HVAC Partners 801S, 80DSS, 801P, 80DSP Installation Instructions Manual

ISO 9001:2008
INSTALLATION INSTRUCTIONS
FOR DOWNFLOW SINGLE STAGE GAS FURNACES
(-)801S DOWNFLOW SERIES (-)801P DOWNFLOW SERIES
(-)(-)80DSS DOWNFLOW SERIES (-)(-)80DSP DOWNFLOW SERIES
U.L. and/or C.S.A. recognized fuel gas and CO (carbon monoxide) detectors are rec­ommended in all applications, and their installation should be in accordance with the manufacturer’s recommendations and/or local laws, rules, regulations, or customs.
Factory Use Only
92-24161-143-01
SUPERSEDES 92-24161-143-00
TABLE OF CONTENTS
1 TABLE OF CONTENTS. . . . . . . . . . . . . . . . . . . . . . . 2
2 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . 3
Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Contents
California Proposition 65 Note . . . . . . . . . . . . . . . . . . 4
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 SAFETY INFORMATION. . . . . . . . . . . . . . . . . . . . . . 6
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Important Information About Efficiency and Quality. . 7
4 LOCATION REQUIREMENTS . . . . . . . . . . . . . . . . . 8
Site Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Clearance – Accessibility . . . . . . . . . . . . . . . . . . . . . . 8
Upflow Dimensions & Clearance Table . . . . . . . . . . . 9
5 DUCTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Downflow Installations . . . . . . . . . . . . . . . . . . . . . . . 10
6 COMBUSTION AND VENTILATION AIR . . . . . . . . 12
Combustion Air Requirements . . . . . . . . . . . . . . . . . 12
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
“B-1” Vertical Venting . . . . . . . . . . . . . . . . . . . . . . . . 16
Special Vent Systems (SVS) . . . . . . . . . . . . . . . . . . 17
Power Vent Systems . . . . . . . . . . . . . . . . . . . . . . . . 18
Existing Vent Systems . . . . . . . . . . . . . . . . . . . . . . . 18
7 GAS SUPPLY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Gas Supply and Piping. . . . . . . . . . . . . . . . . . . . . . . 19
Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Setting Gas Pressure . . . . . . . . . . . . . . . . . . . . . . . . 22
9 ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . . . . . 23
Reversing the Electrical Connection . . . . . . . . . . . . 23
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
8 LP CONVERSION . . . . . . . . . . . . . . . . . . . . . . . . . . 25
10 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Field Installed Option Accessories. . . . . . . . . . . . . . 26
Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
4-Inch Flue Adapter . . . . . . . . . . . . . . . . . . . . . . . . . 26
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
RXGW-B01 Chimney Adapter . . . . . . . . . . . . . . . . . 26
11 TWINNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Furnace Twinning Installations. . . . . . . . . . . . . . . . . 27
Control Boards . . . . . . . . . . . . . . . . . . . . . . . . . . 28-29
12 HIGH ALTITUDE . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Natural Gas at High Altitudes . . . . . . . . . . . . . . . . . . 30
LP Gas at High Altitudes. . . . . . . . . . . . . . . . . . . . . . 32
13 STARTUP PROCEDURES . . . . . . . . . . . . . . . . . . . 33
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . 33
14 DIAGNOSTICS & FAULT CODES . . . . . . . . . . . . . 34
15 LOCKOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
16 FIELD SELECTIONS & ADJUSTMENTS . . . . . . . 36
Field Selections – Dipswitches. . . . . . . . . . . . . . . . . 36
17 FAULT CLEAR. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
18 FAULT RECALL. . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
19 FLAME STATUS L.E.D.. . . . . . . . . . . . . . . . . . . . . . 37
20 TIMING DIAGRAM. . . . . . . . . . . . . . . . . . . . . . . . . . 37
21 ADJUSTING OR CHECKING FURNACE INPUT . 38
22 SETTING INPUT RATE . . . . . . . . . . . . . . . . . . . . . . 39
23 AIRFLOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Blower Speed Selection . . . . . . . . . . . . . . . . . . . . . . 41
24 SAFETY FEATURES. . . . . . . . . . . . . . . . . . . . . . . . 42
25 MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Gas Furnace (Direct Drive) Instructions. . . . . . . . . . 43
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
26 SYSTEM OPERATION INFORMATION . . . . . . . . . 44
27 ANNUAL INSPECTION . . . . . . . . . . . . . . . . . . . . . . 45
28 REPLACEMENT PARTS. . . . . . . . . . . . . . . . . . . . . 45
24 DIAGNOSTICS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
30 WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . 47
IMPORTANT: TO INSURE PROPER INSTALLATION AND OPERATION OF THIS PRODUCT, COMPLETELY READ ALL INSTRUC­TIONS PRIOR TO ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE, MAINTAIN OR REPAIR THIS PRODUCT. UPON UNPACKING OF THE FURNACE, INSPECT ALL PARTS FOR DAMAGE PRIOR TO INSTALLATION AND START-UP.
2
GENERAL INFORMATION
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
JUNCTION BOX DOOR SWITCH CAPACITOR MAIN PRESSURE SWITCH INDUCED DRAFT BLOWER (IDB) MAIN LIMIT BURNER FLAME SENSOR OVER T EMPERATURE SWI TCH IGNITOR GAS VALVE GAS VALVE TRANSFORMER FLUE PIPE ENCLOSURE HEAT ASSISTED LIMIT CONTROL (HALC) FLUE CONNECTION CONTROL MOUNTING PLATE FURNACE CONTROL LOW V OLTAGE TERMINAL BLOWER
16
17
18
19
1
2
3
4
5
6
7
8
11
9
10
12
13
14
15
ST-A1220-13-X0
NOTE: A heat loss calculation should be performed to properly determine the required furnace BTU size for the structure. Also, the duct must be properly designed and installed for proper air­flow. Existing ductwork must be inspected for proper size and to make sure that it is properly sealed. Proper airflow is necessary for both user comfort and equipment performance.
Before opening the furnace carton, verify that the data tags on the carton specify the furnace model number that was ordered from the distributor and are correct for the installation. If not, return the unit without opening the carton. If the model number is correct, open the carton and verify that the furnace rating label specifies the same furnace model number that is speci­fied on the carton label. If the model numbers do not match, re­turn the furnace to the distributor.
