Hussmann LBN, LBN-10, LBN-4, LBN-5, LBN-6 Installation And Service Instructions Manual

...
Page 1
January 2006
INSTALLATION & SERVICE
INSTRUCTIONS
FOR
LBN MODELS
Low Temperature – Self Contained M erchandiser
For
First Call for help (US and Canada):
1-800-922-1919
Soporte Tècnico y Asistencia (Mèxico):
01-800-522-1900
For a Service Network Locator and other Information visit us at
www.hussmann.com
select Worldwide Locations
HUSSMANN - GLOVERSVILLE
P/N OII – LBN
January 2006
Page 2

TABLE OF CONTENTS

Page Location – Clearance Initial Set-Up Skid 4 Leveling Sealing 5 Access Panel Removal 5 Compressor 5 Electrical Connections 5 Serial Plate Information 6 Start – Up and Loading 6 BTU’s – Electrical – Dimensions 7
General Upkeep and Cleaning 8 Routine Maintenance 8
Operation and Maintenance Power Switch 10 Temperature Control 10 Thermometer 10 Electrical Box 10 Defrost Time Clock 11 Defrost Thermostat 11 Defrost Heater Replacement 12 Lighting 13 Condensate Heaters 13 End Panel Heaters 13 Front Glass Heater and Replacement Procedure 14 Nose Heater 14 Condensate Heater Limit Thermostat 14 Refrigeration 15 Leak Testing 15 Evacuation 15 Operational Data 16 Refrigerant Control 16 Crankcase Pressure Regulator 16
Trouble Shooting 18 Light Problems and Solutions 20
2
Page 3
TABLE OF CONTENTS
Con’t
Page Accessories & Options Countertop 21 Stainless Steel Top 21 Superstructure w/Lighted Canopy 21 Superstructure w/o Lighted Canopy 21 Product Shelf Kit 21 Bag Rack 21 Dial Thermometer 22 Lid Lock Kit 22 Caster Kit 22 Novelty Basket 22 Warranty Ordering Replacement Parts 22 Warranty Parts Procedure 22 Compressor Replacement Procedure 23 Internal Leak Warranty Policy 23 Electrical Components Replacement List 25
3
Page 4
The LBN series are low temperature, self-contained cabinets designed for pre-packaged ice cream, ice cream novelties, and frozen food at below freezing temperatures. Design features include non-heated glass lids; efficient foamed in place non-CFC insulation, interior mirror reflectors, front-air discharge condensing unit, (except LBN-10) and a balanced refrigeration system for energy saving performance.
There are also a number of options available for the LBN series. See
ACCESSORIES & OPTIONS section in back of this booklet.
LOCATION – CLEARANCE
AND
INITIAL SET-UP and START-UP
AND
BTU’S – ELECTRICAL – DIMENSIONS
Upon receipt of the cabinet, carefully examine the crating for damage. If crate is damaged, make a note on the delivery ticket before signing. Carefully remove shipping crate and examine the cabinet for “concealed” damage. If damage is found, contact the delivering carrier immediately and have his agent prepare an inspection report for the purpose of filing a claim.
THIS IS YOUR RESPONSIBLILTY.

LOCATION

Avoid locating the cabinet where direct sunlight would shine into the fixture or where drafts from air conditioning grills, fans, and open doors could effect it operation.
Because the condensing unit is located at the bottom of the cabinet, a two (2) foot clearance should be allowed in front of the louvered access panel to provide free air movement to and from the condenser for maximum operating efficiency.
The LBN-10 must also maintain a two- (2) inch clearance at the rear of the cabinet because, unlike the other LBN models, it is not front air discharge.
INITIAL SET-UP
SKID –
The skid should be left on the cabinet until it is near its final location. The skid provides protection for both cabinet and floor. The skid is removed by removing the bolts holding the cabinet to the base, then sliding the cabinet off the skid. A “mule” bracket is built in the end of the cabinet base frame for this purpose.
4
Page 5
LEVELING - SEALING
Proper drainage of the evaporator condensate water requires the cabinet to be properly leveled. This means left to right as well as front to back.
Silicone Seal ant
Floor
Shimming under the cabinet base frame may level the cabinet. A slight pitch from front to back is desirable. The cabinet back should never be higher than the front. Once level the cabinet should be approved material such as General Electric RTV-102 silicone sealer or an equivalent.

ACCESS PANEL REMOVAL The louvered panel on the lower right front of the cabinet provides access to the condensing unit and electrical box.

There is also a back panel that covers the rear of the condensing unit compartment that can be removed to again access to the back of the compartment. The drain trap should be filled with water. This prevents warm air from migrating back through the drain to the evaporator coil. Failure to fill the trap with water,
could result in excessive frosting of the evaporator coil.
Access to the trap is achieved by removing the back panel that
covers the rear of the compressor compartment .
On the LBN-10 this back panel is a wire grill that allows the discharge air to flow through the condensing unit compartment.
Before removing this panel, make sure the power supply to cabinet is disconnected.

COMPRESSOR

The compressor is banded for
shipping. Remove the two bolts holding the compressor bar in place, then you can pull out the condensing unit.
Cut the steel band, which holds down the compressor during shipping. The compressor should now float freely on the mounting springs. DO NOT LOOSEN NUTS.

