Hussmann MBC, MBCR Installation And Service Instructions Manual

Page 1
January 2006
INSTALLATION & SERVICE
INSTRUCTIONS
FOR
MBC MULTI-DECK GONDOLA INSERT
First Call for help (US and Canada):
1-800-922-1919
Soporte Tècnico y Asistencia (Mèxico):
01-800-522-1900
For a Service Network Locator and other Information visit us at
www.hussmann.com
select Worldwide Locations
HUSSMANN - GLOVERSVILLE
P/N OII – MBC
Page 2
SETTING MBC TEMPERATURE CONTROL
1. Hold down top button until R-1 appears
2. Go to R-5, push both buttons, set to F, push both again
3. Go to D=3, push both buttons, set to 6, push both again
4. Go to D-4, push both buttons, set to 30, push both again
5. Go to R-1, push both buttons, set to 8, push both again
6. Go to R-2, push both buttons, set to 45, push both again
7. Go to R-3, push both buttons, set to 30, push both again
Wait for actual temperature to appear. Push both buttons and set to 32.0. Push both again. Push both a third time and let flash until it stops flashing.
2
Page 3

TABLE OF CONTENTS

Model Description Page 4 Application Page 4 Inspection upon Receipt Page 4 Shipping Page 4
Leveling Page 5 Location Page 5 Rear Close-Off Panel Page 5 Condensate Removal – Self Contained Page 5 Installing drip piping Remotes Page 5
Exterior loading, Interior loading Page 6 Care and Cleaning Page 6 Electrical Page 7
Refrigeration, Expansion Valve Adjustment, Refrigerant Page 7-8
Multiplexing, Line Sizing, Oil Traps, Pressure Drop Page 8 Insulation Page 9 Controls and Adjustments Page 9 Temperature Controls Page 10 EKC Controls and Info Page 13 Controller Application setting parameters (if needed) Page 14
Warranty and Parts Information Page 11 Compressor Replacement Procedure Page 11
Page 4
MODEL DESCRIPTION –
This instruction manual covers the mer­chandisers listed below. All models are available in 36” or 48” lengths.
MBC – Self-Contained Self Service Beverage Case
MBCR – Remote Self Service Beverage Case – Remote case requires a separate condenser unit connection.
APPLICATION -
The MBCR and MBC refrigerated mer­chandisers are designed for use only in air condi­tioned stores where temperature and humidity are maintained at or below 75ºF dry bulb tem­perature and 55% relative humidity.
These Beverage Cases are intended for the storage and display of non -potentially hazardous, bottled or canned products only.
INSPECTION UPON RECEIPT –
All equipment should be thoroughly exam­ined for shipping damage before and during un­loading. This equipment has been carefully i n­spected at our factory and the carrier has as­sumed responsibility for safe arrival.
If damage, either apparent or concealed, is found a claim must be submitted to the ca rrier.
Apparent Loss or Damage – If there is ob­vious loss or damage, it must be noted on the freight bill or express receipt and signed by the carrier’s agent; otherwise, the carrier may refuse the claim. The carrier will supply necessary forms.
Concealed Loss or Damage – When loss or damaged is not apparent until after equip­ment is uncrated, a claim for concealed damage is made.
Upon discovering damage, make a re­quest in writing to the carrier for inspection within 15 days and retain all packing. The ca r­rier will supply the inspection report and r e­quired claim forms.
SHIPPING –
Move the fixture as close as possible to its permanent location and then remove all crating. Check for damage before discarding packing. Remove all separately packed accesso­ries such as kits and shelves.
LEVELING –
Merchandisers must be installed level to ensure proper operation of the refrigerant sy s­tem and to ensure proper drainage of defrost water.
Levelers are shipped with the case and should be installed in the same holes that the skid bolts were installed in.
Place pry-bar under metal base and lift. DO NOT LIFT END PANEL. Turn leveler, with
wrench clockwise to raise, and counter clock­wise to lower. Repeat process with other level­ers until case is level.
NOTE: To avoid removing concrete flooring, begin lineup leveling from the highest point of the store.
4
Page 5
LOCATION –
Like other open merchandisers, these are sensitive to air disturbances. Air currents pas s­ing around merchandisers will seriously impair their operation. Do NOT allow air conditioning, electric fans, open doors or windows, etc. to cre­ate air currents around the merchandisers.
