Hussmann Safe-NET Technician Manual

®
Safe-NET™
Technician’s Manual
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
November 2005
P/N 0461391A
INTRODUCTION
What is Safe-NET . . . . . . . . . . . . . . . . . . . . . 1-1
Components . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Display Module . . . . . . . . . . . . . . . . . . . . . 1-2
Digital Sensors . . . . . . . . . . . . . . . . . . . . . . 1-2
Optional Wireless Hand-held Controller
and/or PC Control . . . . . . . . . . . . . . . . . . . 1-2
INSTALLATION
Self-Contained Case . . . . . . . . . . . . . . . . . . . 2-1
Three-Button Rules . . . . . . . . . . . . . . . . . . . . 2-1
SAFE-NET DISPLAY & ALARM MODULES
Description . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Safe-NET Display Module . . . . . . . . . . . . 3-1
Alarm Module . . . . . . . . . . . . . . . . . . . . . . 3-1
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Normal . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Product Temperature Alarms . . . . . . . . . . 3-2
Power Failure . . . . . . . . . . . . . . . . . . . . . . 3-2
Low Battery . . . . . . . . . . . . . . . . . . . . . . . 3-2
Connection Failure . . . . . . . . . . . . . . . . . . 3-2
Modifying ARL/ARV Settings . . . . . . . . . . 3-3
Password . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Modifying Set Points . . . . . . . . . . . . . . . . . . 3-5
Wiring Diagram for Display Module
and Alarm Module . . . . . . . . . . . . . . . . . . 3-6
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
SEnS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
noSn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
dSHi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
dSLo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
CoM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
PrHi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
PrLo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
SC-C . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
SC-L . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
SC-r . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Door Open . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
MENUS
Menu Presentation Conventions . . . . . . . . . 4-1
Menu Navigation Overview . . . . . . . . . . . . . 4-2
Time Outs . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Password . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Inactivity . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Escape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Clear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Button Action . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Display Symbol Identification . . . . . . . . . . . 4-4
Top Level Menus . . . . . . . . . . . . . . . . . . . . . 4-5
Setup Menu . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Password Protection . . . . . . . . . . . . . . . . . 4-8
DSET . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
PSEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
CNTN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
DSPN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
RST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
iiiP/N 0461391A
CONTENTS
IMPORTANT
KEEP IN STORE FOR FUTURE REFERENCE
Quality that sets industry standards.
12999 St. Charles Rock Road • Bridgeton, MO 63044 U.S.A. • (314) 291-2000 • FAX (314) 298-4767
®
NSEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13
LGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
DEGR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
DUTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
DIFF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17
FSET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
CTRL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-19
PD-L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
PRHI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
PRLO . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
ADLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
HIGH . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
LOW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25
INPT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26
CASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27
Default Settings and
Case Type Descriptions . . . . . . . . . . . . 4-28
Clock Menu . . . . . . . . . . . . . . . . . . . . . . . . . 4-29
Defrost Menu . . . . . . . . . . . . . . . . . . . . . . . . 4-30
DTYP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-30
STOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
START . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-32
FCTL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-33
TSET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-34
DURA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-35
TTYP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-36
STAR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-36
NDEF . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-38
Temperatures Menu . . . . . . . . . . . . . . . . . . . 4-38
Valve Menu . . . . . . . . . . . . . . . . . . . . . . . . . 4-40
CLAV . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
DSVR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
DHVR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
CSVR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
CHVR . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-41
C-OF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-42
V-OF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-42
NORL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43
CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43
OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-43
SREF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44
VTYP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-44
VPOS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-45
Display Default . . . . . . . . . . . . . . . . . . . . . . . 4-46
Dimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-46
WARRANTY
iv
P/N 0461391A
CONTENTS (Continued)
P/N 0461391A 1-1
INTRODUCTION
WHAT IS Safe-NET™
Safe-NET is an advanced, electronic system for monitoring or controlling case temperatures in one or more locations. It will help you ensure continuous, reliable refrigeration and safer, fresher foods, 24 hours a
Alarm Module
day.