ELECTRICAL CONNECTIONS

The LBN-4, 5, 6, 7 and 8 models have a power cord attached to the unit with a ground prong. Do not remove the grounding prong under any circumstances. The cord is rated 115v/15 amp. The LBN-7,
5
Page 6
and –8 also require a circuit breaker or a time delay fuse rated at 15 amps for the circuit being run to them.
The LBN-10 requires conduit connections of both 115v and 208­230v with an amperage rating of 15 amps for each circuit. Marked leads are provided for these connections in the field. If wiring the LBN-10 to a “3-wire” system is preferred, a 20amp, 208­230 v circuit needs to be provided.
See the diagram below concerning a “3-wire” system.
All of these models are 60hz, 1ph. If another voltage, hertz, or phase is required, please consult the factory.
IT IS VERY IMPORTANT TO YOU AND YOUR CUSTOMERS TO HAVE THE CABINET PROPERLY GROUNDED. A qualified electrician in accordance with the National Electrical Code and/or local codes should do the electrical installation.
NOTE: Connecting this unit to any electrical supply other than specified on the serial plate will void the warranty and may result in serious damage to the unit. The cabinet should be supplied with its OWN service.
SERIAL PLATE INFO.
The serial plate is located on the left-hand end of the case interior, and a second one in the condensing unit compartment. It has all the pertinent information needed for proper electrical installation. The serial plate should not be removed for any reason.
INITIAL START UP AND LOADING
Set the defrost timer for the
correct time of day, making sure the defrost pins are secure in the face of the clock. The LBN­4 through –8 models are factory set for one (1) defrost period in 48 hrs. @ 12 a.m. and LBN-10 is factory set for one (1) defrost period in 24 hrs. @ 12 a.m.
Check the cabinet thoroughly
for loose nuts and bolts and electrical connections. Inspect the refrigeration lines for any visible damage or chafing.
Replace the louvered access
panel.
6
Page 7
Start the cabinet and allow to
pull down to operating temperature before loading.
BTU CAPACITIES
RATINT TEMPS
o
F BTU/HR EVAP COND AMB LBN-4 2380 -25 110 90 LBN-5 2830 -25 110 90 LBN-6 3325 -25 110 90 LBN-7 3990 -25 110 90 LBN-8 4600 -25 110 90 LBN-10 5410 -25 110 90
ELECTRICAL
UNIT RUN FUSE SHIP H.P. HZ/PH VOLTS AMPS SIZE WT. LBN-4 ½ 60/1 115* 10.2 15 515 LBN-5 ½ 60/1 115* 10.2 15 585 LBN-6 ½ 60/1 115* 10.2 15 663 LBN-7 ¾ 60/1 115* 11/5 11+ 745 LBN-8 ¾ 60/1 115* 12.0 15+ 815 LBN-10 1 60/1 115 2.7 15 967 208-230 7.0 15 * 115V/15amp grounded power cord included + 15 amp time delay fuse or circuit breaker required
DIMENSIONS
Cu. Exterior Interior Ft. Cap. L W H L H W LBN-4 9.5 48 1.2 31 ½ 39 ¾ 44 ¼ 21 26 LBN-5 13.2 60 31 ½ 39 ¾ 55 7/8 21 26 LBN-6 16.8 72 31 ½ 39 ¾ 67 7/8 21 26 LBN-7 20.5 84 31 ½ 39 ¾ 79 7/8 21 26 LBN-8 24.9 95 5/8 31 ½ 39 ¾ 91 ½ 21 26 LBN-10 31.8 118 7/8 31 ½ 39 ¾ 114 ¾ 21 26
7
Page 8
GENERAL UPKEEP, CLEANING
AND

ROUTINE MAINTENANCE

CARE AND CLEANING

To insure good sanitation, appearance, and minimum maintenance, the cabinet should be cleaned and washed regularly as use demands. Clean with mild detergent and warm water. DO NOT USE AN ABRASIVE
condenser shroud is removable. Slit the upper corners of the gasket on the front of the condenser, remove the screws holding the shroud top into the shroud ends, and remove the top to gain full access to the condenser.
CLEANER OR STEEL WOOL, AS THEY WILL MAR THE FINISH.
ROUTINE MAINTENANCE
Under normal conditions, after
the cabinet is installed and running, very little maintenance should be required. However, the following list of housekeeping practices will assure trouble­free operation.
Check operation of condenser
fan motor. Fan blade must turn freely.
The condenser is of bare-tube
construction on the LBN-4 through –8 to reduce the amount of maintenance required, and fin-and-tube construction on the LBN-10. To keep the cabinet at top efficiency, periodic cleaning is required. To ease in the cleaning of the bare-tube condenser, the top of the
The glass lids are made of
tempered, non-heated glass. The lids slide up to open and can be locked open for product loading. The lids are not self­closing. The lids will close easily by hand and with the assistance of gravity. There is a nylon glide on the edge of the glass to assist in closing. The lid tracks must be cleaned periodically to allow the lids to close freely.
Manually defrost cabinet as
usage dictates. The LBN series
8
Page 9
are gravity-cooled cabinets. The sidewalls have refrigeration tubing in them to cool the lower portion of the interior and there is an upper evaporator that drops cold air down onto the product. The upper coil is equipped with defrost heaters that defrost the coil. THE
SIDE WALLS OF THE CABINET WLL BUILD UP FROST AND ICE ON THEM OVER TIME AND DO NEED TO BE MANUALLY DEFROSTED AS USAGE AND BUILD UP DEMANDS.
The interior of the cabinet has
load line markings showing how high product can be loaded. Loading product above these lines is above the refrigerated area in the case and will adversely affect the product in this area.
Clean the cabinet with mild
detergent. This will insure good sanitation, and minimize maintenance. Never use an abrasive as this could mar the finish.
9
Page 10
OPERATION
MAINTENANCE

