inlets.
2. Keep the coil free of grass clippings, leaves, weeds, and other debris. NOTE: Coil may occasionally require cleaning with a liquid solution. The coil must be cold when cleaning. Use an alkaline based cleaner only. Cleaning a hot coil or using an acid based cleaner will remove the paint from the fins and may clog the coil.
3. Never use a weather cover over the outdoor unit unless it is a ventilated type or made of breathable fabric that will allow moisture to evaporate rapidly. A cover that holds moisture in the unit will cause more rust build−up and damage than normal exposure to weather.
421 01 5203 02 9
Specifications subject to change without notice.
Copyright 2014 International Comfort Products
Lewisburg, TN 37091 USA
Loading...