1.1 SHIPPING DAMAGE
General
All equipment shouldbe thoroughly
examined for shipping damage before and
during unloading.
This equipmenthasbeen carefully
inspectedat our factory and the carrier
hasassumed responsability for safe
arrival.If damage ,either apparent or
concealed,claim mustbe madeto the
carrier.
PB2402474A
Location
Thesemerchandisersaredesigned for
indoor operation witharecommended
operating room ambient temp. of 65 ºF
(18 ºC)/50 % RHto 90 ºF(32 ºC)/65%
RH. Their Performance is affected by store
air currents when the doorsare open.Do
Not allow air conditioning, electric fans ,
or opened doors and windows to create air
currents around these merchandisers nor
should they be exposed to direct sunlight
or other heat sources.
Apparent Loss or damage
All equipment shouldbe thoroughly
examined for shipping damage before and
during unloading.
This equipmenthasbeen carefully
inspectedat our factory and the carrier
hasassumed responsability for safe
arrival.If damage ,either apparent or
concealed,claim mustbe madeto the
carrier.
Concealed Loss or Damage
When loss or damage is not apparent until
NOTE:
The condensing unit draws ambient air
through the front of the unit and
discharges hot air out the rear of the unit .
In order to maintain proper refrigerator
performance and compressor life,a
minimun space of4” (10 cm)must be
maintained between the refrigerator and
surrounding surfaces.
after equipment is uncrated,claim for
concealed damage ismade.Upon
discovering damage ,make requestin
writing to carrier for inspection within15
days and retain all packing. The carrier
will supply inspection report and required
claim forms
Page 4
SERIES
MERCHANDISERS
MEDIUMTEMPERATURE
PB2402474A
2.1 CABINET PREPARATION BEFORE OPERATION
Leveling Cabinet
This merchandiser mustbeinstalled
leveled (from back and end to end) to
allow maximun draining of the condensate
water as well as proper door aligment and
operation.
The merchandiserhas been shipped with
adjustable cabinet levelers installed and
Shelf instalation
After the cabinet has been leveled and is in
itsfinalposition,the shelves maybe
installed. There are two differents shelves,
one of them isa solid shelf, this must be
placed on the botton next to theback.
Others shelves maybeinstalled, Shelf
spacing is adjustableby positioning the
shelfclipsaccording to your loading
requirements.
adjustment can be made if required.
shelves
Solid shelf
Levelers
NOTE:
Do not move the Solid
shelf to the front
Page 5
SERIES
MERCHANDISERS
MEDIUMTEMPERATURE
2.1 CABINET PREPARATION
FOR OPERATION
Door Seal
Hinge doors . Check to ensure the door
torque is capable of closing the door
automatically. Open the door45
and relase it , the door should close and
seal.
To adjust the torque,placeawrench on
each of the2 nuts located on the botton
hinge. Hold the top wrench firmly and lose
degrees
PB2402474A
3.1 DIMENSION
W
H
the botton nut.Torque is increased or
decreaseby rotating the top nut. After
adjustment hasbeen made,Tighten the
botton nut.
Lamps
This merchandiser does not have Lighting
switch,Interior lamps are eqipped with a
plastic shield,besure the shield is
installed properly.
All uprightmerchandisersare equipped
withahermetic or semi-hermetic
compressor. The condenser is fin and tube
construction. The air is takenin the frontdown of the cabinet and discharged out by
the front down of the cabinet .(see fig.1)
The temperature control is located inside
They us e an special system so that both
units work at the sametimes, only during
the first day, after that , they will work
alternating day by day.
Clean condensing every month.
the all in one unit.(see fig.1 A).
Others merchandisers with2 doors, have
two condenser units,their function is
different than merchandisers with one
door.
A
FIG. 1
Page 7
SERIES
MERCHANDISERS
MEDIUMTEMPERATURE
5.1 STARTUP /OPERATION
Temperature control
The temperature control is located on the
condensing unit on the wall, For these
merchandisers the control set at number 4
position will mantain product temparature
in a range of 36 ºF to 42 ºF(2.2ºC to 5.5
ºC) .
The control is adjustableby runinig the
dial one number at clockwise to obtain
colder temperatures.Turn it
counterclockwise to obtain warmer
temparatures.
PB2402474A
Electrical Supply
WARNING
Equipment MUST be
GROUNDED!
Wiring of the unit iscomplete when it is
shipped form the factory.The unit is
suppliedwith a three conductor electrical
cord wich extends from the rear of the
unit. Plug the unit into correct grounded
outlet. It is recommendedthat a separate
circuitbe run for each cabinet to prevent
the posibility of another appliance blowing
Lighting
Interior light and lighted sign remain on
all time. An electronic ballast is locate on
the top or on condensing unit.
Defrost Water Evaporation
External drain plumbing is not required .
Behind the cooling unit housing cover ,
there is a tray for gathering and directing
defrost water from the evaporator coil to
a fuse, causing subsequent loss of product.
condensing unit area,it servesas a
reservoir for the storage of the water until
it is evaporatoredby a hot gasloop from
the compressor.
