Q3MV-BC Lifting and Transport Instructions 8
Front Body Panel Install 9
Fasten Front Body Panel Install 9
Fasten Rear Body Panel Install 9
Leveling
Leveler Adjustment 10
Shim The Case 10
Joining
Parts List 11
Q3-MV-BC Case Adjustments 12
Joining Preparation 15
Electrical 20
Electrical Info
Merchandiser Electrical Data 20
Electrical Connections 20
Field Wiring 20
Miatech Fogging System 27
Setup and Installation
Fogging System Mounting 28
Fogger Nozzle Install 28
Water and Air Hose Routing 30
Case Settings 31
Miatech Controller Settings 31
Reverse Osmosis Filter 31
Field Electrical Connections 32
System Clock 34
Fogger System Troubleshooting 37
General
Start Up 38
Load Limits 38
Maintenance
Case Cleaning 41
Exterior Surfaces 41
Interior Surfaces 41
Troubleshooting 43
DOE 2012
Energy Eciency
Compliant
Hussmann refrigerated merchandisers congured for sale f
meet or surpass the requirements of the DOE 2012 energy eciency standards.
2
Page 3
Notice
1. DO NOT overload or stand over top of case. Glass breakage may occur if
precautions are disregarded.
*Broken glass can cause lacerations, cuts, and puncture wounds which
may result in severed arteries or tendons, amputations, eye injuries, or
exposure to disease.
WARNING
3
Page 4
General Information
CaseDescripon:
Description: Refrigerated Vertical Blower Meat Service Merchandiser
Shipping Damage: All equipment should be thoroughly examined for shipping damage before and
during unloading. This equipment has been carefully inspected at our factory and the carrier has
assumed responsibility for safe arrival. If damaged, either apparent or concealed, claim must be
made to the carrier Immediately.
Apparent Loss or Damage: If there is an obvious loss or damage, it must be noted on the freight bill
or express receipt and signed by the carrier’s agent; otherwise, carrier may refuse claim. The carrier
will supply necessary claim forms.
Concealed Loss or Damage: When loss or damage is not apparent until after all equipment is
uncrated, a claim for concealed damage is made. Make request in writing to carrier for inspection
within 15 days, and retain all packaging. The carrier will supply inspection report and required claim
forms.
Shortages: Check your shipment for any possible shortages of material. If a shortage should exist
and is found to be the responsibility of Hussmann Chino, notify Hussmann Chino. If such a shortage
involves the carrier, notify the carrier immediately, and request an inspection. Hussmann Chino will
acknowledge shortages within ten days from receipt of equipment.
Hussmann Chino Product Control: The serial number and shipping date of all equipment has been
pertaining to warranty or parts ordering must include the serial number of each piece of equipment
involved, in order to provide the customer with the correct parts.
Location/Store Conditions: The Q3-MV-BC refrigerated merchandiser has been designed for use only
in air conditioned stores where temperature and humidity are maintained at 80°F and 55% relative
humidity or 75°F and 55% relative humidity. DO NOT allow air conditioning, electric fans, ovens, open
doors or windows (etc.) to create air currents around the merchandiser, as this will impair its correct
operation.
Keep this booklet with the case at all times for future reference.
/CHINO
A publication of HUSSMANN® Chino
13770 Ramona Avenue • Chino, California 91710
(909) 628-8942 FAX
(909) 590-4910
(800) 592-2060
AT TENTION
INSTALLER
This equipment is to be installed
to comply with the applicable
NEC, Federal, State , and Local
Plumbing and Construction
Code having jurisdiction.
4
Page 5
52
(1051)
Q3-MV-BC
End
Q3-MV-BC
Case Sections
Multi-Deck Service Deli Case
26 1/2
(673)
12(305)
1/4
(1327)
22
7/8
5
(149)
24 3/4
(629)
7/8
(581)
153/8
(391)
10 3/8
(264)
221/8
(562)
14(356)
7/8 (708)
27
413/8
251/8
(638)
25 1/8
(638)
23 1/8
(587)
253/4
(654)
57/8
(149)
281/8
(714)
10 3/8
(264)
Panels
1 1/8
(29)
8
(203)
(127)
Fogging
Elec
System
customer side
48
(1219)72(1829)96(2438)
5
Drain
C
L
6 1/8
(156)
Refrig
41 7/8
(1064)
144
(3658)
5
Page 6
Installation
Snapping Chalk Lines
NOTICE
Do NOT remove Foam Blocks from shelves
and glass until the merchandisers are
positioned for installation. Shelves or
merchandising glass may be damaged.
Wrapped Top
and Shelves
Loose
Items
Foam Blocks
in place
Case is to arrive at store as was shipped form
factory. See reference above for proper shipment
referencing.
Warning
Labels
Preparepermanentpositioningbymarkingoors
with Chalk snap lines where cases are to be
located. Chalk lines are to run along the base or
legs of cases.
Receiving Case
Upon receiving your new Hussmann Case all
equipment should be thoroughly examined for
shipping damage before and during unloading.
This equipment has been carefully inspected at
our factory. Any claim for loss or damage must
be made to the carrier. The carrier will provide
any necessary inspection reports/ or claim form.
If there is obvious loss or damage, it must be
noted on the freight bill or express receipt and
signed by the carrier’s agent; otherwise carrier
may refuse claim.
6
Page 7
Inser
Underneath
Deck
Installation (cont’d)
Placement
Important: See lifting instructions to properly lift
case when being placed on dollies or permanent
location. (See page 8 for Lifting Instructions.)
First remove Blocks and L Brackets around the
case from pallet.
Remove Block
and L bracket
panels. Check for damage before discarding
packaging.
In the case a fork lift truck is not available follow
the demonstration below to properly lift case using a Johnson Bar (J-Bar) to place on dollies to
trafcfromstartpointtoplacementarea.
Proceedbysettingforkliftsunderspeciedloca-
tions as instructed in the Lifting Instructions
(pg. 8.) Be careful not to damage drains or near
components when placing forks underneath
case. A spotter is mandatory to ensure no damage is caused to the case. Lift case and replace
with dollies, place near or in permanent location.
t Forks
Place J-Bar underneath base of merchandiser
to gain leverage, once lifted place Dollie underneathrstendandslowlylowerontodollieensuring merchandiser is placed on stable location.
Proceed to opposite end and repeat.
Movethextureascloseaspossibletoitspermanent location and then remove all packaging
and preparing to remove off Skid. Remove all
separately packed accessories such as kits, and
7
Page 8
Installation (cont’d)
Drain
Q3-MV-BC Lifting and Transport
Instructions
1. The Q3-MV-BC can be lifted by a forklift at
typical lifting points.
J-Bar Lift Points
(Underneathe
Base Structure)
Forklift Points
(Underneathe
Deck)
J-Bar Lift Points
(Underneathe
Base Structure)
5. The Q3-MV-BC merchandiser can be raised
at one end underneath the deck with a forklift
to allow the placement of rollers or dollies.
6. Evenly support the entire base structure on
rollers or dollies before attempting to move.