The Safe-NET system is composed of sensors, harnesses, control modules, display modules, relay modules and a power supply.
Safe-NET technology provides an ideal system for verifying and maintaining compliance with Federal Department of Agriculture (FDA) and National Sanitation Foundation (NSF) regulations. It uses a standard communication protocol compatible with many third party systems to enable communication with a PC.
Temperature Monitoring
Safe-NET lets you monitor temperatures in up to 10 different areas of each case: discharge air, return air, product temperatures, coil inlet and outlet temperatures, etc. Temperature readings are logged for later review. The
Power Supply (Transformer)
Display Module
Sensor
Harness
Temperature Sensor
ARV / ARL Kit Alarm
Typical Safe-NET™ Installation
system sends an alarm if temperatures exceed predefined limits.
COMPONENTS
All components of the Safe-NET system (displays, sensors, and control modules) are factory installed. A single case-to-case plug-in connector is all that is required for field installation.
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Typical Safe-NET™ Components
Safe-NET™
1-2
INTRODUCTION
Display Module
The display module is a slim four-digit binary coded decimal LED unit which mounts in the case fascia panel. It lets you check temperatures at a glance and performs a variety of other monitoring and control functions via pushbuttons or the hand-held controller.
Safe-NET™ Display Module
Up to 10 sensors can be connected to each display module.
OOppttiioonnaall
Wireless Hand-held Controller and/or PC
Control
The wireless controller communicates with the display unit through an infrared sensor. This allows setups and queries which can also be performed via PC over the network.
Digital Sensors
Up to 10 digital sensors can be installed in each case with a single cable connection. There are 14 types of sensors. Each sensor has an electronic identifier so it can be recognized by the display module. This eliminates the need for separate wiring. Sensors in each case are harnessed together to a single wire leading to the display module. Sensors are designed for rugged durability. Should a sensor fail, it can be replaced.
Safe-NET™ Hand Held Controller
If the wireless controller is not available, it is possible to program the controller directly with buttons located on the display module.
Typical Safe-NET™ Sensor Harness
P/N 0461391A
SELF-CONTAINED CASE
Safe-NET components are factory-installed. Once power
is supplied to the case as specified in the case’s installation
and service manual, Safe-NET settings are ready to be
selected.
Settings are retained when power is interrupted. Thus, a
self-contained case can be moved without re-entering
selected settings.
Startup of a new Self-Contained case is quite simple:
1. Verify case type selected.
2. Set the clock.
3. Check or set the temperature setpoint.
THREE BUTTON RULES
• Always start by pushing the SELECT button, watch
what is displayed. Which menu are you in?
— StUP — CLOC — DEFr — tEM — VALv —
DiSP — and cycles back to StUP
• Press the SELECT button until you are in the proper
menu. Once in the proper menu press the UP or DOWN
button to enter the menu and to scroll through the menu.
• Once at the menu item that you want, press the
SELECT button until the item flashes between the value
and the title. You may have to press the SELECT button
more than once to get the item to flash.
• Then press the UP or DOWN button to change the item.
• Remember to push the SELECT button to save the item.
Also remember to set the passcode before any items can be
changed.
• Pressing the UP or DOWN buttons at the same time
acts as an escape to go back out of the menus.
P/N 0461391A 2-1
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
INSTALLATION
DESCRIPTION
Safe-NET Display Module
The Safe-NET Display Module, shown in Figure 1 and Figure 2, is a temperature­monitoring device. The display module reads and displays temperature sensed by the product simulator temperature sensor mounted in the refrigerated space. The display module notifies the user of alarms based on preset alarm conditions.
Alarm Module
The alarm module, shown in Figure 3, is an additional feature to Safe-NET. The alarm module supplies power to the display module via an 8-wire cable. The alarm module provides battery back up power to the display module during loss of A.C. power. The display module communicates with the alarm module via a 2-wire cable. Additionally, the alarm module is equipped with a beeper to provide audible notification of alarms.
OPERATION
Normal
During normal operating conditions, the product simulator temperature is displayed. The GREEN LED on the alarm module is lighted (as shown in Figure 3).
