Hussmann SHM-4, SHM-5, SHM, SHM-3, SHM-6 Installation And Service Instructions Manual

...
January 2006
Specialty Horizontal Merchandisers
INSTALLATION & SERVICE
INSTRUCTIONS
FOR
SHM
First Call for help (US and Canada):
1-800-922-1919
Soporte Tècnico y Asistencia (Mèxico):
01-800-522-1900
For a Service Network Locator and other Information visit us at
www.hussmann.com
select Worldwide Locations
HUSSMANN - GLOVERSVILLE
P/N OII – SHM

TABLE OF CONTENTS

Page
Inspection 3 Location 3 Skid, Leveling, Drains, Legs 3 & 4
Cleaning Exterior, Interior 4 Cleaning Stainless Steel Surfaces 4
Serial Plate 5 Power Requirements 5 Electrical Box 5 Power Switch 5 Defrost Time Clock 6
Temperature Control 7 Condensing Unit 8 Shelves 8 Thermometer 8
Refrigeration 9 Evaporator Fan Motors 9
Page 2
GENERAL, INSTALLATION, CARE and CLEANING
GENERAL –
The Hussmann Models SHM have been carefully designed to offer versatility in the display of food items such as pre­made sandwiches, fresh fruit, and vegeta­bles, cheeses, and deli items.
So that you can realize maximum benefit from this fine piece of equipment we urge both you and your installer to carefully read and follow this brief set of instructions prior to installation of the equipment.
INSPECTION –
The equipment has been skidded and crated prior to shipment from the fac­tory. It is the carrier’s responsibility to de­liver it to you in good condition until such time as you sign for it. Upon receipt of the cabinet, examine the packaging for dam­age. If the packing is damaged, make spe­cific notation on the delivery ticket as to the location and extent of damage prior to sign­ing for the piece.
Carefully remove packaging and examine the cabinet for damage. If dam­age is found, contact the delivering carrier immediately and request that his agent pre­pare an inspection report for the purpose of filing a claim. THIS IS YOUR RE­SPONSIBILITY NOT THE FACTORY’S. Save all packaging materials and move the cabinet as little as possible prior to inspec­tion.
LOCATION –
Avoid locating the cabinet where di­rect sunlight would shine into the fixture or where drafts from air conditioning grills, fans, and open doors could affect its opera­tion. A minimum distance of two feet should be allowed in the front of the case to allow proper free air movement to and from the condenser for maximum operating effi­ciency.
SKID -
The skid should be left on the cabinet until it is near its final location. The skid provides protection for both case and floor. The skid is removed by raising one end of the case approx. 6”, block securely and re­move the 2 skid bolts on the raised end and screw back into the holes 2 leg levelers.
The procedure is repeated on the op­posite end. When the leg levelers are in place, the case may be slid off the skid and placed in its final location.
LEVELING –
The cabinet must be leveled properly to insure full drainage of condensate water from the evaporator coil. Level the case from front to rear and end to end. Optional legs can be provided for this purpose.
DRAINS
-
Remote draining is not required in self-contained models. The condensate wa­ter from the evaporator drains out
Page 3
through the bottom of the cabinet into the condensing unit compartment to a heated condensate pan.
The pan uses a thermistor to sense the presence of water in the pan and ad­justs the amount of heat required to evapo­rate the water. Care should be taken to insure the drain hose is properly trapped and in the pan.
LEGS – (optional)
If required by Health Inspectors the levelers can be removed and replaced with NSF Approved legs to raise the case 6 inches for cleaning purposes. An optional skirt kit can be provided to snap on the legs.
CARE and CLEANING – EXTERIOR –
When cleaning the exterior of the cabinet, use a soft cloth or sponges with wa­ter and a mild detergent. Rinse and wipe dry. Do not use an abrasive cleanser on the painted surfaces as this will mar the finish.