Each Base Leg must have its own dollie to
properly support the case.
Lifting Points are typical and dependent upon
size of case and refrigeration application, drain-
agecongurationswillcallforaltercationsin
Lifting Zones.
Belowarethefollowingdrainagecongurations
and lifting should be altered to the expected
model.
Q3 MV-BC Drain Location
WARNING
Improper placement of forks may damage
drainage piping. Use a spotter when placing
forks. Make sure that piping will not be damaged. Use J-Bars or Jacks if forks cannot be
used safely
2. Ensure lower body panels are removed before lifting with a forklift. Serious damage will
occur if the body panels are not removed.
3. Make sure that fork spacing and width will not
damage drain or come in contact with piping,
or electrical lines
4. Be sure that the forks are long enough to
support beyond the center of the case but not
damage near components. Check for proper
balance before moving. A minimum fork
length of 36” is recommended for 68” wide
cases
8
Page 9
Installation (cont’d)
P
1
Front Body Panel Install
A Phillips Screw Driver/Bit will be needed to
install body panels.
To begin Bottom panel assembly place panel A
along side the base of the case and lower panel
on to support hooks along the bottom of the base
(See illustration below for details).
Resting Hooks
Panel A
anel B
A
Fasten Rear Body Panel Install
(1) Align pre drilled holes to base of case
(2) Secure top and bottom of rear panel using
fasteners as shown below.
Detail A
Fasten Front Body Panel Install
(1) Secure Panel A with top fasteners only.
(2) Overlay Panel B to bottom of Panel A as
shown in illustration below
*Note Panel B will be attached freely with no pre
drilled holes.
Allow front and rear body panels to slide down
resting on support hooks. 2.Place L Bracket
along the underside of deck to hold body panel
top in place against base wall of case.
1
2
Panel B
Panel A
2
9
Page 10
Installation (cont’d)
Level
Leveler Adjustment
Position the case at the highest point. Set a long
magnetized level (4ft [1220 mm] or more) on
either underneath the deck or on top of the case.
Ensure to level case from front to back and side
to side.
Note:Toavoidremovingconcreteooring,begin
line up levelling from the Highest point of the
storeoor.
Shim The Case
(4 ft[1220mm])
NOTICE
Longer length cases may require shims
along the center portion of the case to
maintain proper case performance and
drainage.
Use shims at each corner of the case to level
out any discrepancies in order to optimize case
performance and proper drainage.
Note: Shims are not Factory supplied. Contractor
should carry available components. Metal Shims
are recommended for use to eliminate any
deterioration from shims over time.
3) Installjoining part 1and 2(seepartlist) usingsilicone adhesive andpushbackall theway.
4) Installtop joiningpartusing silicone adhesive (see part list)and push allthe wayforward.
5) Usingdoubleside3M® adhesive tape installjoining parts3and4(see part list)
6) Reinstalldeckpansand modularDSCHs.
Page 18
Refrigeration
Refrigerant
The correct type of refrigerant will be stamped
on each merchandiser’s serial plate. The case
refrigeration piping is pressurized with a nitrogen
holding charge, leak tested and factory sealed.
Before making refrigeration hookups, depress
universal line valve (Shraeder Valve) to ensure
that coils have maintained pressure during shipment. In the case pressure was not maintained
contact your Hussmann Service Tech for further
assistance.
Serial Plate Location
Refrigerant piping
The refrigerant line connections are at the right
hand end of the case (as viewed from the front)
beneath the display pans. The merchandiser will
beforehand ensure an earlier cut hole through
the pod to exit the merchandiser for the refrigeration lines. After connections have been made,
make certain to seal this outlet thoroughly if not
sealed at factory already. Seal both the inside
and outside. We recommend using an expanding
polyurethane foam insulation.
Line Sizing
Refrigerant should be sized as shown on the
refrigeration legend that is furnished for the store
or according to the ASHRAE guidelines
Oil Traps
P-traps (oil traps) must be installed at the base
of all suction line vertical risers.
CAUTION
Refrigeration lines are under pressure.
Refrigerant must be recovered before
attempting to make any connections.
It is the contractor's responsibility to install
case(s) according to local construction and
health codes.
Piping Location
18
Page 19
NSF 7 TYPE M NSF 7 TYPE M NSF 7 TYPE M6'TBDTBDTBD
6',8',12'390330202427~29 31~328'TBDTBDTBD
12'TBDTBDTBD
*DISCHARGE AIR MEASURED INSIDE DISCHARGE AIR GRILL IN THE REAR OF THE CASE
**REFRIGERATION NOTES:
1) BTU'S INCLUDE CANOPY LIGHTS AND TWO ROWS OF SHELF LIGHTS.
2) AHRI 1200 RATING POINT FOR ENERGY CONSUMPTION COMPARISON ONLY
MEAT SERVICE CASE, VERTICAL GLASSREVISION DATE03/01/18
HUSSMANN - Q3-MV-BC-R (CHINO)
REFRIGERATION DATA:
CAPACITY **
CASE LENGTHS CASE USAGE
3) USE DEW POINT FOR HIGH GLIDE REFRIGERANTS. CARE SHOULD BE TAKEN TO USE THE DEW POINT IN P/T TABLES
FOR MEASURING AND ADJUSTING SUPERHEAT. ADJUST EVAPORATOR PRESSURE AS NEEDED TO MAINTAIN THE
DISCHARGE AIR TEMPERATURE SHOWN.
4) RATING CONDITION FOR NSF TYPE I IS 75°F/55% RH
5) RATING CONDITION FOR TYPE M IS 68°F/50% RH
6) MISTING OPERATION NOT RECOMMENDED AT 20°F
(BTU/HR/FT)
REFRIGERATION DATA CONTINUED:
TIME
(MIN)
USAGE
CUT IN
(ºF)
DEFROST
TYPE****
MEAT3534 OFF TIME3045N/A21.125
TEMPERATURE (ºF)
EVAPORATOR DISCHARGE AIR*
DEFROST
FREQUENCY
(#/DAY)
TERM.
COIL
ONLY
DRIP
TIME
31.25
VELOCITY
(FT/MIN)
DEFROST
WATER
(LBS/DAY/FT)
LENGTHS
# OF END
***AIR SENSOR PLACED IN RETURN AIR UNDER DECK PAN
****DEFROST IS CARRIED OUT BY CASE CONTROLLER. DO NOT SCHEDULE DEFROSTS ON THE STORE CONTROLLER.
ELECTRICAL DATA:
CASE LENGTH
STANDARD FANS, HEATERS, LED LIGHTS (115 VOLT)
EVAPORATOR FANS
# OF
BLADE
DIA.
(IN.)
BLADE
PITCH (°)
WATTSAMPS WATTS
AMPS
EVAP
FANS
AIRSWEEP FAN
# OF
FANS
CANOPY
LIGHTS LED
WATTS AMPS WATTS
AMPS
OPTIONAL LED
SHELF LIGHTS
MAX. LED LOAD
(W/ ALL OPTIONS)
WATTS AMPS WATTS
AMPS
HEATERS****
6'
EST.
