Hussmann MZ3-S Installation & Operation Manual

Manual
Installation
& Operation
/CHINO
MZ3-S
MULTI-ZONE REFRIGERATED, SELF SERVICE,
SELF CONTAINED
MZ3-S
MULTI-ZONE REFRIGERATED, SELF SERVICE,
SELF CONTAINED
P/N IGSS-MZ3-S-0909
INSTALLATION & OPERATION GUIDE
General Instructions
This equipment is to be installed to comply with the applicable NEC, Federal, State , and Local Plumbing and Construction Cod e h a ving jur i s d i ction.
IGSS-MZ3-S-0909
Table of Contents
General Instructions.....................................................2
Cut and Plan Views ......................................................3
Installation .....................................................................4
Location ..................................................................................... 4
Uncrating the Stand ................................................................... 4
Exterior Loading ......................................................................... 4
Leveling .....................................................................................4
Plumbing .......................................................................4
Self Contained Cases ................................................................ 4
Installing Condensate Drain (When Applicable) ........................ 4
Refrigeration .................................................................5
Refrigerant Type ........................................................................ 5
Control Settings - Remote ......................................................... 5
Access to TX Valves and Drain Lines ........................................ 5
Electronic Expansion Valve (Optional) ....................................... 5
Thermostatic Expansion Valve Location .................................... 5
Expansion Valve Adjustment ..................................................... 5
Measuring the Operating Superheat.......................................... 5
Omni-STAT Location .................................................................. 5
Refrigeration Data ...................................................................... 6
Defrost Data ............................................................................... 6
Physical Data ............................................................................. 6
Glycol Requirements ................................................................. 6
Electrical........................................................................7
Wiring Color Code ..................................................................... 7
Electrical Circuit Identication .................................................... 7
Electrical Service Receptacles (When Applicable) .................... 7
Attachment Plugs ....................................................................... 7
Field Wiring and Serial Plate Amperage .................................... 7
Ballast Location .........................................................................7
User Information ........................................................... 8
Stocking ..................................................................................... 8
Important Steps ........................................................................8
Case Cleaning ........................................................................... 8
Cleaning Glass and Mirrors ....................................................... 9
Plexiglass and Acrylic Care ....................................................... 9
Cleaning ..................................................................................... 9
Antistatic Coatings ..................................................................... 9
Maintenance .................................................................. 9
Replacing Fluorescent Lamps ................................................... 9
Evaporator Fans ........................................................................ 9
Copper Coils .............................................................................. 9
Tips and Troubleshooting .......................................................... 9
Stainless Steel Cleaning and Care .......................................... 10
Wiring Diagram ........................................................... 11
Piping Schematic........................................................13
Appendices ................................................................14
Appendix A. - Temperature Guidelines .................................... 14
Appendix B. - Application Recommendations .......................... 14
Appendix C. - Field Recommendations ................................... 14
Appendix D. - Recommendations to user ................................ 15
This Booklet Contains Information on: MZ3 Self Contained:
The MZ3 is a multi-zone, self-service, self-contained, refrigerated merchandiser which contains low and medium temperature refrigerated zones and an additional dry shelf zone to accommodate multiple product refrigeration requirements. For low temperature needs, the MZ3 uses Hussmann's FMSS-LT case and for medium Temperature needs, the MZ3 uses Hussmann's RCD case. Both are combined in a convenient single case package.
SHIPPING DAMAGE
All equipment should be thoroughly examined for shipping damage before and during unloading. This equipment has been carefully inspected at our factory and the carrier has assumed responsibility for safe arrival. If damaged, either apparent or concealed, claim must be made to the carrier.
APPARENT LOSS OR DAMAGE
If there is an obvious loss or damage, it must be noted on the freight bill or express receipt and signed by the carrier’s agent; otherwise, carrier may refuse claim. The carrier will supply necessary claim forms.
CONCEALED LOSS OR DAMAGE
When loss or damage is not apparent until after equipment is uncrated, a claim for concealed damage is made. Make
request in writing to carrier for inspection within 15 days, and retain all packaging. The carrier will supply inspection report and required claim forms.
SHORTAGES
Check your shipment for any possible shortages of material. If a shortage should exist and is found to be the responsibility of Hussmann Chino, notify Hussmann Chino. If such a shortage involves the carrier, notify the carrier immediately, and request an inspection. Hussmann Chino will acknowledge shortages within ten days from receipt of equipment.
HUSSMANN CHINO PRODUCT CONTROL
The serial number and shipping date of all equipment
has been recorded in Hussmann’s les for warranty and
replacement part purposes. All correspondence pertaining to warranty or parts ordering must include the serial number of each piece of equipment involved, in order to provide the customer with the correct parts.
The Hussmann warranty is printed on the back of
this guide.
Keep this booklet with the case at all times for future reference.
