Hussmann RLN, RLT, RLNI, RLNIE, RLTI Installation Instruction

...
1
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Dew Point and
Humidistat Control
for Reach-In Merchandisers
Installation Instruction
Merchandisers
Model Description
Honeywell Model H409A Dew Point Control
Honeywell Model H46N-1005i Humidistat Control
GENERAL INFORMATION
Kit Application
Both of the controls shown on Page 12 are designed for energy conservation. They supply power to the anti-condensate heaters in the door only when necessary to maintain the sur­face temperature of the glass doors above the dew point.
The humidistat control is non­adjustable, factory-set to cycle off the door anti-condensate heaters when the store humidity drops to the set point of 35% relative humidity or lower. This control carries a maximum load of 10 Amps (see Table 1, Amperage).
The dew point control is a more versatile control offering six adjustable set-points, with a maximum setting of 40% relative humidity. This control carries maximum load of 16 Amps (see Table 1, Amperage).
The capacity of these controls may be increased by using relays whose coils are wired parallel with the control and the relay contacts connected to power supply. Refer to wiring diagrams for detail.
For a line-up of cases, one case is designated as the master case with the control installed. Note that each narrow island side is wired separately.
All other cases in the line-up are designated as slave cases with a relay energized from the control on the master case (side of an island).
The location of either dew point control or humidistat control must be in an area that reflects the store ambient con­dition where the merchandiser is located.
All wiring for these controls must comply with NEC and local regulations.
P/N 0387094A
April, 2002
P/N 0387094A
Merchandisers
®
2
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Table 1
Door heater amperages cycable by dew point or humidistat control (120 V).
Model
Door Condensate Heater Amps
Anthony Innovator
RL2, RLN2, RLNI2* 2.18 1.5
RL3, RLN3, RLNI3* 3.27 2.31
RL4, RLN4, RLNI4* 4.36 3.08
RL5, RLN5, RLNI5* 5.45 3.86
*RLNI values are per side.
Control Location — Reach-in and Narrow Reach-in
Skid/External Base
Electrical Wireway
Front
5-Door Shown
Relay & Terminal Block Location
Bottom Front Support
Refrigeration Outlet
Dew Point/ Humidistat
Location
Electrical
Field Wiring
Connection Point
Control Locations — Narrow Island Reach-in
Rear Relay & Terminal Block Location
Electrical Wireway
Refrigeration Outlet
Dew Point/ Humidistat
Location
Skid/External Base
Electrical Wireway
Front
5-Door Shown
Front Relay & Terminal Block Location
Bottom Front Support
Dew Point/ Humidistat
Location
Refrigeration Outlet
Electrical
Field Wiring
Connection Point
Dew Point and Humidistat Control Installation Instruction
P/N 0387094A
3
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Lower Right Hand of Case
R
B
W
Color Coded Harness
Identification Tag
Upper Right Hand of Case
Red
Black
White
Honeywell Dew Point Control M/N409A or Honeywell Humidistat Control M/NH46N
COMPONENT LOCATION FOR DEW POINT / HUMIDISTAT CONTROL
P/N 0387094A
Merchandisers
®
4
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Notes:
Dew point or Humidistat
Anti-sweat control.
White wire not used on
Humidistat control.
Field wiring for slave case
relay coil(s).
• Yellow terminals 1 through 8 are 208V Defrost Circuit.
• Terminals 1 through 3 are internally jumpered.
• Terminals 4 and 5 are internally jumpered.
• Terminals 6 through 8 are internally jumpered.
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Terminals 13 and 14 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 through 24 are jumpered with a removable push-in jumper.
Kits FL28 and FL29 Diagrams 0423658 and 0423689
RL Wiring Diagram for Dew Point or Humidistat Control
Fans and Anti-Condensate Heaters on Common Power Circuit.
Only Cycles Door Anti-Condensate Heater.
(Electric Defrost)
Rear Defrost
Front Defrost
Fans
Fan Relay
COM
COM
N.C.
N.O.
N.C.
N.O.
208V
Anti-Sweat Relay
120V
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
Lights
L
Switch
Thermostats
Defrost Limit
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
1234567810111213141617202122242526
Defrost Heaters (208V)
Defrost Heaters (208V)
Lights (120V)
Lights (Neutral)
B
1
2
Fans & Anti-Sweat (120V)
R
W
O.O.R .
Relay Control
C.O.R.
Defrost Termination
C.O.R.
Fans & Anti-Sweat (Neutral)
3
Dew Point and Humidistat Control Installation Instruction
P/N 0387094A
5
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Notes:
Field wiring from the dew
point/humidistat master case Terminals 12 & 21.
