Hussmann HGM-1BS, HGM-3BS, HGM-2BS, HGM-1TS, HGM-2TS Installation And Service Instructions Manual

...
January 2006
INSTALLATION & SERVICE
INSTRUCTIONS
FOR
HGM-1, 2 & 3 BS,TS SELF-CONTAINED
Medium Temperature Glass Door Merchandiser
First Call for help (US and Canada):
1-800-922-1919
Soporte Tècnico y Asistencia (Mèxico):
01-800-522-1900
For a Service Network Locator and other Information visit us at
www.hussmann.com
select Worldwide Locations
P/N OII – HGM BS-TS Self-Contained
HUSSMANN - GLOVERSVILLE

TABLE OF CONTENTS

Introduction 2 Inspection Upon Receipt – Proper Location and Clearance 2
Skid 2 Leg Installation 2 Leveling and Sealing 3 Condensate Pan 3
Bottom Louvered Panel Removal 3 Top Decorative Panel Removal 3 Shelves 3
Air Distribution and Rear Flue Spacer 3 Serial Plate Information Electrical Connections 4
Electrical, BTU Capacities 4 Initial Start Up and Loading 4 General Upkeep and Cleaning 5
Power Switches, Temperature Controls 5 Thermometer 6 Electrical Enclosure 6 Lighting 6
Refrigeration 7 Leak Testing 7 Evacuation 7 Operational Data and Refrigerant Control 8
Trouble Shooting, and Lights Trouble Shooting 9 & 10 Warranty and Electrical Components Replacement List 11 & 12
Commercial Door Literature 13-16
Page 1
Introduction –
The HGM-BS/TS models are self con­tained, medium temperature, vertical glass door merchandisers designed for the display of dairy products, deli items, beverages, and wine. Design features include self-closing glass doors, efficient foamed in place non­CFC insulation, and balanced R-134a refrig­eration systems for energy saving perform­ance.
Inspection upon receipt –
Upon receipt of the cabinet, carefully examine the crating for damage. If crate is damaged, make a note on the delivery ticket before signing. Carefully remove shipping crate and examine cabinet for “concealed” damage. If damage is found, contact the de­livery carrier immediately and have his agent prepare an inspection report for the purpose of filing a claim. THIS IS YOUR RESPONSI­BILITY.
Proper Location & Clearance –
allowed in front of the case and six (6) inches of clearance at the rear to provide the necessary free air movement to and from the condenser.
INITIAL SET-UP Skid –
The skid should be left on the case until it is near its final location. The skid provides pro­tection for both case and floor. The skid is re­moved by raising one end of the case approxi­mately six inches. Block securely and remove the two skid bolts on the raised end. The proce­dure is repeated on the opposite end. When the skid bolts are removed, the case may be slid off the skid.
Leg Installation – Top Mounts only
After the case is near its final location and the skid has been removed, the NSF ap­proved legs should b e installed. The legs are packaged inside the cabinet. Replace the tape and door blocks. To install legs, raise one end of the cabinet approximately eight (8) inches, block securely, and install two legs.
Avoid locating the cabinet where direct sunlight would shine into the fixture or where drafts from air conditioning grills, fans and open doors could affect its operation.
Because the condensing unit is located at the top of the HGM-TS, at least twelve (12) inches of clearance should be allowed at the rear of the cabinet and at the top of the case. This clearance is necessary to provide free air movement to and from the condenser for maximum operating efficiency.
Because the condensing unit is located on the bottom of the HGM-BS, at least twenty four (24) inches of clearance should be
Page 2
The leg mounting plates are factory in­stalled and contain a ½ x 13 tapped hole to mate with the leg assembly. The procedure is re­peated on the opposite end. The 3-door requires legs in the center. With cabinet legs installed, the cabinet should be positioned in its final loca­tion and leveled.
The cabinet is leveled by turning the bottom sec­tion of each leg. The self-closing doors require the cabinet to be properly leveled. End to end leveling will make the door (s) close with uni­form speed and tightness. A slight pitch from front to rear is desirable.
THE CABINET BACK SHOULD
NEVER BE HIGHER THAN THE FRONT.
electrical box to allow the electrical box to
slide out for servicing.