POWER SWITCH

The power switch is located at the electrical box that is behind the front, louvered access panel. A slot in one of the louvers allows access to the switch. The switch will shut off all power to the cabinet on the LBN-4 through –8 and shut off the 208-230 circuit on the LBN-10.
TEMPERATURE CONTROL
The temperature control is
located between the electrical box and condenser behind the bottom louvered access panel. The temperature control does not have an “OFF” position. Turn the adjustment knob on the face of the control to make adjustments. Turning it clockwise will give colder temperatures while counter­clockwise will give warmer temperatures. It is not good practice to operate the case with the temperature control at the coldest position, as it will shorten compressor life.
The control is factory set for
approximately –15
o
F. The temperature should be checked with a thermometer other than the cabinet thermometer after it is running to insure that the cabinet is running at the proper temperature for the product. Ice cream should be kept at –
AND
o
10
F to –15oF. Frozen food
should be kept at 0F to –5oF.
If it should become necessary to
replace the temperature control, the sensing control capillary will need to be pulled out of the control well. When doing this, mark the length of capillary pulled out of the control well so that the same amount can be replaced (approx. 19 – 19 ½”), otherwise the temperature control will not react properly and cabinet temperature will be adversely affected.

THERMOMETER

The cabinet has a thermometer located on the left-hand end of the nose screen that is just below the upper mirror reflector and light fixture. The thermometer is a “pencil” type and reads from –40
o
F to +80oF on 2o increments. To replace, remove the two screws and install the replacement.

ELECTRICAL BOX

The electrical box contains the defrost time clock, terminal boards, and power switch. The box is capable of sliding out for servicing convenience and access is gained by removing the cover. THE
CABINET SUPPLY BREAKERS
10
Page 11
SHOULD BE DISCONNECTED BEFORE REMOVING THE ENCLOSURE COVER.

DEFROST TIME CLOCK

The timer is factory pre-set for
one (1) defrost cycle per 48 hours on the LBN-4 through –8 and for one (1) defrost cycle per 24 hours on the LBN-10 at 12:00 a.m. with a 40 minute failsafe.
The timer must be adjusted to
the proper time of day when the cabinet is started. The timer is adjusted by turning the knurled adjustment knob in the center of the dial face counter­clockwise until the time indicator corresponds with the correct time of day.
The defrost pins should be
checked for tightness. The timer will require re-adjusting after a power failure or the cabinet supply is turned off for extended periods of time. If an additional defrost is required due to ambient or cabinet usage conditions, do not put a
defrost during the middle of the day. Put any additional
defrosts during the night or at a time when the cabinet has the lowest usage.
Defrost is time initiated and
temperature terminated.
If the thermostat should fail,
the timer is equipped with a failsafe set at 40 minutes that will allow defrost to terminate on time.

DEFROST THERMOSTAT

The defrost thermostat is
located on its mounting plate which is located on the right hand end of the evaporator coil attached to the air scoop which is a right angle piece of metal running in front of the evaporator behind the nose screen. The thermostat is a bi­metal thermostat that is tied in series with the defrost time clock solenoid to end defrost when the temperature has been satisfied which is 85
o
F.
11
Page 12
To remove the thermostat if it
needs replacing, disconnect power. Remove the nose screen from in front of the evaporator.
Remove the stainless steel
mirror reflector over the light fixture.
Consult the wiring diagram for
the wiring terminations for the thermostat and disconnect.
Remove the air scoop which is
in front of the evaporator coil and has the defrost Thermostat mounting plate attached to it. Remove the thermostat and disconnect wires.
Reverse the procedure to
reinstall the new thermostat.

DEFROST HEATER REPLACEMENT

The cabinet is equipped with
two (2) defrost heaters which are wired in parallel, except for the LBN-4 through –8, 220 volt which are wired in series. Wiring them this way allows for lower wattage which increases the life of the heater. The
drain pan does not have to be removed to replace the heaters.
The heaters are equipped with
plug-in connections that plug into the underside of the light fixture. Disconnect the power supply
Remove the stainless steel
reflector. Remove the nose screen in front of the evaporator area.
The heaters are held up against
the evaporator by spring clips.
Press the heaters down and pull
up on the front edge of the heater clips. The heaters can be pulled forward.
When replacing be sure the
back pass of the rear defrost heater goes into the retaining clip at the back of the drain pan. This is necessary to prevent ice build up in the drain pan.
12
Page 13

