If the information in these instructions are not followed
exactly, a fire or explosion may result, causing property
damage, personal injury or death.
Installation and service must be performed by a qualified
installer or service agency.
READ THE ENTIRE MANUAL BEFORE
INSTALLING OR USING THIS EQUIPMENT.
The unit uses R-290 (propane) gas as the refrigerant.
R-290 (propane) is flammable and heavier than air. It
collects first in low areas but can be circulated by the
fans. If propane gas is present or even suspected, do not
allow untrained personnel to attempt to find the cause.
The propane gas used in the unit has no odor. The lack
of smell does not indicate a lack of escaped gas. If a
leak is detected, immediately evacuate all persons from
the store, and contact the local fire department to advise
them that a propane leak has occurred. Do not let any
persons back into the store until the qualified service
technician has arrived and that technician advises that it
is safe to return to the store. No open flames, cigarettes
or other possible sources of ignition should be used
inside or in the vicinity of the units.
with R290 Refrigerant
Installation &
Operation Manual
FAILURE TO ABIDE BY THIS WARNING COULD
RESULT IN AN EXPLOSION, DEATH, INJURY AND
PROPERTY DAMAGE.
IMPORTANT
Keep in store for future reference!
MANUAL - SELF CONTAINED R290 VRM I/O
P/N 3034041_D
October 2018
Spanish 3034047
French 3034046
Page 2
2 InstallatIon
BEFORE YOU BEGIN
Read these instructions completely and carefully.
PERSONAL PROTECTION EQUIPMENT (PPE)
Personal Protection Equipment (PPE) is required whenever installing or servicing this
equipment. Always wear safety glasses, gloves, protective boots or shoes, long pants, and a
long-sleeve shirt.
1. If the information in these instructions are not followed exactly, a fire or explosion may result, causing property damage, personal
injury or death.
2. Installation and service must be performed by a qualified installer or service agency.
3. This unit is designed only for use with R-290 (propane) gas as the designated refrigerant.
THE REFRIGERANT LOOP IS SEALED. ONLY A QUALIFIED TECHNICIAN SHOULD ATTEMPT TO SERVICE!
• Propane is flammable and heavier than air.
• It collects first in the low areas but can be circulated by the fans.
• If R-290 (propane) is present or even suspected, do not allow untrained personnel to attempt to find the cause.
• The propane gas used in the unit has no odor.
• The lack of smell does not indicate a lack of escaped gas.
• If a leak is detected, immediately evacuate all persons from the store, and contact the local fire department to advise them that a pro
pane leak has occurred.
• Do not let any persons back into the store until the qualified service technician has arrived and that technician advises that it is safe to
return to the store.
• A hand-held propane leak detector (“sniffer”) shall be used before any repair and/or maintenance.
• No open flames, cigarettes or other possible sources of ignition should be used inside the building where the units are located until
the qualified service technician and/or local fire department determines that all propane has been cleared from the area and from the
refrigeration systems.
• Component parts are designed for propane and non-incendive and non-sparking. Component parts shall only be replaced with identical
repair parts.
FAILURE TO ABIDE BY THIS WARNING COULD RESULT IN AN EXPLOSION, DEATH, INJURY AND PROPERTY DAMAGE.
situation which, if not avoided, will
result in death or serious injury.
• WARNING – Indicate[s] a hazardous
situation which, if not avoided, could
result in death or serious injury.
• CAUTION – Indicate[s] a hazardous
situation which, if not avoided, could
result in minor or moderate injury.
Do NOT remove shipping crate until
the merchandiser is positioned for
installation.
Excessive ambient conditions may
cause condensation and therefore
sweating of doors. Facility operators
should monitor doors and oor
conditions to ensure safety of persons.
• NOTICE – Not related to personal injury –
Indicates[s] situations, which if not avoided,
could result in damage to equipment.
These merchandisers are manufactured to meet
ANSI / UL 471 standard requirements for
safety. Proper installation is required to maintain
this listing. Near the serial plate, each case
carries a label identifying the type of conditions
for which the merchandiser was tested.
ANSI/NSF-7 Type I – Display
Refrigerator / Freezer Intended for
75°F / 55% RH Ambient Application
ANSI/NSF-7 Type II – Display
Refrigerator / Freezer Intended for
80°F / 55% RH Ambient Application
ANSI/NSF-7 – Display Refrigerator
Intended for Bulk Produce
FEDERAL / STATE REGULATION
These merchandisers, at the time they are
manufactured, meet all federal and state /
provincial regulations.