Leveling and Sealing

– Bottom
Mounts only
The case can be leveled by shimming un­der the cabinet base frame, or be installing op­tional levelers. The self-closing doors require the cabinet to be properly leveled. End to end leveling will make the door (s) close with uni­form speed and tightness. A slight pitch from front to rear is desirable.
Silicone Sealant
Condensate Pan –
Floor
An electrically heated (300w, 115v) con­densate pan is provided to evaporate the defrost water. The heated condensate pan slides onto the slide plate on the cabinet bottom on TS cases and has a thermistor. On BS cases the pan is screwed to the base of the case. The pan is removable for cleaning. A vinyl drain tube is provided for connection to the heated conden­sate pan. The drain must be trapped to guard against drain line freezing and for good sanita­tion practice.
Bottom Louvered Panel Removal –
The louvered panel provides access to the condensing unit and the electrical box.
Remove panel by removing the shipping screw (s) at bottom and lifting up and pulling forward. Remove shipping screw on
Top Decorative Panel Removal –
The top decorative panel is removed by
lifting up and pulling forward.

Shelves

Each cabinet is provided with 4 cantile­ver shelves per door that are adjustable on 1­inch increments and are tiltable. Each cabinet also has one bottom shelf per door. These shelves have one-inch legs to allow proper air­flow in the cabinet. Behind the shelves are wire flue spacers which also allow for proper airflow. All shelves and flue spacers are white, epoxy coated for durability and ease of clean­ing. Shelves should be adjusted to desired op­erating height.
When loading product, into the cabinet, care should be taken not to load product so that it touches the evaporator coil cover. Do not extend product past the front edge of the shelf. Extending past the edge will seriously effect internal air flow through out the cabinet.
Shelves are UL rated for a maximum load of 123 lbs. DO NOT OVERLOAD SHELVES.
Air Distribution and
Rear Flue Spacer –
Air is drawn through the evaporator from front to rear and is discharged down the back wall, returning up the face of the glass door to the return air grill. NOTE: Rear flue
Page 3
spacer must be in place as this forms a dis­charge air flue at the back of the cabinet.
Electrical Connections –
The HGM-1 and 2 cases are supplied with a supply cord as charted below with a grounding prong for operation on a 115v power supply. Do not remove the grounding prong under any circumstances. The HGM-3 requires hard wiring to a 30 amp, 115v circuit.
Cord Plug Nema Model Amperage Designation
HGM-1-BS/TS 15 5 – 15 P HGM-2-BS/TS 20 5 – 20 P
Serial Plate Information –
The serial plate is located in the upper left-hand corner of the case interior. It has all the pertinent information needed for proper electrical installation. The serial plate should not be removed for any reason.
NOTE: Connecting this unit to any electrical supply other than specified on the serial plate will void the warranty and may result in serious damage with its own service.
Electrical –
Unit Run Ship H.P. Hz/Ph Volts Amps Fuse Size Wt.
1-BS 1/3 60/1 115 2-BS 1/2 60/1 115 12.5 20 amp 825 3-BS 3/4 60/1 115 20.5 30 amp 1096
1-TS 1/3 60/1 115 2-TS 1/2 60/1 115 12.5 20 amp 776 3-TS 3/4 60/1 115 20.5 30 amp 1050
BTU Capacities –
Rating Temps ºF
BTU/HR EVAP COND AMB 1-TS/BS 2300 +25 110 90 2-TS/BS 2570 +25 110 90 3-TS/BS 3620 +25 110 90
The HGM cases use R-134a refrigerant. Check the serial plate for the specific refrigerant charge used.
Page 4
Initial Start-up and Loading –
Check the cabinet thoroughly for loose nuts
and bolts and electrical connections. In­spect the refrigeration lines for any visible damage or chafing.
Replace the electrical box cover.
Start the cabinet and allow to pull down to
operating temperature before loading.
General Upkeep and Cleaning –
1. To insure good sanitation, appearance, and minimum maintenance, the cabinet should be cleaned and washed regularly as sue de­mands. Clean with mile detergent and warm water. DO NOT USE AN ABRA­SIVE CLEANER OR STEEL WOOL AS THEN WILL MAR THE FINISH.