Plug in Instalation
Page 8
SERIES
MERCHANDISERS
ONLY FOR BCH6,8,10
ELECTRICAL SPECIFICATIONS
VOLTAGE (VOLTAJE)115 V
FRECUENCY (FRECUENIA)60 Hz
MAX.LEAKAGE CURR ENT (CORRIENTE DE FUGA ) 0.5 mA
MAX. RESISTENCE (RESISTENCIA MAX)0.14
(CONDITIONS STD ASHRAE)
BLACK (NEGRO)
WHITE (BLANCO)
BLACK (NEGRO)
WHITE (BLANCO)
SWITCH
(INTERRUPTOR)
WHITE
RED (ROJO)
CONDENSER
FAN MOTOR
(MOTOR CONDE NSADOR)
EVAPORATOR
FAN MOTOR
(MOTOR EVAPORA DOR)
BALLAST
(BALASTRA)
EXTERIOR LAMP
INTERIOR LAMP
BLACK (NEGRO )
BLACK
MEDIUMTEMPERATURE
ONLY FOR BCH13,16,18,27
WARNING
UNPLUG THE COOLER BEFORE
DESSERVICE TO AVDID INJURIES
ADVERTENCIA
ANTES DE HACER CUALQUIER REPARACION
DESCONECTE EL APARATO DE LA TOMA
DE CORRIENTE PARA EVITAR ACCIDENTES
BLUE ( AZUL)
BLUE (AZUL)
RED (R OJO)
START
CAPACITOR
BLACK
10
THERMOSTAT
(TERMOSTATO)
12
RELAY
THERMIC
11
13
BLACK
14
3
BLACK
2
ELECTRICAL S PECIFICATI ONS
VOLTAGE (VOLTAJE )1 15 V
FRECUENCY (FRECUENIA)60 Hz
MAX.LEAKAGE CURRENT (CORRIENTE DE FUGA) 0.5 mA
MAX. RESISTENCE (RESISTENCIA MAX)0.14
(CONDITIONS STD ASHRAE)
BLACK
WHITE
RED
RED
CONDENSER
FAN MOTOR
(MOTOR CONDENSADOR)
EVAPORATOR
FAN MOTORS
(MOTOR EVAPORADOR)
SWITCH
(INTERRUPTOR)
(OPCIONAL)
WHITE
WHITE
(2)
RED
BLACK
BALLAST
(BALASTRA)
EXTERIOR LAMP
INTERIOR LAMP
BLACK
BLACK
PB2402474A
WARNING
UNPLUG THE COOLER BEFORE
DESSERVICE TO AVDID INJURIES
RED
10
12
RELAY
THERMIC
ADVERTEN CIA
BLUE
BLUE
BLUE
BLUE
START
CAPACITOR
BLACK
11
13
BLACK
14
3
BLACK
2
ANTES DE HACER CUALQUIER REPARACION
DESCONECTE EL APARATO DE LA TOMA
DE CORRIENTE PARA EVITAR ACCIDENTES
THERMOSTAT
(TERMOSTATO )
BLACK
WHITE
BLACK
CONDENSER
FAN MOTOR
(MOTOR CONDENSADOR)
EVAPO RATOR
FAN MO TORS
(MOTOR EVAPORADOR)
(2)
SWITCH
(INTERRUPTOR)
BLACK
MOTOPROTECTOR
(OPCIONAL)
-
+
115 VOLTS
ONLY FOR BCH37/45/68
ELECTRICAL SPECIFICATIONS
VOLTAGE (VOLTAJE)115 V
FRECUENC Y ( FRECUENI A)60 Hz
MAX.LEAK AGE CURRE NT (CORR IENTE DE FUG A) 0.5 mA
MAX. RES ISTENCE (RESISTENCI A MAX)0.14
BLACK
BLACK
(CONDITIONS STD ASHRAE)
RED
RED
RED
RED
BLACK
WHITE
EXTERIOR LAMP
EXTERIOR LAMP
INTERIOR LAMP
THERMOSTAT
(TERMOSTATO)
C2
C1
L1
N
BALLAS T
(BALASTRA)
RED
10
12
RELAY
THERMIC
BLUE
11
13
14
3
2
BLUE
CAPACITOR
BLACK
BLACK
BLUE
BLUE
BLUE
BLUE
START
BLACK
BLACK
WARNING
UNPLUG THE COOLER BEFORE
DESSERVICE TO AVDID INJURIES
ADVERTENCIA
ANTES DE HACER CUALQUIER REPARACION
DESCONECTE EL APARATO DE LA TOMA
DE CORRIENTE PARA EVITAR ACCIDENTES
RED
CONDENSER
FAN MOTOR
(MOTOR CONDENSADOR)
EVAPORATOR
FAN MOTORS
(MOTOR EVAPORADOR)
(2)
SWITCH
(INTER RUPTO R)
WHITE
BLACK
BLACK
BLACK
WHITE
10
12
RELAY
THERMIC
+
115 VOLTS
11
13
14
3
2
MOTOPROTECTOR
(OPCIONAL)
-
START
CAPACITOR
BLACK
BLACK
BLACK
WHITE
-
115 VOLTS
MOTOPROTECTOR
(OPCIONAL)
N
Page 9
SERIES
MERCHANDISERS
MEDIUMTEMPERATURE
6.1 Spare Parts
9
23
8
6
24
29
5
28
4
27
PB2402474A
17
10
11
19
12
16
9
14
15
20
6
19
1
21
22
20
26
18
8
16
13
7
2
3
Page 10
HUSMANN CORPORATION
1299 St Charles Rock Road
Bridgeton MO63440-2483
MEXICO D.F.
Arroz No 155
Col. Santa Isabel Industrial C.P. 09820
Iztapalapa, Mexico D.F.
Tel. (52)558503-1993
Fax. (52) 5585031985
Monterrey N.L.
Carretera Mexico Laredo Km 1009
Cienega de Flores, Nuevo Leon
C.P. 65550
Tel (52) 818318-6403
Fax: (52) 8183186496
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.