GLYCOL (20°F
REFG.
CASE
CHRG.
(LBS)
(R404A)
INLET, 6° RISE)
GPMPSI
END PANEL WIDTH KEY
PNLS
(IN.)
LENGTH (IN.)
TOTAL ADDED
WIDTH
11.125
DEFROST
OUTLETS (OPTIONAL)
OUTLETS
2.25
CONVENIENCE
#
VOLTS
AMPS
CASE LENGTH
LIGHTS
OPTIONAL SHELF
MAX. H.O. LED
LOAD
AMPS WATTS AMPSWATTS AM PS WATTS
19
Page 20
Electrical
Merchandiser Electrical Data
Technical data sheets are shipped with this
manual. The data sheets provide merchandiser
electrical data. Refer to the technical data sheets
and merchandiser serial plate for electrical
information.
Electrical Connections
All wiring must be in compliance with NEC and
local codes. All electrical connections including
both supply circuits are to be made in the electrical J-Box.
ALWAYS CHECK THE SERIAL PLATE FOR
COMPONENT AMPERES
Field Wiring
Field wiring must be sized for component amperes stamped on the serial plate (refer to pg 16
for location). Actual ampere draw may be less
colored plastic bands. These bands correspond
to the color code sticker (shown below) located
inside the merchandiser’s wireway cover.
WARNING
--LOCK OUT/ TAG OUT--
To avoid serious injury or death from electrical
shock, always disconnect the electrical power
at the main disconnect when servicing or
replacing any electrical component. This
includes, but is not limited to, such items as
doors, lights, fans, heaters, and thermostats.
20
Page 21
Electrical Cont’d
y
Remove Rear Raceway
The Merchandisers Electrical access is located
at the rear of the case. Fasteners must be removed in order to gain access. See illustration
below.
Remove Rear Raceway from rear of case.
Electrical Conduit (Electrical Box)
The Merchandisers Electrical conduit can be
found inside the compartment at the rear. Removing the raceway will gain access to the electrical components inside the J-Box allowing any
maintenance necessary.
Electrical Conduit
Fogging System Controls
Removing the rear panel will allow access to the
control to the Fogging System Control unit.
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
Electrical Wiring Diagram
D
3055096
DIAGRAM-Q3-MV-BC-8R
W/AK-CC-210 FOR /MISTING
SYSTEM
REVISION HISTORY
ALL SINGLE
RECEPTACLES TO BE
TIED TO DUPLEX GFCI
RECEPTACLE
GFCI DUPLEX
125-01-3178
BLK # 14
CIRCUIT #3
A ECN-CAP-0011 187 201 8/02/01RELEA SED TO PRO DUCTIONCBCBCB
B ECN- CAP-0011188 2018/02/02REMOV ED AIR SWEEP HEAT ERCB CBCB
C ECN-CAP -0011190 2018/02/09ADDED FIELD INSTRUCTIO NSCBCBCB
REVECNDATE REVISION D ESCRIPTIONREV BY CHKD BY APPR BY
CIRCUIT #2
D ECN-CAP-0011191 2018/02/14 ADDED ADDITIO NAL FIELD INSTRUCTION S CBCBCB
RJ-45 NETWORK JACK
125-01-0202
GRN # 14
WHT # 14
INCOMING POWER
~120 VAC -60 Hz
BUNDLE
YELLOW
EVAP FAN MOTOR
(4) 0477653
4W .12A @120VAC
M
REF -
THIRD
ANGLE
PROJECTION
SHEET 1 OF 3
ECN-CAP-0011187
.010
u
v
2
u
.03, .XXX
u
ANGLES
TOLERANCES ARE:
APPROVED BY - CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
MATERIAL - N/A
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
DRAWN BY -CRAIG BOOREY
DATE DRAWN - 2-1-18
DECIMALS .XX
M
M
AIR SWEEP FAN
MM
(2) 0404551
15W .20A @120VAC
M
BUNDLE
BROWN
WHITE #14
BLACK #14
L1 N
MCA= 1.1A
MOP= 15A
~120 VAC - 60 Hz.
CIRCUIT #1
120V
LOADING
4.4
L1
4' L.E.D. LIGHT
4' L.E.D. LIGHT
LIGHT CIRCUIT
0.91A 98.6W @ 120V
SHELVES
LEDGE
CANOPY
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT HO
4' L.E.D. LIGHT HO
3' L.E.D. LIGHT
3' L.E.D. LIGHT
BLUE -
RED +
BLUE -
RED +
LED DRIVER
LIGHT SWITCH
TIPPETTE
125-01-0311
LED DRIVER
L
BUNDLE
ORANGE
WHT#14
BLK #14
L1 N
MCA= 1.14A
MOP= 15A
~120 VAC - 60 Hz.
22
Page 23
HUSSMANN_GDF_1.1 SHEET SIZE D
NOTES:
CASE MUST BE GROUNDED
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
L1 N
~120 VAC - 60 Hz
#125-01-0713
GRÄSSLIN FM/1 DIGI 20 - 120
MISTING SYSTEM BY OTHERS
Electrical Wiring Diagram (Cont’d)
WHITE #14
GRN # 14
YELLOW
L1
~120 VAC -60 Hz
DIAGRAM-Q3-MV-BC-8R
ECN-CAP-0011187
MATERIAL - N/A
DRAWN BY -CRAIG BOOREY
DATE DRAWN - 2-1-18
BLACK #14
E
S
A
C
A
C
R
Y
E
V
T
R
5
1
A
A
E
D
1
N
H
2
O
@
0
IR
C
A
3
E
A
1
.6
-
N
1
' S
2
R
8
0
W
U
-
0
R
T
REVISION HISTORY
A ECN-CAP-0011 187 201 8/02/01RELEA SED TO PRO DUCTIONCBCBCB
B ECN- CAP-0011188 2018/02/02REMOV ED AIR SWEEP HEAT ERCB CBCB
C ECN-CAP -0011190 2018/02/09ADDED FIELD INSTRUCTIO NSCBCBCB
REVECNDATE REVISION D ESCRIPTIONREV BY CHKD BY APPR BY
5
0
E
O
2
1
F
3
R
D ECN-CAP-0011191 2018/02/14 ADDED ADDITIO NAL FIELD INSTRUCTION S CBCBCB
C
A
R
E
E
V
S
T
5
1
A
A
E
1
C
Y
H
2
@
R
0
IR
A
A
3
A
1
.6
IM
-
N
1
R
2
R
0
W
P
U
-
0
R
T
5
0
E
O
2
3
1
F
R
WIRES AT
CONTROL
INPUTS/OUTPUTS
NOTE:
BUNDLE
PURPLE
BUNDLE
PURPLE
DANFOSS® CONTROLLER
AK-CC 210 115V # 084B8534
1H56892500
14GA MAX
DEF.
