Husky E85 STB Owner's Manual

Model #6360
Recommended Installation, Maintenance
and Inspection Instructions
E85 Reconnectable Safe-T-Break
®
RECONNECT
WARNING This device separates at less than 200 lbf / 889.6 N pull force!
INSTALLATION INSTRUCTIONS
1. Attach scale to where the Safe-T-Break® will be installed. Apply 200 lbf / 889.6 N pull force at various angles and check dispenser and hose for damage. Refer to UL 567 for details. If no damage occurred, release pull and complete installation.
2. Install Safe-T-Break® in the direction of the ow arrows.
3. Use pipe thread sealant (not Teon tape) approved for E85 on the male threads of the
hose section.
4. Tighten approximately 1 to 2 turns past hand tight - do not overtighten.
5. Only connect to E85 compatible ttings.
6. High hose dispenser – Install the Safe-T-Break® between the hose sections. Verify that the whip hose is the correct length.
7. Low hose dispenser – Install the Safe-T-Break® down stream of any hose retractor cable coupling.
8. Pressurize system and visually inspect for leaks.
DO NOT OVERTIGHTEN. DO NOT WRENCH ACROSS COUPLING.
DO NOT INSTALL DIRECTLY TO THE DISPENSER.
RECONNECT INSTRUCTIONS
• Shut off dispenser and relieve line pressure.
• Before Reconnecting:
Inspect the entire dispensing system and Safe-T-Break® for damage. Conduct pull test for dispenser integrity (see Step 1 of Installation Instructions above). Lubricate seal and valve halves.
• After Reconnected:
Check reconnected Safe-T-Break® for proper engagement. Check for electrical conductivity. Check for leaks at Safe-T-Break®. Check for proper ow of fuel.
ONLY PROPERLY TRAINED PERSONNEL SHOULD RECONNECT SAFE-T-BREAKS
TESTING / MAINTENANCE / INSPECTION
E85 STB
®
.
Daily
• Check for leaks / stains.
• Check for damage.
Monthly
• Check "remove by" date.
Annually
• Conduct pull test – disconnect,
inspect interior for debris, discoloration, and foreign matter.
Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
• All drive aways, maintenance and
inspection activities must be logged using the serial number of the individual product.
• Apply city, state, or federal testing regulations as appropriate.
ANY TEST / INSPECTION FAILURE
REQUIRES IMMEDIATE EQUIPMENT
REPLACEMENT OR REMOVAL FROM
SERVICE.
MADE IN THE USA
Page 1 009211-2 7/2010
ALWAYS ADHERE TO INSTALLATION / USAGE INSTRUCTIONS AND WARNINGS.
Improper use may result in injury, damage, or hazardous spill.
GENERAL WARNINGS / INSTRUCTIONS
• Use of equipment is at individuals’ own risk.
• Always abide and adhere to city, state, and
federal regulations regarding use and
installation of dispensing equipment.
• Always follow the dispenser manufacturer ’s
instructions.
• Always turn off all power to dispenser
during maintenance and inspection activities.
• Always close the shear valves during
maintenance and inspection activities.
• Always relieve pressure from system prior
to performing maintenance activities.
• Always check continuity after installation
using a megohmeter (Refer to PEI RP 400
for details).
• Always replace or remove from service
damaged or leaking dispensing equipment
immediately.
• Always report leaks / spills / accidents
to appropriate authorities.
• Always wear appropriate safety equipment
during maintenance activities.
• Always have appropriate re extinguishing
equipment within 5 ft / 1.5 m of dispensers.
• Always use pipe sealant approved for
E85 fueling.
• Always place containers on the ground
before lling.
• Always discharge static electricity before
using or servicing equipment by touching
a metal part of the dispenser before and
after fueling vehicle.
• Never smoke within 20 ft / 6.1 m of
dispensers.
• Never keep in service past recommended life.
• Never leave the nozzle unattended while
dispensing fuel.
• Never use sparking or aming devices within
20 ft / 6.1 m of dispensers.
• Never use power tools near dispensers or
to aid in the installation process.
• Never use cell phone within 20 ft / 6.1 m of
dispensers.
• Never reenter car when fueling vehicle.
• Never allow gasoline to touch eyes or skin.
• Never use at ow rates in excess of
regulatory guidelines.
• Never use at ow rates less than 5 gpm /
18.9 Lpm.
• Never dispense ammable material into
unapproved containers.
• Never dispense fuel without a valid
driver’s license.
Listings (pending)
WARRANTY
VAPOR PRODUCTS – Husky Corporation will, at its option, repair, replace, or credit the purchase price of any Husky
manufactured product which proves upon examination by Husky, to be defective in material and/or workmanship for a period of one (1)
year of installation or fteen (15) months from the manufacture date of shipment by Husky, whichever occurs rst. The warranty period on
repaired or replacement vapor recovery products is only for the remainder of the warranty period of the defective product.
CONVENTIONAL PRODUCTS – Husky Corporation will, at its option, repair, replace, or credit the purchase price of any Husky
manufactured product which proves upon examination by Husky, to be defective in material and/or workmanship for a period of one (1)
year from the manufacture date of shipment by Husky.
Buyer must return the products to Husky, transportation charges prepaid. This Warranty excludes the replaceable bellows,
bellows spring assembly, spout assembly and scuff guard, unless (i) damage is obvious when the product is removed from shipping carton
and (ii) the defective product is returned to Husky prior to use. This Warranty does not apply to equipment or parts which have been installed
improperly, damaged by misuse, improper operation or maintenance, or which are altered or repaired in any way.
The Warranty provisions contained herein apply only to original purchasers who use the equipment for commercial or
industrial purposes. There are no other warranties of merchantability, tness for a particular purpose, or otherwise, and any other such
warranties are hereby specically disclaimed.
Husky assumes no liability for labor charges or other costs incurred by Buyer incidental to the service, adjustment, repair, return,
removal or replacement of products. Husky assumes no liability for any incidental, consequential, or other damages under any warranty,
express or implied, and all such liability is hereby expressly excluded.
Husky reserves the right to change or improve the design of any Husky fuel dispensing equipment without assuming any
obligations to modify any fuel dispensing equipment previously manufactured.
Husky Corporation • 2325 Husky Way • Pacic, MO 63069 • Phone: (800) 325-3558 • Fax: (636) 825-7300 • www.husky.com
Page 2 009211-2 7/2010
Loading...
+ 2 hidden pages