For plexiglass surfaces, use an ap­proved plexiglass cleaner such as Craftics 20/20 Plasti-Cleaner
To check the interior drain – SHUT OFF POWER TO THE CABINET! This may be accomplished by turning off the cabinet power switch or by turning off the breaker located in the store electrical panel. Remove the product from the cabi­net. Lift up and remove the stainless steel shelves. The drain is located in the center of the interior bottom directly behind the evaporator coil. Remove any pricing
Labels, product wrappers, etc., that may be found over the drain opening. When fin­ished checking, assemble cabinet in reverse order, turn back on the power and allow cabinet to pull down to proper operating temperatures before restocking.
INTERIOR –
For cleaning the interior of the prod­uct compartment, remove the product, dis­connect the electrical power, and allow cabi­net to warm to room temperature.
Use a soft cloth or sponge with a mild detergent to wash the interior. The drain­age area and drain should be checked to in­sure that they have not become clogged.
If the condensate drain hose is re­moved from the electric condensate pan for cleaning, it must be reinstalled prior to op­erating the case. Do not use an abrasive cleanser on the painted surfaces as this will mar the surface.
Wipe dry before restarting the cabi­net. The time clock (see Electrical section) should be reset to the correct time of day. Allow the cabinet to cool down to proper temperature before reloading product.
CLEANING STAINLESS STEEL
Generally soap and water will be suf­ficient for most cleanings when done often and regularly.
Page 4
When necessary several cleaning agents can be used. Some of them are Comet, Bab-O, Liquid NuSteel, Cooper’s Stainless Steel Cleaner, Allen’s Stainless Steel Cleaner, etc.
SERIAL PLATE –
The serial plate is located on the inte­rior left wall of the cabinet. It contains all per­tinent information such as model, cabinet se­rial number, amperage rating, refrigerant type and charge. This information will be needed to install, service, or order parts for this piece of equipment.
POWER REQUIREMENTS –
The SHM –3, 4, 5 & 6 use a 115/60/1 power source, with the SHM-3 and –4 models using a 15 amp cord and the SHM-5 and –6 using a 20 amp cord. The SHM-8 requires 208/230-60/1 power and uses a 20 amp plug. It is very important for the safety of you and your customers to have each circuit grounded properly.
A qualified electrician should perform all wiring in accordance with the National Electrical Code and/or all local codes
Separate circuits are recommended for each case in order to prevent product loss due to overloading or malfunction of other equip­ment on the same circuit. Fuses or circuit breakers should be supplied for each circuit.
For proper operation of equipment, voltage as measured at the compressor must not vary more than 5% from the cabinet serial plate rating.
If either a high or low voltage condition ex­ists, contact your electrician, local power company, or equipment manufacturer.
ELECTRICAL BOX –
The electrical box is located behind the louvered access panel. The box contains the items described below. On remote units the box is used to bring the field supply to. There is a grounding lug provided on these models for grounding purposes.
POWER SWITCH
The main power switch is located be­hind the louvered access panel covering the condensing unit compartment on the cus­tomer side of the case.
This switch controls all power to the case.
Temprature Control
Timer
Page 5
Power Switch
The cabinet power switch must be in the OFF position before starting any cleaning or service work on the equipment.
DEFROST TIME CLOCK –
The time clock, located in the electri­cal box, provides a definite off-time so that the evaporator will clear itself of frost.
The clock is provided with pins to initiate defrost. The failsafe setting sets the length of defrost (from 2 minutes minimum to 110 maximum).
The clock is factory preset for 1 de­frost per day at 40 minutes, which should be sufficient for most applications.
Additional defrost may be required for cases located in high humidity or high usage cases. If possible, avoid setting a de­frost during the day or peak usage periods. The clock time pointer should be set to the correct time of day when the cabinet is ready to be started.