L1
N
WHITE #14
HEATER RELAY ( NO )
N
N
6
4
5
2
4
6
3
1
ONLY
125-01-1343
SOLENOID
225-01-0878
.14A @ 120VAC
FOR PRIMARY CASE
L1
L1
BLACK #14
L1
GFCI DUPLEX
125-01-3178
BLK # 14
S
R
E
T
A
R
E
O
H
I F
M
C
E
F
T
S
G
S
Y
D
R
E
S
E
T
G
H
A
T
IN
IC
T
D
O
IS
E
Y
M
B
D
INSTALL TO
TERMINAL 1 IF
MISTING
SYSTEM IS
INSTALLED
N
WHT # 14
BUNDLE
D
3055096
W/AK-CC-210 FOR /MISTING
SYSTEM
REF -
THIRD
ANGLE
PROJECTION
SHEET 2 OF 3
.010
u
v
2
u
.03, .XXX
u
ANGLES
TOLERANCES ARE:
APPROVED BY - CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
DECIMALS .XX
COMP.
AK-CC 210
®
Danfoss
DISCHARGE AIR
SENSOR AKS-12
L1
L
SWITCH
125-01-0311
125-01-3178
CIRCUIT #5
LABELED AS
SWITCHED AT
PANEL
N
L1
GFCI DUPLEX
N
120 VAC
L1
SOLENOID
225-01-0878
.14A @ 120VAC
FOR 8' SECONDARY CASE
WHITE #14
N
BUNDLE
BLK # 14
WHT # 14
YELLOW
GRN # 14
5
4
3
C NO NC
2
M
1
N
N
L1
~120 VAC - 60 Hz
BLACK #14
BUNDLE
WHITE #14
BLACK #14
YELLOW
WHITE #14
BLACK #14
L1 N
SECONDARY CASE WIRING.
USE WAGO CONNECTORS FOR
JOINING WIRES
23
Page 24
HUSSMANN_GDF_1.1 SHEET SIZE D
NOTES:
CASE MUST BE GROUNDED
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
Electrical Wiring Diagram (Cont’d)
D
3055096
DIAGRAM-Q3-MV-BC-8R
W/AK-CC-210 FOR /MISTING
SYSTEM
REVISION HISTORY
WHITE #14
A ECN-CAP-0011 187 201 8/02/01RELEA SED TO PRO DUCTIONCBCBCB
B ECN- CAP-0011188 2018/02/02REMOV ED AIR SWEEP HEAT ERCB CBCB
C ECN-CAP -0011190 2018/02/09ADDED FIELD INSTRUCTIO NSCBCBCB
D ECN-CAP-0011191 2018/02/14 ADDED ADDITIO NAL FIELD INSTRUCTION S CBCBCB
REVECNDATE REVISION D ESCRIPTIONREV BY CHKD BY APPR BY
E
S
A
C
R
Y
E
T
R
A
A
E
D
N
H
O
IR
C
E
A
S
N
'
R
8
U
R
8' SECONDARY CASE
T
E
O
F
R
BUNDLE IN RACEWAY
AND LABEL SECONDARY
CASE RETURN AIR
BLACK #14
N
L1
HEATER
LEADS TERMINATED IN
RACEWAY FOR BOTH
BUNDLE IN RACEWAY
CASES TO BE FIELD
CONNECTED
AND LABEL SECONDARY
SUCTION STOP
SOLENOID
FOR 8' SECONDARY CASE
L1
N
CASE SUCTION
SOLENOID VALVE
REF -
THIRD
ANGLE
PROJECTION
SHEET 3 OF 3
ECN-CAP-0011187
.010
u
v
2
u
.03, .XXX
u
ANGLES
TOLERANCES ARE:
APPROVED BY - CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
MATERIAL - N/A
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
DRAWN BY -CRAIG BOOREY
DATE DRAWN - 2-1-18
DECIMALS .XX
LABEL SUCTION STOP
SOLENOID TO TIE INTO 8'
LABEL RETURN AIR
HEATER TO TIE INTO 8'
SECONDARY CASE
N
L1
SECONDARY CASE
L1
N
8' PRIMARY CASE
FROM PRIMARY CASE
FROM PRIMARY CASE
RETURN AIR HEATER
SUCTION STOP SOLENOID
24
Page 25
HUSSMANN_GDF_1.1 SHEET SIZE D
NOTES:
CASE MUST BE GROUNDED
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
Electrical Wiring Diagram (Cont’d)
B
3053568
DIAGRAM-Q3-MV-BC-12R
W/AK-CC-210 FOR /MISTING
SYSTEM
REVISION HISTORY
ALL SINGLE
RECEPTACLES TO BE
TIED TO DUPLEX GFCI
RECEPTACLE
GFCI DUPLEX
125-01-3178
BLK # 14
CIRCUIT #3
CIRCUIT #2
A ECN- CAP-0010812 2018/01/12RELEASED TO P RODUCTIONCBCBCB
B ECN- CAP-0011188 2018/02/02REMOV ED AIR SWEEP HEAT ERCB CBCB
REVECNDATE REVISION D ESCRIPTIONREV BY CHKD BY APPR BY
GRN # 14
WHT # 14
INCOMING POWER
~120 VAC -60 Hz
M
M
BUNDLE
YELLOW
EVAP FAN MOTOR
(6) 0477653
4W .12A @120VAC
M
REF -
THIRD
ANGLE
PROJECTION
SHEET 1 OF 2
ECN-CAP-0010812
.010
u
v
2
u
.03, .XXX
u
ANGLES
TOLERANCES ARE:
APPROVED BY - CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
MATERIAL - N/A
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
DRAWN BY -CRAIG BOOREY
DATE DRAWN - 1-12-18
DECIMALS .XX
M
RJ-45 NETWORK JACK
125-01-0202
M
M
AIR SWEEP FAN
MM
(3) 0404551
15W .20A @120VAC
M
BUNDLE
BROWN
WHITE #14
BLACK #14
L1 N
MCA= 1.7A
MOP= 15A
~120 VAC - 60 Hz.
CIRCUIT #1
120V
LOADING
6.4
L1
6' L.E.D. LIGHT
LEDGE
CANOPY-REAR
LIGHT CIRCUIT
1.37A 148.6W @ 120V
SHELVES
CANOPY-FRONT
6' L.E.D. LIGHT
3' L.E.D. LIGHT
3' L.E.D. LIGHT
3' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT
4' L.E.D. LIGHT HO
4' L.E.D. LIGHT HO
4' L.E.D. LIGHT HO
BLUE -
RED +
BLUE -
RED +
BLUE -
RED +
LED DRIVER
LED DRIVER
LIGHT SWITCH
TIPPETTE
125-01-0311
LED DRIVER
L
BUNDLE
ORANGE
WHT#14
BLK #14
L1 N
MCA= 1.21A
MOP= 15A
~120 VAC - 60 Hz.
