Hussmann C3LGE Datasheet

HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
P/N 0412043A
Note: Changed items have been underlined
.
Merchandisers
®
E
E
E
E
C3LGE
Data Sheet Set
P/N 0412043A
NSF
®
Certified
August 2004
Item Part # Description Wiring Item #
F
AN ASSEMBLIES AND THERMOSTATS
A. 9W Fan Assembly (1)
0047000 Fan Motor, Evaporator 0315470 Fan Blade
embossing toward motor
B. 0411744 Standard Non-adjustable (2)
Defrost Thermostat
C. 0137880 Optional Adjustable (3)
Refrigeration Thermostat
Item Part # Description Wiring Item #
L
AMPS AND BALLASTS
D. 0428648 Ballast, Electronic
2 lamps (4)
D. 0428649 Ballast, Electronic
3 lamps (4)
E. Fluorescent Lamp (5)
Replace with like fixtures
2 of 8
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
C3LGE Data Sheet
Dimensions shown as inches and (mm).
Engineering
Plan View
8 ft 12 ft
General
(A) Case Length (without ends or partitions) 96 3/8 (2448) 144 1/2 (3670)
Maximum O/S dimension of case back to front (includes bumper) 46 1/4 (1174) 46 1/4 (1174) Back of case to front of splashguard 38 5/
8 (981) 38
5
/
8 (981)
Back of case to O/S edge of front skid rail 29
1
/
2 (749) 29
1
/
2 (749)
Width of skid rail 4
1
/2 (114) 4 1/2 (114)
RH end of case to outside edge of external support 5 1/
2 (140) 5
1
/
2 (140)
Distance between edges of external support and center support 40
5
/
8 (1032) 40
5
/
8 (1032)
Distance between edges of center supports NA 44 (1118) Stub-up area between front skid rail and splashguard 7 (178) 7 (178)
Electrical Service (Electrical Field Wiring connection point)
(B) RH End of case to center of farthest knockout 88
3
/8 (2245) 136 1/2 (3467) Back of case to center of knockout 35 3/8 (899) 35 3/8 (899) Length of electrical raceway 34 5/
8
(878) 34
5
/
8
(878)
Waste Outlet
(C) RH End of case to the center of waste outlet 24
1
/8
(613) 72
1
/4
(1835)
LH End of case to the center of waste outlet 72
1
/4 (1835) 72 1/4 (1835) Back O/S of case to center of waste outlet 27 1/
2 (699) 27
1
/
2 (699)
Water Seal
Edge of water seal to center of waste outlet 4 (102) 4 (102) Outside diameter of the drip pipe 1
1
/2 (38) 1 1/2 (38)
NOTE: Water seal outlet must clear front skid rail; water seal rotation in forward direction only due to low base.
Refrigeration Outlet
Back of case to center of refrigeration outlet 30 5/
8 (778) 30
5
/
8 (778)
(D) RH end of case to center of refrigeration outlet 9 (230) 9 (230)
01-2004
Dairy/Delicatessen Precut & Packaged
Produce
35 3/8
(899)
Electrical
72 1/4
(1835)
40 5/8
(1032)
7 (178)
B
4 1/4 (108)
27 1/2
(699)
Waste Outlet
Water Seal
(See note)
Front
40 5/8
(1032)
Refrigeration
Outlet
30 5/8
(778)
4 (102)
C
D
51/2 (140) 13/8 (35)
41/2 (114)
29 1/2
(749)
38 5/8
(981)
46 1/4
(1174)
A
P/N 0412043A
3 of 8
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
19
(483)
26
30 1/4
(660)
(766)
(Note*)
(Note*)
(305)
12
18
(457)
(1670)
5 1/8
(132)
(Note*)
48
(1219)
3 3/4
(95)
46 1/4
(Note:* Optional accessory items).
7 3/4
(197)
FAN
C O
I
L
(Note*)
18
(457)
(Note*)
27 1/2
(699)
29 1/2
(749)
30 5/8
(778)
35 3/8
(899)
(981)
38 5/8
(1174)
65 3/4
14 1/8
(359)
6 1/8
(156)
REFRIGERATION DATA
Note: This data is based on store temperature
and humidity that does not exceed 75°F and 55% R.H.
C3LGE Discharge Air °F 30 Evaporator °F 21 Unit Sizing °F 19
Btu/hr/ft** C3LGE Parallel 1280 Conventional 1360
**For all refrigeration equipment other than Husssmann, use conventional BTU values.
DEFROST DATA
C3LGE Frequency (hr) 6 Defrost Water (lb/ft/day) 6
(±15% based on case configuration and product loading.
O
FFTIME C3LGE
Temp Term °F 48°F Failsafe Minutes 30
ELECTRIC OR GAS Not Recommended
Standard Defrost Thermostat
Close on rise: close 48°F – open 33°F
CONVENTIONAL CONTROLS
Low Pressure Backup Control CI/CO** 14/4°F
Indoor Unit Only, Pressure Defrost Termination** 48°F
**Use a Temperature Pressure Chart to determine PSIG conversions.
PHYSICAL DATA
Merchandiser Drip Pipe (in.) 1 1/2 Liquid Line (in.)
3
/8
Suction Line (in.)
7
/8
Estimated Charge (lbs)***
C3LGE 8 ft 2.7 12 ft 3.9
***This is an average for all refrigerant types actual refrigerant charge may vary by approximately half a pound.
Length (in.) Added to Lineup by Each End or Insulated Partition 1
1
/2
Impact C3LGE
Delicatessen/Dairy
Precut & Packaged Produce
Multi-deck, 4 Display Levels
Dimensions shown as inches and (mm).