LIGHTING

Cool white fluorescent bulbs
located on the underside of the stainless steel mirror reflector provide interior lighting. The bulbs are sleeved to maintain proper heat around the bulb for maximum light intensity and to protect the product in case of breakage.
The tubes can be replaced
without removing the doors. To replace, twist the bulb and slide the prongs clear of the lampholder. When reinstalling this type of bulb be sure the prongs on the bulb twist and lock into place.
There is a convenient ON/OFF
switch located on the right hand end, inside the cabinet, behind the mirror reflector. This switch only controls the lights. The 115-volt power must be shut off at the main power supply source located within the store prior to starting any service or maintenance work. The lights should always be left on to prevent moisture from forming on the mirror reflector, which is especially possible in high humidity applications.
The light ballast is located in
the light fixture. To gain access remove the mirror reflector.
CONDENSATE HEATERS
There are condensate heaters behind the stainless steel end panels, around the front glass, and behind the nose screen. These heaters are thermostatically controlled in case the cabinet malfunctions and the thermostat senses above 101
o
F at which time the heaters will shut off. At normal ambients and cabinet operation the heaters will remain on.
END PANEL HEATERS
The end panel heaters are located behind the end panel stainless steel reflectors. They can be removed by removing the screws on the bottom edge of the panel and pulling down on the bottom edge.
The heater is on adhesive foil on the backside of the panel.
13
Page 14

FRONT GLASS HEATER

The front glass heater surrounds the perimeter of the front glass. The purpose of the heater is to keep the aluminum trim surrounding the glass free of condensation. If the cabinet is located in a high humidity environment, the center of the glass may have a trace of condensation across it.
TO REPLACE THE HEATER
Disconnect power to cabinet.
Remove the cabinet top by removing the screws that hold it into the back of the cabinet, and on each end.
Lift the top off the cabinet. Remove the lids. Remove the screws holding the
backs of the lid tracks to the galvanized sub-top and the screws holding the center tracks to the aluminum rail on top of the front glass.
Remove the plastic arm trim
breakers in the end aluminum trim pieces to expose the screws in them. Remove screws and remove end trim.
Remove the trim from the top of
the front glass.
Pull the front glass up and out
exposing the wires at the right hand end of the glass and disconnect.
Take note of the heater layout
on the glass with reference to where the connectors are, and then replace heater.
Reverse procedure to
reassemble.
NOSE HEATER
The nose heater is located behind the nose screen that is in front of the evaporator. Remove the nose screen and replace heater.

CONDENSATE HEATER LIMIT THERMOSTAT

The condensate heater limit
thermostat is a safety feature that will shut off the condensate heaters just discussed when the thermostat senses 101
o
F.
The thermostat is located on the
defrost thermostat mounting bracket which is on the air scoop behind the nose screen in front of the evaporator. To
14
Page 15
replace see the procedure described under “Defrost Thermostat”.

REFRIGERATION

As stated previously, the LBN
series are self-contained. They feature semi-hermetic compressors, a bare tube, front­air discharge condenser, combination cold wall tubing with upper evaporator coil, and capillary tube.
The exception is the LBN-10,
which has a fin-and-tube condenser and horizontal, straight through air discharge.
If it should become necessary to
leak test the system, please adhere to the following notice:
NOTICE: Because of the CFC atmospheric considerations being taken today, we ask that leak testing be done with refrigerant 22 mixture with nitrogen. If the condensing unit nameplate designates a refrigerant other than R-22 remove all R-22 from the immediate area to avoid confusion after leak testing and evacuating the unit. Recharge the unit with proper refrigerant.

LEAK TESTING

The test gas cylinder must be
equipped with a pressure gauge and regulator so that system test pressures do not exceed maximum allowable limits. Do not ever use anything other than an R- 22 / Nitrogen mixture for leaks testing.
Attach a refrigerant test gas
cylinder to your service manifold and connect the manifold to the charging port on the liquid line valve. Charge an R-22 / Nitrogen mixture into the system, raising the pressure to the unit’s nameplate for the low side and high side pressures. Using an electronic detector, carefully check the entire system for leaks. Take special care to inspect all brazed and flare connections.

EVACUATION

After the system is proven leak tight, thoroughly evacuate the system according to the following procedure:
Discharge the refrigerant-
nitrogen mixture, allowing it to blow from the system as rapidly as possible, into an empty cylinder. Be sure that all service valves and solenoid valves are open to allow all of the mixture to be discharged.
Connect a deep-drain vacuum
pump to both the high and low side of the system. Pull a
15
Page 16
vacuum on the system to at least 1500 microns.
Break the vacuum by adding
refrigerant into the system until the pressure is above 0 PSIG. Always charge the refrigerant line into the system through a new drier in the charging manifold line. A 16 cubic inch drier is sufficient for this purpose.
Repeat steps 2 and 3 two more
times, the third time evacuating the system to 500 microns.

OPERATIONAL DATA

The following is typical data for the LBN series based on lab tests, and may vary under field operating conditions.
Amb. Temp. 75
o
F Head Press 230-250 psi Suct. Press 6-8 psi *Discharge Temp. -25
o
F
*Discharge temperature is the temperature taken off the lower half of the nose screen.