25
Page 26
HUSSMANN_GDF_1.1 SHEET SIZE D
NOTES:
CASE MUST BE GROUNDED
WHEN PASSING WIRES THROUGH METAL HOLES A GROMMET MUST BE USED
L1 N
~120 VAC - 60 Hz
#125-01-0713
GRÄSSLIN FM/1 DIGI 20 - 120
MISTING SYSTEM BY OTHERS
Electrical Wiring Diagram (Cont’d)
REVISION HISTORY
WHITE #14
BLACK #14
C
A
R
V
E
5
T
1
A
1
E
A ECN- CAP-0010812 2018/01/12RELEASED TO P RODUCTIONCBCBCB
B ECN- CAP-0011188 2018/02/02REMOV ED AIR SWEEP HEAT ERCB CBCB
REVECNDATE REVISION D ESCRIPTIONREV BY CHKD BY APPR BY
H
0
@
R
A
0
I
1
3
A
1
.9
-
N
1
3
R
0
W
U
-
0
T
5
5
E
2
4
R
1
BUNDLE
PURPLE
6
5
6
3
B
GFCI DUPLEX
125-01-3178
BLK # 14
GRN # 14
S
R
E
T
A
R
E
O
H
I F
M
C
E
F
T
S
G
S
Y
D
R
E
S
E
T
G
H
A
T
IN
IC
T
D
O
IS
E
Y
M
B
D
4
2
4
1
N
WHT # 14
BUNDLE
YELLOW
~120 VAC -60 Hz
DIAGRAM-Q3-MV-BC-12R
ECN-CAP-0010812
MATERIAL - N/A
DRAWN BY -CRAIG BOOREY
DATE DRAWN - 1-12-18
3053568
W/AK-CC-210 FOR /MISTING
SYSTEM
REF -
THIRD
ANGLE
PROJECTION
SHEET 2 OF 2
.010
u
v
2
u
.03, .XXX
u
ANGLES
TOLERANCES ARE:
APPROVED BY - CRAIG BOOREY
REVIEWED BY -CRAIG BOOREY
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES.
DECIMALS .XX
DISCHARGE AIR
WIRES AT
NOTE:
GFCI DUPLEX
DANFOSS® CONTROLLER
CONTROL
INPUTS/OUTPUTS
14GA MAX
AK-CC 210
®
Danfoss
SENSOR AKS-12
L1
L
SWITCH
125-01-0311
CIRCUIT #5
125-01-3178
N
L1
L1
AK-CC 210 115V # 084B8534
1H56892500
DEF.
COMP.
120 VAC
N
BLK # 14
GRN # 14
WHT # 14
HEATER RELAY ( NO )
125-01-1343
N
SOLENOID
225-01-0878
.14A @ 120VAC
L1
N
L1
BLACK #14
WHITE #14
BUNDLE
YELLOW
5
BUNDLE
4
3
C NO NC
2
M
1
WHITE #14
BLACK #14
YELLOW
WHITE #14
BLACK #14
L1
N
L1
~120 VAC - 60 Hz
L1 N
26
Page 27
Miatech Fogging System
SOP MIATECH FOGGING SYSTEM
Q3-MV-BC-R SETUP AND INSTALLATION
Be advised, for case lineups co nsisting of two 8-foot cases (or other compatible combinations), the
fogger system may be shared over 2 cases to reduce cost. One case will be designated as the primary
case and will house the fogger system. Any secondary case will be directly adjacent to the primary case
and will share case control, fogging control and apparatus. A 12 foot case will always have a dedicated
fogging system.
These are the notable differences between the primary and the secondary case.
The primary case will house the Danfoss AK-CC 210 controller (orange arrow) in the rear panel. The
secondary case will not have a controller.
The primary case will have a large removeable access panel on the lower rear skirt (blue arrow). Behind
the access panel, there will be a tray to slide the fogger system into along with a set of GFCIs to plug both
the fogger system and the heated nozzles. The secondary case will not have an access panel, tray or GFCIs
underneath the case.
The primary case will house the system clock and heat er relay behind the rear controller panel. There will
be n o clock or relay on the secondary case.
The primary case will have 2 rocker switches (green arrow), one for lights, the 2
secondary case will have 1 rocker switch for lights only.
nd
for fogger power. The
Figure 1: An 8 foot primary case as viewed from the rear.
27
Page 28
1. FOGGER SYSTEM MOUNTING
Skirt
a. Physical location
i. Remove the rear skirt for easy access to the tray, GFCIs and case thru hole(s).
ii. When ready, connect the fogger power to the GFCI labeled “Fogging System”.
This circuit is switched at the case control panel as opposed to the adjacent GFCI
which is hot once the case power connections are made.
Figure 2: Rear of case showing panel cutout and access
panel.
Figure 3: The provided tray directly behind the
access panel.Remove lower skirt for system
installation. The access panel is provided for ease
of system access during operation.
Figure 4: Provided case drop to route hoses and nozzle heater wiring.
2. FOGGER NOZZLE INSTALLATION
a. Heated nozzles must be utilized. Standard (non-heated) nozzles will freeze and render the
system inoperable. The bracketry design will not accommodate non-heated nozzles.
b. Gain access to the coil area by removing the deck pans. The coils, fans and refrigeration
piping will be exposed. Locate the nozzle mount ing bracketry
28
Page 29
c. T he number and location of nozzles: Each fogger nozzle will mist a 3’ or 4’ section of the
Case
Number of
Location
case. The nozzles will be mounted in the close-offs for the crumb tray under the rear
discharge air grills.
Length
Figure 7: Remove indicated screws and remove
close off and mount nozzles.
d. The nozzle locations are described in the figure below. T he number in the bubbles
indicate the nozzle location for various case sizes. See the table above for case length vs
nozzle locations.
Heated Nozzles
411
622, 3
822, 3
1232, 3, 5
Figure 6: Pre-installed brackets shown with
nozzles installed. The required bracketry will
be factory installed.
(see drawing bel ow)
Figure 5: The close off with nozzle
brackets.
29
Page 30
3. WATER AND AIR HOSE ROUTING
a. Trim the black hard plastic tubing (see figure 6, pg 3) surrounding the 3 lines coming out
of each heated nozzle, ahead of the case drop (figure 4, pg 2). Do not pass the hard
plastic through the case drop.
b. Pass the nozzle tubes and wiring through the case drop and ensure no excess tubing
remains in the case. Leave enough slack so that the tubes do not kink when passing
through the drop and nozzle service can be accomplished.
c. IMPORTANT! - Ensure that the water lines DO NOT COME IN CONTACT with the below
freezing temperature of the refrigeration suction lines.
d. Make the appr opriate water and air connections to the fogge r system under the case.
e. Make t he appropriate electrical connections for the nozzle heaters. Plug the heaters
into the provided GFCI when the fogger system is ready to run. Do not plug it into the
“fogging system” GFCI. Note: The heater GFCI is electrically hot once the case electrical
connections are made, therefore the nozzles will be heated once the heater is plugged in.
f.IMPORTANT! - Seal case drop with a silicone based sealant once installation is finalized.
Allow the recommended time to cure before first operation of the fogging system.
Figure 8: Do not plug the heater into the Fogging System GFCI and vice versa.