1. Under normal conditions, after the cabinet is installed and running, very little mainte­nance should be required. However, the fol­lowing list of housekeeping practices will assure trouble-free operation.
a) Check operation of condenser fan motors.
Fan blades must turn freely.
a) Check drain pan and heater to prevent acci-
dental overflow.
a) Make sure doors are closing properly and
that the gaskets seal.
a) Make sure all evaporator fan motors are
running. These can be seen through grill inside cabinet.
a) Clean the cabinet with a mild detergent.
this will insure good sanitation, and mini­mize maintenance. Never use an abrasive as this could mar the finish.
a) A regular program should be set up for the
cleaning of the fin-and-tube condenser. Normally, this cleaning is required every 3 to 4 months, but the individual store appli­cation may shorten or lengthen this time pe­riod. Dust and dirt accumulation can cause serious efficiency loss.
a) On the BS cases (bottom mounts) access is
gained to the unit area by removing the lou­vered grille. The unit slides forward to fa­cilitate cleaning and for service. Care should be taken when pushing the unit back in place to insure that the pullout coil does not become kinked or damaged in some way.
OPERATION AND MAINTENANCE
Power Switches –
The power switch is located at the elec­trical box which is behind the top decorative panel (TS models) or bottom louvered panel (BS models). The switch will shut off al power to the case.
Temperature Control –
The electrical temperature control is located in the electrical box. The temperature control does not have an ‘OFF’ position.
Adjustments may be made by turning the knob on the face of the dial. Turning it clockwise will give warmer temperatures while counter-clockwise will give colder tempera­tures.
Page 5
There is also and adjustable tempera­ture differential (the difference between the cut­in temperature and the cut-out temperature) located on the back of the temperature control cover. When adjusting the differential, the tem­perature setting may also have to be adjusted. See figure below for internal adjustment loca­tions.
The control has a range of –20º F to +220º F with a differential of 1º to 30º. It is fac­tory set for approximately 29ºF with a 10º dif­ferential. The temperature should be checked with a thermometer other than the case ther­mometer after it is running to insure that the case is running at the proper temperature for the product.
A picture of A319 Electronic Tempera­ture Control and Board Layout is located on the last page of this booklet.
Thermometer –
The thermometer is located by looking through the right hand door onto the right hand end of the fan plenum.
The thermometer will also warm up rather rapidly when the case door is held open for a time such as when the case is being re­stocked or a shopper is making a decision on a product. After the door is closed it will take some time for the thermometer to pull back down to the case temperature. The thermome­ter and temperature control sense discharge air temperature which is 5-10º colder than the case temperature.
The thermometer may be replaced by removing the two screws securing it to the evaporator fan grill. Lower the evaporator coil cover by removing the brass thumb screws
located at each end of the cover, and backing out the thumb screws located along the front edge of the cover.
Follow the sensing lead from the ther­mometer until you locate the sensing element. Loosen the clamp securing the element and re­move the element. Remove the thermometer. Assemble is the reverse order making sure you first thread the element through the hole in the evaporator fan grill. Cleaning of the sensing element may also be accomplished in this man­ner.
Electrical Enclosure –
For servicing convenience, access is gained by removing the access panel and elec­trical box cover. The cabinet supply breakers should be disconnected before removing the en­closure cover.
Lighting –
Electronically powered T-8 lamps lo­cated inside each doorway provide interior lighting. The tubes are enclosed in a patented lens system to maintain proper heat around the bulb for maximum light intensity and to protect the product in case of breakage. See the Commercial instructions for the lens removal, attached at the back of this booklet.
Each HGM model has a convenient ON/ OFF switch so lights may be turned off to con­serve energy during hours when the store is closed. The switch is located inside the cabinet above the left hand door. This switch only con­trols the lights. 115 volt power must be shut off at the main power supply source located within the store prior to starting any service or main­tenance work.
Page 6
Light ballasts are located on mullions of the door frames. See the Anthony ballast re­moval instructions at the back of the booklet.
Commercial Doors
See Door Instructions at
the back of this booklet.
