Hussmann RLN, RLT, RLNI, RLNIE, RLTI Installation Instruction

...
1
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Dew Point and
Humidistat Control
for Reach-In Merchandisers
Installation Instruction
Merchandisers
Model Description
Honeywell Model H409A Dew Point Control
Honeywell Model H46N-1005i Humidistat Control
GENERAL INFORMATION
Kit Application
Both of the controls shown on Page 12 are designed for energy conservation. They supply power to the anti-condensate heaters in the door only when necessary to maintain the sur­face temperature of the glass doors above the dew point.
The humidistat control is non­adjustable, factory-set to cycle off the door anti-condensate heaters when the store humidity drops to the set point of 35% relative humidity or lower. This control carries a maximum load of 10 Amps (see Table 1, Amperage).
The dew point control is a more versatile control offering six adjustable set-points, with a maximum setting of 40% relative humidity. This control carries maximum load of 16 Amps (see Table 1, Amperage).
The capacity of these controls may be increased by using relays whose coils are wired parallel with the control and the relay contacts connected to power supply. Refer to wiring diagrams for detail.
For a line-up of cases, one case is designated as the master case with the control installed. Note that each narrow island side is wired separately.
All other cases in the line-up are designated as slave cases with a relay energized from the control on the master case (side of an island).
The location of either dew point control or humidistat control must be in an area that reflects the store ambient con­dition where the merchandiser is located.
All wiring for these controls must comply with NEC and local regulations.
P/N 0387094A
April, 2002
P/N 0387094A
Merchandisers
®
2
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Table 1
Door heater amperages cycable by dew point or humidistat control (120 V).
Model
Door Condensate Heater Amps
Anthony Innovator
RL2, RLN2, RLNI2* 2.18 1.5
RL3, RLN3, RLNI3* 3.27 2.31
RL4, RLN4, RLNI4* 4.36 3.08
RL5, RLN5, RLNI5* 5.45 3.86
*RLNI values are per side.
Control Location — Reach-in and Narrow Reach-in
Skid/External Base
Electrical Wireway
Front
5-Door Shown
Relay & Terminal Block Location
Bottom Front Support
Refrigeration Outlet
Dew Point/ Humidistat
Location
Electrical
Field Wiring
Connection Point
Control Locations — Narrow Island Reach-in
Rear Relay & Terminal Block Location
Electrical Wireway
Refrigeration Outlet
Dew Point/ Humidistat
Location
Skid/External Base
Electrical Wireway
Front
5-Door Shown
Front Relay & Terminal Block Location
Bottom Front Support
Dew Point/ Humidistat
Location
Refrigeration Outlet
Electrical
Field Wiring
Connection Point
Dew Point and Humidistat Control Installation Instruction
P/N 0387094A
3
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Lower Right Hand of Case
R
B
W
Color Coded Harness
Identification Tag
Upper Right Hand of Case
Red
Black
White
Honeywell Dew Point Control M/N409A or Honeywell Humidistat Control M/NH46N
COMPONENT LOCATION FOR DEW POINT / HUMIDISTAT CONTROL
P/N 0387094A
Merchandisers
®
4
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A.
Notes:
Dew point or Humidistat
Anti-sweat control.
White wire not used on
Humidistat control.
Field wiring for slave case
relay coil(s).
• Yellow terminals 1 through 8 are 208V Defrost Circuit.
• Terminals 1 through 3 are internally jumpered.
• Terminals 4 and 5 are internally jumpered.
• Terminals 6 through 8 are internally jumpered.
• Gray terminals 10 through 17 are 120V Power.
• Terminals 14 and 16 are internally jumpered.
• Terminals 10 and 11 are jumpered with a removable push-in jumper.
• Terminals 13 and 14 are jumpered with a removable push-in jumper.
• Blue terminals 20 through 26 are 120V Neutral
• Terminals 24 through 26 are internally jumpered.
• Terminals 21 through 24 are jumpered with a removable push-in jumper.
Kits FL28 and FL29 Diagrams 0423658 and 0423689
RL Wiring Diagram for Dew Point or Humidistat Control
Fans and Anti-Condensate Heaters on Common Power Circuit.
Only Cycles Door Anti-Condensate Heater.
(Electric Defrost)
Rear Defrost
Front Defrost
Fans
Fan Relay
COM
COM
N.C.
N.O.
N.C.
N.O.
208V
Anti-Sweat Relay
120V
Rod Heater (Drain)
Frame Anti-Sweat
Door Anti-Sweat
Lights
L
Switch
Thermostats
Defrost Limit
The heavy lines drawn inside the terminal blocks represent permanent internal jumpers.
The heavy bracketed lines drawn outside the terminal blocks represent removable external push-in jumpers.
1234567810111213141617202122242526
Defrost Heaters (208V)
Defrost Heaters (208V)
Lights (120V)
Lights (Neutral)
B
1
2
Fans & Anti-Sweat (120V)
R
W
O.O.R .
Relay Control
C.O.R.
Defrost Termination
C.O.R.
Fans & Anti-Sweat (Neutral)
3