Hussmann B3XC-LEP Specifications

P/N_0487015_D
C
A
C
D
D
D
B
G
E
G
B3XC-LEP
Technical Data Sheet
P/N 0487015_D
®
Certified
March 2010
Item Part # Description Wiring Item #
F
AN ASSEMBLIES
8 Ft & 12 Ft
A. 12W Standard Fan Assembly (1)
0047000 Fan Motor, Evaporator
(MO.4410103)
0461805 Fan Blade (FB.4780446) 12W Energy Efficient Fan Assembly (1) 0477655 Fan Motor, Evaporator
(MO.4410546)
0461805 Fan Blade (FB.4780446)
6 Ft Only
A. 7W Standard Fan Assembly (1)
0058698 Fan Motor, Evaporator
(MO.4410102)
0142780 Fan Blade (FB.0142780) 7W Energy Efficient Fan Assembly (1) 0477654 Fan Motor, Evaporator
(MO.4410545)
0142780 Fan Blade (FB.0142780)
Item Part # Description Wiring Item #
T
HERMOSTATS
B. Optional Adjustable Refrigeration Thermostat (2)
LAMPS AND BALLASTS
C. Ballast, Electronic (3)
0480130 2 lamps (BA.4481676) 0480131 3 lamps (BA.4481654) 0480132 4 lamps (BA.4481677)
D. Fluorescent Lamp (4)
Replace with like fixtures
LED F
IXTURES AND POWER SUPPLY
E. 0501213 Power Supply (EP.4481861) (5)
F. LED Canopy Fixture (6)
Replace with like fixtures — See Page 5.
G. LED Shelf Fixture (7)
Replace with like fixtures — See Page 5.
©2010 HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-522-1900 • WWW.HUSSMANN.COM
We reserve the right to change or revise specifications and product design in connection with any feature of our products. Such changes do not entitle the buyer to corresponding changes, improvements, additions or replacements for equipment previously sold or shipped.
Note: Revision D adds Btu note (page 3), EcoShine LED (page 4) and parts (page 5), and revises canopy wiring diagram (page 6). Other changes marked by bar, underline or circle.
2 of 12
U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-522-1900
B3XC-LEP Technical Data Sheet
Engineering
Plan Views
Dimensions shown as inches and (mm).
Bulk Convertible
05-2006
NOTE: Case-to-Case Electrical Connections are made IN FRONT OF SPLASHGUARD.
4 3/4 (122)
Wireway
26 1/2
(673)
Splashguard
35 5/8
(905)
46
(1168)
A
42 3/4
(1086)
3 In.
(77 mm)
Required
Air Gap
Refrigeration
Outlet
Electrical
Stub Up Area
6 x 6
(152x152)
Waste Outlet
Waste Outlet
FRONT
30 1/4
(768)
B
D
8 (203)
3 7/8 (98)
12 (305)
42 3/4
(1086)
45 1/8
(1146)
C
3 1/8 (80)
3 (76)
28
(712)
37 3/8
(950)
Electrical Field Connection
34 3/8
(873)
B3XC
6 ft 8 ft 12 ft
General
(A) Case Length (without ends or partitions) 72 3/8 (1838) 96 3/8 (2448) 144 1/2 (3670)
(Each end and insulated partition adds 1 1/2 in. (38 mm) to case line up.)
Maximum O/S dimension of case back to front
(includes bumper) 46 (1168) 46 (1168) 46 (1168)
Back of case to front of splashguard 37 3/8 (950) 37 3/8 (950) 37 3/8 (950) Back of case to O/S edge of front leg 34 3/8
(873) 34
3
/8
(873) 34
3
/8
(873)
Distance between edges of external legs and center legs 29
1
/2 (750) 42 3/4 (1085) 42 3/4 (1085) Distance between edges of center legs NA NA 45 1/8 (1146) Distance between front legs and splashguard 2 5/8 (66) 2 5/8 (66) 2 5/8 (66)
Electrical Service (Electrical Field Wiring connection point)
(B) RH End of case to center of stub up area 60 1/4 (1530) 84 1/4 (2140) 132 3/8 (3363)
Back of case to center of stub up area 28 (712) 28 (712) 28 (712) Length of electrical wireway 26 1/2 (673) 26 1/2 (673) 26 1/2 (673)
(C) RH End of case to LH end of wireway 66 1/8 (1680) 90 1/8 (2289) 138 1/4 (3511)
Waste Outlets (One each end)
(D) RH End of case to the center of LH waste outlet 60 3/8 (1533) 84 3/8 (2143) 132 1/2 (3366)
RH End of case to the center of RH waste outlet 12 (305) 12 (305) 12 (305) Back O/S of case to center of waste outlets 35 5/8 (905) 35 5/8 (905) 35 5/8 (905) Schedule 40 PVC drip pipe 1 1/4 (32) 1 1/4 (32) 1 1/4 (32)
Refrigeration Outlet
Back of case to center of refrigeration outlet 30 1/4 (768) 30 1/4 (768) 30 1/4 (768) RH end of case to center of refrigeration outlet 8 (203) 8 (203) 8 (203)
PHYSICAL DATA
Merchandiser Drip Pipe (in.) 1 1/4 Merchandiser Liquid Line (in.)
3
/8
Merchandiser Suction Line (in.)
7
/8
Wireway
REFRIGERATION DATA
Note: This data is based on store temperature and humidity that does not exceed 75°F and 55% R.H.
B3XC-LEP DAIRY/DELI/PRODUCE
U
NLIT
LIT
Discharge Air °F 34 32
Evaporator °F 28 26
Unit Sizing °F 26 24
For red meat application, lower evaporator
temperature and unit sizing 3°F. increase Btu 5%.