REFRIGERANT CONTROL

Refrigerant flow to the evaporator is controlled through the use of a capillary tube. The capillary tube is soldered for a specified length to the suction line, forming one integral piece to assure proper heat exchange.
Because the suction line capillary tube assembly, sometimes referred to as heat exchanger or pullout coil, has no moving parts, it very rarely if ever needs servicing.
However, should a leak occur in the system, it is possible that dirt, dust, or moisture may collect in the capillary tube causing the system to go into a vacuum. Should this occur, it is recommended that dry nitrogen or a dry refrigerant be forced through the system to clear the blockage.
If attempts to clear the restriction by this method are unsuccessful, the ENTIRE ASSEMBLY, NOT THE CAPILLARY TUBE ONLY, should be replaced with a new factory ordered replacement.
CRANKCASE PRESSURE REGULATOR
The LBN series employ a
crankcase pressure regulator in the suction line and is considered part of the heat exchanger. The CPR is set for 10 psi. The purpose of the valve is to maintain a low suction pressure on start-up so that the compressor will start properly.
On start-up, the valve will hold
the suction pressure at the desired setting until the suction pressure has dropped below the setting, then the valve will open.
16
Page 17
If it becomes necessary to check
or reset the setting, the cabinet must be warm such as after a defrost cycle or from an initial warm cabinet condition.
Put a suction compound gauge
on the compressor suction valve, start the compressor. If the pressure needs to be reduced turn the adjustment screw clockwise or, counterclockwise to raise the pressure.
DO NOT SET THE VALVE
BASED ON THE NAMEPLATE AMPERAGE RATING AS THE PRESSURE SETTING WILL BE TOO HIGH AND THE COMPRESSOR WILL NOT START PROPERLY.
17
Page 18

TROUBLE SHOOTING

SYMPTON
Compressor runs continuously product too warm
PROBABLE CAUSE (S) POSSIBLE SOLUTION
1. Short of refrigerant 1. Leak check, change drier, evacuate, and recharge
2. Inefficient compressor 2. Replace
3. Dirty condenser 3. Clean
4. Evaporator oil logged 4. Blow oil out of evaporator
High Head Pressure 1. Cabinet location too
1. Relocate cabinet
warm
2. Restricted condenser
air flow
2. Clean condenser to remove air flow restriction
3. Defective condenser
3. Replace
fan motor
4. Air or non-
condensable gases in system
4. Leak check, change drier, evacuate, and recharge
Warm storage temperatures
1. Temperature control not set properly
1. Reset control
2. Short of refrigerant 2. Leak check, change drier, evacuate, and recharge
3. Cabinet location too
3. Relocate
warm
4. Too much refrigerant 4. Change drier, evacuate, and recharge
5. Low voltage.
5. Check power
Compressor cycling on overload
6. Condenser dirty 6. Clean
18
Page 19
SYMPTON PROBABLE CAUSE (S) POSSIBLE SOLUTION
Compressor runs
1. Defective control 1. Replace continuously product too cold
2. Control feeler not in
tube properly
2. Assure proper length in tube
3. Short on refrigerant 3. Leak check change
drier, evacuate, and recharge
Compressor will not start no noise
2. Defective or broken
1. Blown fuse or breaker 1. Replace fuse or reset
breaker
2. Repair or replace
wiring
3. Defective overload 3. Replace
4. Defective
4. Replace
temperature control
5. Power disconnected 5. Check service cord or
wiring connections
Compressor will not
1. Low voltage 1. Contact electrician start cuts out on overload
2. Defective compressor 2. Replace
3. Defective relay 3. Replace
4. Restriction or
moisture
4. Leak check, replace drier, evacuate and recharge
5. Inadequate air over
5. Clean condenser
condenser
6. Defective condenser
6. Replace
fan motor
7. CRO not set properly Reset to 10 psi.
19
Page 20
SYMPTON PROBABLE CAUSE (S) POSSIBLE SOLUTION
Icing condition in drain pan under evaporator
1. Low voltage 1. Check voltage at
compressor
2. Cabinet not level 2. Check front to rear
leveling
3. Defective defrost
3. Replace
heater
4. Drain trap does not
have water in it
4. Pour water down drain
Low suction pressure
1. CPR not set properly 1. Reset to 10 psi Low head pressure
2. Defective CPR 2. Replace
3. Cap tube blocked due
to moisture or dirt
3. Change drier, evacuate, and recharge
4. Short of refrigerant 4. Leak check, change
drier, evacuate, and recharge
Pressures normal ­cabinet warm
1. Top coil blocked with
frost
1. Check defrost system
2. Evaporator oil logged 2. Blow oil out of
evaporator
LIGHT PROBLEMS / SOLUTIONS
Lights won’t work 1. Check light switch
2. Check continuity to ballast
3. Check to see if bulbs inserted
properly in sockets
4. Check voltage
20
Page 21
LIGHTS - Con’t
Lights flicker 1. Allow lamps to warm up
2. Check lamp sleeve for cracks
3. Check sockets for moisture and
proper contact
4. Bulb replacement may be
necessary
5. Check voltage
6. New bulbs tend to flicker until
used
Ballast hums 1. Check voltage
2. Replace ballast