Field wiring from an adjoin-
ing slave case anti-sweat relay coil.
• Yellow terminals 1 through 8 are 208V Defrost Circuit.
• Terminals 1 through 3 are internally jumpered.
• Terminals 4 and 5 are internally jumpered.
• Terminals 6 through 8 are internally jumpered.
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Terminals 13 and 14 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 through 24 are jumpered with a removable push-in jumper.
RL Wiring Diagram for Dew Point or Humidistat Slave Relay
Fans and Anti-Condensate Heaters on Common Power Circuit.
Only Cycles Door Anti-Condensate Heater.
(Electric Defrost)
Kit BF53 Diagrams 0423658 and 0423689
Fan Relay
N.C.
COM
N.O.
N.C.
COM
N.O.
208V
Anti-Sweat Relay
120V
Rear Defrost
Front Defrost
Fans
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
Lights
L
Thermostats
Switch
Defrost Limit
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
N.C.
COM
N.O.
Relay Spot Dew Point / Humidistat
1234567810111213141617202122242526
120V
Defrost Heaters (208V)
Defrost Heaters (208V)
Lights (120V)
Lights (Neutral)
Fans & Anti-Sweat (120V)
Fans & Anti-Sweat (Neutral)
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
O.O.R .
Relay Control
C.O.R.
Defrost Termination
C.O.R.
P/N 0387094A
Merchandisers
®
6
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Notes:
Dew point or Humidistat
Anti-sweat control.
White wire not used on
Humidistat control.
Field wiring for slave case
relay coil(s).
• Yellow terminals 1 through 8 are 208V Defrost Circuit.
• Terminals 1 through 3 are internally jumpered.
• Terminals 4 and 5 are internally jumpered.
• Terminals 6 through 8 are internally jumpered.
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 and 22 are jumpered with a removable push-in jumper.
Kits FL44 and FL45 Diagrams 0423665 and 0423689
RL Wiring Diagram for Dew Point or Humidistat Control
Fans and Anti-Condensate Heaters on Separate Power Circuits.
Only Cycles Door Anti-Condensate Heater.
(Electric Defrost)
Rear Defrost
Front Defrost
Fans
Fan Relay
COM
COM
N.C.
N.O.
N.C.
N.O.
208V
Anti-Sweat Relay
120V
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
Lights
L
Switch
Thermostats
Defrost Limit
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
1234567810111213141617202122242526
Defrost Heaters (208V)
Defrost Heaters (208V)
Fans (120V)
Lights (120V)
Anti-Sweat (120V)
B
R
1
W
2
Lights (Neutral)
Anti-Sweat (Neutral)
O.O.R .
Relay Control
C.O.R.
Defrost Termination
C.O.R.
Fans (Neutral)
3
Dew Point and Humidistat Control Installation Instruction
P/N 0387094A
7
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
RL Wiri
idi
Notes:
Field wiring from the dew
point/humidistat master case Terminals 12 & 21.
Field wiring from an adjoin-
ing slave case anti-sweat relay coil.
• Yellow terminals 1 through 8 are 208V Defrost Circuit.
• Terminals 1 through 3 are internally jumpered.
• Terminals 4 and 5 are internally jumpered.
• Terminals 6 through 8 are internally jumpered.
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 and 22 are jumpered with a removable push-in jumper.
Fans and Anti-Condensate Heaters on Separate Power Circuits.
Kit FL43 Diagrams 0423665 and 0423689
N.C.
COM
N.O.
COM
N.C.
N.O.
Anti-Sweat Relay
ng Diagram for Dew Point or Hum
stat Slave Relay
Only Cycles Door Anti-Condensate Heater.
(Electric Defrost)
Rear Defrost
Front Defrost
Fans
Fan Relay
208V
120V
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
Lights
L
Switch
Thermostats
Defrost Limit
O.O.R .
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
COM
Relay Spot Dew Point / Humidistat
1
N.C.
120V
N.O.
2
1234567810111213141617202122242526
Fans (120V)
Lights (120V)
Lights (Neutral)
Anti-Sweat (Neutral)
Defrost Heaters (208V)
Defrost Heaters (208V)
Anti-Sweat (120V)
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
Relay Control
C.O.R.
Defrost Termination
C.O.R.
Fans (Neutral)
P/N 0387094A
Merchandisers
®
8
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Notes:
Dew point or Humidistat
Anti-sweat control.
White wire not used on
Humidistat control.
Field wiring for slave case
relay coil(s).
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Terminals 13 and 14 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 through 24 are jumpered with a removable push-in jumper.