Apparent Loss or Damage
If there is an obvious loss or damage, it must
be noted on the freight bill or express receipt
and signed by the carrier’s agent; otherwise,
carrier may refuse claim.
Concealed Loss or Damage
When loss or damage is not apparent until
after equipment is uncrated, retain all packing
materials and submit a written response to the
carrier for inspection within 15 days.
LOCATION
These merchandisers are designed for
displaying products in air conditioned stores
where temperature is maintained at or below
the ANSI / NSF-7 specified level and relative
humidity is maintained at or below 55%.
HUSSMANN PRODUCT CONTROL
The serial number and shipping date of all
equipment is recorded in Hussmann’s files
for warranty and replacement part purposes.
All correspondence pertaining to warranty or
parts ordering must include the serial number
of each piece of equipment involved. This is
to ensure the customer is provided with the
correct parts.
SHIPPING DAMAGE
All equipment should be thoroughly examined
for shipping damage before and during
unloading. This equipment has been carefully
inspected at our factory. Any claim for loss
or damage must be made to the carrier. The
carrier will provide any necessary inspection
reports and/or claim forms.
Recommended operating ambient
temperature is between
60°F (15.6°C) to 80°F (26.7°C).
Maximum relative humidity is 55%.
Placing refrigerated merchandisers in direct
sunlight, near hot tables or near other heat
sources could impair their efficiency. Like
other merchandisers, these merchandisers
are sensitive to air disturbances. Air currents
passing around merchandisers will seriously
impair their operation. Do NOT allow air
conditioning, electric fans, open doors or
windows, etc. to create air currents around
the merchandiser. VRM units in take air and
exhaust air through the front of the case, and
require no clearance space on top, at back or
either side.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
VRM Merchandisers
Page 6
6 InstallatIon
36 in.
Front
Air Exhaust
Air Intake
SELF CONTAINED (LOCATION)
Product should always be maintained at proper
temperature. This means that from the time the
product is received, through storage, preparation
and display, the temperature of the product
must be controlled to maximize the life of the
product.
Besuretopositionselfcontained
merchandisersproperly.
VRM models have vented base panels to allow
air circulation through the condensing unit.
Allow for a minimum 36 in. clearance in the
front. Blocking or restricting air flow will
adversely affect performance and may damage
the refrigeration system.
Move the merchandiser as close as possible to
its permanent location and remove all packaging.
Check for damage before discarding packaging.
Remove all separately packed accessories such as
kits and shelves.
Improper handling may cause damage to the
merchandiser when unloading. To avoid damage:
1. Do not drag the merchandiser out of the
trailer. Use a Johnson bar (Mule).
2. Use a forklift or dolly to remove the
merchandiser from the trailer.
Remove the top of the crate and detach walls
from each other (if applicable). Lift crate from
the skid. Unscrew the case from the skid. The
merchandiser can now be lifted off the crate
skid. Lift only at base of skid! Remove any
braces and/or skids attached (blanket wrapped
merchandiser may have skids).
DO NOT TILT MERCHANDISER ON ITS
SIDE OR END WHEN REMOVING SKID.
Once the skid is removed, the merchandiser
must be lifted —NOT PUSHED— to
reposition. To remove the skid, remove screws
attaching skid to the merchandiser.
Check floor where merchandisers are to be set
to if it is a level area. Determine the highest
part of the floor.
Do NOT stand or walk on top of
merchandiser. Do not store items or
ammable materials atop the unit.
EXTERIOR LOADING
Do NOT walk on top of the merchandiser or
damage to the merchandisers and serious
personal injury could occur.
merchandisersarenotstructurally
designedtosupportexcessiveexternal
loadingsuch as the weight of a person. Do
not place heavy objects on the merchandiser.
SHIPPING SKID
Each merchandiser is shipped on a skid to
protect the merchandiser’s base and to make
positioning the case easier.
August 31, 2018
This warning does not mean that Hussmann products
will cause cancer or reproductive harm, or is in
violation of any product-safety standards or
requirements. As clarified by the California State
government, Proposition 65 can be considered more of
a ‘right to know’ law than a pure product safety law.