3-1
Safe-NET™DISPLAY & ALARM MODULES
P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
Figure 1. Safe-NET Display Module with Top Cover
LED Indicators
Figure 2. Safe-NET Display Module with Cover Removed
Figure 3. Safe-NET Alarm Module
Green LED
SELECT Button
UP Button
DOWN Button
DOWN Button
Product Temperature Alarms
The display module generates an alarm if the product simulator temperature rises above the high alarm set point or drops below the low alarm set point for the preset time duration.
When the display module generates a high temperature alarm, the RED LED on the display module is lighted. Every 12 seconds, PrHi is displayed for 3 seconds; for the remaining time, the product simulator temperature is displayed.
When the display module generates a low temperature alarm, the RED LED on the display module is lighted. Every 12 seconds, PrLo is displayed for 3 seconds; for the remaining time, the product simulator temperature is displayed.
For either alarm, the beeper on the alarm board beeps every 6 seconds.
Power Failure
If external power to the unit is interrupted, the backup battery on the alarm board supplies power to maintain the non-volatile memory in the display module.
To conserve power, the display LEDs are blanked except for a period of 6 seconds every 3 minutes when product temperature is displayed.
Product temperature alarms can be generated during external power loss. The audible alarm is active only for product temperature alarms.
Low Battery
During normal operating conditions, the alarm module monitors battery condition. The display shows bAtt when the battery becomes low on power and the beeper on the alarm board beeps every 2 minutes to indicate a low battery condition. The low battery audible alarm is
active only when external power is applied.
Connection Failure
Loss of communication between the display module and the alarm module activates an alarm. When the display module generates a loss of communication alarm, the RED LED on the display module is lighted. Every 12 seconds, A-Er is displayed for 3 seconds; for the remaining time, the product simulator temperature is displayed. The beeper on alarm board beeps every 30 seconds. The A-Er audible alarm is active only when external power is applied.
Precedence of Alarms
Severity of the alarm determines the beeper action. The following table shows the priority of the alarms.
3-2
P/N 0461391A
DISPLAY & ALARM MODULES
Alarm
Display
Action
Beeper OFF Time (seconds)
Severity
Product
HIGH/LOW
Alarm
PrHi/PrLo 6 1
Connection
Failure
A-Er 30 2
Low Battery bAtt 120 3
An alarm with higher severity takes precedence over a low severity alarm. For example, if there is a product alarm and low battery alarm:
• The alarm board beeper beeps every 6 seconds to indicate the product temperature alarm.
• Indication of the low battery alarm is ignored by the beeper, but is active in the display.
• Every 12 seconds, the display shows PrHi for 3 seconds followed by bAtt for 3 seconds. For the remaining time, product simulator temperature is displayed.
Alarm Set Points
Following are the alarm set points for ARL and ARV cases:
Notes:
• A high temperature alarm typically activates
during case startup. This is normal since the refrigerated space requires an extended period to reach operating temperature. Product must not be loaded until operating temperature is reached. Premature stocking may result in product loss.
• Battery backup operation is possible for up to
6 hours. The initial condition of the battery determines the length of time. Operation of Safe-NET is compromised once the battery runs low. Product integrity cannot be ensured until power is restored and the battery is replaced.
MODIFYINGARL/ARV SETTINGS
The Safe-NET display module stores alarm set points and alarm delay times for monitoring ARL and ARV cases. The suggested default set points may be modified.
Use a flat, narrow tool such as a small screw­driver to remove the cover of the display module.
IMPORTANT!
Hussmann recommends against changing any parameter value other than those described herein. Modification of any other parameter may result in unpredictable Safe-NET operation.
• The user must monitor each case after altering product alarm set points and/or product alarm time delays to verify proper operation.
3-3P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
Case
Model
Set
Point
Product
High Alarm
Set Point
Product
Low Alarm
Set Point
Product Alarm
Delay
(Minutes)
ARL 8ºF 2ºF 22ºF 90
ARV 36ºF 43ºF 32ºF 60
There are three visible buttons on the left hand side of the display board, as indicated in Figure 2 on Page 1. Although labels are not clear, buttons can be determined by their location.