SETTING THE TIMER – Extra pins are provided with the timer.
a. Put pin in the hole in dial face for the
time you wish cabinet to defrost. Note that there is an AM and PM section on the dial face. Be sure the pin is tight.
b. Set the length of time for the defrost
(failsafe). Push down on the adjustment and slide it to the length of time. (Do not set the time longer than 60 minutes.
c. Set the time pointer to the proper time of
day and start cabinet.
Page 6
START UP AND OPERATION –
It is important that the four previous sections of this installation booklet have been read and followed carefully before at­tempting to start up the equipment.
A thorough inspection should be made prior to start up to assure that there are no loose nuts, bolts, electrical connec­tions or refrigeration lines rubbing or chaf­ing.
Turn the power switch to the ON po­sition. Allow the system to reach normal operating temperature prior to loading any product in it.
This cabinet has a forced-air curtain that flows over the top of the product. See Shelves under this section for special load­ing instructions.
Air flows out of the honeycomb dif­fuser located above the product, across the product, and into the return duct. The hon­eycomb can be removed for cleaning.
E
N
I
L
D
A
LO
TEMPERATURE CONTROL –
Interior cabinet temperatures are controlled through the use of a bulb and capillary type temperature control.
The body portion of the control is located in the electrical enclosure. Access to the enclosure is gained by removing the louvered panel on the front of the cabinet. If you have a BW version of the SHM, the electrical enclosure is located behind the louvered panel on the rear of the cabinet. The sensing element of the control is lo­cated on top of the evaporator coil fins of the left end of the evaporator.
PRIOR TO PERFORMING ANY SERVICE OR CONTROL REPLACE­MENT, DISCONNECT THE POWER TO THE CABINET.
The dial face of the control is adjust­able from –10 to +50º. The control is fac­tory pre-set at between 26 and 28ºto main­tain interior cabinet temperatures of 35 to 40º. The control also has an adjustable dif­ferential that determines the cut-in and the cut-out temperature. This is adjustable from 5 to 20º. The factory setting is 9º to insure proper off time to keep the evapora­tor from icing.
When replacing the control, make sure to reseal the penetration in the cabinet bottom to prevent moisture from leaking through.
A picture of this control is on the next page.
Page 7
CONDENSING UNIT –
A regular program should be set up for cleaning the fin-and-tube condenser. Dust and dirt accumulation can cause seri­ous efficiency loss.
Access is gained to the unit area by removing the louvered grille. Before at­tempting to slide out condensing unit you must first remove the screws holding the condenser baffles with a phillips screw driver.
Penn A19-AHA-2D
Differential
The unit slides forward to facilitate clean­ing and for service. Care should be taken when pushing the unit back in to insure that the pullout coil does not become kinked or damaged in some way. Double check to make sure the drain hose is in the drain pan before putting the access grille back on. The rear access panel is also re­movable if it is necessary to work at the back of the case.
SHELVES –
The cabinet is equipped with shelves for the display of your product. THERE IS A 'LOAD LINE' LABEL ON THE BACK
WALL OF THE INNER LINER.
NOT
THE PRODUCT WILL BE IN THE DIS­CHARGE AIR FLOW AND ADVERSELY AFFECT THE CABINETS PERFORM­ANCE . THERMOMETER –
A thermometer is provided that has both Fahrenheit and Centigrade. The ther­mometer is located in the back interior cor­ner.
Its reading will be 5º to 7ºF warmer than the discharge air off the honeycomb.
A solar powered thermometer is provided with each cabinet. Temperature display in Fahrenheit degrees is standard. Celsius display is available as an option. The thermometer is located in the cabinet interior in the top left hand rear corner.
.
LOAD ABOVE THIS LINE AS
DO
Page 8
To replace the thermometer, remove the two screws holding the thermometer to its mounting bracket. Remove the sensing element from its clip. Install the replacement thermometer in reverse order.