Btu/hr/ft‡— Unlit Shelves
‡‡
B3XC-LEP DAIRY/DELI/PRODUCE
Parallel Conventional
U
NLIT 1215 1295
Optional energy efficient motors reduce the
refrigeration load by 27 Btu/hr/ft.
‡‡
Add 10 Btu/hr/ft per shelf row for LED fixtures.
Add 20 Btu/hr/ft per shelf row for fluorescent lamps.
DEFROST DATA
B3XC-LEP
Frequency (hr) 8
Defrost Water (lb/ft/day) 7
(±15% based on case configuration and product loading.
O
FFTIME B3XC-LEP
Time (minutes) 30
ELECTRIC OR
GAS
Not Recommended
CONVENTIONAL CONTROLS
Low Pressure Backup Control
CI/CO*
B3XC-LEP
DAIRY/DELI/PRODUCE
Temp (°F) 19°F / 9°F
Indoor Unit Only,
Pressure Defrost Termination* 48°F
*Use a Temperature Pressure Chart to determine PSIG conversions.
For red meat application, reduce low pressure
backup control by 3°F.
Estimated Charge** B3XC-LEP
6 ft 2.3 lb 37 oz 1.0 kg
8 ft 3.2 lb 51 oz 1.5 kg
12 ft 4.5 lb 72 oz 2.0 kg
**This is an average for all refrigerant types. Actual refrigerant charge may vary by approximately half a pound.
Dimensions shown as inches and (mm).
P/N 0487015_D 3 of 12
HUSSMANN CORPORATION • BRIDGETON, MO 63044-2483 U.S.A. • WWW.HUSSMANN.COM
4 1/2 (114)
35 5/8 (905)
4 3/4 (120)
34 3/8 (873)
46 (1168)
37 3/8 (950)
30 1/4 (768)
34 1/8
(867)
19 5/8
(498)
FAN
C O
I
L
B3XC-LEP
17 1/4
(438)
3 In. (77 mm)
Required
Air Gap
26 3/8
(670)
6 (152)
Electrical
Case to Case
Connections
21 1/8
(536)
59 7/8
(1521)
Refrigeration
Outlet
3 5/8
(92)
39 1/4
(997)
37 1/8
(943)
11
(279)
Impact
Excel
B3XC-LEP
Bulk Convertible
Multi-deck, Wide Footprint, Extended Canopy Low Front, 3 Display Levels
NSF Certification
This merchandiser model is manufactured to meet ANSI/NSF (National Sanitation Foundation) Standard #7 requirements for construction, materials & cleanability.
See Page 11 for shelf arrangement.
Electrical Data
6 ft 8 ft 12 ft Number of Fans—12W 2 3 Number of Fans—7W 2
Amperes Watts
6 ft 8 ft 12 ft 6 ft 8 ft 12 ft Evaporator Fan
120V 60Hz Standard 1.00 1.30 1.95 78 100 150 120V 50Hz Standard 1.10 1.50 2.25 84 114 171 230V 60Hz Export 0.50 0.66 0.99 78 100 150 230V 50Hz Export 0.56 0.76 1.14 84 114 171 120V 60Hz Energy Efficient 0.38 0.60 0.90 28 36 54 230V 60Hz Energy Efficient 0.20 0.30 0.45 28 36 54
Minimum Circuit Ampacity
120V 60Hz Standard 1.20 1.50 2.15 120V 50Hz Standard 1.30 1.70 2.45 230V 60Hz Export 0.70 0.86 1.19 230V 50Hz Export 0.76 0.96 1.34 120V 60Hz Energy Efficient 0.58 0.80 1.10 230V 60Hz Energy Efficient 0.40 0.50 0.65
Maximum Over Current Protection 120V 20 20 20 Maximum Over Current Protection 230V 15 15 15
Standard Lighting (T-8 fluorescent)
1 Row Canopy 0.51 0.51 0.77 59 59 85
Optional Lighting (T-8 fluorescent)
1 Row Rail Light 0.51 0.51 0.77 59 59 85 1 Row of Shelves 0.51 0.51 0.77 59 59 85 2 Rows of Shelves 1.02 1.02 1.54 118 118 170 3 Rows of Shelves 1.53 1.53 2.31 177 177 255
EcoShine Multi-deck Canopy Normal (CRI) — 120VAC, 50/60Hz
2 Row Canopy (Front & Rear) 0.28 0.55 0.82 33 66 98 1 Row of Shelves 0.10 0.20 0.29 12 24 35 2 Rows of Shelves 0.20 0.39 0.58 24 47 70 3 Rows of Shelves 0.29 0.58 0.88 35 70 105
EcoShine Multi-deck Canopy High CRI — 120VAC, 50/60Hz
2 Row Canopy (Front & Rear) 0.32 0.63 0.93 38 75 112 1 Row of Shelves 0.12 0.23 0.35 14 28 42 2 Rows of Shelves 0.23 0.47 0.70 28 56 84 3 Rows of Shelves 0.35 0.70 1.05 42 84 126
Optional Always*Bright LED Lighting — 120VAC, 50/60Hz
2 Row Canopy 0.55 0.71 1.08 66 85 130 1 Row of Shelves 0.19 0.23 0.38 23 28 45 2 Rows of Shelves 0.34 0.47 0.67 41 56 80 3 Rows of Shelves 0.53 0.74 1.11 63 89 133
120V Lighting Circuit Total = Standard Lighting + Total Optional Lighting + Optional Shelf Lighting 230V Lighting Circuit Total = Multiply 120V Lighting Circuit Total by 0.52
4 of 12
U.S. & CANADA 1-800-922-1919 • MEXICO 1-800-522-1900
B3XC-LEP Technical Data Sheet