The SELECT button is located near the top edge of the display board. It is used to select the menus and to edit the menus.
The UP button is the left button of the two buttons located on the bottom lineup of the display board. The DOWN is the right button of the two buttons located on the bottom lineup of the display board. The UP and DOWN buttons are used to move within and between menus, and to increment or decrement values.
Notes:
• The SELECT button is used to scroll through the following menus:
StUP – Setup CLoC – Clock dEFr – Defrost tEM – Temperature uALu – Valve diSP – Display Default
• User must enter valid password to edit
parameter settings.
• To edit any menu item, press either the UP or
DOWN button to enter the selected menu.
• Use the SELECT button to modify and save the
parameter once the UP or DOWN button is pressed.
• The display cycles between menu item and edited menu value once the edited value is entered using the SELECT button, .
• The display returns to showing the product simulator temperature if no button is pressed for 12 seconds once the menu is displayed. User must scroll through the menus using the SELECT button to return to the SETUP menu.
• Holding a button down has the same effect as pressing once.
PASSWORD
Entering the password is done in the SETUP menu. At the top of the SETUP menu, press the UP button. The display will begin to cycle between PASS and 0.
While 0 is being displayed, press the SELECT button to allow editing of the value. With the Safe-NET display module flashing 0, use the UP /DOWN buttons to increment or decrement the value until it reaches 595. 595 is the password value.
Once 595 is displayed, press the SELECT button. The display will revert to cycling between PASS and 595. This enables editing of parameters.
The user may now navigate the menu system and edit parameters as necessary.
3-4
P/N 0461391A
DISPLAY & ALARM MODULES
Note:
The password protected access remains active for 5 minutes. Each time a new parameter is entered by pressing the ENTER key on the Hand-Held device or the SELECT button on the Safe-NET display module, the 5 minute timer is restarted. After 5 minutes with no parameter entries, the password value reverts to 0 and the password entry process must be performed to regain access to critical parameters. The SETUP menu can be navigated without a valid password in a “view only” mode.
MODIFYING SET POINTS
With the password active and the display reading product temperature, use the SELECT button to scroll through the menus. Once the display reaches the StuP menu, use the UP button until the display shows the parameter to be modified:
• To change the product low alarm set point, press the UP button until the display cycles between PrLo and the current product low alarm set point.
• To change the product high alarm set point, press the UP button until the display cycles between PrHi and the current product high alarm set point.
• To change the product alarm delay, press the UP button until display cycles between P-dL and the current product alarm delay.
Once the desired menu item is displayed, press SELECT button. The display cycles between the corresponding menu item and the VALUE. Press the UP button to increment the value or the DOWN button to decrement the value. The value of the parameter can be modified only within the following specified ranges:
When the entered value begins flashing, press the SELECT button to store the new value. The display cycles between the new value and the menu item. Within 12 seconds after button activation, the display starts showing the product temperature.
Replace top cover of the display module after modifications are complete. Verify that alarm LED indicators are on the left side as shown in Figure 1 on page 1.