Refrigeration –
As stated previously, these cases are self­contained with the condensing unit mounted at the top or bottom. they are equipped with a hermetic compressor and a capillary tube. The condenser is of fin and tube construction and should be periodically cleaned to maintain effi­cient operation.
If it should become necessary to leak test the system, please adhere following notice:
NOTICE considerations being taken today, we ask that leak testing be done with refrigerant 22 mixed with nitrogen. If the condensing unit nameplate designates a refrigerant other than R-22 re­move all R-22 from the immediate area to avoid confusion after leak testing and evacuating the unit. Recharge the unit with proper refriger­ant.

Leak Testing

The test gas cylinder must be equipped
Because of the CFC atmoshperic
- CAUTION
with a pressure gauge and regulators so that system test pressures do not exceed maximum allowable limits. Do not ever use anything other than an R-22/Nitrogen mixture for leak testing.
Attach a refrigerant test gas cylinder to your service manifold and connect the manifold to the charging port on the liquid line valve. Charge an R-22/Nitrogen mixture into the sys­tem, raising the pressure to the remote unit’s nameplate for the low side and high side pres­sures. Using the electronic detector, carefully check the entire system for leaks. Take special care to inspect all brazed and flare connections.
Evacuation –
After the system is proven leak tight, thoroughly evacuate the system according to the following procedure:
Discharge the refrigerant-nitrogen mixture,
allowing it to blow from the system as rap­idly as possible, into an empty cylinder. Be sure that all service valves and solenoid valves are open to allow all of the mixture to be discharged.
Connect a deep-drain vacuum pump to both
the high and low side of the system. Pull a vacuum on the system to at least 1500 mi­corns.
Break the vacuum by adding refrigerant
into the system until the pressure is above 0 psig. Always charge the refrigerant line into the system through a new drier in the charg­ing manifold line. A 16 cubic inch drier is sufficient for this purpose.
Page 7
Repeat steps 2 and 3 two more times, the
third time evacuating the system 500 microns.

Operational Data

The following is typical data for HGM
models based on lab tests, and may vary under field operating conditions.
Ambient Temperatue Head Pressure (psi) 120-135 Suction Pressure (psi) 9-12
75ºF
Refrigerant Control
Refrigerant flow to the evaporator is con­trolled through the use of a capillary tube.
Because the suction line capillary tube as­sembly (sometimes referred to as heat exchanger or pull-out coil) has no moving parts, it very rarely if ever, needs servicing. However, should a leak occur in the system, it is possible that dirt, dust, or moisture may collect in the capillary tube causing the system to go into a vacuum. Should this occur, it is recommended that dry nitrogen or a dry refrigerant be forced through the system to clear the blockage.
If attempts to clear the restriction by this method are unsuccessful, the entire assembly, not the capillary tube only, should be replaced with a new factory ordered replacement.
Page 8
TROUBLE SHOOTING
Symptom Probable Cause (s) Possible Solution (s)
Compressor runs continuously Product too warm
1. Short of refrigerant 1. Leak check, change drier, evacuate, and recharge
2. Inefficient compressor 2. Replace
3. Dirty condenser 3. Clean
High Head Pressure 1. Cabinet location too warm 1. Relocate cabinet
2. Restricted condenser air flow 2. Clean condenser to remove air flow restriction
3. Defective condenser fan mo-
3. Replace
tor
Warm storage temperatures 1. Temperature control not set
4. Air or non-condensable gases
in system
4. Leak check, change drier, evacuate, and recharge
1. Reset control
properly
2. Short of refrigerant 2. Leak check , change drier, evacuate, and recharge
3. Cabinet location too warm 3. Relocate
4. Too much refrigerant 4. Change drier, evacuate, and recharge
5. Low voltage. Compressor
5. Check power
cycling on overload
6. Condenser dirty 6. Clean
Compressor runs continuously
1. Defective control 1. Replace
product too cold
Compressor will not start no
2. Short on refrigerant 2. Leak check, change drier,
1. Blown fuse or breaker 1. Replace fuse or reset breaker
noise
2. Defective or broken wiring 2. Repair or replace
3. Defective overload 3. Replace
4. Defective temperature control 4. Replace
5. Power Control 5. Check service cord or wiring
Page 9
evacuate, and recharge
conditions
TROUBLE SHOOTING CON’T
Symptom Probable Cause (s) Possible Solution (s)
Compressor will not start cuts out on overload
1. Low voltage 1. Contact electrician
2. Defective compressor 2. Replace
3. Defective relay 3. Replace
4. Restriction or moisture 4. Leak check, replace drier, evacuate and recharge
5. Inadequate air over con-
5. Clean condenser
denser
6. Defective condenser fan
6. Replace
motor
Trouble Shooting Lighting System
Problem Solution
Light’s won’t start 1. Check light switch
2. Check continuity to ballast
3. Check to see if bulbs inserted properly into socket
4. Check voltage
Light’s flicker 1. Allow lamps to warm up
2. Check lamp shield for cracks
3. Check sockets for moisture and proper contact
4. Bulb replacement may be necessary
5. Check voltage
6. New bulbs tend to flicker until used
Ballast hums 1. Check voltage
2. Replace ballast
This HGM case was manufactured in Gloversville, New York. Our phone #’s are (518) 725­0644 for NY state residents, and toll free 800-753-7790 or outside NY. Any questions not covered in this manual, please call the factory.