IMPORTANT: Proper application, installation and maintenance of this furnace and system is a must if consumers are to receive the full benefits for which they have paid.
FIGURE 1
FURNACE COMPONENTS
The (-)801S/(-)801P series furnaces are design certified by CSA for use with natural and propane gases as follows:
As a Category I furnace, it may be vented vertically with type B­1 vent pipe and also may be common vented as described in these instructions.
This furnace should be installed in accordance with the American National Standard Z223.1 - latest edition booklet entitled “National Fuel Gas Code” (NFPA 54), and the requirements or codes of the local utility or other authority having jurisdiction including local plumbing or waste water codes.
With the introduction of higher efficiency furnaces, special attention must be paid to the venting system. Only listed venting systems may be used as stated in the installation instructions and the Na- tional Fuel Gas Code, ANSI Z223.1 (NFPA 54),. Since furnace technology and venting requirements are changing, awareness of local, state, and federal codes and industry changes is imperative.
General Information
ST-A1220-13-X0
3
GENERAL INFORMATION (cont.)
Install this furnace in accordance with the American National Stan­dard Z223.1 – latest edition entitled “National Fuel Gas Code”
NFPA54) and requirements or codes of the local utilities or other
( authorities having jurisdiction. This is available from the following:
National Fire Protection Association, Inc. Batterymarch Park
General Information
Quincy, MA 02269
RECEIVING
Immediately upon receipt, all cartons and contents should be in­spected for transit damage. Units with damaged cartons should be opened immediately. If damage is found, it should be noted on the delivery papers, and a damage claim filed with the last carrier.
• After unit has been delivered to job site, remove carton taking care not to damage unit.
• Check the unit rating plate for unit size, electric heat, coil, volt­age, phase, etc. to be sure equipment matches what is re­quired for the job specification.
• Read the entire instructions before starting the installation.
• Some building codes require extra cabinet insulation and gas­keting when unit is installed in attic applications.
• If installed in an unconditioned space, apply caulking around the power wires, control wires, refrigerant tubing and conden­sate line where they enter the cabinet. Seal the power wires on the inside where they exit conduit opening. Caulking is re­quired to prevent air leakage into and condensate from forming inside the unit, control box, and on electrical controls.
• Install the unit in such a way as to allow necessary access to the coil/filter rack and blower/control compartment.
• Install the unit in accordance with any local code which may apply and the national codes. Latest editions are available from: “National Fire Protection Association, Inc., Batterymarch Park, Quincy, MA 02269.” These publications are:
• ANSI/NFPA No. 70-(Latest Edition) National Electrical Code.
• NFPA90A Installation of Air Conditioning and Ventilating Sys­tems.
• NFPA90B Installation of warm air heating and air conditioning systems.
• The equipment has been evaluated in accordance with the Code of Federal Regulations, Chapter XX, Part 3280.
CALIFORNIA RESIDENTS ONLY
IMPORTANT: All manufacturer products meet current Federal
OSHA Guidelines for safety. California Proposition 65 warnings are required for certain products, which are not covered by the OSHA standards.
California's Proposition 65 requires warnings for products sold in California that contain, or produce, any of over 600 listed chemi­cals known to the State of California to cause cancer or birth de­fects such as fiberglass insulation, lead in brass, and combustion products from natural gas.
All “new equipment” shipped for sale in California will have labels stating that the product contains and/or produces Proposition 65 chemicals. Although we have not changed our processes, having the same label on all our products facilitates manufacturing and shipping. We cannot always know “when, or if” products will be sold in the California market.
You may receive inquiries from customers about chemicals found in, or produced by, some of our heating and air-conditioning equip­ment, or found in natural gas used with some of our products. Listed below are those chemicals and substances commonly as­sociated with similar equipment in our industry and other manu­facturers.
• Glass Wool (Fiberglass) Insulation
• Carbon Monoxide (CO)
• Formaldehyde
• Benzene
More details are available at the Websites for OSHA (Occupa­tional Safety and Health Administration), at www.osha.gov State of California's OEHHA (Office of Environmental Health Haz­ard Assessment), at www.oehha.org. portant since the chemicals and substances on the list are found in our daily lives. Most consumers are aware that products pres­ent safety and health risks, when improperly used, handled and maintained.
Consumer education is im-
and the
4
Installation Instructions remain with the furnace as a reference guide to the servicing contractor. We recommend that performance and installation data be recorded for future reference on this sheet to meet service and warranty
bligations so that job site information is available when required.
o
Installation Checklist
REFER TO INSTALLATION INSTRUCTIONS
GAS SUPPLY
______ Correct pipe size (record size)
______ Correct supply pressure (during furnace operation) (record pressure)
______ Manifold pressure (record upstream pressure)
______ No gas leaks
______ L.P. Kit Number (if applicable) (record kit number)
ELECTRICAL
______ 115 V.A.C. supply (Dedicated Circuit) (record voltage)
______ Polarity observed
______ Furnace properly grounded
Checklist
______ Correct wire size (record type and gauge)
FURNACE INSTALLATION
______ Correct clearance to combustibles (record clearance)
______ Correct clearance for service (at front) (record clearance)
DUCT STATIC PRESSURE
______ in. w.c. on heating speed (record static pressure)
______ in. w.c. on cooling speed (record static pressure)
______ Air temperature rise in heat (record air temperature rise)
______ Air temperature rise in cool (record air temperature rise)
VENTING
______ Correct vent pipe diameter and length (according to NFGC tables) _________________ Vent connection size
______ Correct venting material (according to NFGC tables)
______ Correct lining for masonry chimneys
______ Adequate clearance from combustibles
______ Proper negative pressure reading in the vent
______ Vent pipe secured to induced draft blower housing
COMBUSTION AIR
______ Proper source of combustion air
______ Correct combustion air opening size
______ Optional attic combustion air pull
______ Non-attic combustion air pull
5
SAFETY INFORMATION
WARNING
!
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME!! THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME. DOING SO COULD CAUSE FIRE, PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
WARNING
!
INSTALL THIS FURNACE ONLY IN A LOCATION AND PO­SITION AS SPECIFIED IN THE LOCATION REQUIRE­MENTS AND CONSIDERATIONS SECTION OF THESE INSTRUCTIONS.