To clean the sensing element of the thermometer, follow replacement procedure. Clean the element with a water and mild detergent solution. Make sure the sensing element is wiped clean of any residue to ensure proper temperature readings
REFRIGERATION
The SHM 3, 4, 6 models use a R-134a refrigerant and the SHM-5 and –8 models use R-404A refrigerant. All models use a hermetic compressor.
The systems employ capillary tubes for refrigerant flow control. The capillary tube is soldered to the suction line pull-out coil for proper heat exchange. If the capillary should be come plugged or damaged for some reason IT IS BEST TO REPLACE THE WHOLE HEAT EXCHANGER WITH A NEW ONE. Consult the factory for the proper replacement.
Listed below are BTU requirements for the SHM series cabinets at a +20º F evaporator and 110º F condenser temperature. SHM-3 2900 SHM-4 3000 SHM-5 4400 SHM-6 5400 SHM-8 6400
The following pressures are optimum when the case is in a 75º to 80ºF ambient and is running from 35º to 40ºF cabinet temperature and are for reference only:
SHM-3,4,6 SHM-5 –8 Head Pressure 110-120 psig Head Pressure 280-290 psig Suction Pressure 15-20 psig Suction Pressure 36-40 psig
Consult the serial plate for the correct refrigerant charge. This charge is critical and should be weighed in.

EVAPORATOR FAN MOTORS

To replace an evaporator fan motor, the product must be removed from the cabinet and the step shelves also removed. The shelves are only set in place.
Next, remove the plate covering the fans by removing the two screws holding this in place. The fans are now accessible.
Page 9
WARRANTY
Please read carefully to assure prompt and
accurate service
Ordering Replacement Parts –
Contact your nearest
Hussmann Distributor.
Always specify model and serial number of cabinet.
If correct part number is not known, give a
clear description of part itself and its
function in the cabinet or remote unit.
Warranty Parts Procedure –
Same as items above
Give original installation date of cabinet and, if possible, forward a copy of the origi-
nal invoice or delivery receipt.
All shipments of in-warranty replacement parts
will be invoiced
from the factory un-
til such time as the defective part is ret urne d an d proved to be defective by our Qu al -
ity Control Department.
Contact your Hussmann Distributor for instructions on returning in-warranty parts.
Warranty parts must be returned to the factory
within 30 days of date of failure to
assure proper disposition.
Lack of any of the above information may
result in the shipment of the wrong part,
or a delay in shipment.
Compressor Replacement Procedure –
Replacement compressors will not be shipped from the Hussmann factory. They
may be obtained from your nearest Copeland Wholesaler.
Your wholesaler will replace,
free
of
charge, any compressor found to be defective
Page 10
For any defective compressor beyond the twelve or twenty month time period, a sal-
vage value credit
will
be given too partially
offset the invoice for the replacement.
within twelve months of installation, not to exceed twenty months from the date of manufacture, as determined by the compressor serial number on the compressor se­rial plate.
EVAP. FAN
EVAP. FAN
EVAP. FAN
WIRE HARNESS
3 4
1 2
3-S-226
TIME CLOCK
T
2N
4
BLK
5 6
1
3
9 10
7 8
TEMP. CONTROL
X
RED
WHT
11 12
23 24
25 26
ELEC-TRO N
WHT
BLK
PROTECTOR
#1 RELAY
BLK
COMPRESSOR
C
2
1
COND.
FAN
GRD
115 V 60 Hz
1 Ph
POWER CORD
GRN
REV.
BLK
XX/XX/XX
DATE
BLK
S1
POWER SWITCH
WHT
XXX
BY
CONDENSATE PAN
S3
NOTE: USE COPPER,COPPER CLAD ALUMINUM
OR ALUMINUM CONDUCTORS ONLY.
XXXX
E.C.N.
MATERIAL:
XXXXXX-XX
SIZE
XXXXXXXXXX
DIE NO.
XXXX-XXXX
SHEET
SIZE
B
TOLERANCES UNLESS
OTHERWISE SPECIFIED.
