Viron Pool and Spa Heater Page 12
4. If no symbol is present, slide toggle up to allow adjustment, then rotate knurled wheel anti
clockwise (as viewed from above) until “ș” is displayed.
5. Switch off pump.
6. View LCD display to confirm “ș”has disappeared.
7. If “ș” symbol is present when pump is OFF or “ș” does not disappear within 1 (one) second of
pump turning off, the pressure switch must be adjusted.
8. With Pump turned OFF, turn knurled wheel clockwise to increase the pressure required to
activate the switch.
9. Repeat steps 2 to 8 until symbol appears and disappears when pump turns on and off.
10. When the switch is correctly set, slide the toggle down to lock the knurled wheel in position.
11. If pressure switch cannot be made to activate heater when pump is turned on and off, a flow
switch may need to be purchased and fitted. Contact your local Astral Pool office for details.
WARNING: If the pressure switch cannot be adjusted correctly, DO NOT OPERATE THE
HEATER, contact Astral or an Authorised Service Agent for advice.
12. Perform a final check with the heater operating.- See the section below titled “Starting the
heater”.
It is imperative that the heater is installed so that it does not operate when the circulating pump
stops. Recommended methods to achieve this are:
a) Correct adjustment of internal pressure switch. Ensure heater does not turn on two or
three minutes after circulating pump is turned off.
b) Installation of an external flow switch may be preferred under certain installations
where internal pressure switch does not turn heater off when circulator stops.
TESTING INLET PRESSURE
1. Note – gas pressure must be measured when unit is operating.
2. Set thermostat to “OFF”.
3. Remove top cover (2 screws at rear of heater, remove L/H side panel, remove front 2 screws
hidden inside side panel area)
4. Remove electrical enclosure screws and hinge cover forward.
5. Loosen screw from ǩ” brass test point located on inlet side of gas valve
6. Connect manometer tube to test point
7. Set thermostat to “ON” and wait for burner to ignite
8. Once burner has ignited, the manometer must indicate the nominal inlet pressure listed below.
9. Adjust inline pressure to meet minimum required pressure at main gas regulator. Do not
adjust gas valve settings..
10. Tighten test point screw.
11. Refit covers.
Pressure Switch Adjustment
Slide toggle up
to allow
adjustment
Turn wheel in
direction of arrow
to decrease
pressure required
to operate heater