3-5P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
Case
Model
Range of
Product
High Alarm
Set Point
Range of
Product
Low Alarm
Set Point
Range of
Product
Alarm Delay
(Minutes)
ARL
8ºF to 8ºF 24ºF to 8ºF 0 to 240
ARV
36ºF to 52ºF 20ºF to 36ºF 0 to 240
3-6
P/N 0461391A
DISPLAY & ALARM MODULES
Wiring Diagram for Display Module and Alarm Module
Safe-NET™
Battery Backup with Piezo Alarm, revision 1.01
06/17/05 MPK
Display Module
Alarm Module
audible alarm
(piezo)
ALARM
GROUND
RS-485B
ANTI-SWEAT
COMPRESSOR
GROUND
RS-485A
DEFROST
FAN S
12VDC
RCVR
1
2
1
2
3
4
5
6
7
8
red
1
blk
2
grn
1
org
2
blu
3
blk
4
wht
5
ylw
6
brn
7
red
8
P3
1
1
2
2
P1
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
alarm
status
DRY CONTACT
GROUND
RS-485B
ANTI-SWEAT
LIGHTS
GROUND
RS-485A
DEFROST
FAN S
12VDC
PSEN RXD
P2
12VDC
P5 1
3
5
N/C
5VDC
1
2
3
4
2
4
6
P4
1
2 3
4
RS-485B
RS-485A
GROUND
TXD 5VDC
RST GND
SENSE
GROUND
RS-485 unterminated
1
red
2
wht
3
blk
4
product
simulator
12VDC
8
FAN S
12VDC
7
6
5
4
3
2
1
J1
1
2
90VAC - 264VAC
NEUTRAL
Power Supply
1.25A @ 12VDC
(0459302)
T9RKE1250LCP-Y
AC power cord (0459303)
7031116F000
DEFROST
RS-485A
GROUND
COMPRESSOR
ANTI-SWEAT
RS-485B
J4
1
1
2
2
9V Battery
GROUND
ALARMS
A red LED on the board turns on during alarm. The
display will show a four-character word for about 3
seconds alternating with a blank display for 9 seconds.
Following are details of alarms applicable to Self
contained cases.
Alarm with Sensor Number – “SEnS”
This alarm is generated when the control is initialized,
and indicates that the number of sensors entered in the
control is different from the number of sensors connected
to the control. This Alarm can be cleared only by
changing the reading for number of sensors to 0 and
resetting the display module which then updates the
reading to the number of sensors connected. This is
caused by the control not being set up correctly or by a
sensor having failed.
Alarm with Sensor reading – “noSn”
This alarm is generated when the display module is
unable to read the sensors for five consecutive seconds.
This alarm clears automatically when the control is able
to read the sensors. This may be caused by a sensor being
disconnected or shorted. This alarm clears automatically
when the control is able to read the sensors.
Discharge Air High Alarm – “dSHi”
This alarm is generated when the average discharge air
temperature in the case, over the programmed alarm
delay time, is higher than the High Alarm value stored in
the control. This alarm will clear if the average discharge
air temperature goes below the High alarm value. THIS
ALARM IS AVAILABLE ONLY IF DISCHARGE SENSORS ARE
INSTALLED.
Discharge Air Low Alarm – “dSLo”
This alarm is generated when the average discharge air
temperature in the case, over the programmed alarm
delay time, is lower than the Low Alarm value stored in
the control. This alarm will reset if the average discharge
air temperature goes higher than Low alarm value.
T
HIS ALARM IS AVAILABLE ONLY IF DISCHARGE SENSORS ARE
INSTALLED
.
Note: Programmable alarm delay (AdLy) is described in
a later section.
3-7P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
Communication Alarm – “CoM”
If there are no network communication attempts for a
period of more than 30 minutes, the display module sets
a communication alarm and shows it on the display.
When the display module itself is controlling rather than
(dSPn) a network, the Display Number in setup must be
set to “nonE”to prevent alarm generation.
Product High Temperature Alarm – “PrHi”
This alarm will be generated if the product simulator
average is above high alarm set-point for product alarm
delay time
T
HE PRHI AND PRLO ALARMS ARE AVAILABLE ONLY IF
PRODUCT SENSORS ARE INSTALLED.
Product Low Temperature Alarm – “PrLo”
This alarm will be generated if the product simulator
average is below low alarm set-point for product alarm
delay time.
Sectional Faults for
Medium Temperature Impact Cases
with Multiple Coils
A section of the modular coil is above or below the alarm
set point for the period of time set in the programmed
alarm delay.
Center section of a 12-ft case.
Left-hand section of an 8- or 12-ft case.
Right-hand section of an 8- or 12-ft case.
3-8
P/N 0461391A
ALARMS
Door Open Alarm
This alarm will be generated only if the input of the
display is connected to a door switch and the input
configuration on the display board is set to “door”. It is
generated when the door is kept open for more than
2 minutes and will be cleared when the door is closed.
The display alternates two words “cLoS”and “door”until
the door is closed.