WARNING
!
IMPROPER INSTALLATION CAN RESULT IN UNSATISFAC­TORY OPERATION AND/OR DANGEROUS CONDITIONS AND ARE NOT COVERED BY THE MANUFACTURER’S WARRANTY.
WARNING
!
DO NOT BYPASS, JUMPER, OR REMOVE ANY SAFETY SWITCH FROM THE FURNACE CONTROL CIRCUIT. IF A SAFETY SWITCH CAUSES THE FURNACE TO SHUT DOWN OR OPERATE INTERMITTENTLY, IT IS AN INDICA­TION OF A POTENTIAL SAFETY HAZARD THAT MUST BE ADDRESSED BY A QUALIFIED TECHNICIAN, SERVICE AGENCY OR THE GAS SUPPLIER. DO NOT RESET SAFETY CONTROLS WITHOUT CORRECTIVE ACTION
Safety Information
AND/OR VERIFICATION OF PROPER SAFE OPERATION BY A QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
REPLACE ANY SAFETY CONTROL COMPONENT ONLY WITH IDENTICAL OEM REPLACEMENT PARTS. WHEN A NEW SAFETY SWITCH IS INSTALLED, IT MUST BE TESTED FOR A MINIMUM OF 15 MINUTES WITH THE FURNACE OPERATING AT MAXIMUM INPUT RATE AND WITH BOTH BLOWER AND BURNER DOOR INSTALLED. IF THE FURNACE IS INSTALLED IN A CLOSET, THE CLOSET DOOR MUST ALSO BE CLOSED FOR THIS TEST. REPEAT THE TEST AT THE MINIMUM INPUT RATE IF THE FURNACE IS A MULTI-STAGE FURNACE.
WARNING
!
USE ONLY WITH THE TYPE OF GAS APPROVED FOR THIS FURNACE. REFER TO THE FURNACE RATING PLATE.
WARNING
!
COMBUSTION AND VENTILATION AIR MUST BE PRO­VIDED TO THE FURNACE AS REQUIRED BY THE NA­TIONAL FUEL-GAS CODE (U.S.) AND THE COMBUSTION AND VENTILATION AIR SECTION OF THESE INSTRUC­TIONS.
W
AR
N
IN
N
N
N
M O
N S
PR
E
C NLY, AS ECTIO
O
G
T
D
U
TH
C
I
TS
S
SP
N O
FU
MU
F
S
R
N
E
CIFIE
THE
T
A
B
C
E
S
E INS
E
D
T
O
D IN
I
S
C
H
A
A
N
A
P
THE
V
TRUCTIO
R
G
E
PR
OV
ENT P
NS
D
O
U
T
E
D
IPE
.
!
C
O
MB
U
STI
D
O
O
VE
NT S
INST
!
WHEN A FURNACE IS INSTALLED SO THAT SUPPLY DUCTS CARRY AIR CIRCULATED BY THE FURNACE TO AREAS OUTSIDE THE SPACE CONTAINING THE FURNACE, THE RETURN AIR SHALL ALSO BE HANDLED BY DUCT(S) SEALED TO THE FURNACE CASING AND TERMINATING OUTSIDE THE SPACE CONTAINING THE FURNACE.
!
DO NOT OPERATE THE SYSTEM WITHOUT FILTERS. A PORTION OF THE DUST ENTRAINED IN THE AIR MAY TEMPORARILY LODGE IN THE AIR DUCT RUNS AND AT THE SUPPLY REGISTERS. ANY CIRCULATED DUST PAR­TICLES WILL BE HEATED AND CHARRED BY CONTACT WITH THE FURNACE HEAT EXCHANGER. THIS SOOTY RESIDUE WILL SOIL CEILINGS, WALLS, DRAPES, CAR­PETS AND OTHER HOUSEHOLD ARTICLES. SOOT DAM­AGE MAY ALSO RESULT WITH, OR WITHOUT, FILTERS IN PLACE, WHEN CERTAIN TYPES OF CANDLES ARE BURNED, OR CANDLEWICKS ARE LEFT UNTRIMMED.
!
IN COMPLIANCE WITH RECOGNIZED CODES, IT IS REC­OMMENDED THAT AN AUXILIARY DRAIN PAN BE IN­STALLED UNDER THIS FURNACE AND ANY INSTALLED EVAPORATOR COIL THAT IS LOCATED IN ANY AREA OF A STRUCTURE WHERE DAMAGE TO THE BUILDING OR BUILDING CONTENTS MAY OCCUR AS A RESULT OF AN OVERFLOW OF THE A/C COIL DRAIN PAN.
O
R
S
.
C
O
YSTE
ALLA
TIO
WARNING
WARNING
WARNING
-
WARNING
!
NEVER TEST FOR GAS LEAKS WITH AN OPEN FLAME. USE A COMMERCIALLY AVAILABLE SOAP SOLUTION MADE SPECIFICALLY FOR THE DETECTION OF LEAKS TO CHECK ALL CONNECTIONS, AS SPECIFIED IN GAS SUPPLY AND PIPING SECTION OF THESE INSTRUC­TIONS.
6
SAFETY
WARNING
!
BLOWER AND BURNERS MUST NEVER BE OPERATED WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO PRE­VENT DRAWING GAS FUMES (WHICH COULD CONTAIN HAZARDOUS CARBON MONOXIDE) INTO THE HOME THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
WARNING
!
ALWAYS INSTALL THE FURNACE TO OPERATE WITHIN THE FURNACE’S INTENDED TEMPERATURE-RISE RANGE WITH A DUCT SYSTEM WHICH HAS AN EXTER­NAL STATIC PRESSURE WITHIN THE ALLOWABLE RANGE, AS SPECIFIED IN THE DUCTING SECTION OF THESE INSTRUCTIONS. SEE ALSO FURNACE RATING PLATE.
THE FURNACE MAY BE USED FOR HEATING OF BUILD­INGS OR STRUCTURES UNDER CONSTRUCTION.