ACCESSORIES & OPTIONS

COUNTERTOP
The cabinet is provided with a metal countertop as standard but, a 16” and 20” wooden countertop can be provided. The 16” one is flush mount to the back of the cabinet while the 20” one is wider than the cabinet to provide a larger working surface if needed.
STAINLESS STEEL TOP
Like the countertops, the stainless steel top replaces the standard metal countertop for those who need a highly durable working surface.
SUPERSTRUCTURE WITH LIGHTED CANOPY
The cabinet can be provided with a superstructure, which has two shelves, and a lighted canopy that attaches to the back of the cabinet.
The superstructure allows for the storage of dry goods without the need for additional floor space.
SUPERSTRUCTURE WITHOUT LIGHTED CANOPY
The superstructure can also be provided without the lighted canopy. It is still supplied with two shelves.
PRODUCT SHELF KIT
The interior of the LBN series has a raised step over the condensing unit compartment. The product shelf kit is a false bottom that makes the bottom of the cabinet level with the raised step.
BAG RACK
A bag rack can be provided to store various size checkout bags. The
21
Page 22
rack attaches to the back of the cabinet.
DIAL THERMOMETER
The cabinet can be provided with a two inch dial thermometer rather than the standard pencil type thermometer. THIS TYPE MUST BE FACTORY INSTALLED. It is located in the left end of the upper stainless steel reflector above the light fixture.
LID LOCK KIT
For product security, a lid lock kit can be provided. Each kit secures two lids.
WARRANTY, ELECTRICAL COMPONENTS
WIRING DIAGRAMS
ORDERING REPLACEMENT PARTS
Contact your nearest
Hussmann Distributor.
Always specify model and serial
number of cabinet.
If correct part number is not
known, give a clear description of part itself and it functions in the cabinet or remote unit.
CASTER KIT
If the cabinet needs to be moved quite often or for additional health code regulations, the caster kit raises the cabinet approximately 4 ½”. The wheel on the caster itself is 3”.
NOVELTY BASKET
For the storage and display of novelty ice cream items, the novelty basket is ideal. The basket is white epoxy-coated for that clean look and it is 10” x 12” x 6 ½” high. Basket dividers are also available.
WARRANTY PARTS PROCEDURE
First three steps same as
ordering replacement parts.
Give original installation date
of cabinet and, if possible, forward a copy of the original invoice or delivery receipt.
All shipments of in-warranty
replacement parts will be invoiced from the factory until such time as the defective part is returned and proved to be defective by our Quality Control Department.
22
Page 23
Contact your Hussmann
Distributor for instructions on returning in-warranty parts.
Warranty parts must be
returned to the factory within 30 days of date of failure to assure proper disposition.
Lack of any of the information
may result in the shipment of the wrong part, or a delay in shipment.
COMPRESSOR REPLACEMENT PROCEDURE
Replacement compressors will
not be shipped from the Hussmann factory. They may be obtained from your nearest Copeland wholesaler.
Your wholesaler will replace,
free of charge, any compressor found to be defective within twelve months of installation, not to exceed twenty months from the date of manufacture, as determined by the compressor serial number on the compressor serial plate.
For any defective compressor
beyond the twelve or twenty month time period, a salvage value credit will be given too partially offset the invoice for the replacement.
After March 16, 1991 when all
cases have the five-year warranty as standard, the following procedure applies:
FORWARD TO YOUR NEAREST HUSSMANN DISTRIBUTOR:
a) The cabinet model and serial
number
b) A copy of the wholesaler’s
invoice, along with a copy of the salvage value credit.
INTERNAL LEAK WARRANTY POLICY
The LBN series are warranted
from the date of factory shipment for five years for an internal leak. An internal leak not only includes the cold-wall tubing but the upper evaporator as well on these models.