When used as designed, Hussmann believes that our
products are not harmful. We provide the Proposition
65 warning to stay in compliance with California State
law. It is your responsibility to provide accurate
Proposition 65 warning labels to your customers when
necessary. For more information on Proposition 65,
please visit the California State government website.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
VRM Merchandisers
Page 8
8 InstallatIon
MODEL DESCRIPTION
VRM merchandisers are medium temperature
self-contained cabinets, designed for the
display of dairy products, deli items and
beverages.
Design Features
- Contemporary styling places maximum
attention on merchandising
- All VRM merchandisers have the same
access panel design for commonality between
merchandisers
- Self-closing Innovator doors. Positive seal,
torsion type closure system
- Triple-pane thermal insulated glass door
assemblies
- Magnetic door gaskets of one-piece
construction, removable without tools for
ease of cleaning
- Merchandiser can be placed against wall no air gap is required behind the case
- Digital display in center of case air grill
Adjustable
Foot
CABINET LEVELING
This merchandiser must be installed level
(from back to front, and side to side) to allow
maximum draining of the condensate water as
well as proper door alignment and operation.
Choose a level area to install case.
VRM2B and VRM3B also have an adjustable
foot at center front and back. Turn the foot
levelers clockwise to add length to each foot
for leveling.
When optional casters are used, screw them
tight to the merchandiser base. Once in final
position, lock each caster.
After the cabinet is leveled, the shelves may
be installed. Wire shelves are adjustable. Shelf
spacing can be adjusted by positioning the
shelf clips according to individual loading
requirements.
VRM merchandisers have four movable wire
shelves and one bottom wire shelf, per door.
Shelves
LAMPS
This merchandiser has a light switch inside of
the left door frame. The switch controls the
display lighting and interior lighting.
Bottom Shelf
Light Switch
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
VRM Merchandisers
Page 10
10 InstallatIon
STOCKING
Product should NOT be placed in case
until merchandiser is at proper operating
temperature. VRM merchandisers must
remain in operation for at least 24 hours before
product may be loaded into case cabinet.
Proper rotation of product during stocking
is necessary to prevent product loss. Always
bring the oldest product to the front and set
the newest to the back.
AirexhAustAndreturngrillemustremAin
openAndfreeofobstructionAtAlltimes.
Do not allow product, packages, signs, etc. to
block air exhaust or return grille. Do not use
non-approved shelving, baskets, display racks,
or any accessory that could hamper air curtain
performance.
LOAD LIMITS
Product must be within designated load limit
to ensure proper refrigeration and air curtain
performance.
Hussmann Self-Contained Refrigeration Equipment Start Up Check List
***Please note that failure to follow this start-up document may void your factory warranty***
StepStartup Activity Check
1
Locate, read and maintain install/operation manual in a safe place for
future reference.
2 Examine unit. Conrm there is NO damage or concealed damage.
3 Level the unit, side to side and front to rear.
4 Remove all shipping brackets/compressor straps/bolts etc.
5
6
Unit must be run on a dedicated electrical circuit without the use of an
extension cord.
Ensure that the proper electrical requirements for the equipment are
supplied.
7 Verify eld electrical connections are tight.
8
Verify all electrical wiring is secured and clear of any sharp edges or
hot lines.
9 Verify the condensate drain line is properly trapped and pitched.
10 Verify all required clearances on the sides and back of unit.
11
Verify there are no air disturbances external to the unit. Heat and air
registers, fans, and doors etc.
Advise owner/operator that merchandiser must operate at temperature for 24 hrs prior to
loading with product.
Form HSCW01 Rev. 30MAY12 P/N 0525209_B
LEGAL DISCLAIMER:
Hussmann shall not be liable for any repair or replacements made without the written consent of Hussmann, or when the product is installed or operated in a
manner contrary to the printed instructions covering installation and service which accompanied such product.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
The plug cord is 9 ft long and is located on
the right hand rear of the merchandiser.
Disconnect power before servicing. VRM
merchandisers require a dedicated electrical
circuit with ground. 12AWG is the minimum
sized acceptable wire.
Merchandiser must be grounded.
Do not remove the power supply cord ground.
COMPONENT AMPERES
5- P
All Models
• The VRM models require a dedicated
15AMP/115V circuit with a grounded wall
receptacle (NEMA 5-15R).
• Always use a dedicated circuit with the
amperage stated on the unit.
• Plug into an outlet designed for the plug.
• Do not overload the circuit.
• Do not use long or thin extension cords.