INSTALLATION MUST COMPLY WITH ALL INSTALLATION INSTRUCTIONS INCLUDING:
PROPER VENT INSTALLATION;
-
FURNACE OPERATING UNDER THERMOSTAT­CONTROL; RETURN AIR DUCT SEALED TO THE FURNACE;
-
AIR FILTERS IN PLACE;­SET FURNACE INPUT RATE AND TEMPERATURE­RISE PER RATING PLATE MARKINGS; MEANS FOR PROVIDING OUTDOOR AIR RE-
-
QUIRED FOR COMBUSTION; RETURN AIR TEMPERATURE MAINTAINED BE-
-
TWEEN 55°F (13°C) AND 80°F (27°C); AND CLEAN FURNACE, DUCT WORK AND COMPO-
-
NENTS UPON SUBSTANTIAL COMPLETION OF THE CONSTRUCTION PROCESS, AND VERIFY THAT THE FURNACE OPERATING CONDITIONS INCLUDING IGNITION, INPUT RATE, TEMPERA­TURE RISE AND VENTING, ACCORDING TO THE INSTRUCTIONS AND CODES.
WARNING
!
DUCT LEAKS CAN CREATE AN UNBALANCED SYSTEM AND DRAW POLLUTANTS SUCH AS DIRT, DUST, FUMES AND ODORS INTO THE HOME CAUSING PROPERTY
AMAGE. FUMES AND ODORS FROM TOXIC, VOLATILE
D OR FLAMMABLE CHEMICALS, AS WELL AS AUTOMO­BILE EXHAUST AND CARBON MONOXIDE (CO), CAN BE DRAWN INTO THE LIVING SPACE THROUGH LEAKING DUCTS AND UNBALANCED DUCT SYSTEMS CAUSING PERSONAL INJURY OR DEATH (SEE FIGURE 2).
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LO­CATED IN GARAGES OR OFF-GARAGE STORAGE AREAS - ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIPMENT AND DUCT MUST BE SEALED TO LIMIT THE MIGRATION OF TOXIC FUMES AND ODORS IN­CLUDING CARBON MONOXIDE FROM MIGRATING INTO THE LIVING SPACE.
• IF AIR-MOVING EQUIPMENT OR DUCTWORK IS LO­CATED IN SPACES CONTAINING FUEL BURNING AP­PLIANCES SUCH AS WATER HEATERS OR BOILERS ­ALL JOINTS, SEAMS, AND OPENINGS IN THE EQUIP­MENT AND DUCT MUST ALSO BE SEALED TO PRE­VENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPROD­UCTS INCLUDING CARBON MONOXIDE INTO THE LIV­ING SPACE.
FIGURE 2
MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES
Safety Information
IMPORTANT INFORMATION ABOUT EFFICIENCY AND INDOOR AIR QUALITY
Central cooling and heating equipment is only as efficient as the duct system that carries the cooled or heated air. To maintain effi­ciency, comfort and good indoor air quality, it is important to have the proper balance between the air being supplied to each room and the air returning to the cooling and heating equipment.
Proper balance and sealing of the duct system improves the effi­ciency of the heating and air conditioning system and improves the indoor air quality of the home by reducing the amount of air­borne pollutants that enter homes from spaces where the duct­work and / or equipment is located. The manufacturer and the U.S. Environmental Protection Agency’s Energy Star Program recommend that central duct systems be checked by a qualified contractor for proper balance and sealing.
Adapted from Residential Duct Diagnostics and Repair, with permission of Air Conditioning Contractors of America (ACCA).
7
LOCATION REQUIREMENTS
GENERAL INFORMATION
WARNING
!
WHEN THIS FURNACE IS INSTALLED IN A RESIDENTIAL GARAGE, IT MUST BE INSTALLED SO THE BURNERS AND IGNITION SOURCE ARE LOCATED NO LESS THAN 18 INCHES [450MM] ABOVE THE FLOOR. THIS IS TO PRE­VENT THE RISK OF IGNITING FLAMMABLE VAPORS WHICH MAY BE PRESENT IN A GARAGE. ALSO, THE FUR­NACE MUST BE LOCATED OR PROTECTED TO AVOID PHYSICAL DAMAGE BY VEHICLES. FAILURE TO FOLLOW THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION, RESULTING IN PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
1. IMPORTANT: If using a cooling evaporator coil with this fur- nace, be sure the air passes over the heat exchanger before passing over the cooling coil. The cooled air passing over the warm ambient air inside the heat exchanger tubes can cause condensation inside the tubes resulting in corrosion and even­tual failure. An auxiliary drain pan should extend under any evaporator coil installed with the furnace.
If there are manual dampers, they must be equipped to prevent heating or cooling operation unless the damper is in the full heat or cool position.
2. NOTE: This furnace is shipped with heat exchanger support brackets installed under the back of the heat exchanger. These may be removed before installation, but it is not required.
3. IMPORTANT: This furnace is not approved or recommended
for installation on its back, with access doors facing upwards.
4. This furnace is suitable for installation in buildings constructed on-site. This heating unit should be centralized with respect to the heat distribution system as much as practicable.
5. NOTE: These furnaces are approved for installation in attics, as well as alcoves, utility rooms, closets and crawlspaces.
6. IMPORTANT: Support this unit when installed. Unit may be rein-
stalled on combustible wood floorin if using a supply air plenum. If not using supply air plenum, a combustible floor base is re­quired. See ducting section of this manual.
7. IMPORTANT: If installing in a utility room, be sure the door is wide enough to:
Location
a. allow the largest part of the furnace to pass; or
b. allow any other appliance (such as a water heater) to pass.
WARNING
!
THIS FURNACE IS NOT APPROVED OR RECOMMENDED FOR INSTALLATION ON ITS BACK, WITH ACCESS DOORS FACING UPWARDS.
SITE SELECTION
1. Select a site in the building near the center of the pro­posed, or existing, duct system.
2. Give consideration to the vent system piping when se­lecting the furnace location. Be sure the venting system can get from the furnace to the termination with minimal length and elbows.
3. Locate the furnace near the existing gas piping. Or, if running a new gas line, locate the furnace to minimize the length and elbows in the gas piping.
4. Locate the furnace to maintain proper clearance to combustibles as shown in following Figure 3.
WARNING
!
DO NOT LIFT THE UNIT BY THE HEAT EXCHANGER TUBES. DOING SO CAN DAMAGE THE HEAT EX­CHANGER ASSEMBLY.