Page 10
WARRANTY PARTS PROCEDURE, COMPRESSOR REPLACEMENT,
AND
ELECTRICAL COMPONENTS REPLACEMENT LIST
Ordering Replacement Parts –
Contact your nearest Hussmann Distributor
Always specify model and serial number of cabinet
If correct part number is not know, give a clear description of part itself and its func-
tion in the cabinet or remote unit.
Warranty Parts Procedure
Same as above
Give original installation date of cabinet and, if possible, forward a copy of the original
invoice or delivery receipt.
All shipments of in-warranty replacement parts will be invoiced from the factory until
such time as the defective part is returned and proved to be defective by our Quality control Department.
Contact your Hussmann Distributor for instructions on returning in-warranty parts.
In case of a compressor failure, see next section.
Warranty parts must be returned to the factory within 30 days of date of failure to as-
sure proper disposition.
Lack of any of the above information may result in the shipment of the wrong part, or
a delay in shipment.
Compressor Replacement Procedure
Replacement compressors will not be shipped from the Hussmann Factory. They may
be obtained from your nearest Wholesaler.
Your wholesaler will replace, free of charge, any compressor found to be defective
within twelve months of installation, not to exceed twenty months from the date of manufacture, as determined by the compressor serial number on the serial plate.
Page 11
To obtain reimbursement forward to: Hussmann Corporation 140 East State Street Gloversville, NY 12078 the following information:
1. The cabinet model and serial number
2. A copy of the wholesaler’s invoice, along with tag from old compressor.
Electrical Components Replacement List
Model HGM-1-TS/BS HGM-2-TS/BS HGM-3-TS/BS
Compressor Tecum. AE44484 Tecum. AKYY60Y Cope. RSL4CIE-IAA Cond. Fan Mtr. EMS ESPL25EM1 EMS ESPL25EM1 Evap Fan Mtr Bomax 310-5734 same same Light Ballast Huss. # 6-S-166 same same Fluores. Lamp F040W-T8-60" same same
Page 12
DOOR & FRAME HEATERS
FRAME HEATERS
BLK
WHT
BLK
WHT
DOOR HEATERS
BLU
BLU/WHT
LIGHT SWITCH
LAMP
ORN
ORN
BRN BRN
BLK
3
WHT
4
8
BALLAST 9 10
1
RED
2
RED
5
BLU
6
BLU
7
LAMP
SENSING
BULB
2 1
COMPRESSOR
WHT
SENSOR
BLK
JUMPER
COMM 240 AC 120 NC C NO
WHT
BLK
PUR
GRD
3-S-226
1 2 3 4 5 6 7 8
9 10 11 12 23 24 25 26
ELEC-TRON
3-S-226