REAR CLOSE- OFF PANEL –
To perform electrical and refrigeration work, remove the rear closure panel by removing
the sheet metal screws. Replace when work is complete.
NOTE: Self Contained Models - Do note block the vent openings on the rear closure panel. These allow intake and exhaust air for the con­densing unit. Vents only appear on self­contained models.
CONDENSATE REMOVAL – Self Contained
On the self contained merchandisers the waste outlet is centrally located and accessible from the rear of the case.
The condensate water from the evaporator drains out through the bottom of the evaporator
compartment into the condensing unit area into a heated condensate pan.
The pan has a float that activates the heater when sufficient water is in the pan.
INSTALLING DRAIN PIPING – Remotes
Poorly or improperly installed drip pipes can seriously interfere with the merchandisers’ operation and result in costly maintenance and product losses. Please follow the recommenda­tions listed here when installing drip pipes to en­sure proper installation.
1. Never use drip piping smaller than the nominal diameter of the pipe or water seal supplies with the merchandiser.
2. When connec ting drip piping, the “water seal” must be used as part of the drip pip­ing to prevent air leakage or insect e n­trance. Never use two water seals in series in any one drip pipe. Double water seals in series will cause an air lock and prevent draining.
3. Pitch the drip piping in the direction of flow. There should be a minimum pitch of 1/8” per foot
4. Avoid long runs of drip piping. Long runs make it impossible to provide the pitch necessary for good drainage.
5. Provide a suitable air break between flood rim of the floor drain and outlet of drip pipe.
6. Prevent drip pipes from freezing:
a. Do not install drip pipes in contact
with insulated suction lines. Suction lines should be insulated with a nonab-
sorbent insulation material.
b. When drip pipes are located in dead
air spaces, such as between merchan­disers or between a merchandiser and a store wall, provide means to prevent freezing.
5
Page 6
EXTERIOR LOADING –
Do NOT walk on top of merchandiser or damage to the merchandiser and serious personal injury could occur. They are not structurally de­signed to support excessive external loading such as the weight of a person.
INTERIOR LOADING –
In order to maximize product life, main­tain a constant and proper product temperature from the time the product is received through storage, preparation and display.
Products should not be placed in merchan­disers until all refrigeration controls have been adjusted and merchandisers are at proper ope r­ating temperature. Again, air discharge and re­turn air flue MUST be unobstructed at all times to provide proper refrigeration.
CARE and CLEANING –
Long life and satisfactory performance of any equipment is dependent upon the care it re­ceives. To ensure long life, proper sanitation and minimum maintenance costs, merchandisers should be thoroughly cleaned, all d ebris removed and the interiors washed down, weekly.
Exterior Surfaces –
The exterior surfaces must be cleaned with a mild detergent and warm water to protect and maintain their attractive finish. NEVER use abrasive cleansers or scouring pads.
CAUTION – Shut power off during cleaning.
DO NOT USE –
Mineral oil based solutions, as these will di s-
solve the butyl sealants used in the construc­tions of the merchandisers.
Abrasive cleansers and scouring pads, as
these will mar the finish.
DO –
Remove the product and all loose debris
to avoid clogging the waste outlet.
Thoroughly clean all surfaces with soap
and hot water. Do NOT use steam or high water pressure hoses to wash the interior. These will destroy the mer­chandisers’ sealing causing leaks and poor performance.
Rinse with hot water but do NOT flood.
Never introduce water faster than the waste outlet can remove it.
NOTE – Self-contained Models
The evaporator pan must be moni­tored for overflow conditions. Provide drainage if necessary. After cleaning and rinsing, purge the pan of any standing w a­ter.
Care should be taken to minimize direct
contact between fan motors and cleaning or rinse water.
Allow the merchandisers to dry before
resuming operation.
At the back of this booklet there is a supple­ment for sealing and cleaning of this unit. Please read for further instructions.
6
Page 7
ELECTRICAL –
Condensing
Self-Contained Model Installation – Me r-
chandisers need only to be connected to a 120V / 60 hz electrical supply., and are sup­plied with a 20 amp cord.