If it is felt that there is an
internal leak in the cabinet, care should be taken to actually determine that there is a leak.
To do this properly, the
cabinet’s evaporator section must be isolated from the condenser section.
Unbraze the tubes going into
the back of the cabinet at the end of the heat exchanger.
Pinch or cap the larger tube and
braze shut.
23
Page 24
Add a schrader valve to the
smaller tube.
Attach the high side gauge of a
compound gauge to the valve and pressurize the cabinet with nitrogen or otherwise suitable gas.
There should be at least 300 psi
on the system.
Mark the pressure on the gauge
and leave it, returning 24 hours later.
Note the pressure. If it has
fallen more than 150-200 psi then the system may have an internal leak.
If it only drops a small amount
this does not mean that you have an internal leak but that the gas in the cabinet is cooler and has reduced its pressure because of this.
If the cabinet has an internal
leak contact the nearest Hussmann distributor or the factory to receive authorization to return the cabinet to the factory.
NO CABINET WILL BE ACCEPTED AT THE FACTORY WITHOUT A LETTER OF AUTHORIZATION FOR RETURN.
24
Page 25
ELECTRICAL COMPONENTS REPLACEMENT LIST
LBN-4 LBN-5
Compressor (R-404A) KAGB-005E-IAA KAGB-005E-IAA Hermetic as of 11/03 J2212GK
Condenser Fan Motor EMS ESPL25EM1 EMS ESPL25EM1 Light Ballast 8G3706 8G3706 Fluorescent Lamp F30T8CW F40T12CW Lamp Starter FS4 FS4
LBN-6 LBN-7 Compressor (R-404A) KAGB-005E-IAA KAAB-007E-CAA (Compressors are Copeland) Condenser Fan Motor EMS ESPL25EM1 EMS ESPL25EM1 Light Ballast 8G3706 (2) 8G3706 Fluorescent Lamp F40T12CW (2) F30T8CW Lamp Starter (1) FS4 (2) FS4
LBN-8 LBN-10 Compressor (R-404A) KAAB-007E-CAA KALB-010E-CAV (Compressors are Copeland) Condenser Fan Motor EMS ESPL25EMI EMS ESPL25EM2 Light Ballast (2) 8G3706 8G1024 Fluorescent Lamp (1) F40T12CW (2) F40T12CW (1) F30T8CW Lamp Starter (2) FS4
R-404A compressor (models with “E”) require the use of a polyol ester oil, made by Mobil under part No. EAL ARCTIC 22 CC. An acceptable alternate if this is not available is ICI EMKARATE RL 32S. Do not use any other oil in these compressors. The polyol ester oil is very susceptible to absorbing moisture, so every effort should be made to keep systems closed during repair, as well as during the handling of the oil itself.
25
Page 26
REV.
R
FAN MOTOR
CONDENSER
LIGHT FIXTURE
BLK
YEL
YEL
BALLAST
LAMP
BLU
WHT
LAMP
BLU
RED29RED
LIGHT SWITCH
50
2
12
23 17
1
511 37
10 8 46 9
31 32
152124
13
22 19
16 18
14 20
25 26
39
28 27
30
40
48
46 44 42
ELECTRICAL BOXLIGHT FIXTURE
51 52 49 47
45 43 41
PRP
2
1
11
5 3
7
10
8
4
6
9
12
31
32
15
24
21
23 17
13 22
19
16 141820
25 26
39
28 27
30 29
40
COMPRESSOR
TIMER
YEL
CONTROL
TEMPERATURE
DWG. NUMBER
M100-1450 B
Gloversville, N.Y. 12078
M.L.
ELECT. BOX
RED
BRN
S
X
N
4
2
3
1
C
SWITCH
S1 S3
S2 S4
 1/32"
OTHERWISE SPECIFIED.
FRACTIONAL
TOLERANCES UNLESS
SIZE
SHEET
MATERIAL:
10-88
LBF-10 WIRING DIAGRAM
DATE
DRAWN
CHECKED
E
TYPE
CODE
TITLE
 1/64"
1.0 = 1.0
 0.031"
 1ü
FINISH
HOLE LOCATION
& SPACING
SCALE:
DECIMAL
ANGULAR
C
DIE NO.
SIZE
4358
4510
E.C.N.
BY
S.S.
M.L.
DATE
07-86
10-88
A
BLK
WHT
RED
208-230 V.
230 V.
SUPPLY BOX
/1 0
60 HZ
115 V.
SUPPLY BOX
7
8
18
9
20
19
CONDUCTORS.
USE COPPER, COPPER-CLAD
ALLUMINUM, OR ALLUMINUM
L.H. BREAKER HTR.
NOSE HEATER
R.H. BREAKER HTR.
3
13
BLK
BRN
FRONT GLASS HEATER
ANTI-CONDENSATE
HEATER THERMOSTAT
115 V.
/1 0
60 HZ
2
28
29
30
26
COIL HEATER
39
40
COIL HEATER
B
LBF-10 STANDARD
REV.
DEFROST THERMOSTAT
115 V. ELECTRICAL CIRCUIT
208-230 V. ELECTRICAL CIRCUIT
Page 27
DEFROST THERMOSTAT
HEATER THERMOSTAT
115V
60 Hz
COIL HEATER
COIL HEATER
NOSE HEATER
L.H. END HEATER
R.H. END HEATER
ANTI-CONDENSATE
BRN
BLK
RED
BLK
19
22
RED
BALLAST
WHT
17
23
24
15
13
21
BLK
29
WHT
16
BRN
2
26 30
27
39 40
7
18
RED
8
RED
19
RED
20
RED
9
29
40
30
28
26
39
25
YEL
YEL
C
WHT
18
20
16
14
X
3
4
N
2
1
4
PURP
RED
J
TEMPERATURE
S1