1 2 3 4 5 6 7 8
9 10 11 12 23 24 25 26
ELEC-TRON
BLK
EVAP FANS
BLK
BLK
BLK
WHT
S3
S4
REV EO # REV DATE REV BY
APPROVED BY
-
-
-
-
-
-
--
-
CONDENSATE PAN HEATER
BLK
S1
GRD
WHT
S2
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
115 V 60 Hz
15 AMP
POWER PLUG
-
-
1 PH
JWL
1/29/96
ANTHONY FRAME
HGM-1-BS
SCALE
INCHES
SHEET #
1 OF 1
PLUG
END
DETAIL
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2021
DOOR AND FRAME HEATERS
LIGHT
SWITCH
BLU
BLU/WHT
ANTHONY T8 ELECTRONIC LIGHTING
SENSING
BULB
CONDENSOR
FANS
1
C
COMPRESSOR
FRAME HEATERS
WHT
PUR
BLK
WHT
WHT
GRN
DOOR
HEATERS
BLK
WHT
BLK
WHT
BLK
1 2 3 4
5 6
7 8
9 10
11 12
23 24 25 26
BLU
BLU
BLK
3
WHT
ORN
8
BALLAST
ORN
9
ORN/BLK
10
ORN/BLK
BLU/WHT
BLU/WHT
1
LAMP
4
RED
2
RED
5
BLU BLU
LAMP
ORN/BLK ORN/BLK
LAMP
ORN ORN
8 9 10 1
BALLAST
BLK
3
WHT
4
RED
2
RED
5
BLU
66
BLU
77
LAMP
ANTHONY FRAME
BLK
EVAPORATOR FANS
BLK
SENSOR
1 2 3 4
5 6
BLK
COMM
120
240
AC
NOCNC
PUR
WHT
BLK
7 8
9 10 11 12 23 24
25 26
BLK
WHT
S4
BLK
S3
REV EO # REV DATE REV BY
-
APPROVED BY
-
-
-
-
-
WHT
S2
GRN
BLK
S1
--
-
1 PH
60 Hz
115 V
25 AMP
CONDENSATE
PAN
HEATER
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JLS
SCALE
INCHES
SHEET #
12/01/03
-
1 OF 1
HGM-3-BS
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2023
DOOR AND FRAME HEATERS
LIGHT
SWITCH
BLU
BLU/WHT
ANTHONY T8 ELECTRONIC LIGHTING
SENSING
BULB
CONDENSOR
FANS
1
C
COMPRESSOR
FRAME HEATERS
WHT
PUR
BLK
WHT
WHT
GRN
DOOR
HEATERS
BLK
BLK
WHT
ORN/BLK ORN/BLK
ORN ORN
8 9 10 1
BALLAST
BLK
3
WHT
4
RED
2
RED
5
BLU
6
BLU
7
BALLAST
BLK
3
WHT
4
RED
2
RED
5
BLU
6
BLU
7
BLU
BLU/WHT
LAMP
BLK
WHT
BLU
BLU/WHT
LAMP
LAMP
DOOR FRAME
1 2
3 4
5 6
7 8
9 10
11 12
23 24
25 26
BLK
EVAPORATOR FANS
SENSOR
BLK
BLK
CONDENSATE
PAN HEATER
BLK
COMM
120
240
AC
BLK
WHT
PUR
NOCNC
WHT
BLK
S4
S3
WHT
S2
BLK
S1
REV EO # REV DATE REV BY
-
APPROVED BY
-
-
-
-
-
-
1 PH
60 Hz
115 V
GRN
25 AMP
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32"
--
DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
HGM-2-TS
GLOVERSVILLE, NY 12078
-
JLS
SCALE
INCHES
SHEET #
12/01/03
-
1 OF 1
WIRING DIAGRAM
M100-2028
SENSING
BULB
FRAME HEATERS
2 1
COMPRESSOR
DOOR & FRAME HEATERS
BLK
WHT
WHT
SENSOR
BLK
JUMPER
COMM 240 AC 120 NC C NO
WHT
BLK
PUR
GRD
DOOR HEATERS
BLU
BLU/WHT
LIGHT SWITCH
ORN ORN BRN BRN
8
9
10 1
ANTHONY T8 ELECTRONIC LIGHTING
BLK
3
WHT
4
BALLAST
RED
2
RED
5