Post Construction Clean-up – After the first
two weeks of a major store remodel or new store operation, the grill should be removed and the condensing unit and condenser face cleaned due to the accumulated dirt and de­bris generated during construction.
Remote Model Installation – Connections –
All wiring must be in compliance with NEC and local codes. Electrical connections for refrigerated models are made in the electri­cal box on the back of the case behind the rear close-off panel.
Field Wiring – Field wiring must be sized
for components amperes stamped on the se­rial plate. Actual ampere draw may be less than specified. Always check the serial plate.
Evap Fan Light Condensate
Model Amps Amps Pan Amps Unit Amps Circuit
Refrigerant ( * ) R-22 R-404A
MBC24-3661/74 0.38 0.15 5.0 10 9.2 16 14 20 MBC24-3684 0.38 0.35 5.0 10 9.2 16 14 20 MBC243661R/74R 0.38 0.15 N/A N/A N/A 15 15 15 MBC243684R 0.38 0.35 N/A N/A N/A 15 15 15
MBC24-4861/74 0.57 0.20 5.0 10 10.1 16 16 20 MBC24-4884 0.57 0.44 5.0 10 10.1 16 16 20 MBC244861R/74R 0.57 0.20 N/A N/A N/A 15 15 15 MBC244884R 0.57 0.44 N/A N/A N/A 15 15 15
Minimum
Amps
R-22 R-404A
Fuse Amps
Check Serial Plate for Refrigerant type and amount used. Self-Contained cases were changed from R-22 to R-404a starting September, 2001.
REFRIGERATION – Expansion Valve Adjustment
Expansion valves must be adjusted to fully feed the evaporator. To achieve the proper setting, the merchandiser must first have been in operation long enough to have reached the approximate intended operating temperature. Air flow should not be restricted by heavy frost formation on the evaporator. Adjust valves as follows:
7
Page 8
Attach two sensing probes (either thermocouple or thermistor) to the evaporator. One under the clamp holding the expansion valve bulb and the other securely taped to the evaporator inlet line as close to the coil as practical.
Some “hunting” of the expansion valve is normal. The valve should be adjusted so that during the hunting the greatest difference between the two probes is 3º-5ºF for remote merchandisers. With this adjustment, during a portion of the hunting the temperature difference between the probes will be le ss than 3ºF (at times as low as 0ºF). Make adjustments of no more than one-half turn of the valve stem at a time and wait for at least 15 minutes before rechecking the probe temperature and making further adjustments.
Self-contained merchandiser should be adjusted using the same technique with a temperature difference of 6º to 8ºF.
REFRIGERANT – The correct type of refrigerant will be stamped on each merchandiser’s serial plate
located inside the merchandiser.
Refrigerant Piping – (Remote Cases) Connection Sizes Liquid Line 1/4” OD
Suction Line 3/8” OD The refrigerant line connections are behind the rear close-off panel, underneath the
drain tub, on the left hand end of the merchandiser as viewed from the rear.
After connections have been made, seal this outlet thoroughly. Seal both inside and outside. We recommend using an aerosol dispensed urethane type of insulation.
Multiplexing -
Piping of remoted merchandisers operating on the same refrigeration system may be run from merchandiser to merchandiser through the end frame saddles provided for this purpose
DO NOT RUN REFRIGERANT LINES THROUGH MERCHANDISERS THAT ARE NOT ON THE SAME REFRIGERANT SYSTEM - as this may result in poor refrigeration control and compressor failure.
Line Sizing –
Refrigerant line should be sized as shown on the refrigeration legend that is furnished for the store (not furnished by Hussmann). If a legend has not been furnished, refer to Hussmann Application Engineering Manual for guidance.
8
Page 9
Oil Traps –
P-Traps (oil traps) must be installed at the base of all suction line vertical risers.
Pressure Drop – Pressure drop can rob the system of capacity. To keep the pressure drop to a
minimum, keep the refrigerant line run as short as possible using a minimum number of elbows. Where elbows are required, use long radius elbows only.
Insulation –
The suction and liquid lines should be clamped or taped together and insulated for a minimum of 30’ from the merchandiser. Additional insulation is recommended wherever condensation drippage is objectionable.