Never use adapters.
• If in doubt, call an electrician.
Risk of Electric Shock. If cord or plug
becomes damaged, replace only with a
cord and plug of the same type.
Nominal
Voltage
Minimum
Voltage
Maximum
Voltage
120108132
— LOCK OUT / TAG OUT —
To avoid serious injury or death from electrical
shock, always disconnect the electrical power
at the main disconnect when servicing or
replacing any electrical component. This
includes, but is not limited to, such items as
doors, lights, fans, heaters, and thermostats.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
VRM Merchandisers
Page 14
14 ElEctrIcal / rEfrIgEratIon
Before Beginning Any Service or Repair:
Use a hand-held propane leak detector (“sniffer”)
to ensure no propane is present in the immediate
area, the inside of the display case and the inside
of the refrigeration system. R-290 is an odorless
refrigerant. Keep the area clear of all customers
and non- essential or unauthorized personnel.
Only Hussmann or factory
trained technicians should
Verify that all repair parts are identical models
to the ones they are replacing. Do not substitute
parts such as motors, switches, relays, heaters,
compressors, power supplies or solenoids. Failure
to do so can result in an explosion, death, injury
and property damage. Parts used on hydrocarbon
cases must meet specic UL certication for nonincendive or non-sparking components. Use only
Hussmann approved parts approved through the
Hussmann Performance Parts Website.
https://parts.hussmann.com/
Brazing must not begin before all propane has
been cleared from the immediate area — the
inside of the displays case and the inside of the
refrigeration system.
If a leak is detected, follow store safety
procedures. It is the store’s responsibility to have
a written safety procedure in place. The safety
procedure must comply with all applicable codes
such as local re department’s codes.
At minimum, the following actions are required:
• Immediately evacuate all persons from the
store, and contact the local re department to
advise them that a propane leak has occurred.
• Call Hussmann and/or a qualied service
agent and inform them that a propane sensor has
detected the presence of propane.
• Do not let any persons back into the store
until the qualied service technician has arrived
and that technician advises that it is safe to
return to the store.
service or repair this R-290
(propane) equipment.
Failure to follow
instructions can result in
an explosion, death, injury
and property damage.
• The propane gas used in the unit has no odor.
The lack of smell does not indicate a lack of
escaped gas.
• A hand-held propane leak detector
(“sniffer”) should be used before any repair and/
or maintenance is attempted. All repair parts
must be identical models to the ones they are
replacing.
• No open flames, cigarettes or other possible
sources of ignition should be used inside the
building where the units are located until the
qualied service technician and/or local re
department determines that all propane has been
cleared from the area and from the refrigeration
systems.
Only Hussmann service technicians or
technicians qualified to handle R-290
(propane) refrigerant should service or repair
this R-290 (propane) equipment Failure to
components, and servicing shall be done by
factory authorized service personnel only, so
as to minimize the risk of possible ignition
due to incorrect parts or improper service.
follow instructions can result in an explosion,
death, injury and property damage.
Extreme care must be taken not to overll the
refrigeration system. After charging, carefully
disconnect the hoses, attempting to minimize
CHARGING
the quantity of refrigerant released. Further
leak check the service ports, hoses, refrigerant
A calibrated scale with +/-2 gram accuracy
must be used to charge the system. The charge
amount is shown on the serial plate. Only R-290
grade refrigerant can be used. Standard propane
tanks. The service ports shall be checked for
leaks using a hydrocarbon leak detector with a
sensitivity of 3 grams/year (0.106 Oz/year) leak
rate.
does not meet the purity/moisture content of
R-290, and therefore cannot be used to charge
cases.
Thoroughly leak check the service ports. If no
leak is present, use a pinch-off tool to close
the ends of the service tubes before brazing
No gas charge adjustments are allowed. When
connecting hoses between the refrigeration
system, manifold gauges, and refrigerant
cylinder, ensure that the connections are secure
them shut. If a Schrader valve is used on the
compressor service tube, it must be removed and
the previous steps followed in order to braze the
service tube shut.
and there are no potential sources of ignition
nearby. Ensure that contamination of different
refrigerants does not occur when using charging
equipment.
Use dedicated hoses to service R-290 (propane)
refrigeration systems. Hoses or lines should be
as short as possible to minimize the amount of
refrigerant contained in them.