30
Page 31
4. CASE SETTINGS
a. Defrost – IMPORTANT! – THE SUPPLIED CASE CONTROLLER WILL CONTROL DEFROST
AND IS PROGRAMMED AT THE FACTORY WITH THE SETTINGS BELOW. This case does
not need a defrost from the rack. A rack defrost will lead to erratic operation and
potential loss of product.
i. Danfoss controller defrost frequency (d03):8 hours
ii. Danfoss controller defrost duration (d04):30 minutes
b. Discharge air (for reference)
i. 30-32° (in type M ambient conditions 68° DB, 50% Rh) measured 2 hours afte r
c. Superheat
i. Target 3-5° for superheat.
d. Evaporator suction temp
i. IMPORTANT! - 24°. Lower temps may precipitate freeze-up of the fogger
e. Controller setpoints are as follows:
i. Setpoint (cutout):35°
ii. Differential (r01):1°
defrost. Will vary depending on time of measurement and actual store
conditions.
system and degradation of case performance. Higher temps may jeopardize
product temperatures.
NOTE: You may notice that the controller setpoint is higher than the specified discharge air temp. This is because the
controller air sensor has been placed in the return air stream under the deck pans. This was done because the fogger
spray into the discharge air confused the controller and led to erratic operation.
Figure 9: Air probe for controller setpoint located in return air stream on the primary case only.
5. IMPORTANT! - MIATECH AQUA FOGGER CONTROLLER SETTINGS:
a. Power switch: On
b. Water pressure: 5 psi
c. Mist time: 45 seconds
d. Off time: 3 minutes
e. Heaters plugged into proper GFCI socket (labeled at Heater)
6.
REVERSE OSMOSIS FILTER
Total dissolved solids to be less t han 100 PPM.
31
Page 32
7. FIELD ELECTRICAL CONNECTIONS
a. IMPORTANT! - For primary/secondary case lineups; the secondary case doe s not have
controls for the suction solenoid or defrost air heater. Two sets of leads will be bundled
in both cases for a field connection when the cases are placed and bolted together.
Trim excess wiring and make the indicated electrical connections for t he solenoid and
return air heater as per below:
Figure 10: The dotted lines indicate the secondary solenoid and secondary return air heater.
Figure 11: Locate the 2 sets of leads in the rear raceway of both cases after case placement. Connect the
secondary case solenoid leads to the leads for the solenoid on the primary case. Do the same for the return
air heater.
32
Page 33
b.
IMPORTANT! - Heater relay connection: T he return air heater ships from the factory
disabled. If a fogging system is installed, the return air heater m ust be connected. The lead
will be labeled as “Install to terminal 1 if fogging system is installed.”
i. The relay is located behind the rear panel of the primary case (green arrow).
ii. Make the connection of the unconnected wire to terminal 1 on the heater relay.
Figure 13: Green arrow is the Heater relay. Blue arrow is the Time
Clock. Re d arrow is the Danfoss controller.
Figure 12: Connect the unconnected lead (purple) to
terminal 1 on the heater relay.
NOTE: The ro cker switch for the fogge r system is lighted. Press the lighted part of
the switch to turn the system on. If the light does not turn on when the switch
turned on, one or more of the conditions for fogging engagement is not met. Thefollowing conditions will interrupt fogger operation:
o…the Grasslin Time Clock (blue arrow above) is in off mode. The factory
default off-time is 10pm – 6am CST (over night). This w ould be indicated by an open circle.
In figure 14, the program is engaged indicated by a closed circle.
o…the Danfoss controller is in defrost and the he a ter relay is
energized. An icicle with rain falling (below) will be indicated on the
Danfoss controller. The main display will show “- d -“.
When the circle i s filled, as in figure
14, the timer is in the on mode and
the fogger power is not interrupted
by the time clock.
33
7
Figure 14
Page 34
8. SYSTEM CLOCK: The Fogging system has a clock located behind the rear raceway panel.
Figure 16: The system clock interrupts the fogging system during nondisplay hours. The factory settings are listed below. If different, the
store’s actual times should be programmed into the clock. The factory
clock setting is set to CST. Adjust to your time zone as necessary.
Figure 15: Grasslin FM1D20-120
programmable time clock to match store's
meat department display times with an
overlap.
The factory default settings are:
a. Clock factory set to CST
b. On: 6am – 10 pm
c.Off: 10pm – 6 am
The benefits of interrupting the fogger system are:
•The RO filter life will be extended
•An y ice build-up will be cleared by this interruption.
•The life of the case will be extended by reducing the total fogging time.
It is not recommended that product remain in the case overnight. The product should be covered, removed to
cold storage and re-stocked in the morning. However, if product is kept in the case, the clock should not interrupt
the fogging system operation and must be re-programmed.
IMPORTANT! Check with the store personal to understand if they will be removing product for nighttime storage and if so, what are their display times. If the factory default fogging times and/or the
local time differ, the clock must be re-programmed.
-Basic quick instructions below. See Grasslin’s website for the full manual for model
FM1D20-120U.
a.Make the case electrical connections to power time clock. A circle ¾ circle with a “1” will be displayed when
AC power is applied to the case. Confirm that the timer is in “AUTO” mode. This will be indicated with a
small arrow above the “AUTO”.
b.Adjust the time to match the current time by pressing the “Menu” button. Adjust up and down with “+” and
“-“ keys. Press the “OK” key to confirm the item and cycle to the next entry.
c.After the day of the week is set, the next step is to set the fogging time: “prog 1”. Change the fogger start
time for the morning as per the store’s display time. Continue to enter the evening turn-off time. Once
complete press the “Menu” button to exit programming.
d.The “OVR” button can be used to either turn off or turn on the fogger depending on its current state.
e.To permanently run the fogging system, the time clock will need to be reprogrammed to run 23 hours and 59
minutes. You will notice all of the hash marks from 0-24 are on.
34
Page 35
DISCHARGE AIR GRILLS: The discharge grills are positional. The center grills all have the same outlet
PN 3052446. Left hand grill
PN 3052447. Right hand grill
PN 3052448. Center grill. In
pattern. The case ends (defined as bordering a case end panel) will have a slightly more open pattern.
Ensure that the grills are located in the correct positions:
as viewed from the front of
the case. 1 per case or lineup.
as viewed from the front of
the case. 1 per case or lineup.
all positions except ends.
See above.
35
Page 36
PROCEDURE AND CHECKLIST:
Hussmann Responsibility
□ Make the heater relay connection at terminal 1 (pg 8).
□ If applicable, make the appropriate primary to secondary case electrical connections for the return
air heater and suction solenoid. See page 6 for details.
□ Set suction pressure to a 24° equivalent. Ensure stable temperature.
□ Ensure the TXV superheats are within specs.
□ Ensure the controller settings are per the specs for setpoint, differential and defrost (see pg 5).
□ Confirm discharge air setting meets the specification. Adjust the setpoint if needed.
□ Ensure the discharge air grills are properly positioned inside the case and/or line-up. See the
previous page for details.
Miatech Responsibility
□ Remove rear skirt and slide the fogger system into the tray located under the case.
□ Mount the heated nozzles into designed position under the di scharge air grill.