Kits FL28 and FL29 Diagrams 0423677 and 0423689
COM
RL Wiring Diagram for Dew Point or Humidistat Control
Fans and Anti-Condensate Heaters on Common Power Circuit.
Only Cycles Door Anti-Condensate Heater.
(Gas Defrost)
Thermostats
Defrost Limit
N.C.
N.O.
Fan Relay
208V
Fans
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
O.O.R .
Anti-Sweat Relay
N.C.
COM
120V
N.O.
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
Lights
L
Switch
10 11 12 13 14 16 17 20 21 22 24 25 26
Lights (120V)
Lights (Neutral)
B
1
Fans & Anti-Sweat (120V)
R
W
2
Relay Control
C.O.R.
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
Fans & Anti-Sweat (Neutral)
3
Dew Point and Humidistat Control Installation Instruction
P/N 0387094A
9
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Notes:
Field wiring from the dew
point/humidistat master case Terminals 12 & 21.
Field wiring from an adjoin-
ing slave case anti-sweat relay coil.
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Terminals 13 and 14 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 through 24 are jumpered with a removable push-in jumper.
RL Wiring Diagram for Dew Point or Humidistat Slave Relay
Fans and Anti-Condensate Heaters on Common Power Circuit.
Only Cycles Door Anti-Condensate Heater.
Kits BF53 Diagrams 0423677 and 0423689
Fans
Fan Relay
N.C.
COM
208V
N.O.
(Gas Defrost)
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
Thermostats
Defrost Limit
O.O.R .
Anti-Sweat Relay
N.C.
COM
120V
N.O.
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
1
N.C.
COM
N.O.
Relay Spot Dew Point / Humidistat
2
Lights
Switch
10 11 12 13 14 16 17 20 21 22 24 25 26
120V
L
Lights (120V)
Lights (Neutral)
Fans & Anti-Sweat (120V)
Relay Control
C.O.R.
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
Fans & Anti-Sweat (Neutral)
P/N 0387094A
Merchandisers
®
10
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Notes:
Dew point or Humidistat
Anti-sweat control.
White wire not used on
Humidistat control.
Field wiring for slave case
relay coil(s).
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 and 22 are jumpered with a removable push-in jumper.
Kits FL44 and FL45 Diagrams 0423679 and 0423689
RL Wiring Diagram for Dew Point or Humidistat Control
Fans and Anti-Condensate Heaters on Separate Power Circuits.
Only Cycles Door Anti-Condensate Heater.
(Gas Defrost)
Fan Relay
N.C.
COM
Anti-Sweat Relay
N.C.
COM
N.O.
208V
N.O.
120V
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
Fans
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
Lights
L
Switch
10 11 12 13 14 16 17 20 21 22 24 25 26
Fans (120V)
Anti-Sweat (120V)
B
R
1
W
2
Lights (120V)
Lights (Neutral)
Anti-Sweat (Neutral)
Thermostats
Defrost Limit
O.O.R .
Relay Control
C.O.R.
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
Fans (Neutral)
3
Dew Point and Humidistat Control Installation Instruction
P/N 0387094A
11
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Notes:
Field wiring from the dew
point/humidistat master case Terminals 12 & 21.
Field wiring from an adjoin-
ing slave case anti-sweat relay coil.
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 and 22 are jumpered with a removable push-in jumper.
RL Wiring Diagram for Dew Point or Humidistat Slave Relay
Fans and Anti-Condensate Heaters on Separate Power Circuits.
Only Cycles Door Anti-Condensate Heater.
Kits FL43 Diagrams 0423679 and 0423689
Fans
Fan Relay
N.C.
COM
208V
N.O.
(Gas Defrost)
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
Thermostats
Defrost Limit
O.O.R .
Anti-Sweat Relay
N.C.
COM
120V
N.O.
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
1
N.C.
COM
N.O.
Relay Spot Dew Point / Humidistat
2
Switch
10 11 12 13 14 16 17 20 21 22 24 25 26
Anti-Sweat (120V)
120V
Lights
L
Fans (120V)
Lights (120V)
Lights (Neutral)
Relay Control
C.O.R.
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
Fans (Neutral)
Anti-Sweat (Neutral)
P/N 0387094A
Merchandisers
®
12
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
NOTE: When replacing the cover on the control, be sure the cover’s vents are located over the control as shown.
DEW POINT CONTROL
HONEYWELL MODEL #H409A
HUMIDISTAT CONTROL
Vents
Adjustment
Mounting Plate
Electrical Switch Box
Note directional arrow when installing in vertical position
Control
Control
Cover
Cover