Door Open
If the doors are left open for more than 5 minutes even
after the alarm, the fans are turned back on.
3-9
P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
G
MENU PRESENTATION CONVENTIONS
Denotes that the Safe-NET Display is cycling between displayed menu items and parameter values.
DOWN arrow or button press.
Denotes circular menu navigation.
Denotes menu item or value on display.
UP arrow or button press
UP or DOWN arrow or button may be used
ENTER Key or SELECT Button Press
Automatic Menu Navigation
4-1
MENUS
P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
DSPN
Value
MENU NAVIGATION OVERVIEW
The presentation of the Safe-NET Menu system and
associated button and key operation vary somewhat
according to the currently displayed menu item and/or
action to be performed. Individual menu items, definition
of purpose, associated action and keypad/button
behavior is described in detail in the following sections.
Some actions and behaviors of the Safe-NET Menu
system are consistent throughout. These should be taken
into account to avoid confusion when navigating the
Safe-NET Menu system.
TIME OUTS
Password
Once the valid ‘595’PASSWORD has been entered, it will
remain active for 5 minutes. A 5 minute timer is restarted
each time a new value is confirmed with the ENTER key
on the Hand-Held device or pressing the SELECT button
on the Safe-NET Display module. Re-setting the Safe-
NET Display module clears the PASSWORD entry and
sets the 5-minute timer to 0. Therefore, if a setting is
modified that requires the Safe-NET Display module to
be reset and subsequent values require modification, the
PASSWORD must be re-entered.
Inactivity
Anytime the display is moved from the default display
whether a PASSWORD has been entered or values and
settings are simply being viewed and not modified, the
display will revert to the default display after 10 seconds.
This occurs if no key is pressed on the Hand-Held device
or button on the Safe-NET Display module. If a valid
PASSWORD has been entered, and the display reverts to
the default display due to keypad and/or button activity,
the PASSWORD will remain active for the remainder of
the aforementioned 5-minute timeout period. To resume
modifying values, re-enter the menu of interest while the
PASSWORD is active and continue modifying values.
ESCAPE
To leave a Menu and return to the default display, press
the ESCAPE key on the Hand-Held device or press the
UP and DOWN buttons on the Safe-NET Display module
simultaneously. If a valid PASSWORD has been entered
it will remain active for the remainder of the 5-minute
time out period. This allows for exiting one menu and
entering another for the purpose of modifying a value
without having to re-enter the PASSWORD.
4-2
P/N 0461391A
MENUS
A modified value will revert to its original value if the
value has been modified but the ENTER key or SELECT
button has not been pressed before pressing the ESCAPE
key on the Hand-Held device or simultaneously pressing
the UP and DOWN buttons on the Safe-NET Display
module.
CLEAR
Pressing the CLEAR key on the Hand-Held device while
editing a menu item value clears numeric values to 0 and
resets text items to the initial available selection.
BUTTON ACTION
This photo identifies the buttons and the corresponding
action on the Safe-NET Display Module.
This photo identifies the buttons and the corresponding
actions and alternate actions on the Safe-NET Hand Held
Controller.
4-3P/N 0461391A
Hussmann Corporation • Bridgeton, Missouri 63044-2483 U.S.A.
Safe-NET™
Safe-NET™ Hand Held Controller
SELECT Button
UP Button
Safe-NET™ Display Module
Button Action
DOWN Button
SETUP
Discharge
TEMPS
Left
ESCAPE
Back
Inlet
CLOCK
Return
VALVE
Center
ENTER
Outlet
DEFROST
Terminate
DISPLAY DEFAULT
Right
CLEAR
Drain
Product
DIMMERSHIFT
®
DISPLAY SYMBOL IDENTIFICATION
4-4
P/N 0461391A
MENUS
Not
Used
A
b
C
c
d
E
F
G
g
Not
Used
h
i
J
k
L
M
n
o
P
Not
Used
Not
Used
r
S
t
U
v
W
w
x
y
1
2
3
4
5
6
7
8
9
H
Not
Used
q
Not
Used
z
0
Loading...
+ 43 hidden pages