CLEARANCE – ACCESSIBILITY
The design of forced air furnaces with input ratings as listed in the tables under Figure 3 are clearances to com­bustible materials shown in inches.
See name/rating plate and clearance label for specific model number and clearance information.
Service clearance of at least 24 inches (30 cm) is recom­mended in front of all furnaces.
NOTE: Use recommended 24” (30 cm) clearance if accessi­bility clearances are greater than fire protection clearances.
ACCESSIBILITY CLEARANCES, WHERE GREATER, MUST TAKE PRECEDENCE OVER FIRE PROTECTION CLEAR­ANCES.
WARNING
!
COMBUSTIBLE MATERIAL MUST NOT BE PLACED ON OR AGAINST THE FURNACE JACKET. THE AREA AROUND THE FURNACE MUST BE KEPT CLEAR AND FREE OF ALL COMBUSTIBLE MATERIALS INCLUDING GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQ­UIDS. PLACEMENT OF COMBUSTIBLE MATERIALS ON, AGAINST OR AROUND THE FURNACE JACKET CAN CAUSE AN EXPLOSION OR FIRE RESULTING IN PROP­ERTY DAMAGE, PERSONAL INJURY OR DEATH. THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FUR­NACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSES.
8
FIGURE 3
DOWNFLOW DIMENSIONS
Ship.
Back Top Front Vent
REDUCED CLEARANCE (IN.)
Left Right
/8
5
/8
1
20
/16
1
28
May require 3” to 4” or 3” to 5” adapter.
May be 0” with type B vent.
May be 1” with type B vent.
/8
5
26
/8 DIA.
/8 DIA.
7
7
/16
7
24
/8 DIA.
5
1
D
/16
3
/8
/8 0 4 0 1 3 685 lbs.
/8 0 30 1 3 6105 lbs.
/8 0 30 1 3 6115 lbs.
/8 0 0 0 1 3 6120 lbs.
/8 0 0 0 1 3 6140 lbs.
1
5
5
/8 0 0 0 1 3 6150 lbs.
1
5
5
3
20
/8
3
6
23
/8 13
/8 16
/8 16
/8 20
/8 23
3
1
1
/32 10
/32 12
/32 12
27
11
11
/2 16
/2 16
1
1
Model A B C D E
05 14 12
CLEARANCE TO COMBUSTIBLE MATERIAL (INCHES)
DOWNFLOW MODELS
Side Side Wgts.
10(A) 17
07 17
/8 23
7
5
5
/32 13
/32 15
/32 15
27
11
11
/2 23
/2 23
1
1
10(B) 21 19
12 24
15 24
/4
3
19
/8
5
R.A.
B
A
/8
5
/4
3
SIGHT
34
GLASS
AIRFLOW
S.A.
E
/8
3
23
/8
3
Location
20
/16
3
6
TOP BOTTOM
/2
1
24
/8
5
26
C
LOW VOLTAGE
/16
13
26
GAS CONNECTION
ELECTRIC CONNECTION
NOTE: IN DOWNFLOW CONFIGURATION, OPTIONAL AIR CUTOUT IS NOT PERMITTED.
9
DUCTING
roper air flow is required for the correct operation of this
P furnace. Restricted air flow can cause erratic operation and can damage the heat exchanger. The duct system must carry the correct amount of air for heating and cooling if summer air conditioning is used.
WARNING
!
SOME HEATING AIRFLOW VALUES MAY BE HIGHER THAN THOSE REQUIRED FOR COOLING. BE SURE TO SIZE DUCT FOR THE MAXIMUM POS­SIBLE AIRFLOW VALUE.
SIZE AIRFLOW DISTRIBUTION SYSTEM TO AC­CEPTABLE INDUSTRY STANDARDS AND METH­ODS. TOTAL STATIC PRESSURE DROP OF THE AIR DISTRIBUTION SYSTEM SHOULD NOT EXCEED .8 INCHES W.C. THIS WILL INCLUDE ANY AIR CONDI­TIONER COIL, AIR FILTRATION SYSTEM, ZONING SYSTEM, DUCTWORK, ETC. REFER TO ADDED EQUIPMENT TECHNICAL INFORMATION TO OBTAIN PRESSURE DROP INFORMATION WHEN EQUIP­MENT IS OPERATING AT RECOMMENDED HEAT­ING OR COOLING CFMS.
IMPORTANT: When using outside air, design and adjust
the system to maintain a return air temperature ABOVE 55° F during the heating season.
NOTE: Return air grilles and warm air registers must not be obstructed or closed.
5. Connect the return air ducting to the return air opening at the top of the unit. Make the connection air tight to prevent the migration of toxic fumes and odors includ­ing carbon monoxide from migrating into the living space from an adjacent fuel-burning appliance.
NOTE: In downflow configuration, side return air cut
out is not permitted. Do not take return air from the back of the unit.
6. If a filter is installed near the furnace, be sure to
have adequate space for installation and removal of the unit filter.
NOTE: DO NOT take return air from furnace rooms,
garages or cold areas. Avoid return air from utility rooms, kitchens, laundry rooms and bathrooms.
WARNING
!
BLOWER AND BURNERS MUST NEVER BE OPERATED WITHOUT THE BLOWER DOOR IN PLACE. THIS IS TO PREVENT DRAWING GAS FUMES (WHICH COULD CON­TAIN HAZARDOUS CARBON MONOXIDE) INTO THE HOME THAT COULD RESULT IN PERSONAL INJURY OR DEATH.
FIGURE 4
DOWNFLOW INSTALLATIONS
WARNING
!
A DOWNFLOW INSTALLATION IS CERTIFIED FOR INSTALLATION ON A NON-COMBUSTIBLE FLOOR. USE THE SPECIAL BASE SPECIFIED ON THE FUR­NACE CLEARANCE LABEL. FAILURE TO INSTALL THE SPECIAL BASE MAY RESULT IN FIRE, PROP­ERTY DAMAGE, PERSONAL INJURY OR DEATH. THIS BASE IS AVAILABLE AS AN ACCESSORY.
1. Position the unit to minimize long runs of duct or runs of duct with many turns and elbows.
2. If summer air conditioning is desired, position the in­door coil on the supply-air side of the unit. Ensure that no air can bypass this coil.