/CHINO
A publication of Hussmann® Chino 13770 Ramona Avenue • Chino, California 91710 (909) 628-8942 FAX (909) 590-4910 (800) 395-9229
2
Rev. 0909
83 3/8"
12 3/4"
33 1/2"
54"
64"
71"
6"
20 1/4"
18 1/4"
16 1/4"
37 1/4"
30 7/8"
27 5/8"
19 3/4"
10 7/8"
9 3/8"
9 3/8"
1 5/8"
1 7/8"
1 7/8"
1 5/8"
50 3/8"
47 1/4"
37 1/4"
6"
ELECTRICAL CONNECTION 2 POWER CORDS
1. NEMA 5-15P
2. NEMA L5-20P
MZ3-4S
PLAN VIEW
RCD
FMSS-LT
Condensing
Unit
MZ3
SELF SERVICE MERCHANDISER
Cut and Plan Views
3
Installation
It is the contractor's responsibility to install
case(s) according to local construction and
health codes.
Location
The refrigerated merchandisers have been designed for use only in air conditioned stores where temperature and humidity are maintained at or below 75°F and 55% relative humidity. DO NOT allow air conditioning, electric fans, ovens, open doors or windows (etc.), to create air currents around the merchandiser, as this will impair its correct operation.
Product temperature should always be maintained at a constant and proper temperature. This means that from the time the product is received, through storage, preparation and display, the temperature of the product must be controlled to maximize life of the product.
Uncrating the Stand
Place the xture as close to its permanent position as
possible . Remove the top of the crate. Detach the walls from each other and remove from the skid. Unbolt the case
from the skid. The xture can now be lifted off the crate
skid. Lift only at base of stand!
Exterior Loading
These models have not been designed to support excessive external loading. Do not use the lower surfaces, glass,
or shelves as a stepping ladder. Do not stand in Lower cases to gain access to the upper portion of the case. Do not stand on any opening in the side panels. Failure
to observe these warnings could result damage to the case and serious personal injury.
IGSS-MZ3-S-0909
Leveling IMPORTANT! It is imperative that cases be leveled from front to back and side to side. A level case is necessary to insure proper operation, water drainage, glass alignment, and operation of the hinges supporting the glass. Leveling the case correctly will solve most hinge operation problems.
NOTE: A. To avoid removing concrete ooring, begin lineup
leveling from the highest point of the store oor.
B. When wedges are involved in a lineup, set them rst.
All cases were leveled and joined prior to shipment to
insure the closest possible t when cases are joined in the eld. When joining, use a carpenters level and shim legs
accordingly. Case must be raised correctly, under legs where support is best, to prevent damage to case.
1. Check level of oor where cases are to be set. Determine the highest point of the oor; cases will
be set off this point.
2. Level and set the case. Case must be raised under legs where support is best to prevent damage to case. Internal bracing may be removed at this time.
Plumbing
Self Contained Cases
MZ3 self-contained cases do not require that a condensate drain be connected because all of the condensate is contained by the condensate pan. However it is required that the condensate pan be cleaned on a regular basis. Additionally, the condensing unit should be cleaned at the same time using a light, non-abrasive brush to remove
accumulated dust. If a lter is installed, it should be cleaned
at this time as well.
Installing Condensate Drain (When Applicable)
Poorly or improperly installed condensate drains can seriously interfere with the operation of this refrigerator, and result in costly maintenance and product losses. Please follow the recommendations listed below when installing condensate drains to insure a proper installation:
1 . Never use pipe for condensate drains smaller
than the nominal diameter of the pipe or P-TRAP supplied with the case.
2 . When connecting condensate drains, the P-TRAP
must be used as par t of the condensate drain to prevent air leakage or insect entrance. Store
plumbing system oor drains should be at least 14"
off the center of the case to allow use of the P-TRAP pipe section. Never use two water seals in series in any one line . Double P-TRAPS in series will cause a lock and prevent draining.
3 . Always provide as much down hill slope (“fall”) as
possible; 1/8" per foot is the preferred minimum.
PVC pipe, when used, must be supported to
maintain the 1/8" pitch and to prevent warping.
4 . Avoid long runs of condensate drains. Long runs
make it impossible to provide the “fall” necessary for good drainage.
5 . Provide a suitable air break between the ood rim of
the oor drain and outlet of condensate drain. 1" is
ideal.
4
Rev. 0909
Plumbing (Cont'd)
6 . Prevent condensate drains from freezing:
a. Do not install condensate drains in contact with
non-insulated suction lines. Suction lines should be insulated with a nonabsorbent insulation
material such as Armstrong’s Armaex.
Refrigeration
Refrigerant Type
The standard refrigerant will be R-404 unless otherwise
specied on the customer order. Check the serial plate on
the case for information. Piping for more than one case on a condensing unit is run
underground with either common suction and liquid lines from the machine room or individual suction and liquid lines joined together in the machine room.
Refrigeration Lines
LIQUID SUCTION 3/8” O.D. 5/8” O.D.