CONTROLS and ADJUSTMENTS –
The object of the controls and settings listed in this section is to maximize product shelf life.
TEMPERATURE CONTROLS – Discharge Air Temperature F 32
Evaporator Temperature F 20 Refrigerant Controls Thermostat Cut-out F 32 Defrost Controls Frequency (Qty per day) 4 Length of defrost (min) 30
ELECTRONIC CONTROLLERS – On page 13 at the end of this booklet.
The control is factory set and should not need Field adjustment. If they do, use the Quick Guide on the next page for reference.
SHELVING -
The MBC models come equipped with shelves. They are adjustable on one inch increments. When loading the shelves with product, they should be loaded so that the product does not extend over the front edge of the shelf. Product loaded over the edge will interfere with air circulation in the cabinet. It is also desirable to leave a small space between the rear interior wall and the product on the shelves to allow air to enter the cabinet interior through the perforations in the rear wall.
9
Page 10
The shelves are rated for 130 pounds each load capacity. When installing the shelves, first install the shelf support bracket at the desired height. Place the rear of the bracket in the desire slot. Raise the front of the bracket towards the rear of the cabinet. Once the ends are in the slot, rotate the bracket forward locking it in place. Place the shelf on the bracket. Load the product. The shelves are not to be slanted. They must remain in a horizontal position.
QUICK GUIDE REFERENCE – At the end of the booklet on page 14 Controller application setting parameters
Settings and read-off parameters Parameter
Codes
Temperature controller, Temperature Thermostat
Differential r01 Max. limitation of set temperature r02 Min. limitation of set temperature r03 Adjustment of temperature indication r04 Temperature unit (ºC/ºF) r05
Defrost Interval between defrost starts d03 Max. defrost duration d04 Temperature alarm delay after defrost d11 Delay of display view after defrost stop d12
10
Page 11
Fault code display Fault in controller E1 Disconnected case sensor E2 Short-circuited case sensor E3
WARRANTY AND PARTS INFORMATION
IMPORTANT – Please read carefully to assure prompt and accurate service.
ORDERING PARTS REPLACEMENT –
Contact your nearest Hussmann Distributor.
Always specify model and serial number of cabinet.
If correct part number is not know, give a clear description of part itself and its function in the cabinet or remote unit.
Same as first three items in Ordering Replacement Parts Procedure.
Give original installation date of cabinet and, if possible, forward a copy of the original invoice or delivery receipt.
All shipments of in-warranty replacement parts will be invoiced from the factory until such time as the defective part is returned and proved to be defective by our Quality Control Department.
Contact your Hussmann Distributor for instructions on returning in-warranty parts.
Warranty parts must be returned to the factory within 30 days of date of failure to assure proper disposition.
Lack of any of the above information may result in the shipment of the wrong part, or a delay in shipment.
COMPRESSOR REPLACEMENT PROCEDURE –
Replacement compressors will not be shipped from the Hussmann factory. They may be obtained from you nearest Copeland Wholesaler.
Your wholesaler will replace, free of charge, any compressor found to be defective within twelve months of installation, not to exceed twenty months from the date of manufacture – as determined by the compressor serial number on the compressor serial plate.
11
Page 12
For any defective compressor beyond the twelve or twenty month time period, a salvage value credit will be given too partially offset the invoice for the replacement.
To obtain reimbursement forward to : Hussmann Corporation 140 East State Street Gloversville, NY 12078 the following information:
The cabinet model and serial number
A copy of the wholesaler’s invoice.
