REFRIGERATION DATA
Note: This data is based on store
temperature and humidity that does not
exceed 75°F and 55% R.H.
P4 P4E
Discharge Air °F 29 31
Evaporator °F 21 24
Unit Sizing °F 19 22
Btu/hr/ft** P4 P4E
Parallel 1535 1455
Conventional 1650 1585
**For all refrigeration equipment other than
Husssmann, use conventional BTU values.
DEFROST DATA
P4 P4E
Frequency (hr) 66
Defrost Water(lb/ft/day)99
(±15% based on case configuration and
product loading.
O
FFTIME P4 P4E
T emp Term °F 48°F 48°F
Failsafe Minutes 30 30
ELECTRIC OR GAS Not Recommended
Standard Defrost Thermostat
Close on rise: close 48°F – open 33°F
CONVENTIONALCONTROLS
Low Pressure Backup Control
P4 P4E
CI/CO** 14/4°F 17/7°F
Indoor Unit Only, Pressure Defrost
Termination** 48°F
**Use a Temperature Pressure Chart to
determine PSIG conversions.
PHYSICALDATA
Merchandiser Drip Pipe (in.) 1 1/2
Liquid Line (in.)
3
/8
Suction Line (in.)
7
/8
Estimated Charge (lbs)***
P4 P4E
8 ft 2.7 3.2
12 ft 3.9 4.5
***This is an average for all refrigerant
types actual refrigerant charge may vary
by approximately half a pound.
Length (in.) Added to Lineup
by Each End or Insulated
Partition 1
1
/
2
Impact P4
All Produce
Multi-deck, 2 Display Levels
Dimensions shown as inches and (mm).
NSF Certification
These merchandisers are manufactured to meet ANSI /National
Sanitation Foundation (NSF ®) Standard #7 requirements.