Ensure that the refrigeration system is properly
grounded prior to charging the system with
refrigerant, to avoid the potential for static
build-up.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
SCALE 1:2.29
FIX IN THE WALL
.30
GAP BTW EDGE
OF BASE AND SENSOR
VRM Merchandisers
Page 18
18 ElEctrIcal / rEfrIgEratIon
CONTROLLER
Hussmann Controller Operation RTN
1. Plug the merchandiser plug into its receptacle.
a. The controller display will illuminate.
b. The interior light will illuminate.
2. After the control preprogrammed time
delay of up to 6 minutes, the compressor and
evaporator fan(s) will start if the control is
calling for cooling.
3. The control will cycle the compressor but
may also cycle evaporator fan(s) on and off
determined by the Set-Point and Differential
temperatures.
a. The Set-Point is the adjustable
preprogrammed temperature.
b. The Differential is the non-adjustable pre
programmed temperature.
c. The Control is designed to read and display
a cabinet temperature not a product
temperature.
Taking as an example a VRL case, freezer, If the
Set-Point is -12°F and the Differential is 9°F.
(Set-Point) -12°F + 9 (Differential) = -3°F. The
compressor and evaporator fan(s) will cycle off
-12°F and back on at -3°F.
Main Features:
• Panel-mounted
• Energy saving algorithms and optimised
defrost control
• 8 preloaded applications
• Defrost at single / double evaporator
• Frame Heater
• Local network auto-conguration
• Direct load connection (up to 2 HP)
• Supply voltage control LVD
• Presence of an open collector output
This cabinet temperature may reflect the
refrigeration cycle of the Set-Point and it’s
Differential. The most accurate temperature
on a cabinets operation is to verify the product
temperature.
KDEPLUS BUTTONS
The KDEPlus keyboard has 4 keys, as shown in the illustration:
(heatings, modulated heaters, reverse cycle, hot gas)
• Evaporator fans and condenser fans
• Frame Heater
• AUX
• Light
• Door switch
• ON /OFF
• Deep cooling cycle
• Day / Night
• Diagnostics
• “Easy Map” programming
• Programmable inputs/outputs
• LINK2 local area network
• RS485 communication protocol: Modbus
• Compatible with Device Manager (DM)
• Compatible with Unicard and Multi-function key
TECHNICAL DATA
Classification:electronic automatic control (not safety) device for incorporation
Mounting:panel mounting
Type of action:1.B
Pollution class:2
Material class:IIIa
Overvoltage category:II
Nominal pulse voltage:2500V
Temperature:Use: –5 … +55°C - Storage: -30 … +85°C
Power supply:SMPS 100-240Va ±10% 50/60 Hz
Power consumption:5.5W max
Fire resistance category:D
Software class:A
RTC battery life:In absence of external power, the clock battery will last 3 years.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
VRM Merchandisers
Page 20
20 ElEctrIcal / rEfrIgEratIon
2 - SPECIFICATIONS
TECHNICAL DATA
Classification:electronic automatic control (not safety) device for incorporationMounting:panel mountingType of action:1.BPollution class:2Material class:IIIaOvervoltage category:IINominal pulse voltage:2500VTemperature:Use: –5 … +55°C - Storage: -30 … +85°CPower supply:SMPS 100-240Va ±10% 50/60 HzPower consumption:5.5W maxFire resistance category:DSoftware class:ARTC battery life:In absence of external power, the clock battery will last 3 years.
:The technical specifications stated in this document regarding measurement (range, accuracy, resolution, etc.) refer to
Dimensions:121x92 mm
Terminals:faston and screw for wires with cross-section of 2.5mm
Connectors:
Humidity:
TTL for Unicard / Device Manager connection (via DMI)
Usage / Storage: 10...90% RH (non-condensing)
REGULATIONS
Electromagnetic compatibility:The device complies with Directive 2004/108/EC
Safety:The device complies with Directive 2006/95/EC
Food Safety:The device complies with standard EN13485 as follows:
• Suitable for storage.
• Application: air.
• Climate range A
• measurement class 1 in the range from -25°C to 15°C (*)
(* with Eliwell probes only)
2
NOTE
the instrument alone and not to any accessories provided, such as the probes.
This means, for example, that the error introduced by the probe must be added to the error of the instrument.
The KDEPlus keyboard has 4 keys, as shown in the illustration:
UP
1
DOWNSET
Each key has a different function depending on whether it is:
• Pressed and released
• Pressed for at least 5 seconds
• Pressed and held at start-up
• Pressed in combination with another key.