12
Page 13
Page 14
Page 15
Page 16
MAIN POWER HARNESS TO TOP OF CASE
ELECTRICAL BOX
COMPRESSOR
HIGH PRESSURE SWITCH
GRN
BLK
WHT
LOW PRESSURE SWITCH
115V,5 AMP CONDENSATE PAN
NOTE: 2 FANS ON MBC 36 WIDE CASES
WHT
BLU
WHT
EVAPORATOR FANS
WHT
WHT
BLK
GRN
BLK
GRN
BLK
YELLOW
RED
GRN
WHT
GRN
BLU
TEMP PROBE
BLK
GRN
BLK
GRN
BLU
GRN
BLK
GRN
YELLOW
RED
WHT
BLK
WHT
BLK
WHT BLK
WHT
GRN
10
BLK
24V TRANSFORMER
BLK BLK
BLK
WHT
BLU
BLK
A1 L1
T1
BLK
L2
T2
WHT
5
WHT
4
9
3
8
2
7
1
6
BLK
GRN
WHT
TERMINAL BLOCK & CONTACTOR
WHT
A2
WHT
BRN BRN
BLK
BLK
8 9
1 2
6 7
BRN
BRN
DANFOSS
CONTROLLER
WIRING DIAGRAM FOR MODELS- ALL SELF-CONTAINED MBC'S
115V 60HZ 1 PH
20 AMP POWER CORD
SHEET 1 OF 3 SEE SHEET 2 & 3 FOR LIGHTS
REV EO # REV DATE REV BY
5256-REV A
APPROVED BY
-REROUTED POWER CORD FROM TERM BLOCK TO CONTACTOR AND WIRES FROM CONTACTOR TO TERMINAL BOARD T1 & T2
-
-
-
-
09-10-03 JJH
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
5256-REV A
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JJH
04/20/2001
SCALE
SHEET #
INCHES
1 OF 1
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2213 A
Page 17
UPPER WIRE BALLAST RACEWAY ( 1 LAMP BALLAST)
WHT
(SEE SHEET 3 FOR OPTIONAL TOP SIGN LIGHT)
LIGHT SWITCH (PUSH BUTTON)
RED
BLUE BLUE
RED
BLK GRN
WHT
SINGLE LAMP BALLAST
RED
BLUE
POWER SWITCH
INTERIOR CASE LIGHT
BLUE BLUE
RED RED
GRN
BLK
BLK
JUMPER
RED RED
GRN
BLUE
BLK
BLK
BLUE
BLUE
8 POSITION PLUG
8 POSITION CAP
BLK
RED
BLUE
BLUE
BLUE
RED
RED
RED
RED
GRN
GRN
GRN
BLUE
WHT
BLK
4 POSITION PLUG 4 POSITION CAP
GRN
BLUE
WHT
BLK
INNER LIGHT FIXTURE ASSY
WIRING DIAGRAM FOR MODELS-MBC-24 X 36 X 61 & 74 MBC-24 X 48 X 61 & 74
SHEET 2 OF 3
REV EO # REV DATE REV BY
5256-REV A
APPROVED BY
-REROUTED POWER CORD FROM TERM BLOCK TO CONTACTOR AND WIRES FROM CONTACTOR TO TERMINAL BOARD T1 & T2
-
-
-
-
09-10-03 JJH
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
5256-REV A
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JJH
04/20/2001
SCALE
SHEET #
INCHES
1 OF 1
POWER HARNESS FROM ELEC BOX
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2213 A
Page 18
WIRING DIAGRAM FOR MODELS-MBC-24 X 36 X 84 MBC-24 X 48 X 84
UPPER WIRE BALLAST RACEWAY (2 LAMP BALLAST)
WHT
UPPER SIGN LIGHT
GRN
BLUE
BLUE RED
RED
BLK
GRN
WHT
BLUE
TO CASE POWER FEOM ELEC BOX 4 POSITION PLUG
LIGHT SWITCH (PUSH BUTTON)
RED
BLUE
RED
GRN
BLUE
BLUE BLUE
YEL YEL RED RED
2 LAMP BALLAST
BLK GRN WHT
GRN
BLK
RED
YEL
BLK
BLUE
BLUE
BLK
BLUE
8 POSITION PLUG
INTERIOR LIGHT FIXTURE
RED
BLUE
POWER SWITCH
INTERIOR CASE LIGHT
BLK
JUMPER
RED RED
GRN
SHEET 3 OF 3
REV EO # REV DATE REV BY
5256-REV A
APPROVED BY
-REROUTED POWER CORD FROM TERM BLOCK TO CONTACTOR AND WIRES FROM CONTACTOR TO TERMINAL BOARD T1 & T2
-
-
-
-
09-10-03 JJH
-
8 POSITION CAP
BLUE
RED
BLK
RED
RED
GRN
BLUE
BLUE
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
5256-REV A
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JJH
04/20/2001
SCALE
SHEET #
INCHES
1 OF 1
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2213 A
Loading...