3. If installing on a combustible floor and not using an air conditioning plenum, install the special non-com­bustible floor base. See Table 1 and Figure 5.
4. Connect the furnace to the supply air plenum. See Fig­ure 4.
Ducting
10
21 5/8"
F
LOOR
M
ATE RIA L
NON-COM
FLOOR BASE
FLOOR CUTOUT
DIMENSIONS
FLOOR
BASE NO.
CABINET
WIDTH
FLOOR CUTOUT
DIMENSION “A”
RXGC-B14
RXGC-B17
RXGC-B21
14.0”
17.5”
21.0”
13.4”
17.0”
20.0”
RXGC-B24
24.5”
23.5”
A
21 5/8"
TABLE 1
ON-COMBUSTIBLE FLOOR BASES
N
Floor Base Size
No. Cabinet
RXGC-B14 14
RXGC-B17 17
RXGC-B21 21
RXGC-B24 24
DUCTING
FIGURE 5
NON-COMBUSTIBLE FLOOR BASE INSTALLATION INSTRUCTIONS
COMBUSTIBLE
FLOOR
MATERIAL
NON-COM-
BUSTIBLE
FLOOR
BASE
FLOOR CUTOUT
DIMENSIONS
ST-A1194-43-00
Ducting
11
COMBUSTION AND VENTILATION AIR
COMBUSTION AIR REQUIREMENTS
IMPORTANT: This is not a direct vent furnace. Review venting instructions before installing.
WARNING
!
Combustion Air
HIS FURNACE AND ANY OTHER FUEL-BURNING APPLI-
T ANCE MUST BE PROVIDED WITH ENOUGH FRESH AIR FOR PROPER COMBUSTION AND VENTILATION OF THE FLUE GASES. MOST HOMES WILL REQUIRE THAT OUT­SIDE AIR BE SUPPLIED INTO THE FURNACE AREA. FAIL­URE TO DO SO CAN CAUSE DEATH FROM CARBON MONOXIDE POISONING.
WARNING
!
ADEQUATE FACILITIES FOR PROVIDING AIR FOR COM­BUSTION AND VENTILATION MUST BE PROVIDED IN AC­CORDANCE WITH SECTION 5.3, AIR FOR COMBUSTION AND VENTILATION, OF THE NATIONAL FUEL GAS CODE, ANSI, Z223.1 LATEST EDITION OR APPLICABLE PROVI­SIONS FOR THE LOCAL BUILDING CODES, AND NOT OBSTRUCTED SO AS TO PREVENT THE FLOW OF AIR TO THE FURNACE.
1. IMPORTANT: Air for combustion and ventilation must not come from a corrosive atmosphere. Any failure due to corro­sive elements in the atmosphere is excluded from warranty coverage.
2. Combustion air must be free of acid forming chemicals; such as sulphur, fluorine and chlorine. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, air fresheners, paint and varnish removers, refrigerants and many other commercial and household products. Vapors from these products when burned in a gas flame form acid compounds. The acid compounds increase the dew point temperature of the flue products and are highly corrosive after they condense.
3. The following types of installation may require OUTDOOR AIR for combustion, due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical storage areas.
4. If combustion air is exposed to the following substances (but not limited to the following), it should not be used and the fur­nace may require outdoor air for combustion.
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry curing and acid washing materials
WARNING
!
ALL FURNACE INSTALLATIONS MUST COMPLY WITH THE NATIONAL FUEL GAS CODE AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO CAN CRE­ATE HAZARDOUS CONDITIONS RESULTING IN PROP­ERTY DAMAGE, BODILY INJURY OR DEATH FROM SMOKE, FIRE OR CARBON MONOXIDE.
Combustion air requirements are determined by whether the furnace is in an open (unconfined) area or in a con­fined space such as a closet or small room.
When the furnace is installed in the same space with other gas appliances, such as a water heater, be sure there is an adequate supply of combustion and ventilation air for the furnace and the other appliances. Do not delete or reduce the combustion air supply required by the other gas appli­ances in this space. See Z223.1, National Fuel Gas Code (NFPA 54). An unconfined space must have at least 50 cubic feet (volume) for each 1,000 BTUH of the total input of all appliances in the space. If the open space containing the appliances is in a building with tight construction (contempo­rary construction), outside air may still be required for the appliances to burn and vent properly. Outside air openings should be sized the same as for a confined space.
IMPORTANT: ONLY THE CURRENT VENT INSTRUC­TIONS APPLY. All gas furnaces cannot be common-
vented.
OVERTEMPERATURE SAFETY SWITCHES
Furnaces are equipped with safety switches in the burner compartment to protect against over-temperature condi­tions caused by inadequate combustion air supply. The switches are located in the burner compartment. If a switch is tripped it must be manually reset after clearing the fault condition which caused it to open.
WARNING
!
Y
T
E
F
A
S
Y
N
A
E
V
O
M
E
R
R
O
,
R
E
P
M
U
J
,
S
S
A
P
Y
B
T
O
N
O
D
C
T
I
W
S
T
E
F
A
S
N
W
O
D
O
N
O
I
T
E
R
D
D
A
C
N
E
G
A
T
E
F
A
S
O
/
D
N
A
Q
A
Y
B
S
S
A
G
A
L
P
E
R
T
N
E
D
I
M
O
R
F
H Y
Y R
U
C C
I
C
T
I
W
S
E
P
O
R
O
T
O
P
A
F
B
D
E
S
S
H
T
R
O
Y
T
N
O
C
F
I
R
E
V
E
I
F
I
L
A
U
R
E
I
L
P
P
Y
N
A
E
E
O
L
A
U
F
E
H
T
U
A
C
H
I
E
T
A
R
L
A
I
T
N
E
U
Q
A
Y
S
A
G
E
W
S
L
O
R
N
O
I
T
A
C
I
T
S
N
I
D
.
T
E
F
A
S
L
P
E
R
M
E
C
A
N
R
E
H
T
S
E
S
N
A
A
Y
I
M
R
E
T
T
E
F
A
S
D
E
I
F
I
L
I
L
P
P
U
S
T
U
O
H
T
I
R
P
F
O
,
R
E
L
L
T
N
O
C
E
M
E
C
A
R
T
N
O
C
T
O
S
R N
A
N
R
U
F
Y
L
T
N
E
T
R
A
Z
A
H
Y
T
E
I
N
H
C
E
O
D
.
