Hussmann C5NLE Datasheet

HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
D
D
E
B
E
A
C
E
P/N 0441000
Merchandisers
Item Part # Description Wiring Item #
AN ASSEMBLIES AND
THERMOSTATS
A. 9W Fan Assembly (1)
0047000 Fan Motor, Evaporator 0401532 Fan Blade
embossing toward motor
B. 0411744 Standard Non-adjustable (2)
Defrost Thermostat
C. 0137880 Optional Adjustable (3)
Refrigeration Thermostat
Item Part # Description Wiring Item #
L
AMPS AND B
ALLASTS
D. 0376409 Ballast, 2 lamps (4) D. 0376410 Ballast, 3 lamps (4) D. 0376411 Ballast, 4 lamps (4)
E. Fluorescent Lamp (5)
Replace with like fixtures
C5NLE
Data Sheet Set
P/N 0441000
NSF
®
Certified
May, 2003
®
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
C5NLE Data Sheet Set
2 of 6
Engineering
Plan Views
C5NLE
Narrow Footprint
Convertible
Dairy and
Delicatessen
5-2003
Dimensions shown as in. & (mm).
8 ft 12 ft
General
(A) Case Length (without ends or partitions) 96 3/
8 (2448) 144
1
/
2 (3670)
Maximum O/S dimension of case back to front
(includes bumper) 40
5
/
8 (1030) 40
5
/
8 (1030)
Back of case to front of splashguard 33 (840) 33 (840) Back of case to O/S edge of front skid rail 25
1
/
2 (646) 25
1
/
2 (646)
Width of skid rail 4
1
/
2 (114) 4
1
/
2 (114)
RH end of case to outside edge of external support 5
1
/
2 (140) 5
1
/
2 (140)
Distance between edges of external support and center support 40
5
/
8 (1032) 40
5
/
8 (1032)
Distance between edges of center supports NA 44 (1118) Stub-up area between front skid rail and splashguard 5
5
/
8 (143) 5
5
/
8 (143)
Electrical Service (Electrical Field Wiring connection point)
(B) RH End of case to center of farthest knockout 88
3
/8 (2245) 136 1/2 (3467)
(C) Back of case to center of knockout 29
1
/8 (739) 29 1/8 (739)
Length of electrical raceway 35 5/8 (903) 35 5/8 (903)
Waste Outlet
(D) RH End of case to the center of waste outlet 24 1/8 (613) 74 1/4 (1835)
LH End of case to the center of waste outlet 74 1/4 (1835) 74 1/4 (1835)
Water Seal
Edge of water seal to center of waste outlet 4 (102) 4 (102) Outside diameter of the drip pipe 1 1/2 (38) 1 1/2 (38)
*NOTE:Water seal outlet must clear front skid rail;
water seal rotation in forward direction only due to low base.
Refrigeration Outlet
Back of case to center of refrigeration outlet 27 1/2 (699) 27 1/2 (699)
(E) RH end of case to center of refrigeration outlet 9 (230) 9 (230)
29
Electrical
A
1
72
/4 (1835)
1
/8
(739)
40
(1032)
5
/8
5
5
/8
(143)
Waste Outlet
Water Seal (see note*)
B
1
4
/4 (107)
27
(686)
5
40
/8
(1032)
Refrigeration Outlet
(102)
27
(699)
4
C
1
/2
D
4
5
1
1
/2 (114)
1
/2 (140)
3
/8 (035)
25
(648)
1
/2
33
(840)
5
40
/8
(1030)
3 of 6P/N 0441000
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
(Optional
2 Row
Lights)
Refrigeration Outlet
FAN
38
1
/8 (969)
31/8 (79)
71/2
(190)
251/2 (646)
27 (687)
271/2 (699)
291/8 (739)
33 (840)
405/8 (1030)
19
(483)
C O
I
L
4
1
/4
(114)
53/4
(146)
55/8
(143)
C5NLE
33/4 (95)
561/4
(1429)
813/8
(2067)
241/2
(623)
(Optional Rail Lights)
(Optional 16 in. Shelves)
61
(1549)
Impact C5NLE
Dairy / Delicatessen
Dimensions shown as in. & (mm).
REFRIGERATION DATA
Note: This data is based on store temperature
and humidity that does not exceed 75°F and 55% R.H.
C5NLE
Deli Dairy Discharge Air (°F) 29 31 Evaporator (°F) 21 24 Unit Sizing (°F) 19 22
Btu/hr/ft*
LIT &U
NLIT SHELVES
Deli Dairy
Parallel 1580
1500
Conventional 1720
1635
HUSSMANN PEG SHELVES
Parallel 1630
NA
Conventional 1760
NA
*For all refrigeration equipment other than Hussmann, use conventional Btu values.
DEFROST DATA
C5NLE Frequency (hr) 6 Defrost W ater (lb/ft/day) 10.25
(± 15% based on case configuration and
product loading).