KEYS
The following table summarizes the function of each key:
NoKey
1
2
• Scrolls through menu items
• Decreases values
• Scrolls through menu items
• Decreases values
2
Pressed and releasedPress for at least 5 secsStart-up
Activates the Manual Defrost function
(from outside menus).
Function can be configured by the user
(from outside menus).
(see parameter H32)
Action
STANDBY or ESC
3
4
---
---
• Returns to the previous menu
3
4
set
level
• Confirms parameter value
• Displays any alarms
(if active)
• Opens Machine Status menu
• Confirms commands
Activates the Stand-by function
(from outside menus).
Opens the Programming Menu
(User and Installer parameters)
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
---
When pressed during
start-up it enables
the user to select the
application to be loaded.
VRM Merchandisers
Page 24
24 ElEctrIcal / rEfrIgEratIon
SETPOINT: SETTING AND EDIT LOCK
To display the Setpoint value, press the
set
key to enter the “Machine Status” menu, then press the
set
key again when the “SEt” label is displayed.The Setpoint value appears on the display. To change the Setpoint value, press the and keys within 15 seconds.Press
set
to confirm the modification.
set
set
set
It is possible to disable the keypad on this device.The keypad can be locked by programming the “LOC” parameter appropriately.With the keypad locked, you can still access the “Machine Status” menu by pressing
set
to display the Setpoint, but you cannot edit
it. To disable the keypad lock, repeat the locking procedure.
DISPLAY PROBES VALUE
To display the value read by probes connected to the device, press the
set
key and enter the “Machine Status” menu, then press
the key again when one of the probe-related labels “Pb1...Pb5” press the
set
key again. The value measured by the associated
probe will appear on the display.
NOTE: The displayed value is read-only and cannot be modified.
SETPOINT: SETTING AND EDIT LOCK
To display the Setpoint value, press the
label is displayed.
The Setpoint value appears on the display. To change the Setpoint value, press the and keys within 15 seconds.
Press
to confirm the modification.
set
set
set
key to enter the “Machine Status” menu, then press the
set
set
key again when the “SEt”
set
It is possible to disable the keypad on this device.
The keypad can be locked by programming the “LOC” parameter appropriately.
With the keypad locked, you can still access the “Machine Status” menu by pressing
it. To disable the keypad lock, repeat the locking procedure.
set
to display the Setpoint, but you cannot edit
DISPLAY PROBES VALUE
To display the value read by probes connected to the device, press the
the key again when one of the probe-related labels “Pb1...Pb5” press the
probe will appear on the display.
NOTE: The displayed value is read-only and cannot be modified.
KDEPLUS BUTTONS
The KDEPlus keyboard has 4 keys, as shown in the illustration:
set
key and enter the “Machine Status” menu, then press
set
key again. The value measured by the associated
UP
1
DOWNSET
2
KEY-ACTIVATED FUNCTIONS
All models have the UP key set to enable the “Manual Defrost” function.
The DOWN and ESC keys can also be set to activate any other function required by the user.
The parameters for configuring the two keys are:
• H11 = DOWN key configuration
• H33 = ESC key configuration
The values that can be set apply to both keys and the functions that can be activated are:
To reduce the risk of fire, electrical shock or
injury when cleaning this merchandiser:
• Unplug the merchandiser before cleaning;
• Keep all liquids away from electrical and
electronic components;
• Do not use any mechanical device or other
means to speed the defrost process, except
as recommended by the manufacturer.
CARE AND CLEANING
Long life and satisfactory performance of
any equipment is dependent upon the care it
receives. To ensure long life, proper sanitation
and minimum maintenance costs, this unit
should be thoroughly cleaned, all debris
removed and the interiors washed down.
Cleaning often will control or eliminate odor
buildup. Frequency of cleaning is dependent
on usage and local health requirements.
cleAnsersorscouringpAds.
The interior surfaces may be cleaned with most
domestic detergents and sanitizing solutions
with no harm to the surface. Always read and
follow the manufacturer’s instructions when
using any cleaning product.
Inspect all LED connections and plug/
receptacles for signs of arcing. Replace any
component that shows signs of arcing. Make
sure all unused receptacles have close-off covers
securely attached.
CLEANING UNDERNEATH THE CASE
The case can be moved to facilitate cleaning.