NSF Certification
These merchandisers are manufactured to meet ANSI /National Sanitation Foundation (NSF
®
) Standard #7 requirements.
4 of 8
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
C3LGE Data Sheet
Impact C3LGE
Delicatessen/Dairy Precut & Packaged Produce
Electrical Data
8 Ft 12 Ft
Number of Fans — 9W 2 3
Amperes Watts
Merchandiser 8 Ft 12 Ft 8 Ft 12 Ft
Fans
Standard (120V 60Hz) 1.40 2.10 100 150
Energy Efficient (120V 60Hz) 0.76 1.14 50 75
Export (230V 50Hz) 0.76 1.14 114 171
Constant on Anti-sweat Heaters NA
Cycling Anti-sweat Heaters NA
Minimum Circuit Ampacity
With Standard Fans (120V 60Hz) 1.60 2.30
With Energy Efficient Fans (120V 60Hz) 0.96 1.34
Export (230V 50Hz) 0.96 1.34
Maximum Over Current Protection 120V 20 20
Maximum Over Current Protection 230V 15 15
Supplemental Gas Heaters NA
208V 1ΦΦElectric Defrost NA
Standard Lighting
1 Row Canopy 0.51 0.77 59 85
Optional Lighting
1 Row Canopy and 1 Rail 1.02 1.54 118 170
2 Rows Canopy 1.02 1.54 118 170
2 Rows Canopy and 1 Row Rail 1.53 2.31 177 255
Optional Shelf Lighting
1 Row of Shelves 0.51 0.77 59 85
2 Rows of Shelves 1.02 1.54 118 170
3 Rows of Shelves 1.53 2.31 177 255
P/N 0412043A
5 of 8
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Defrost
Termination
Thermostat
Refrigeration
Thermostat
Dark Blue
3
To Condensing Unit
}
Light Blue
2
Grayed components in 12 foot models only.
R = Red Y = Yellow G = Green BL = Blue B = Black W = White
= 120V P
OWER = 120V NEUTRAL = Field GROUND
WARNING
All components must have mechanical ground, and the merchandiser must be grounded.
CIRCLED NUMBERS = PARTS LIST ITEM NUMBERS
Fan Wiring
Offtime Defrost
= Case GROUND
Connector
Connector
G
Connector
Connector
Connector
Connector
Connector
Optional Shelf Harness and Light Circuits for One Row of Shelves
120 V Power
B
W
G
B
BL
BL
BL
G
G
R
R
BL
BL G
W
BL
Shelf Harness
Shelf Light Circuits
BL
G
R
5
4
W
BL
R
5
BL
R
G
G
R
R
R
G
Shelf Lighting
G G
R
BL
5
BL
Connector
Connector
B
4 & 6 Fans
120V NEUTRAL
BROWN BAND
120V POWER
Fans
1
B
ROWN BAND
6 of 8
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
Light Circuits
C3LGE Data Sheet
Standard Lighting 1 Row Canopy or Optional 1 Row Rail
120V NEUTRAL
ORANGE OR TAN BAND
120V POWER
ORANGE OR TAN BAND
Light
Switch
W
B
4
Optional Lighting 2 Rows Canopy
120V NEUTRAL
ORANGE OR TAN BAND
120V POWER
ORANGE OR TAN BAND
Light
Switch
B
W
4
W
B
4
BL
R
BL
BL
BL
BL
5
R
R
BL
BL
5
R
5
BL
R
55
BL
R
5
R
5
R
5
R
5
WARNING
All components must have mechanical ground, and the merchandiser must be grounded.
CIRCLED NUMBERS = PARTS LIST ITEM NUMBERS
Grayed components in 12 ft models only.
R = Red Y = Yellow G = Green BL = Blue B = Black W = White
= 120V POWER
= 120V NEUTRAL
7 of 8
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
P/N 0412043A
SHELF CONFIGURATION
This merchandiser is designed for three (3) shelves.
The depth of the shelves used are critical to case performance.
The use of peg shelves is NOT recommended on C3LGE cases. Depth and angle requirements are listed below.
Top Shelf
Shelf Depth Shelf Angle
12 inches 0 º,10 º,15º,30 º,45 º
14 inches 30 º,45º
Second Shelf
Shelf Depth Shelf Angle
14 inches 0 º,10 º,15º,30 º,45 º
16 inches 30 º,45º
Third Shelf
Shelf Depth Shelf Angle
16 inches 0 º,10 º,15º,30 º,45 º
18 inches 30 º,45º
Top Shelf
(12 in., 15o Shown)
Second Shelf
(16 in., 15o Shown)
Third Shelf
(18 in., 15o Shown)
8 of 8
HUSSMANN CORPORATION, Bridgeton, MO 63044-2483 U.S.A.
C3LGE Data Sheet
REPLACING CANOPY AND SHELF LAMP BALLAST
The ballast for the canopy and shelf lamps are located above the light tray on the right-hand end (when facing case) of the merchandiser.
To access the ballast:
1. Remove screws from the front-lip of light tray flange covering the bottom edge of the canopy. Also remove screws located near the middle-rear of light tray.
3. Swing front of light channel down on it’s rear hinge.
4. Service or replace ballasts as required.
5. Reassemble items as they were originally installed. Make sure that wires are not pinched by re-installed light tray.
NOTE: Rail lamp ballast is located behind the lower front panel.
Remove Screws
Light Tray
Ballast
Light Tray
Hinge
Light Tray