HVAC Controls RTC70.XX Instructions For Use Manual

RTC70.XX electronic heating thermostat
This type electronic thermostat for mounting in standard wall box, the thermostat is adjustable to required temperature from +5/+40C, the LED shows that the heat is On, the thermostat is recommended for control of electric heating devices or on/off valve actuator used in water-based heating systems
Temperature Setting
Thermostat Adjustment
When the room temperature has been stabilized, the thermos­ tat set position may be adjusted to match actual room tempera­ ture. Measure the temperature of the room with an accurate thermometer. Remove control knob(1) and spin the pole(D), then reposition the control knob so that the indicated tempera­ ture line shows the same as the measured temperature (picture 2). We have adjusted the temperature, please do not spin the pole when installation.
Max./Min. Temperature Setting
A locking mechanism is positioned behind the control knob to limit the amount of adjustment possible. By loosening the little screw C (picture2)the scale range can be locked, e.g. Between 20 and 25 . The red ring indicates the maximum tempera­ ture and the green ring indicates the minimum temperature.
Dimension:
Mounting of Floor Sensor
Floor sensor should be placed in installation pipe which is embed­ ded in floor, the pipe is thickened in the end and placed as high as possible in the concrete layer. Sensor cable may be extended up to 50 m with separate cable f or power current. Two conductors in a multi-conducting cable, which e.g. is used for supply of heating cable, may not be used. Voltage signals, which may disturb the function of the thermostat, may occur. If the cable is used with screen, the screen may not be connected to the ground, but must be connected to terminal 7, the best installation is attained with a separate cable for the sensor, which is then mounted in a separate conduit.
Temperature and Value of Floor Sensor
Temperature ( ) Value ( )
5 22070 10 17960 20 12091 30 8312 40 5827
Placement of Thermostat
Thermostat is to be mounted on the wall with free air circulation around it . Furthermore it has to be placed where it is not influenced by any other heating sources (e.g. the sun), draft from doors or windows, or by the temperature of an exterior wall.
Operation manual
.
.
40
30
20
86mm
RTC70.13 3A built-in sensor
RTC70.26 16A floor sensor
for control of on/off electric or electro-thermal actuator
control of electric heating devicesfor
Selection Table
On/Off
-On -Off
Temperature setting 540
Indicator the light is red when heat is on
Mounting Instructions
RTC70.XX Electronic Heating Thermostat
Model Current Sensor Application
Technical data:
Voltage : AC230V(AC110V / AC24V available) Power consumption : 5W Setting range : 5 40 Switching differential : 0.5K Ambient temperature : -5 50 Protective housing : IP20 Housing material : anti-flammable PC Floor sensor : NTC sensor, cable length is 3m
rubber-thermoplastic
RTC70.16 16A built-in sensor
.
.
40
30
20
10
.
Parts
Knob
Cover
Internal frame
Thermostat
External frame
Mounting Instructions
RTC70.XX Electronic Heating Thermostat
Mounting steps:
Sensor
RTC70.13 Imax=3A
RTC70.16 Imax=16A
RTC70.26 Imax=16A
RTC70.22 Imax=20A
Loading...