R
E
R
R
O
C
A
S
R
E
P
E
C
I
V
R
E
O
C
L
O
T
R
A
P
T
C
R
I
C
L
O
M
S
O
T
E
C
,
C N
C
S
N
A
S
I
T
I
T
A
H
T
D
E
S
,
N
A
I
S
E
R
T
O
A
E
V
I
T
E
P
O
E
F
C
N
E
G
A
N
E
N
O
P
.
Y
L
N
O
A
F
I
.
T
I
U
T
U
H
I M R
E
T
C
A
R
Y
T
-
A
C
I
D
N
E
B
T
S
U
E
C
I
V
T
N
O
I
N
O
I
T
E
H
T
R
O
H
T
I
W
12
COMBUSTION AND VENTILATION AIR (cont.)
TABLE 7: MINIMUM SPACE REQUIREMENTS FOR UNCONFINED SPACE, NON-DIRECT VENT*
Input
(BTUH)
Minimum
Space
(Cubic Ft)
Minimum Area
with 8
Ceilings (sq )
Typical Room
Size w/ 8'
Ceilings ( x )
50,000
2,500
313
16 x 20
75,000
3,750
470
24 x 20
100,000
5,000
625
32 x 20
125,000
6,300
790
36 x 30
150,000 7,500 940 32 x 30
TABLE 8: MINIMUM FREE AREA OPENING REQUIRED FOR A FURNACE LOCATED IN A CONFINED SPACE USING INDOOR AIR FOR COMBUSTION.
Input (BTUH)
Free Area for Each
Opening (sq inches)
50,000
100
75,000
100
100,000
100
125,000
130
150,000 150
COMBUSTION AIR REQUIREMENTS: CONFINED AND UNCONFINED SPACES
ARNI
W
!
ALL FURNACE INSTALLATIONS MUST COMPLY WITH THE NATIONAL FUEL GAS CODE, NFPA 54 AND LOCAL CODES TO PROVIDE ADEQUATE COMBUSTION AND VENTILATION AIR FOR THE FURNACE. FAILURE TO DO SO CAN RESULT IN EXPLOSION, FIRE, PROPERTY DAM­AGE, CARBON MONOXIDE POISONING, PERSONAL IN­JURY OR DEATH.
For improved indoor air quality, added safety and product per­formance we recommend direct vent type installations. If non-di­rect type vent system is used, the requirements for combustion air must be provided as identified in the National Fuel Gas Code.
Combustion air requirements are determined by whether the fur­nace is in an open (unconfined) area or in a confined space such as a closet or small room.
WARNING
!
N
A
D
A
E
R
M
T F N S M D
A
S
T
N
E
V
L
A
N
O
I U
O T
E
A
E
C
A
N
R
E
R
I
D
-
N
I
T
C
U
R
A
F
T
N
E
G
A
M
FURNACE LOCATED IN AN UNCON­FINED SPACE
USING INDOOR AIR FOR COMBUSTION:
An unconfined space must have at least 50 cubic feet for each 1,000 BTUH of total input for all appliances in the space. Table 1 below specifies minimum space requirements and a few exam­ples of the room sizes required for different inputs. The sizes are based on 8-foot ceilings.
If the open space containing the furnace is in a building with tight construction, outside air may still be required for the furnace to operate and vent properly. Outside air openings should be sized the same as for a confined space.
NG
-
E
R
I
U
Q
E
R
G
N
I
T
N
E
V
L
A
R
E
N
E
G
E
H
T
W
O
L
L
O
F
D
N
O I
,
D
I
U
G
D
G
N
I
T
N
E
L
L
A
T
S
N
I
N
E
V
T
C
T
N
I
S
N
E
,
E
R
U
O
S
R
E
P
S
E
N
I
L
E
R
I
U
Q
E
R
N
O
I
T
A
L T H Q
N
F
.
)
G
N
I
N
A
M
S
I
E
M
P
I
U
J
N
I
L
A
I
H
T
F
O
T
N
E
M
E
L
C
N
I
(
S
E
R
U
L
I
A
C
L
A
U
M
A
D
T
N
R
O
Y
R
U
U
N
A
M
S
T
R
E
P
S
G
N
I
D
U
O
F
O
T
S
E
R
N
A
P
,
E
G
A
H
T
A
E
D
R
O
F
L
A
G
N
I
N
I
A
T
C
E
R
I
D
W
O
L
L
N
I
T
L
U
R
E
P
O
R .
-
I
D
D
A
L
L
A
O
T
D
N
A
-
N
I
L
L
A
-
P
I
U
Q
E
Y
T
FURNACE LOCATED IN A CONFINED SPACE
A confined space is defined as any space for a given furnace input rating which is smaller than that which is specified in Table 1 as minimum for an “unconfined” space. If the space is less than that specified in this table, the space is defined as “confined”.
If the space is small enough to be designated as “confined”, it must have openings into the space which are located in accor­dance with the requirements set forth in the following subsections A and B. Size connected to the heated area or to the outside, and by the input of ALL
If the confined space is within a building with tight construction, combustion air must be taken from outdoors or from an area freely communicating with the outdoors.
A. USING INDOOR AIR FOR COMBUSTION:
IMPORTANT: Air should not be taken from a heated space
with a fireplace, exhaust fan or other device that may pro­duce negative pressure.
If combustion air is taken from the heated area, the openings must each have at least 100 square inches of free area. Each opening must have at least one square inch of free area for each 1,000 BTUH of total input in the space. Table 2 shows some typical examples of openings required for com­bustion air openings required for a confined space.
TABLE 2: MINIMUM FREE AREA OPENING REQUIRED FOR A FURNACE LOCATED IN A CONFINED SPACE USING INDOOR AIR FOR COMBUSTION.
appliances in the space.
Combustion Air
TABLE 1: MINIMUM SPACE REQUIREMENTS FOR UNCONFINED SPACE, NON-DIRECT VENT
B. USING OUTDOOR AIR FOR COMBUSTION:
IMPORTANT: Do not take air from an attic space that is
equipped with power ventilation. The confined space must communicate with the outdoors in
accordance with Methods 1 or 2 below. The minimum dimen­sion of air openings shall not be less than 3 inches. Where ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect.