OFFTIME C5NLE
Temp Term (°F) 48°F Failsafe (minutes) 35
ELECTRIC OR GAS Not Recommended
Standard Defrost Thermostat
Close on rise: close 48°F — open 33°F
CONVENTIONAL CONTROLS
Low Pressure Backup Control CI/CO** Deli Dairy
14°F / 4°F 17°F / 7°F
Indoor Unit Only, Pressure Defrost Termination** 48°F
**Use a Temperature Pressure Chart to determine PSIG conversions.
PHYSICAL DATA
Merchandiser Drip Pipe (in.) 1 1/2 Merchandiser Liquid Line (in.)3/
8
Merchandiser Suction Line (in.)7/8
Estimated Charge (lb)*** 8 ft 3.2 12 ft 4.5
***This is an average for all refrigerant types. Actual refrigerant charge may vary by approximately half a pound.
Length (in.) added to Lineup by Each End or Insulated Partition 1
1
/2
NOTE: The bumper is 4 in. (102 mm) wide. The center of the top bumper
is 14
1
/8 in. (359 mm) from the floor and the center of the bottom
bumper is 6 in. (152 mm) from the floor.
Multi-deck, 5 Display Levels, Narrow Footprint
NSF Certification
These merchandisers are manufactured to meet ANSI /National Sanitation Foundation (NSF
®
) Standard #7 requirements.
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
C5NLE Data Sheet Set
4 of 6
Impact C5NLE
Dairy / Delicatessen
Electrical Data
8 ft 12 ft
Number of Fans — 9W 4 6
Amperes Watts
Merchandiser
8 ft 12 ft 8 ft 12 ft
Fans
Standard: 120V 60 hz 2.80 4.20 220 330 Energy Efficient: 120V 60 hz 1.52 2.28 100 150 Export: 230V 50 hz 1.12 1.68 176 264
Anti-sweat Heaters
Constant on NA NA Cycling NA NA
Minimum Circuit Ampacity
With Standard Fans 3.00 4.40 With Energy Efficient Fans 1.72 2.48 With Export Fans 1.32 1.88
Maximum Over Current Protection 20 20
Supplemental Gas Heaters NA NA
208V 1ΦΦElectric Defrost NA NA
Standard Lighting
1 Row Canopy 0.51 0.77 59 85
Optional Lighting
1 Row Canopy and 1 Row Rail 1.02 1.54 118 170 2 Rows Canopy 1.02 1.54 118 170 2 Rows Canopy and 1 Row Rail 1.53 2.31 177 255 1 Row Ledge Lights 0.51 0.77 59 85
Optional Shelf Lighting
1 Row of Shelves 0.51 0.77 59 85 2 Rows of Shelves 1.02 1.54 118 170 3 Rows of Shelves 1.53 2.31 177 255 4 Rows of Shelves 2.04 3.08 236 340
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
5 of 6P/N 0441000
Fan Wiring
4 & 6 Fans
Fans
120V POWER
ROWN BAND
B
Optional Shelf Harness and Light Circuits for One Row of Shelves
Shelf Harness
Connector
W
B
120 V
Power
Connector
G
B
W
1
W
G
4
G
BL
R
BL
BL
G
R
BL
Connector
120V NEUTRAL
B
ROWN BAND
B
G
BL
R
Connector
BL G
R
Connector
Defrost
Termination
Thermostat
Dark Blue
Off-time Defrost
2
Refrigeration
Thermostat
Light Blue
Shelf Lighting
G
BL
R
R
Connector
3
To Condensing Unit
}
G
BL
Shelf Light Circuits
BL
Connector
G
Connector
G G
R
5
BL
R
5
Connector
BL
WARNING
All components must have mechanical ground, and the merchandiser must be grounded.
CIRCLED NUMBERS = PARTS LIST ITEM NUMBERS
Grayed components in 12 foot models only.
R = Red Y = Yellow G = Green BL = Blue B = Black W = White
= 120V P
OWER = 120V NEUTRAL = Field GROUND = Case GROUND
R
5
C5NLE Data Sheet Set6 of 6
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Light Circuits
Standard Lighting — 1 Row Canopy Optional Lighting — 1 Row Rail or 1 Row Ledge
120V NEUTRAL
ORANGE OR TAN BAND
120V POWER
ORANGE OR TAN BAND
Light
Switch
W
B
4
BL
Optional Lighting — 2 Rows Canopy
120V NEUTRAL
ORANGE OR TAN BAND
120V POWER
ORANGE OR TAN BAND
Light
Switch
W
B
B
4
W
BL
R
BL
BL
R
5
R
BL
5
5
BL
R
5
R
5
R 5
4
R
BL
BL
5
BL
R
5
R
5
WARNING
All components must have mechanical ground, and the merchandiser must be grounded.
C
IRCLED NUMBERS = PARTS LIST ITEM NUMBERS
Grayed components in 12 foot models only.
R = Red Y = Yellow G = Green BL = Blue B = Black W = White
= 120V POWER
= 120V NEUTRAL