Hussmann C2X-LGE, C4-LE, C4-LGE, C5-E, C5-LE Quick Reference

...
IMPACT Quick Reference Data
Recommended Control Settings
(See installation instructions
for complete information)
C2E
C2LE
C2LGE
C2XE
C2XLE
C2XLGE
C2XGE
CONVERTIBLES
CW2GE CW2XGE CW2UGE CW2EGE CW2XGE
CW2UXGE CW2EXGE
C3LGE
C4LE
C4LGE
C5LE
C5E C5GE C5HE C5LE
C6E C6GE C6HE CGLE
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Failsafe Off Time Duration Min. ** Temp Term °F
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
17/7
6 30 48
17/7
6 30 48
NOTE
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
17/7
6 45 48
14/4
6 30 48
14/4
6 30 48
14/4
4
Recommended Control Settings
(See installation instructions
for complete information)
D5 D5L D5R
D5LR D5HR
D5E D5LE D5RE
D5LRE
D5G D5H
D5HE D5HRE D5NLE
D5NE
DAIRY/DELI
D5GE D5NHE D5NGE
D5NLGE
D6G D6H
D6GE D6HE
D6
D6L
D6E
D6LE
D5ELE
D5EE
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Failsafe Off Time Duration Min. ** Temp Term °F
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
14/4
6 30 48
17/7
6 35 48
14/4
NOTE
17/7
6
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
17/7
6
14/4
6
17/7
14/4
6
6
17/7
6
6 35 48
17/7
6 35 48
Recommended Control Settings
(See installation instructions
for complete information)
M1E
M1GE
M2E
M2GE
M3
MEAT
M3E M3G
M3GE
M4
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Failsafe Off Time Duration Min. ** Temp Term °F
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
14/8
6 35 43
14/8
6 35 43
NOTE
14/4
6 30 48
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
12/2
6 30 48
14/4
6 35 48
12/2
6 30 48
14/4
8 35 48
12/2
6 25 48
Recommended Control Settings
(See installation instructions
for complete information)
M4E
M4NE
M4G
M4GE
M4NGE
M5
MEAT
M5E
M5NE
M5NGE
M5G
M5GE
MWG
MWGE
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Failsafe Off Time Duration Min. ** Temp Term °F
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
14/4
6 30 48
12/2
6 30 48
14/4
6 35 48
NOTE
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
12/2
6 30 48
14/4
6 30 48
12/2
6 35 48
14/4
6 35 48
12/2
6 60 43
Recommended Control Settings
(See installation instructions
for complete information)
P1
P1RO
PRODUCE
P1E
P2RO
P1ROE
NOTE: Critical temperature produce must be kept at or below 41º F.
P4
P2
P2E
P2ROE
P2NE
P4RO
P4E
P4NE
PW6 PW8
PW12
PWE
PW-
PWW-
4E,8E,12E
PWR-
8E,12E
PWEE
PWWEE
PWREE
PWRIE
4E,6E,8E,12E
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Failsafe Off Time Duration Min. ** Temp Term °F
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
14/4
8 35 43
17/7
8 35 43
14/4
NOTE
17/7
14/4
6
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
8
17/7
14/4
6
6
NA
32
21
14/4
17/7
6
45
NA
6
6
NA
32 24
17/7
6
45
NA
FROZEN FOOD ICE CREAM
F6
Recommended Control Settings
(See installation instructions
for complete information)
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Failsafe Off Time Duration Min. Electric Temp Term °F Failsafe Termination (Minutes) Gas Duration Min.
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
-8
-16
-20/-39
NA
NA
-16
-20/-39
NA
NA
L8,12 L8G,12G
F6L LN8G,12G
-8
LGH
LN8,12 LI8,12
LW8,12 LW8G,12G
LW8GH,12GH
LWU90,90G,90GH
LWU138,138G,138GH
LWE LWEG
LWEGH
-12
-20
-27/-39
8
NA 60 30
NOTE
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
L8,12 L8G,12G
LGH
LN8,12 LI8,12
LW8,12 LW8G,12G
LW8GH,12GH
LWU90,90G,90GH
LWU138,138G,138GH
LWE LWEG
LWEGH
-22
-30
-27/-39
NA
FROZEN FOOD
LN8GH,12GH
LI8G,12G
LI8GH,12GH
-10
-20
-27/-39
NA
ICE CREAM
LN8G,12G
LN8GH,12GH
LI8G,12G
LI8GH,12GH
-20
-30
-27/-39
NA
Recommended Control Settings
(See installation instructions
for complete information)
FROZEN MEAT FROZEN MEAT/SEAFOOD
M1LGE
F2XLG
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Electric Temp Term °F Failsafe Termination (Minutes) Gas Duration Min.
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
-10
-20
-26/-41
6 48 40 15
NOTE
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
-2
-16
-11/-20
6 48 60
NA
RL
RL
REACH-INS
RM
RLN RLNI
RLN
RLNI
RMN
Recommended Control Settings
(See installation instructions
for complete information)
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Off Time Duration Min. ** Electric Temp Term °F Failsafe Termination (Minutes) Gas Duration Min.
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
FROZEN FOOD
-5
-11
-18/-34
NA
ICE CREAM
-12
-19
-26/-45
NA
NOTE
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
DAIRY/DELI
WITH INNOVATOR DOORS
20/10
FROZEN FOOD
-5
-11
-18/-34
NA
ICE CREAM
-12
-19
-26/-45
NA
DAIRY/DELI
20/10
Recommended Control Settings
(See installation instructions
for complete information)
SMB
SMBT
SMBV
SMG
SMGT
SERVICE CASES
SMGV
SSG
SSGT
SSGV
WITH REAR
DOORS
ED1
EDS1
WITHOUT
REAR
DOORS
Discharge Air Temp °F Evaporator Temp °F* Low Pressure Cut In/Cut Out
(With Thermostat) (°F) Defrost Frequency Hrs. Off Time Duration Min. ** Temp Term °F Failsafe Termination (Minutes)
#
Cut Out Pressure = Cut In, less 10 PSIG. Use a Temperature Pressure Chart to determine PSIG conversions.
*For temperature pressure controlled cases, cutout pressure must produce listed evaporator temperature. Differential should preserve product integrity while preventing compressor short cycling. **For temperature pressure termination, set termination control to terminate defrost when evaporator temperature reaches 48 degrees F except when othewise listed. Use for non-critical temperature cases only.
11/
NA
#
13/
NA
#
11/
NA
NOTE
: Reverse air defrost is not recommended for any Impact Merchandiser except M1LGE.
#
13/
NA
#
11/
NA
#
13/
NA
#
11/
#
NA
11/
NA
#
11/