FRACTIONAL
ANGULAR
HOLE LOCATION & SPACING
SCALE:
FINISH
 1/32"
 0.031"DECIMAL
 1ü
 1/64"
XXXXXXXXXX
Gloversville, N.Y. 12078
TITLE
WIRING DIAGRAM, SHM-5, SHM-6
DRAWN
TYPE
CODE
X
DATE
CHECKED
JLS
08/03/94
XXX
DWG. NUMBER
M100-1937
R
REV.
X
EVAP. FAN
WIRE HARNESS
TIME CLOCK
T
EVAP. FAN
EVAP. FAN
2N
3-S-226
3 4
1 2
1
TEMP. CONTROL
4
BLK
X
3
RED
WHT
WHT
#1 RELAY
BLK
COMPRESSOR
C
1
2
PROTECTOR
COND.
FAN
5 6
7 8
11 12
25 26
23 24
9 10
ELEC-TRON
BLK
GRD
CONDENSATE PAN
BLK
115 V 60 Hz 1 Ph
POWER CORD
GRN
BLK
S1
POWER SWITCH
WHT
S3
NOTE: USE COPPER,COPPER CLAD ALUMINUM
OR ALUMINUM CONDUCTORS ONLY.
REV EO # REV DATE REV BY
APPROVED BY
-
-
-
-
-
-
--
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JLS
SCALE
INCHES
SHEET #
8/3/1994
-
1 OF 1
GLOVERSVILLE, NY 12078
WIRING DIAGRAM SHM-3,4
M100-1871
WIRE HARNESS
TIME CLOCK
T
EVAP. FAN
EVAP. FAN
EVAP. FAN
2N
3-S-226
3 4
1 2
WHT
1
4
BLK
5 6
3
X
RED
WHT
WHT
11 12
7 8
9 10
23 24
25 26
ELEC-TRON
TEMP. CONTROL
HIGH PRESSURE
SWITCH
PROTECTOR
COMPRESSOR
C
S
S
1
R
R
2
BLK
CONDENSER
FAN
GRD
115 V 60 Hz 1 Ph
POWER CORD
BLK
GRN
BLK
S1
POWER SWITCH
WHT
CONDENSATE PAN
NOTE: USE COPPER,COPPER CLAD ALUMINUM
S3
OR ALUMINUM CONDUCTORS ONLY.
REV EO # REV DATE REV BY
-
APPROVED BY
-
-
-
-
-
--
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JHB
SCALE
INCHES
SHEET #
-
7/13/2000
1 OF 1
SHM-3
R-404A
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2197
EVAP. FAN
EVAP. FAN
WIRE HARNESS
2
TIME CLOCK
BLK
N
T
1
34X
RED
RED
TEMP. CONTROL
RED
BLK
COMPRESSOR ELEC. BOX TERMINALS
C
1
2
EVAP. FAN
EVAP. FAN
EVAP. FAN
208/230V 60
Hz
1 Ph
20 AMP 250V
POWER CORD
NOTE: USE COPPER,COPPER CLAD ALUMINUM, OR ALUMINUM CONDUCTORS ONLY.
3-S-226
PLUG END
DETAIL
COND.
FAN
1 2
3 4
5 6
7 8
9 10
11 12
23 24
25 26
ELEC-TRON
COND. FAN IN FRONT OF COMPRESSOR
BLK
GRD
RED
CONDENSATE PAN
BLK
BLK
S1 S3 GRN WHT
S2 S4
POWER SWITCH
REV EO # REV DATE REV BY
-
APPROVED BY
-
-
-
-
-
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
--
EO NUMBER
DATE DRAWN DRAWN BY APPROVED BY
-
2/19/98
JHB
-
UNIT
SHEET #
SHM-8
GLOVERSVILLE, NY 12078
SHM-8 WIRING DIAGRAM
INCHES 1 OF 1
M100-2133
Loading...