BLK
S3
CONTROL
BLK
S
LAMP
S
32
31
BLK
BRN
BLK
BLK
BLU
WHT
BLK
WHT
BLK
46
LIGHT
SWITCH
BLK
12
9
7
856
4
3
10
2
11
1
LIGHT FIXTURE
BRN
BLK
27
FRONT GLASS HEATER
26
ELECT. BOX
CONDENSER
42
43
2
FAN
R
1
WHT
S2
POWER
S4
COMPRESSOR
SWITCH
LBF-4,5,6 LBN-5,6 115/60/1
REV EO # REV DATE REV BY
APPROVED BY
9-24-01 JJH
-
ECN 5095 REVE
-REV D BY JWL 1-12-99 ADDED LBN
-
-REV E CHANGED BALLAST WIRING & LAMP HOLDER WIRING
-
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
ECN 5095-REV E
DRAWN BY: DATE DRAWN : APPROVED BY:
JWL
SCALE
INCHES
SHEET #
3/5/91
-
1 OF 1
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-1436 E
Page 28
YELLOW LAMP
(ON DURING DEFROST)
15
BLK
39
RED
BLK
S
BLK
DEFROST S'TAT
COIL HEATER
COIL HEATER
NOSE HEATER
L.H. END HEATER
R.H. END HEATER
ANTI-CONDENSATE HEATER T'STAT
32
31
BRN
RED
WHT
BLUE
LIGHT SWITCH
BLK
8
7
6
12
3
4
9
10
2
11
5
1
LIGHT FIXTURE
BLK
FRONT GLASS HEATER
WHT
ELEC BOX
COMPRESSOR
42
WHT
BLK
4
5
43
CONDENSER FAN
YEL
LAMP
BLK
BALLAST
WHT
18
19
17
23
24
13
21
14 20
16
22
3
4
N
2
1
15
S
X
BLK
BLK
BLK
29 16
2
26
30 39
40
7
18
RED
8
19
RED RED
20
9
RED
BRN
RED
BLK
WHT
BRN
WHT
29
27
40
28
30
4
26
39
25
C
J
PURP
115v 60 Hz 10
POWER SWITCH
S1
S3
S2
S4
BLK
WHT
USAGE: LBN-4 W/HERMETIC COMP. SPECIAL FOR TAIWAN 7-11
BLK
REV EO # REV DATE REV BY
-
APPROVED BY
-
-
-
-
-
-
TEMP CONTROL
--
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JJH
-
09/08/03
SCALE
SHEET #
INCHES
1 OF 1
SHEET 1 OF 2
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2307
Page 29
BLACK
WHITE
#2 TIMER
#4 TIMER
COND. FAN
TEMP. CONTROL
C
5
2
BLACK 43
S
R
RED
4
4
1
START CAP.
WHITE 42
RUN CAP.
RELAY ASSY
N TIMER
USAGE: LBN-4 W/HERMETIC COMP. SPECIAL FOR TAIWAN 7-11
REV EO # REV DATE REV BY
-
APPROVED BY
-
-
-
-
-
--
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JJH
-
09/08/03
SCALE
SHEET #
INCHES
1 OF 1
SHEET 2 OF 2
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2307
Page 30
DEFROST THERMOSTAT
HEATER THERMOSTAT
115V
60 Hz
COIL HEATER
COIL HEATER
NOSE HEATER
L.H. END HEATER
R.H. END HEATER
ANTI-CONDENSATE
BRN
BLK
RED
BLK
BLU
BLK
29
WHT
16
BRN
2
26 30
39 40
7
18
RED
8
RED
19
RED
20
RED
9
29
40
30
4
BALLAST
27
39
28
YEL
C
PURP
S
LAMP
26
25
YEL
BLK
BLK
WHT
BLK
BLU
BALLAST
WHT
19
18
20
14
17
23
16
13
21
22
RED
32
24
31
15
BLK
S
BRN
X
3
4
N
2
1
RED
BLK
J
WHT
TEMPERATURE
S1
BLK
S3
BLK
CONTROL
BLK
S
LAMP
12
9
BLK
WHT
BLK
WHT
LIGHT
46
SWITCH
BLK
7
856
4
3
10
2
11
1
LIGHT FIXTURE
BRN
BLK
WHT
27
FRONT GLASS HEATER
26
ELECT. BOX
CONDENSER
42
43
2
FAN
R
1
WHT
S2
POWER
S4
COMPRESSOR
SWITCH
LBF-7,8 LBN-7,8 115/60/1
REV EO # REV DATE REV BY
1/12/93 JWL
D
APPROVED BY
-
-
-
­ 7/15/99 ADDED LBN
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JWL
SCALE
INCHES
SHEET #
3/5/91
-
1 OF 1
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-1395 D
Page 31
DEFROST THERMOSTAT
COIL HEATER
COIL HEATER
NOSE HEATER
L.H. END HEATER
R.H. END HEATER
ANTI-CONDENSATE
HEATER THERMOSTAT
BRN
BLK
RED
BLK
19
22
RED
17
13
WHT
BALLAST
23
21
24
15
BLK
29
WHT
16
BRN
2
26 30
27
39 40
7
18
RED
8
RED
19
RED
20
RED
9
29
40
30
28
26
39
25
YEL
YEL
C
WHT
18
20
16
14
X
3
4
N
2
1
4
PURP
RED
J
TEMPERATURE
S1
BLK
S3
CONTROL
BLK
S
LAMP
S
32
31
BRN
BLK
BLK
BLK
BLU
BLK
WHT
WHT
12
9
856
4
10
COMPRESSOR
42
43
BLK
46
LIGHT
SWITCH
BLK
7
3
2
11
1
LIGHT FIXTURE
BRN
BLK
27
FRONT GLASS HEATER
26
ELECT. BOX
4
5
CONDENSER
FAN
WHT
S2
POWER
S4
SWITCH
115V
60 Hz
SHEET 1 OF 2
LBN- 4 HERMETIC 115/60/1
REV EO # REV DATE REV BY
APPROVED BY
-
-
-
-
-
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
JJH
-
08/19/03
SCALE
SHEET #
INCHES
1 OF 1
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2305
Page 32
BLACK
WHITE
#2 TIMER
#4 TIMER
COND. FAN
TEMP. CONTROL
C
5
2
BLACK 43
S
R
RED
4
4
1
START CAP.
WHITE 42
RUN CAP.
RELAY ASSY
N TIMER
SHEET 2 OF 2
LBN- 4 HERMETIC 115/60/1
REV EO # REV DATE REV BY
APPROVED BY
-
-
-
-
-
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
JJH
-
08/19/03
SCALE
SHEET #
INCHES
1 OF 1
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2305
Loading...