Unplug the merchandiser, and move it out if
the way in order to sweep and mop the area
underneath the case. Brush away all dirt and
liter from the area. Ensure there is no dirt
build up around the bottom of the case or near
the intake or exhaust.
Do not use HOT water on COLD glass surfaces.
This can cause the glass to shatter and could
result in personal injury. Allow glass fronts,
ends and service doors to warm before applying
hot water.
Exterior Surfaces
The exterior surfaces must be cleaned with a
mild detergent and warm water to protect and
maintain their attractive finish.
Shelves and shelf clips are easily removed for
cleaning the interior as well as the shelves
themselves.
Cleaning Condenser Coils
To maintain peak operating efficiency, the coil
should be cleaned at least once each month. A
dirty coil slows product cooling significantly
and increases energy consumption by as
much as 20%. Dirt buildup on coils can also
cause the compressor to lock up damaging
the condenser unit. All VRM models have
the same access panel design for commonality
between merchandisers.
1. Loosen screws at each side of the front
bottom grille, then lift up and pull off the
grille.
Loosen screws from each side of the bottom grille.
2. Next, detach the merchandiser’s electrical
wire harness.
3. Unscrew the stop bracket that holds the
condensing unit to the rail base.
4. Grab the condensing unit from condensing
unit handle.
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Refrigeration Unit
VRM Merchandisers
Page 28
28 MaIntEnancE
5. Use a soft hand brush attachment on a
vacuum to remove accumulated dust and
debris.
Consult an authorized service technician
if more extensive cleaning is needed. If the
refrigeration unit is damaged, it can be
replaced with a new unit.
TIPS AND TROUBLESHOOTING
There are a few simple things to check before
calling for service:
1. Product not cold? Refrigeration unit
requires 24 hours at initial startup to cool
down to operating temperature with no
productloAded in merchandiser. Ask
when merchandiser was stocked, and what
the usage has been. It may take 30 minutes
or more for product to chill following
stocking.
2. Check the door and door seal for air leaks.
3. Power Supply:
Is the unit plugged in?
Is there power to the unit?
4. Location
What are the ambient conditions—
temperature and humidity, direct sun,
nearby source of heat, such as oven or
grill? Is the unit level? Has the unit been
moved recently?
IMPORTANT
INFORMATION
For prompt service when contacting the
factory, be sure to have the case model and
serial number from the case serial plate.
— LOCK OUT / TAG OUT —
To avoid serious injury or death from electrical
shock, always disconnect the electrical power
at the main disconnect when servicing or
replacing any electrical component. This
includes, but is not limited to, such items as
doors, lights, fans, heaters, and thermostats.
ADJUSTING CLOSING TORQUE
Adjust closing torque by turning the bottom
hinge pin in the direction the door closes. Use
a 1/2 in. (13 mm) wrench. Turn the hinge pin
until the door closes on its own, usually to
2clicks or 1/2 turn.
DO NOT over-torque the hinge spring
assembly. Excessive torque (over 1 full turn)
will result in damage to the spring assembly
and/or door. If door does not close on its
own after one full turn (5 clicks), look for
obstructions causing the door to hang up.
5. Shelves and Stocking
Are the standard shelves in the correct places?
Is the product stocked properly?
Is the bottom shelf at the proper location?
6. Confirm that the defrost schedule is
properly set.
To adjust door sag (saw-tooth effect from door
to door), loosen the two hinge plate mounting
screws using a Torx Plus no. 27 bit. Adjust
hinge plate as needed, then tighten the screws.
CONDITIONING GASKETS
The manufacturer cannot control the
environment surrounding cases during shipment.
Temperature and humidity fluctuations during
shipment, as well as excessive vibration, may
promote gaps between gasket and frame. These
gaps prevent gaskets from sealing even when
correctly fitted at the factory.
This is not a warranty issue or defect.
4. Monitor all gaps. If gaps remain at the end of
four hours, follow the procedure for Restoring
Gasket Seal, beginning on page 6 of this
manual.
5. Initiate cooling sequence once gaps disappear.
Do not exceed 8 hours of energized circuits
without refrigeration. Doing so may cause
damage to the case and will void the warranty.