□ Rout the water, air and heater wires thro ugh the pr ovided case drop.
□ Connect the water and air lines to the fogger system. Be sure an appropriate amount of slack is
available to service the nozzles. The water lines must not contact the cold suction refrigeration
lines. Freezing could occur and the system will be inoperable.
□ Remove the case rear panel with the case controller to gain access to the rear raceway (pg 7 ) .
□ Ensure that the provided time clock (pg. 7-8) is set to local time. The factory default is CST.
□ Ensure that the provided time clock (pg. 7-8) is programmed to the store’s display hours. The
factory default is 10pm – 6am system off time. Check with the store’s personnel to understand if
the case product will be unloaded and loaded, and if so, at what times. Adjust the time clock
accordingly. If the case is to remain loaded overnight, the fogger system m ust run continuously
and the time clock should be overridden (see pg 8).
□ Plug the fogger system into the switched GFC I socket marked “Fogger System” (see pg 4).
□ Plug the nozzle heater(s) into the GFCI marked “Fogger Heater System” (see pg 4).
□ Turn the fogger system on with the rocke r switch mounted on the case control panel. The rocker
switch light should illuminate. If it does not, see page 7.
□ Adjust the fogger system to the settings o n page 5.
□ Observe for proper operation with the discharge grills removed. Observe spray pattern. The
nozzle spray pattern should shoot into the crumb tray parallel to the bend lines of the crumb tray.
□ Test the RO filter and ensure the proper reduction of TDS between the inlet vs outlet of the RO
system.
□ Seal the case through-hole for the air and water lines.
□ Reassemble deck pans, rear skirt, and rear panel.
□ Ensure the discharge air grills are properly positioned inside the case and/or line-up. See the
previous page for details.
36
Page 37
FOGGER SYSTEM TROUBLESHOOTING
ProblemPossible CausePossible Solution
Ensure the power switch on Miatech unit turned to "ON".
Ensure the "Fogger System" switch on the case is switched
No Power to Fogging
system
Case in defrost cycle
to the "ON" position, and the light is illu min ated.
GFCI on power outlet tripped; reset GFCI via the "RESET"
button. GFCIs have a small green LED. Verify LED is green.
Ensure the case has power supplied to it.
The Fogger time clock is on the nighttime OFF cycle
Wait until defrost cycle has completed. If the case is in
defrost, the characters -d- will be displayed on the
controller.
Little to No
Fog
Fogging system is on the
"Off" time
Ice on discharge air grill
Pinched Air/ Water lines
Iced Nozzle
Frozen water line(s)
Disconnected/punctured air
or water line
The Fogging system will be powered down during off hours.
Off hours are determined by the Fogging system timer. See
the IO manual or SOP t o adjust or override.
Check that discharge air temperatures are between 31°32°F.
Ensure defrost heater is operating during defrost.
Ensure that case controller setpoint have not deviated from
the factory settings. Refer to the specification sheet.
Ensure all lines leading to the nozzles are free of kinks or
anything that may compress or cause a blockage of the line.
Ensure the heaters are plugged into the correct GFCI at all
times.
Ensure the GFCI is not tripped.
Ensure the green LE D on the nozzle is illuminated at all
times.
Call Miatech support 1-800-933-6478.
Ensure that all water lines are not touching the refrigeration
piping.
Ensure all lines are intact, and water is not leaking from any
lines or connections.
Too much
fog/water
build-up inside
case
Water spots
Excessive noise
Miatech system ON time is
too long.
Miatech system OFF time is
too short
Too much water pressure
RO Filter is clogged or
saturated
Too much air pressure
Decrease ON-time.
Increase OFF-time.
Decrease water pressure
Have RO system serviced. Call Miatech support 1-800-933-
6478.
Miatech system needs service. Call Miatech support 1-800933-6478.
37
Page 38
User Information
Start Up
See the merchandisers Data Sheet Set for refrigerant settings and defrost requirements. Bring
merchandisers down to the operating temperatures listed on the Data Sheet.
WARNING
--LOCK OUT/ TAG OUT--
To avoid serious injury or death from electrical
shock, always disconnect the electrical power
at the main disconnect when servicing or
replacing any electrical component. This
includes, but is not limited to, such items as
doors, lights, fans, heaters, and thermostats.
Load Limit
Each Merchandiser has a Load Limit. Shelf life of
perishables will shorten if Load Limit is violated.
AT NO TIME SHOULD THE MERCHANDISER
BE STOCKED BEYOND THE LOAD LIMITS
INDICATED.
DO NOT BLOCK HONEYCOMB OR AIR
RETURN GRILLE.
LOAD LIMIT
DO NOT OVERSTOCK MERCHANDISER
Load Limit
38
Page 39
User Information Cont’d
Important Information
The Q3-MV-BC service cases are easy to work,
attractive merchandising display cases capable
of maintaining superb product quality, with the installation of the proper controlling devices. These
shouldbesetaccordingtoHussmann’sspecications and combined with a properly maintained
fogging system hich will result in product life
mitigated from dehydration, shrinkage and discoloration. Below are a few guidelines to ensure
optimum performance and product life.
• Review the Case Spec Sheet and verify thermostat settings. Do not set temperature too
cold, as this causes product dehydration.
• Temperatures should be achieved by digital thermostat and suction solenoid at each
case. Do not use EPR valves, liquid line
solenoids or electronic control devices of any
kind without consulting Hussmann or Miatech
specialistrst.Thesecontrolsallowtemperature swings causing product dehydration and
excessive energy consumption.
• Defrost is controlled by the provided Danfoss
AK-CC 210 controller. See spec sheet for
derost frequency and duration.
• Clean Fogging System, see Standard Operating Procedure or reference proper system
operation manual.
• Work and rotate product - not to exceed a (4)
hour period.
• At night turn off case lights and cover product
with moistened cheesecloth or fabric towels.
• Keep meat holding box at 32°.
• Keep meat prep room refrigerated at 55°.
• Meat bloom box (if applicable) should be at
36°.
• Meat must enter case at 35° or below. Product deterioration is very rapid above 40°.
• Maintain sanitary conditions throughout the
meat holding, prep and working areas.
• Do not display product outside the load limits.
• Turn and rotate the meat. The blood which
gives the pink color works down in time which
causes surface discoloration and dehydration. When turned before this condition occurs the side is kept in good color (bloom)
condition. The meat can even be turned (3)
three and (4) four times.
• Cold coils remove heat and moisture from the
case and deposit it as frost on the coil. Thus
a defrost is required to remove this frost. Fogging system adds moisture to the case and
helps slow down the dehydration process.
The only other moisture in the case is the
product. A single level of meat in a case will
dry out faster than a fully loaded case with
two to four levels of meat.
• The colder the case, the faster the product
loses its moisture and shelf life. It is very important to maintain a constant even product
temp (see Case Spec Sheet)
WARNING
Retighten glass along hinges after leveling
and rst time case is brought to full
operating temperature!
Re-Adjustment after initial startup
In addition to verifying that the hinges for the
front glass are tightened when the case is delivered, recheck the hinges on the front glass
once the case has been brought to full operating
temperature.