METHOD 1:
Two permanent openings, one located within 12 inches of the top and one located within 12 inches of the bottom of the en­closure, shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
13
COMBUSTION AND VENTILATION AIR (cont.)
TABLE 9 : MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE OUTSIDE THROUGH AN OPENING OR THROUGH A VERTICAL VENT DUCT.*
Total Input for
ALL Gas
Appliances
(BTUH)
Free Area for
Each Opening
when 2 Separate
Openings are
used (sq inches)
Round Pipe Duct
Diameter (Vercal
Duct Only) (inches)
50,000
13
5
75,000
19
5
100,000
25
6
125,000
32
8
150,000 38 8
TABLE 1 0: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
OUTSIDE THROUGH A H ORIZONTAL DUCT.
Total Input for
ALL Gas
Appliances
(BTUH)
Free Area for
Each Opening
when 2 Separate
Openings are
used (sq inches)
Round Pipe Duct
Diameter
(Horizontal Duct
Only) (inches)
50,000
25
6
75,000
38
8
100,000
50
8
125,000
63
10
150,000 75 10
TABLE 1 1: MINIMUM FREE AREA REQUIRED FOR AN O P E N I NG ( W H E N O N E OPENING I S USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
*
Total Input for
ALL Gas
Appliances
(BTUH)
Free Area for an Opening when 1 Opening is used
(sq inches)
Round Pipe Duct
Diameter (inches)
50,000 25 6
75,000
38
8
100,000
50
8
125,000
63
10
150,000 75 10
OUTSIDE.
GAS
WATER
HEATER
FURNACE
12”
MAX
12”
MAX
NOTE: EACH OPENING SHALL HAVE A FREE AREA OF NOT LESS THAN ONE SQUARE INCH PER 1,000 BTU PER HOUR OF THE TOTAL INPUT RATING OF ALL EQUIPMENT IN THE ENCLOSURE, BUT NOT LESS THAN 100 SQUARE INCHES.
AIR FROM HEATED SPACE
COMBUSTION AIR REQUIREMENTS: CONFINED AND UNCONFINED SPACES
TABLE 3: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
Combustion Air
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH AN OPENING OR
3. THROUGH A VERTICAL DUCT.
A. Where directly communicating with the outdoors through an
opening or where communicating to the outdoors through vertical ducts as shown in Figure 7, each opening shall have a minimum free area of 1 square inch for each 4,000 BTUH of total appliance input rating of all equipment in the enclo­sure. Table 3 specifies the minimum area for each of the 2 combustion air openings and minimum round duct diameter for direct openings and vertical ducting only.
B. Where communicating with the outdoors through horizon­tal ducts, each opening shall have a minimum free area of 1 square inch for each 2,000 BTUH of total appliance input rat­ing of all equipment in the enclosure (see Figure 8). Table 4
TABLE 4: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH A HORIZONTAL DUCT.
TABLE 5: MINIMUM FREE AREA REQUIRED FOR EACH OPENING (WHEN TWO OPENINGS ARE USED) WITH A FURNACE:
1. LOCATED IN A CONFINED SPACE
2. USING OUTDOOR AIR FOR COMBUSTION
3. COMMUNICATING DIRECTLY TO THE
3. OUTSIDE THROUGH A HORIZONTAL DUCT.
specifies the minimum area for each of the 2 combustion air openings and minimum round duct diameter for horizontal ducting only.
METHOD 2:
One permanent opening located within 12 inches of the top of the enclosure, shall be permitted where the equipment has clearances of at least 1 inch from the sides and back and 6 inches from the front of the appliance. The opening shall di­rectly communicate with the outdoors or communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum of:
FIGURE 6
AIR FROM HEATED SPACE
14
ST-A1227-01-00
COMBUSTION AND VENTILATION AIR (cont.)
GAS
W
ATER
HEATER
FURNACE
OPTIONAL 1 SQ. INCH PER 4000 BTUH INLET AIR
GABLE
VENT
V
ENTILATED ATTIC GABLE OR SOFFIT VENTS
OUT LET A IR I
N ATT IC MUST BE ABOVE I
NSULATION
1 SQ. INCH PER 4000 BTUH INLET AIR
12” MAX
1 SQ. INCH PER
4
000 BTUH
OUT LET A IR
G
AS
WATER
HEATER
FURNACE
12”
MAX
INLET AIR 1 SQ. INCH
PER 2000 BTUH
OUTLET AIR 1 SQ. INCH
PER 2000 BTUH
OUTLET AIR 1 SQ. INCH PER 4
000 BTUH
I
NLET AIR 1 SQ. INCH PER 4000 BTUH
COMBUSTION AIR REQUIREMENTS: CONFINED AND UNCONFINED SPACES
FIGURE 7
IR FROM ATTIC/CRAWL SPACE
A
A. 1 Square inch for each 3,000 BTUH of the total input rat-
ing of all equipment located in the enclosure and
B. Not less than the sum of the areas of all vent connectors
in the confined space.
If the unit is installed where there is an exhaust fan, sufficient ventilation must be provided to prevent the exhaust fan from cre­ating negative pressure.
It is also acceptable to run the condensate drain (or refriger­ant) line access over the air intake hole as long as a 1" mini­mum clearance is maintained.
Combustion air openings must not be restricted in any manner.
IMPORTANT: When indoor combustion air is used, the inlet air opening at the furnace must be protected from accidental block­age.
ST-A1227-02-00
FIGURE 8
OUTSIDE AIR USING A
ORIZONTAL INLET & OUTLET
H
ST-A1227-03
IMPORTANT: If the furnace is in a location with an exhaust fan, there must be sufficient ventilation to prevent the exhaust fan from creating a negative pressure in the room.
Combustion air openings must NOT BE RESTRICTED in any manner.
CONSULT LOCAL CODES FOR SPECIAL REQUIREMENTS.
B: Method 3
For the optimum in quiet operation, attic air may be brought di­rectly to the furnace.
IMPORTANT: In applications using Method 3 for combustion air, the attic must be ventilated by gable or soffit vents.
Combustion Air
15
Loading...
+ 33 hidden pages