ATTENTION
TO ENSURE PROPER DOOR GASKET SEAL - REMOVE ALL SHIPPING
RETAINERS AND ENERGIZE ALL ANTI-SWEAT, FAN & LIGHT CIRCUITS
2 TO 4 HOURS PRIOR TO INITIATING REFRIGERATION CYCLE.
DO NOT EXCEED 8 HOURS OF ENERGIZED CIRCUITS
WITHOUT REFRIGERATION. DAMAGE OR PRODUCT FAILURE MAY
OCCUR AND VOID THE WARRANTY.
DO NOT REMOVE THIS LABEL UNTIL REFRIGERATION IS INITIATED.
Loosen both
hinge plate
mounting
screws.
Adjusting Door Sag
Follow this procedure to ensure gaps close and
gaskets seal properly:
1. Remove all shipping retainers and all packing
material.
2. Close each door. Use a flashlight to identify
any gaps between frame and gasket.
3. Energize all anti-sweat, fan and light circuits
for at least two hours, but not more than four
hours, prior to initiating the refrigeration cycle.
Gap
Before and After Gasket Conditioning
Gap Closed
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
VRM Merchandisers
Page 30
30 MaIntEnancE
INNOVATOR DOOR MAINTENANCE
As part of an ongoing maintenance program
for Innovator Doors, Hussmann recommends
that the items below be checked annually.
a) Proper door closing torque
b) Gasket performance (check for tearing and
proper sealing)
c) Check the top hinge pin to ensure the pin is
properly seated and not bent
d) Check the bottom hinge plate for excessive
wear (worn cam teeth)
e) Proper operation of hold open brackets
1. Check the doors for proper closing torque:
Test 1: Open door 90 degrees and close it
manually. Make sure the door opens and closes
without binding
Test 2: Open door 90 degrees and release it.
The door should close on its own
Test 3: Open door more than 3” but less than
6” and release it. The door should close on its
own.
Torque adjustment, if needed, should be
performed “one click” at a time. A “zero”
torque door should not require more than
4 clicks. If the torque cam and hinge socket
are severely rusted, both components should
be replaced. A severely rusted cam / socket
assembly will not hold torque. Rust on the cam
socket assembly is usually caused by one of the
following:
• High humidity conditions > ASHRAE Type I
• Cycling of the frame heaters
If the door is seated too far down the torque
rod assembly, it most likely damaged the top
hinge pin sleeve bearing. If the pin is not bent,
replacing the pin’s nylon sleeve bearing will be
sufficient. Although the torque rod assembly’s
sleeve bearing and spacer are replaceable, we
recommend that a severely rusted torque rod
assembly be replaced.
2) Inspect door gaskets:
• Check for tearing gaskets
• Make sure the gasket’s dart is properly
seated into the door’s gasket groove.
3) Inspect the top hinge assembly for excessive
movement at the top hinge socket.
• By design, the door will have a small, but
discernible amount of movement at the top
hinge pin / hinge plate socket joint. If excessive
movement is detected, the hinge pin assembly
should be inspected to ensure that the hinge pin
is not bent (refer to note #1)
4) Inspect hold open bracket:
• Open the door to the “hold open”
engagement position. The “hold open”
bracket should retain the door.
• If the bracket fails to retain the door, replace
the bracket and the shoulder screw.
5) If a door passes the three “open / close”
tests, and there is no excessive movement at the
top hinge pin, then it is highly unlikely that any
components require replacement.
Note 1: A rusted torque cam / socket assembly
can cause excessive wear on the torque rod’s
spacer and sleeve bearing. The result is a door
that can “seat” farther down the rod assembly
to the point that it causes binding at the hold
open bracket. It can also cause the top hinge
pin’s sleeve bearing to deform.
VRM Plan View Dimensions
shown as inches and (mm).
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
VRM Merchandisers
Page 40
40 tEchnIcal data
Evaporator Fans
VRM1BVRM2B
Number of Motors
2
Amperes
0.26
Watts
32
Compressor LRA 14.914.9
Compressor RLA 2.852.85
Electrical Data
DEFROST DATA
Frequency (hr) 12
OFF-TIME DEFROST
PHYSICAL DATA
Refrigerant Charge (R290)
(0.150 kg each system)
VRM1B 5.3 oz 0.150 kg (1 system)
VRM2B 5.3 oz 0.150 kg (1 system)
VRM3B 5.3 oz 0.150 kg (1 system)
Note: This data is based on store temperature
and humidity that does not exceed 80°F and
55% R.H. unless otherwise stated. Schedule
defrost at night while lights are off.