Temperature can affect shapes and sizes of
materials involved and can cause changes in the
securetofthefrontglassandhinges.
39
Page 40
User Information Cont’d
CAUTION
Removing Deck Pans
Always use caution while removing deck pans
from merchandiser. Located below the deck
pans is a heating element to assist in the deforst
process. Due to the increased moisture from the
Fogging system, frost build up must be defrosted
by the heating element creating a HOT SPOT
near the front of the deck pan which if not careful could lead to injury from heating element. The
heating element will only run during defrost but
HOT SPOT will remain for some time after defrost has completed. As a safe measure always
use protective equipment to remove deck pans.
HEATING ELEMENT
UNDERNEATH DECK
PANS
Cal Rod Heater
40
Page 41
User Information Cont’d
Case Cleaning
Long life and satisfactory performance of any
equipment are dependent upon the care it receives. To insure long life, proper sanitation and
minimum maintenance costs, the merchandiser
should be thoroughly cleaned, all debris removed and interiors washed down, weekly.
WARNING
TO PREVENT INJURY ALWAYS SHUT OFF
POWER DURING CLEANING PROCESS.
Exterior Surfaces
The exterior surfaces must be cleaned with a
mild detergent and warm water to protect and
maintaintheirattractivenish.NEVERUSE
ABRASIVE CLEANSERS OR SCOURING
PADS.
Cleaning Stainless Steel Surfaces
Use non abrasive cleaning materials, and always
polish with grain of steel. Use warm water or add
a mild detergent to the water and apply with a
cloth. Always wipe dry after wetting.
Use alkaline chlorinated or non-chlorine containing cleaners such as window cleaners and mild
detergents. Do not use cleaners containing salts
as this may cause pitting and rusting of the stain-
lesssteelnish.Donotusebleach.
Clean frequently to avoid build-up of hard, stubborn stains. A stainless steel cleaning solution
may be used periodically to minimize scratching
and remove stains.
Rinse and wipe dry immediately after cleaning.
Never use hydrochloric acid (muriatic acid) on
stainless steel.
Interior Surfaces
The interior surfaces may be cleaned with most
domestic detergents, ammonia based cleaners and sanitizing solutions with no harm to the
surface.
WARNING
Glass can cause bodily damage. Check
support hinges for periodic maintenance.
When glass is open, it can cause bodily
damage, take adequate safety measures to
protect shoppers.
Cleaning Bumpers
Clean Bumpers with household spray cleaners.
Cleaning Under Merchandiser
Remove lower body panels. Use a vacuum with
a long wand attachment to remove accumulated
dust and debris from under the merchandiser.
Cleaning Coils
NEVER USE SHARP OBJECTS AROUND
COILS. Use a soft brush or vacuum brush to
clean debris from coils. Do not puncture Coils!
Donotbendns.Contactanauthorizedservice
technician if a coil is punctured, cracked, or otherwise damaged.
ICE in or on the coil indicates the refrigeration and defrost cycle is not operating properly.
Contact an authorized Service Technician to
determine the cause of icing and to make proper
adjustments as necessary. To maintain product
integrity, if not done so already, move all product
to a cooler until the merchandiser has returned
to normal operating temperatures.
41
Page 42
User Information Cont’d
Do Not Use:
• Abrasive cleaners and scouring pads, as
thesewillmarthenish.
• A hose on lighted shelves or submerge
shelves in water.
• Solvent, oil or acidic based cleaners on any
interior surfaces.
• A hose on LED Lights or any other electrical
component.
Do:
• Remove the product and all loose debris to
avoid clogging the waste outlet.
• Store product in a refrigerated area such as a
cooler during the cleaning process. Remove
only as much product as can be taken to the
cooler in a timely manner.
• First Turn off Refrigeration, then disconnect electrical power to merchandiser.
• Thoroughly clean all surfaces with soap and
hot water. Do not use steam or high pressure
water hoses to wash the interior. These will
destroy the merchandisers’ sealing causing
leaks and poor performance.
• Ensure to minimize direct contact between
fan motors and cleaning or rinse water.
• Rinsewithhotwater,butDONOTood.
Never introduce water faster than the waste
outlet can drain.
• Allow merchandiser to completely dry before
resuming operation.
• LED lights are magnetized to each shelf and
can be removed easily for any shelf cleaning.
• After cleaning has been completed, remember to restore power back to merchandiser.
WARNING
Product will be degrade and may spoil if
allowed to sit in non-refrigerated area.
42
Page 43
Troubleshooting
ProblemPossible CausePossible Solution
Case temperature is
too warm.
Case temperature is
too cold.
Condensation on
glass.
Ambient conditions may
be affecting the case
operation.
Discharge air temp is out
of spec.
Case is in defrost.Checkdefrostsettings.SeeTechnicalSpecicationssection.
Product load may be over
itslimitsblockingairow.
Coil is freezing over.Return air is blocked, make sure debris is not blocking the
Condensing coil or
evaporator coil is clogged
or dirty.
The t-stat temp is set too
low.
Ambient conditions may
be affecting the case
operation.
Ambient conditions may
be affecting the case
operation.
Inadequate air circulation. Check if air sweep fans are functioning, check electrical
There is not enough heat
providedintheairow.
There are glass gaps on
the side of the case.
Glass is not completely
shut.
Check case position in store. Is the case located near an
open door, window, electric fan or air conditioning vent that
may cause air currents? Case must be located minimum
15 Ft away from doors or windows. Cases are designed to
operate at 55% Relative humidity and a temperature of 75°F.
Check evaporator fan operation. Check electrical connections
and input voltage.
Check case position in store. Is the case located near an
open door, window, electric fan or air conditioning vent that
may cause air currents? Case must be located minimum
15 Ft away from doors or windows. Cases are designed to
operate at 55% Relative humidity and a temperature of 75°F.
Check case position in store. Is the case located near an
open door, window, electric fan or air conditioning vent that
may cause air currents? Case must be located minimum
15 Ft away from doors or windows. Cases are designed to
operate at 55% Relative humidity and a temperature of 75°F.
connections.
Check if air sweep heater is functioning, check electrical
connections.
See glass adjustment section.
Close glass correctly.
43
Page 44
Troubleshooting Cont’d
ProblemPossible CausePossible Solution
Water has pooled
under case.
Case is not draining
properly.
Frost or ice on
evaporator coil.
Lights do not come
on.
Case drain is clogged.Clear drain.
PVC drains under case
may have a leak.
Case tub has unsealed
opening.
If the case is in a lineup, case to case joint is
missing or unsealed.
Evaporator pan is
overowing(ifapplicable).
Case is not level.Level the case.
Drain screen is plugged.Clean drain screen and remove any debris.
Drain or P-trap is clogged. Clear any debris.
Evaporator fans are not
functioning.
Defrost clock is not
functioning.
Coil is freezing over.Return air is blocked, make sure debris is not blocking the
Ballast/light socket wiring. Check electrical connections. See Electrical Section and