BLU
6
BLU
7
LAMP
BLK
3
WHT
4
8
BALLAST 9 10
1
RED
2
RED
5
BLU
6
BLU
7
LAMP
LAMP
BLK
WHT
BLK
WHT
ANTHONY FRAME
3-S-226
1 2 3 4 5 6 7 8
9 10 11 12 23 24 25 26
ELEC-TRON
EVAP FANS
BLK
3-S-226
1 2 3 4 5 6 7 8
9 10 11 12 23 24 25 26
BLK
WHT
BLK
CONDENSATE PAN HEATER
S1
S3
S4
S2
BLK
GRD
WHT
20 AMP
POWER PLUG
115 V 60 Hz
1 PH
PLUG
END
DETAIL
ELEC-TRON
HGM-2-BS
REV EO # REV DATE REV BY
APPROVED BY
-
-
-
-
-
-
--
-
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32" DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
EO NUMBER
DRAWN BY: DATE DRAWN : APPROVED BY:
-
JWL
SCALE
INCHES
SHEET #
1/29/96
-
1 OF 1
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2022
DOOR & FRAME HEATERS
LIGHT SWITCH
BLU
BLU/WHT
BRN/BLK BRN/BLK
ANTHONY T8 ELECTRONIC LIGHT ING
BLK
3
WHT
ORN
8
BALLAST
ORN
9 10 1
4
RED
2
RED
5
RED
6
RED
7
FRAME HEATERS
SENSING
BULB
COMPRESSOR
COND
FAN
LAMP
ANTHONY FRAME
BLK
WHT
DOOR HEATERS
BLK
WHT
BLK
WHT
LAMP
3-S-226
1 2
3 4 5 6
7 8
2
1
WHT
9 10 11 12 23 24 25 26
BLK
ELEC-TRON
EVAP FANS
BLK
SENSOR
BLK
CONDENSATE
PAN
HEATER
BLK
COMM 240 AC 120 NC C NO
PUR
WHT
BLK
S2
S4
S3
S1
WHT
BLK
REV EO # REV DATE REV BY
APPROVED BY
-
-
-
-
-
115 V 60 Hz
1 PH
GRD
PLUG END
DETAIL
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32"
-
-
DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
--
EO NUMBER
-
DRAWN BY: DATE DRAWN: APPROVED BY
JHB
12/1/98
-
UNIT
SHEET #
INCHES 1 OF 1
HGM-1-TS
GLOVERSVILLE, NY 12078
WIRING DIAGRAM
M100-2027
DOOR & FRAME HEATERS
LIGHT SWITCH
ANTHONY T8 ELECTRONIC LIGHT ING
FRAME HEATERS
SENSING
BULB
COMPRESSOR
COND
FANS
BLK
WHT
BLK
3
WHT
ORN
8
BALLAST
ORN
9
BRN/BLK
BLU
BLU/WHT
DOOR HEATERS
BLK
WHT
BLK
WHT
BRN/BLK
LAMP
10 1
4
RED
2
RED
5
RED
6
RED
7
LAMP
BRN/BLK BRN/BLK
LAMP
ORN
8
BALLAST
ORN
9 10
1
BLK
3
WHT
4
RED
2
RED
5
RED
6
RED
7
LAMP
ANTHONY FRAME
3-S-226
1 2
3 4 5 6
7 8
2
1
WHT
9 10 11 12 23 24 25 26
BLK
ELEC-TRON
EVAP FANS
SENSOR
BLK
COMM 240 AC 120 NC C NO
PUR
WHT
BLK
BLK
BLK
CONDENSATE
HEATER
S2
S4
S3
S1
WHT
BLK
REV EO # REV DATE REV BY
APPROVED BY
-
-
-
-
-
PAN
-
GRD
115 V 60 Hz
1 PH
PLUG END
DETAIL
TOLERANCES UNLESS OTHERWISE SPECIFIED: FRACTIONAL 1/32"
-
DECIMAL 0.031" ANGULAR 1° HOLE LOCATION & SPACING 1/64"
--
EO NUMBER
-
DRAWN BY: DATE DRAWN: APPROVED BY
JHB
12/1/98
-
UNIT
SHEET #
WIRING DIAGRAM
INCHES 1 OF 1
HGM-3-TS
GLOVERSVILLE, NY 12078
M100-2029
Loading...