NOTE: The standard coil is piped at 5/8” (suction); however,
the store tie-in may vary depending on the number of coils and the draw the case has. Depending on the case setup, the connecting point in the store may be 5/8”, 7/8”, or 1 1/8”. Refer to the particular case you are hooking up.
Refrigerant lines should be sized as shown on the refrigeration legend furnished by the store.
Install P-TRAPS (oil traps) at the base of all suction line vertical risers.
Pressure drop can rob the system of capacity. To keep the pressure drop to a minimum, keep refrigerant line run as short as possible, using the minimum number of elbows. Where elbows are required, use long radius elbows only.
Control Settings - Remote
See the MZ3-S Technical Data Sheet for the appropriate settings for your merchandiser. Maintain these parameters to achieve near constant product temperatures. Product
temperature should be measured rst thing in the morning,
after having been refrigerated overnight. Defrost times should as directed in the MZ3-S Technical Data Sheet. The number of defrosts per day should never change. The duration of the defrost cycle may be adjusted to meet conditions present at your location.
Control Settings-self Contained
All functions are controlled by Omni-Stat Controllers. See MZ3-S Technical Data Sheet for proper temperature and defrost settings.
Access to TX Valves and Drain Lines
MECHANICAL - Remove product from end of case. Remove product racks. Remove refrigeration and drain access panels (labeled). TX valve (mechanical only) and drain are located under each access panel at end of the case.
b. Where condensate drains are located in dead
air spaces (between refrigerators or between a refrigerator and a wall), provide means to prevent freezing. The water seal should be insulated to prevent condensation.
ELECTRONIC - The Electronic Expansion valve master and slave cylinder(s) are located within the electrical access panel(s).
Electronic Expansion Valve (Optional)
A wide variety of electronic expansion valves and case controllers can be utilized. Please refer to EEV and controller manufacturers information sheet. Sensors for electronic expansion valves will be installed on the coil inlet, coil outlet, and in the discharge air. (Some supermarkets require a 4th sensor in the return air). Case controllers will be located in the electrical raceway or under the case.
Thermostatic Expansion Valve Location
This device is located on the same side as the refrigeration stub. An Alco balanced port expansion valve model is furnished as standard equipment, unless otherwise
specied by customer.
Expansion Valve Adjustment
Expansion valves must be adjusted to fully feed the evaporator. Before attempting any adjustments, make sure the evaporator is either clear or very lightly covered with
frost, and that the xture is within 10° F of its expected
operating temperature.
Measuring the Operating Superheat
1. Determine the suction pressure with an accurate pressure gauge at the evaporator outlet.
2. From a refrigerant pressure temperature chart, determine the saturation temperature at the observed suction pressure.
3. Measure the temperature of the suction gas at the thermostatic remote bulb location.
4. Subtract the saturation temperature obtained in step No. 2 from the temperature measured in step No. 3. The difference is superheat.
5. Set the superheat for 5°F - 7° F
Omni-STAT Location
The Omni-Stat case controllers are located in the access area in the right end panel. To gain access, remove the right louvered panel. Please refer to the MZ3-S Technical Data Sheet for the proper recommended temperature and defrost settings.
5
ELECTRICAL CONNECTION 2 POWER CORDS
1. NEMA 5-15P
2. NEMA L5-20P
MZ3-4S
PLAN
RCD
FMSS-LT
Condensing
Unit
MZ3
SELF SERVICE MERCHANDISER
OMNI-STAT TEMPERATURE CONTROLLER & BALLASTS
OMNI-STAT TEMPERATURE CONTROLLER & BALLASTS
ACCESS COVER
FRONT
Refrigeration (Cont'd)
IGSS-MZ3-S-0909
Refrigeration Data
Note: This data is based on store temperature and humidity
that does not exceed 75F and 55% R.H.
Discharge Air (F) 28
Evaporator (F) 20
Note: Not recommended to control temp by regulating coil
temp allow T-STAT to cycle and control temp.
Btu/hr/ft*
Parallel 400 Conventional 460 Low Temp
Discharge Air (F) -10
Evaporator (F) -20
Note: Not recommended to control temp by regulating coil
temp allow T-STAT to cycle and control temp.
Btu/hr/ft*
Parallel 600 Conventional 690
*For all refrigeration equipment other than Hussmann, use conventional Btu values.
Defrost Data Frequency Hrs 8
OFFTIME Temp Term °F 54 Failsafe Minutes 30 ELECTRIC or GAS Not Recommended
Physical Data
Merchandiser Drip Pipe (in.) 1½ Merchandiser Liquid Line (in.) 3/8 Merchandiser Suction Line (in.) 5/8 Estimated Charge (lb)***
4ft 1.2
5ft 1.5
6ft 1.8
*** This is an average for all refrigerants types. Actual refrigerant charge may vary by approximately half a pound.
Glycol Requirements
GPM PSI
N/A N/A
6
Loading...
+ 11 hidden pages